Palm Beach State College Florida s First Public Community College FIRE PREVENTION PLAN

Similar documents
Stillwater Area Community Services Center Inc.

Fire Prevention Plan. California State University, Chico

Fire Prevention Plan

Fire Prevention Plan

PROSPECT COLLEGE HEALTH AND SAFETY PLANS FIRE PREVENTION PLAN

HOT WORK SAFETY PROGRAM:

Fire Prevention Plan for Alter Hall 3743 Ledgewood Drive

Fire Prevention Plan

Board Policy 6819 Fire Safety and Prevention Plan

Fire Prevention Plan for St. Barbara Hall 3904 Winding Way

Health and Safety Plans Health and Safety Policy Statement Fire Prevention Plan Objective

ADMINISTRATIVE SERVICES MANUAL

Fire Prevention Plan for Campus Services Building 1630 Musketeer Drive

Savard Labor & Marine Staffing, Inc. Fire Prevention Program Rev3/14

Fire Prevention Plan for Residence Life 1625 Musketeer Drive

Fire Prevention Plan for Bellarmine Parish Center 3832 Ledgewood Avenue

BP U.S. Pipelines and Logistics (USPL) Safety Manual Page 1 of 6

Element 14.7 Fire Prevention and Control 2018

Xavier Field Office Fire Prevention Plan. for. Xavier Field Office Dana Avenue

Fire Prevention Plan for McGrath Health and Wellness Center 1714 Cleneay Avenue

WELDING, CUTTING, AND BRAZING SAFETY PROGRAM

Fire Prevention Plan for Xavier Armory 3908 Winding Way

Electrical Safety Program.

FIRE SAFETY AND PREVENTION POLICY

Hot Work Policy. Department of Risk Management. 1. Purpose. 2. Authority. 3. Scope

Fire Prevention Plan for Cintas Center 1624 Musketeer Drive

Fire Prevention Plan

CLARK COUNTY FIRE DEPARTMENT Fire Prevention Bureau

Emergency Evacuation Plan. Kettering Labs. School of Engineering

Purpose: To establish procedures for identifying fire hazards and preventing fires. Scope: All Central New Mexico Community College (CNM) Community.

Fire Prevention Plan

Susquehanna University Annual Fire Safety Report 2015

INTRODUCTION... 1 OBJECTIVES... 1 RESPONSIBILITIES...

FIRE INCIDENT REPORTING

Fire Prevention Plan for Alumni Center 1507 Dana Avenue

Emergency Evacuation Plan South Patterson Building (SPB)

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services 575 E. Flamingo Road, Ls Vegas, NV (702) FAX (702)

Fire Prevention Plan for

CHAPTER 15: FIRE PREVENTION & AWARENESS POLICY

Emergency Action Fire Prevention Plan

Title: Fire Prevention During Welding, Cutting and Other Hot Work Plan (formerly the Cutting & Welding Policy)

Emergency Action and Fire Prevention

Today, we re going to talk about emergency action and fire prevention. We hope we never have to face an emergency situation like a fire in our

Safety Tips for the Office

Fire Prevention Program

2017 Annual Fire Safety Report

Fire Prevention Plan Program

Bloomsburg University of Pennsylvania Hot Work Safety Program Effective Date: July 1, 2015

August Safety Subject

Fire Evacuation Plan Health Sciences & Human Services Library. UMB POLICE or

FIRE SAFETY PRACTICES AND PROCEDURES

Electrical Safety Program

DUQUESNE UNIVERSITY. Fire Protection System Impairment Program (Red etag Permit)

Evacuation Fire Safety Program

OAK GROVE SCHOOL DISTRICT SCHOOL SITE FIRE PREVENTION PLAN

Goals of a Fire Prevention Program Fire Prevention Strategy Housekeeping Issues Flammable and Combustible Liquids Electrical Fire Hazards

University of Maryland FIRE EVACUATION PLAN

Fire Safety Plan (FSP) Review Checklist 1

Fire Evacuation Plan Bressler Research Building. UMB POLICE or

FIRE PREVENTION 29 CFR Ursinus College, Collegeville, PA

COLUMBUS STATE COMMUNITY COLLEGE EMPLOYEE SAFETY MANUAL

Procedure DESCRIPTION/OVERVIEW

Fire Safety Plan (FSP) Review Checklist 1

[Department Name- Division] [Building Name and Address] [Date or Revision Date]

FIRE PREVENTION PLAN EMERGENCY ACTION

Fire Evacuation Plan Davidge Hall. UMB POLICE or

COMPLIANCE WITH THIS PUBLICATION IS MANDATORY

BCIT FIRE SAFETY PROGRAM

Fire Safety Safety Program

UNIVERSITY OF TOLEDO

ALARM SYSTEMS AND EVACUATION PLANS SELF INSPECTION CHECKLIST

Hot Work Program & Operational Guidelines. Environmental Health, Safety and Emergency Management (828)

Table of Contents. EMERGENCY PROCEDURES Policy 190

Exit Routes, Emergency Action Plans, Fire Prevention Plans, and Fire Protection

Annual Fire Safety Report

HUDSON VALLEY COMMUNITY COLLEGE BUILDING EMERGENCY ACTION PLAN FOR OUTSIDE EMERGENCY ASSISTANCE: DIAL 911 TO REACH THE SARATOGA CTY POLICE & FIRE

Housing and Residence Life Fire Reporting

Carthage College. Fire Incidents by Building for 2016

GUIDELINES FOR EMERGENCY PLANNING AND PREPAREDNESS. High-Hazard

ILLINOIS INSTITUTE OF TECHNOLOGY SAFETY POLICY COMMITTEE OFFICE SAFETY POLICY

Office of Residence Life. Director of Residence Life

Academic and Administrative Buildings

Chapter 12 HOT WORK OPERATIONS. Purpose:

OUTLINE FOR FIRE PREVENTION ACTIVITY

Dutchess Community College. Emergency Action Plan. Conklin Hall College Residence

8.2.2 Fire Alarm and Other Emergency Equipment -- Fire and related emergency equipment

FIRE SAFETY POLICY & PROCEDURES TRAINING. Developed by Office of Environmental Health & Safety

This policy is applicable to all DMS-owned, -leased and -managed facilities.

Building Self-Inspection Program

Fire Prevention Plan Program Prepared by: Allied Insurance Brokers, Inc.

Welcome to the Fire Safety module.

ALARM SYSTEMS AND EVACUATION PLANS SELF INSPECTION CHECKLIST

ALARM SYSTEMS AND EVACUATION PLANS SELF INSPECTION CHECKLIST

Annual Fire Safety Report

John Jay College of Criminal Justice HOT WORK PERMIT STANDARD OPERATING PROCEDURES

Fire Hazard Identification Checklist 1

Safe Operating Procedure

Harvard University - OEB Glasshouse Emergency Evacuation Plan

SURREY FIRE SERVICE. Construction Fire Safety Plan Bulletin

Fire Safety Guide. Emergency Number:

Transcription:

Palm Beach State College Florida s First Public Community College FIRE PREVENTION PLAN

Emergency Contact Information Site Organization/Personnel Telephone Number Boca Raton Campus Security (561) 862-4600 (X54600) Belle Glade Campus Security (561) 993-1120 (X31120) Lake Worth Campus Security (561) 868-3600 (X13600) Palm Beach Gardens Campus Security (561) 207-5600 (X25600) Chief Fire Official/Claude Edwards (561) 868-3655 (X13655) External First Responders 911 Page 1 of 14

PALM BEACH STATE COLLEGE FIRE PREVENTION PLAN Table of Contents 1.0 PURPOSE AND SCOPE... 3 2.0 PLAN IMPLEMENTATION RESPONSIBILITIES... 3 2.1 RESPONSIBILITIES FOR INSPECTION AND MAINTENANCE OF FIRE PREVENTION/ DETECTION/SUPPRESSION/CONTROL EQUIPMENT... 3 2.2 FIRE DETECTION/SUPPRESSION EQUIPMENT OUTAGES... 4 2.3 RESPONSIBILITIES AND PROCEDURES FOR THE CONTROL OF FUEL SOURCE HAZARDS AND FIRE-PRODUCING EQUIPMENT... 4 2.3.1 Facility Maintenance Operations... 4 2.3.2 Cafeteria Operations... 4 2.3.3 General Office Operations... 5 3.0 MAINTENANCE AND HOUSEKEEPING PROCEDURES... 5 3.1 GENERAL PROCEDURES... 5 3.2 CONTROLLING ACCUMULATIONS OF COMBUSTIBLE AND FLAMMABLE MATERIALS... 5 3.3 STORAGE AND HANDLING OF HAZARDOUS MATERIALS... 5 3.4 REGULAR MAINTENANCE... 6 3.5 SMOKING... 6 3.6 HOUSEHOLD ELECTRICAL APPLIANCES... 6 3.7 ELECTRICAL CORDS AND POWER STRIPS... 6 3.8 NON-IONIZING RADIATION SOURCES... 6 3.9 CONTROL OF COMMUNICATION DEVICES... 6 3.10 HOT WORK PERMITS... 7 3.11 TENT AND EVENT INSPECTIONS... 7 3.12 CONTROL OF VEHICULAR TRAFFIC... 7 4.0 INFORMATION FOR EMPLOYEES... 7 5.0 FIRE PREVENTION ANALYSES BY TYPICAL FACILITY OR WORK AREA... 7 6.0 REFERENCES... 11 APPENDIX A... 12 APPENDIX B... 13 Page 2 of 14

1.0 Purpose and Scope For work locations with more than 10 employees, OSHA standards (Title 29 Code of Federal Regulations, Section 1910.39, abbreviated 29 CFR 1910.39) require employers to have a written Fire Prevention Plan in the workplace available to employees for review. The Fire Prevention Plan works in concert with other plans and procedures, including those for emergency reporting and emergency response. The fire emergency reporting and evacuation procedures that are to be followed at each Palm Beach State College campus are described in the Palm Beach State College Emergency Operations Plan, which also constitutes the Emergency Action Plan required by OSHA pursuant to 29 CFR 1910.38. These procedures are summarized in Appendix A. In general, upon discovery of a fire, the employee or student is to immediately sound warning, report it and evacuate the area. The employee shall not attempt to fight the fire unless it is an imminent threat to his/her personal safety. This document presents the Palm Beach State College Fire Prevention Plan which addresses the following elements as required by the OSHA standard: Plan Implementation Responsibilities o Names or job titles of those personnel responsible for maintaining equipment to prevent or control sources of ignition or fires o Names or job titles of those personnel responsible for control of fuel source hazards Maintenance and Housekeeping Procedures o Procedures to control accumulations of flammable or combustible waste materials o Proper handling and storage procedures for hazardous materials o Procedures for regular maintenance of safeguards installed on heat-producing equipment to prevent the accidental ignition of combustible materials Information for Employees A list of all typical major workplace fire hazards Potential ignition sources (such as welding, smoking and others) and their control The type of fire protection equipment or systems necessary for each major hazard 2.0 Plan Implementation Responsibilities 2.1 Responsibilities for Inspection and Maintenance of Fire Prevention/ Detection/Suppression/Control Equipment This section provides the typical job titles of those personnel responsible for inspection and maintenance of equipment and systems installed to prevent or control sources of ignition or fires: The Facilities Manager is responsible for maintenance of equipment and systems installed to prevent or control ignitions or fires, including the following facilities-related equipment: Page 3 of 14

o Fire detection systems (inspection and maintenance in accordance with National Fire Protection Association (NFPA) Standard 72, National Fire Alarm Code) o Fire alarms (inspection, testing and maintenance in accordance with NFPA 72 and NFPA Standard 25, Inspection, Testing and Maintenance of Water-Based Fire Protection s) o Building fire suppression systems fire suppression facilities (e.g., pump houses), sprinklers and hoses (inspection and maintenance). Maintenance activities, including preventative maintenance (PMs), are to be specified, documented and verified in the Facilities Department s maintenance management system. In building areas where spray painting is occurring, the Facilities Maintenance personnel or the Facilities Project Manager are responsible for preventing paint overspray from inhibiting fire sprinkler head operation. The Security Department is responsible for inspection of portable fire extinguishers in accordance with NFPA 10, Standard for Portable Fire Extinguishers. 2.2 Fire Detection/Suppression Equipment Outages When necessary, e.g., due to outages or maintenance of fire detection or suppression equipment, fire watches may be established to assure fire preventative measures are maintained. 2.3 Responsibilities and Procedures for the Control of Fuel Source Hazards and Fire- Producing Equipment 2.3.1 Facility Maintenance Operations Facilities Maintenance supervision is responsible for controlling fuel source hazards and equipment that may produce heat, sparks or other actions that may ignite flammable or combustible materials as a result of maintenance activities. The following NFPA Standards are observed in controlling ignition sources as a part of daily operations: NFPA Standard 1, Uniform Fire Code NFPA Standard 30, Flammable and Liquid Code NFPA Standard 45, Standard for Fire Protection for Laboratories Using Chemicals NFPA Standard 51B, Fire Prevention During Welding, Cutting and Other Hot Work NFPA Standard 101, Life Safety Code 2.3.2 Cafeteria Operations The food service vendor is responsible for controlling fuel source hazards and equipment that may produce heat, sparks or other actions that may ignite flammable or combustible materials as a result of food preparation and service activities. Page 4 of 14

2.3.3 General Office Operations The individual organizational manager/supervisor for Palm Beach State College faculty and staff is responsible for ensuring that their direct reports are utilizing approved electrical appliances, electric cords, power bars and electronic equipment in the manner prescribed and are not using any equipment in a manner that may produce heat, sparks or other actions that may ignite flammable or combustible materials as a result of their activities. 3.0 Maintenance and Housekeeping Procedures 3.1 General Procedures All College employees shall work under the clean as you go philosophy to prevent the accumulation of flammable and combustible waste materials and residues that might contribute to a fire emergency. Good common sense and good operating practices also apply. General procedures and good operating practices include, as applicable: Keeping only an operational supply of flammable and combustible paints and solvents, not to exceed one day's use in the work area(s), and returning them to the point of issue or flammable storage cabinets at the end of the shift. Storing these materials in appropriate containers and marked as to their contents in accordance with Hazard Communication Program requirements. The containers should be staged remotely from other operations and be tightly closed when not in use. Upon completion of painting operations, collecting all waste solvents, wiping waste, used masking tape and waste paper and properly disposing of them in accordance with campus procedures. Until properly disposed of, waste should be kept in covered metal containers. Collecting all wastes generated by daily activities, segregating them as necessary and placing them into appropriately designated collection containers. Care must be taken to ensure that flammable wastes are never mixed with reactive wastes. 3.2 Controlling Accumulations of Combustible and Flammable Materials All combustible and flammable materials shall be stored only in appropriate containers in appropriately marked locations or in flammable liquid lockers. Container grounding and bonding is required for proper storage and dispensing these materials and shall be implemented where appropriate. The action of transferring flammable liquids from one container to another can produce static electrical sparks that could ignite the liquid. The method to prevent this static potential is to bond the containers together before pouring. Flammable liquid lockers and large dispensing containers, such as drums or tanks, must be connected to a facility electrical ground. All bonding and grounding connections must be metal to metal. All dirt, paint, rust, or corrosion must be removed from the points of contact before the connections are made. Liquids shall be transferred only into undamaged containers. 3.3 Storage and Handling of Hazardous Materials Hazardous materials shall be stored and handled in accordance with the guidance contained in their associated Material Safety Data Sheets. Page 5 of 14

3.4 Regular Maintenance Regular maintenance of safeguards installed on heat-producing equipment to prevent the accidental ignition of combustible materials shall be conducted by the Facilities Department in accordance with equipment s established PM schedule and protocol. 3.5 Smoking In accordance with Palm Beach State College Board Policy 6Hx-18-1.28, smoking is not permitted in any College building. Smoking is permitted only in the parking lot(s) and in designated smoking areas established by the Provost and Facilities. Failure to adhere to the policy may result in disciplinary action. 3.6 Household Electrical Appliances Household electrical appliances, e.g., refrigerators, microwave ovens, coffee pots, toasters and small electric fans, are allowed on the campuses of Palm Beach State College subject to the provisions in the Palm Beach State College Household Electrical Appliance Procedure (see Appendix B). Appliances that are specifically not allowed include space heaters, immersion heaters, coffee cup warmers, hot plates, box fans in buildings that are air-conditioned and any electrical household-type electrical appliance not acceptable to authorized Facilities personnel. Allowed appliances that are not operated in accordance with the Procedure or that present a hazard or that adversely affect the operation of the building or other equipment may be directed to be removed by authorized Facilities personnel. 3.7 Electrical Cords and Power Strips If utilized improperly, electrical cords and power strips can produce electrical shock or heat and sparks that that may ignite flammable or combustible materials in their vicinity. Overloading electrical outlets, using multi-plug adapters, running extension cords through ceilings, walls, floors, doorways or windows, daisy-chaining of electrical cords and power strips (i.e., the practice of plugging one cord or power strip into another) and placement of electrical cords over open filing cabinet drawers or furniture with sharp edges are examples of improper usage and are prohibited. 3.8 Non-Ionizing Radiation Sources Where lasers are present at a campus, procedures for their operation and maintenance shall be developed to establish controls to prevent both personnel exposure and ignition of combustible and flammable materials. 3.9 Control of Communication Devices Use of communication devices, such as two-way radios and cellular phones, is prohibited within 50 feet of any automotive fuel storage or dispensing areas, where present at a campus. Page 6 of 14

3.10 Hot Work Permits Hot work permits must be obtained from the Facilities Department, e.g., Planning & Construction, for use of heating or spark-producing equipment, such as a roofing tar heater or a welding torch. 3.11 Tent and Event Inspections Tents and facilities set up for special events on any campus must be inspected by the Chief Fire Official for compliance with Life Safety Code requirements prior to their operation. The event coordinator is responsible for contacting the Chief Fire Official to schedule the inspection. 3.12 Control of Vehicular Traffic Vehicular traffic must be controlled in areas where traffic can introduce an ignition source. 4.0 Information for Employees Each campus shall utilize the Hazard Communication Program to apprise its employees of the fire hazards of the materials and processes to which they are exposed. This shall occur prior to working with or potentially being exposed to combustible or flammable materials upon initial assignment to any job involving them. During such training, the employee will be provided with a copy of this Fire Prevention Plan for review or advised on how to access it online. 5.0 Fire Prevention Analyses by Typical Facility or Work Area This section lists all typical major workplace fire hazards, their potential ignition sources (such as welding) and their control and the type of fire protection equipment or systems that can control a fire involving each major fire hazard. Page 7 of 14

Area/Flammable or Combustible Commodity Office Area Paper Carpet Fire Prevention Analyses by Typical Facility or Process Area Fire Hazard Risk 1 Potential Ignition Source(s) Fire Detection Device(s) A Unauthorized Smoke Detectors Electrical Water Flow Alarms Appliances 2 Sprinkler Heads Daisy-Chaining of Power Strips or Electrical Cords 2 A See Office Area Smoke Detectors Water Flow Alarms Sprinkler Heads Chemistry/Biology Laboratory Minor quantities of flammable/combustible chemicals Computer Room Paper Carpet Library Paper Carpet Warehouse A Industrial Trucks Cardboard, wood, packing See Office Area materials Shipping & Receiving A Industrial Trucks Cardboard, wood, packing See Office Area materials 1. Fire Hazard Risk: A = Minimal, B = Moderate, C = Extreme 2. This Potential Ignition Source may be present in every facility or process area. Fire Suppression (s) Wet Sprinkler Fire Extinguisher(s) Wet Sprinkler Fire Extinguisher(s) A See Office Area Smoke Detectors FM-200 Fire Suppression Fire Extinguisher(s) A See Office Area Smoke Detectors Fire extinguisher(s) Smoke Detectors Water Flow Alarms Smoke Detectors Water Flow Alarms Wet Sprinkler Fire Extinguisher(s) Wet Sprinkler Fire Extinguisher(s) Page 8 of 14

Fire Prevention Analyses by Typical Facility or Process Area (Continued) Area/Flammable or Combustible Commodity Fire Hazard Risk 1 Potential Ignition Source(s) Print Shop A Reproduction Paper, cardboard boxes Equipment Minor quantities of See Office Area flammable/combustible liquids Carpentry Shop A Shop Machinery Cardboard, wood, packing See Office Area materials Minor quantities of flammable/combustible liquids Electrical Shop A Shop Machinery Minor quantities of See Office Area flammable/combustible liquids Machine Shop/Metal Shop A Shop Machinery Cutting oils and lubricants Portable Hand Minor quantities of Tools flammable/combustible See Office Area liquids Paint Shop A Industrial Trucks Minor quantities of See Office Area flammable/combustible paints and solvents 1. Fire Hazard Risk: A = Minimal, B = Moderate, C = Extreme Fire Detection Device(s) Smoke Detectors Smoke Detectors Water Flow Alarms Sprinkler Heads Smoke Detectors Smoke Detectors Smoke Detectors Heat Detectors Fire Suppression (s) Wet Sprinkler Fire Extinguisher(s) Wet Sprinkler Fire Extinguisher(s) Wet Sprinkler Fire Extinguisher(s) Wet Sprinkler Fire Extinguisher(s) Wet Sprinkler Fire Extinguisher(s) Page 9 of 14

Fire Prevention Analyses by Typical Facility or Process Area (Continued) Area/Flammable or Combustible Commodity Fire Hazard Risk 1 Potential Ignition Source(s) Fire Detection Device(s) Fire Suppression (s) Welding Shop A Welding Heat Detectors Wet Sprinkler Minor quantities of flammable/combustible liquids Equipment Portable Hand Tools Fire Extinguisher(s) Compressed flammable/ combustible gases See Office Area Vehicle Parking Areas A Vehicles with Internal Visual Sighting Fire extinguisher(s) Fuel in vehicles Combustion Engines Flammable Bulk Storage/Fuel A Vehicles with Internal Visual Sighting Fire extinguisher(s) Dispensing Areas Combustion Engines Hazardous Waste/Hazardous Material Storage A Vehicles with Internal Combustion Engines Visual Sighting Fire extinguisher(s) Minor quantities of flammable/combustible paints, solvents and wastes Ammunition Storage A None Recognized Smoke Detectors FM-200 Fire Suppression Cafeteria/Kitchen A Ovens/Ranges Smoke Detectors Ansul/UL 3000 Fire Grease Electrical Water Flow Alarms Suppression Cooking Oils Appliances See Office Area Type K Fire Extinguisher 1. Fire Hazard Risk: A = Minimal, B = Moderate, C = Extreme Page 10 of 14

6.0 References NFPA 1 Uniform Fire Code NFPA 10 Portable Fire Extinguishers NFPA 25 Inspection, Testing and Maintenance of Water-Based Fire Protection s NFPA 30 Flammable & Combustible Liquid Code NFPA 33 Spray Applications Using Flammable or Combustible Materials NFPA 45 Standard for Fire Protection for Laboratories Using Chemicals NFPA 51B Fire Prevention During Welding, Cutting and Other Hot Work NFPA 72 National Fire Alarm Code NFPA 101 Life Safety Code 29 CFR 1910.39 Fire Prevention Plans Page 11 of 14

APPENDIX A EMERGENCY REPORTING, EVACUATION ROUTES AND PROCEDURES Reporting Fires Fire or Other Emergency Situation or Condition Is Discovered Discoverer: Sound warning in the area by shouting the cause for the emergency, such as fire, or pulling a manual pull-station if alarm has not sounded. Call or direct someone to report the emergency to Security by dialing the appropriate emergency number and/or 911. Provide Security or the 911 dispatcher with the following information: o Your name o The nature and location of the emergency (i.e., address, building, floor, department, area, etc.) o Number of people involved, injuries or life-threatening hazards o Any hazardous material present that may exacerbate the emergency conditions Note: Stay on the telephone until released by the dispatcher Do not attempt to fight the fire unless it is an imminent threat to your personal safety. Immediately evacuate the area. Emergency Sequence Fire Alarm Sounds or Emergency Evacuation is Directed Note: When evacuation is initiated, it shall be total and complete. Emergency Situation Evaluation Post-Emergency/Recovery Typical Emergency Evacuation Emergency Actions Without compromising personal safety, shutoff machinery/equipment. Close area door. Evacuate facility or process area using marked exits. Note: Use alternate evacuation routes in the event fire, smoke, obstruction or other conditions indicate unsafe situations. Report to the designated Safe Assembly Area. Remain in the Safe Assembly Area, regardless of alarm cessation, until all personnel are accounted for, and the "return to work" order or other instruction is given. Note: Be on the lookout for responding emergency vehicles. Follow the instructions issued by the Emergency Management Team Leader. Instructions may include: Returning to the building or another building or leaving the campus in an orderly fashion. Page 12 of 14

APPENDIX B PALM BEACH STATE COLLEGE HOUSEHOLD ELECTRICAL APPLIANCE PROCEDURE In order to comply with applicable provisions of the National Electric Code and State Requirements for Educational Facilities and to promote overall fire safety, household electrical appliances, e.g., refrigerators, microwave ovens, coffee pots, toasters and small electric fans, are allowed on the campuses of Palm Beach State College subject to the following conditions: 1. In accordance with Florida Statutes, the use of College funds to purchase household electrical appliances for the personal convenience of staff is prohibited. 2. Household electrical appliances shall not: Adversely affect the electrical loading, quality or stability of the circuits on which they are located. Adversely affect the operation of other equipment on the circuit. Pose a threat to personnel safety or fire/electrical safety. If authorized Facilities personnel determine that any of these is occurring, the appliance may be subject to removal. 3. All such appliances must be certified or labeled by an accredited testing organization, e.g., Underwriters Laboratory or Factory Mutual (i.e., UL-Listed or Factory Mutual- Approved ). 4. All such appliances should be located only in areas that are suitable for their use, i.e., kitchens, break areas and other areas that are designed or established to accommodate them. 5. Appliances are allowed only in offices that have adequate space and a fire suppression system. Exceptions to this may be approved by the campus Facilities Manager on a caseby-case basis. 6. All appliances must have an electrical cord with a proper grounding prong or polarized plug. 7. All appliances must be connected directly to a wall or floor outlet. The use of power strips or extension cords to connect them to an outlet is prohibited. 8. The appliance owner shall be responsible for its maintenance, replacement and relocation as necessary, as well as its sanitation and cleanliness. Items determined by authorized Facilities personnel to be improperly maintained or in an unsanitary condition may be subject to removal. 9. Microwave and toaster ovens and toasters shall not be operated unattended. 10. Except for refrigerators, appliances should be turned off when not in use. 11. Toasters, toaster ovens and full-size refrigerators are NOT allowed in offices, only in kitchens or designated break areas. The following appliances are NOT allowed at Palm Beach State College: Space heaters Immersion heaters Coffee cup warmers Hot plates Box fans in buildings that are air-conditioned Any other household-type electrical appliance not acceptable to authorized Facilities personnel. Page 13 of 14

12. Particular care must be exercised where appliances are located in areas protected by smoke detectors to ensure that unnecessary fire alarms are not triggered by their operation. If determined by authorized Facilities personnel to have been caused by operation of an appliance, an unnecessary fire alarm or circuit trip may be grounds for its removal. 13. Failure to observe these requirements for any appliance may result in a requirement by authorized Facilities personnel for its immediate removal. The Chief Fire Official shall be the final authority for any appeal of a removal request. Page 14 of 14