Experimental Investigation of a New High Temperature Heat Pump Using Water as Refrigerant for Industrial Heat Recovery

Similar documents
Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Study of R161 Refrigerant for Residential Airconditioning

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

Low GWP Refrigerants for Air Conditioning Applications

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

The Design Of A New Generation Of Twin Screw Refrigeration Compressors

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

Comparison of Energy Efficiencies of Commercial Refrigeration Direct and Indirect Systems

Energy Efficiency of Air-to-Air Mini Heat Pump

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

Development of R744 Two Stage Compressor for Commercial Heat Pump Water Heater

EXPERIMENTAL INVESTIGATIONS ON AUTOMOBILE AIR CONDITIONERS WORKING WITH R134a AND R290/R600a AS AN ALTERNATIVE

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Modelling Of An Automotive Multi-Evaporator Air-Conditioning System

HSPF Calculation of a System Allowing Switching Between a Single-Stage to a Two-Stage Compression System

Theoretical and Experimental Analysis of the Superheating in Heat Pump Compressors. * Corresponding Author ABSTRACT 1.

Performance of an Improved Household Refrigerator/Freezer

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

Purdue e-pubs. Purdue University

The Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities

High Efficiency Heat Pump for Domestic Hot Water Generation

The Innovative Green Technology for Refrigerators Development of Innovative Linear Compressor

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

A Theoretical investigation on HC Mixtures as Possible Alternatives to R134a in Vapor Compression Refrigeration

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid

R32 Compressor for Air conditioning and Refrigeration applications in China

International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

Energy Savings Potential of Passive Chilled Beam System as a Retrofit Option for Commercial Buildings in Different Climates

Performance Evaluation of the Energy Efficiency of Crank-Driven Compressor and Linear Compressor for a Household Refrigerator

Comparison Of Hermetic Scroll And Reciprocating Compressors Operating Under Varying Refrigerant Charge And Load

Enhancement of the Separate Sensible and Latent Cooling Air-Conditioning Systems

Performance Measurement of R32 Vapor Injection Heat Pump System

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

Modelling of an Integrated Supermarket Refrigeration and Heating System Using Natural Refrigerants

Sub-Critical Operation of the CO2 Expander/ Compressor

Performance Comparison of R32, R410A and R290 Refrigerant in Inverter Heat Pumps Application

Experimental Investigation of Closed Loop Oscillating Heat Pipe as the Condenser for Vapor Compression Refrigeration

Hunting Phenomena Of Automotive Air Conditioning Systems With Variable Displacement Compressor

ENERGY SAVINGS THROUGH LIQUID PRESSURE AMPLIFICATION IN A DAIRY PLANT REFRIGERATION SYSTEM. A. Hadawey, Y. T. Ge, S. A. Tassou

AN EXPERIMENTAL STUDY OF A REFRIGERATING PLANT WHEN REPLACING R22 WITH HFCs REFRIGERANTS

Experimental Investigation on the Performance of Ground-source Heat Pump with the Refrigerant R410A

Analysis of Oil Pumping in the Hermetic Reciprocating Compressor for Household Refrigerators

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Performance Evaluation of a Plug-In Refrigeration System Running Under the Simultaneous Control of Compressor Speed and Expansion Valve Opening

Modelling the Performance of a Diffusion Absorption Refrigeration System

Thermodynamics II Chapter 5 Refrigeration

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Performance investigation of Air-conditioning system using ejector as expansion device

Development of an Open Drive Scroll Compressor for Transportation Refrigeration

Performance Characteristics of a Refrigerator- Freezer with Parallel Evaporators using a Linear Compressor

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

System Modeling of Gas Engine Driven Heat Pump

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Experimental Study on the Thermal Behavior of a Domestic Refrigeration Compressor during Transient Operation in a Small Capacity Cooling System

A study of high efficiency CO2 refrigerant VRF air conditioning system adopting multi-stage compression cycle

*Corresponding author;

Performance of CO2 Cycles with a Two-Stage Compressor

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

Experimental Analysis of a Stirling Refrigerator Employing Jet-Impingement Heat Exchanger and Nanofluids

Experimental study of Hydrocarbon Refrigerant Mixture R290/R600a as an alternative to Refrigerant R134a used in a Domestic Refrigerator

Sustainability of Automobile Air- Conditioning System Using Refrigerant R1234yf Instead of R134a

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

A Performance-Enhancing Additive for Vapor- Compression Heat Pumps: Additional Test Results

CASE STUDIES OF THERMALLY DRIVEN HEAT PUMP ASSISTED DRYING. Minh Cuong Tran, Jamy Logie, Bruno Vanslambrouck, Martijn van den Broek

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

Refrigeration Cycles MOHAMMAD FAISAL HAIDER. Bangladesh University of Engineering and Technology

Mini Vapour Cycle System For High Density Electronic Cooling Applications

Numerical Simulation of a New Cooling System for Commercial Aircrafts

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

An Investigation Into The Influence Of Improved Refrigeration Cycle And Refrigerants On An Energy Efficient Domestic Refrigerator

Combination unit to support instruction in Thermodunamics, Fluid Mechanics, and Heat Transfer

A New Control Approach for a Direct Expansion (DX) Air Conditioning (A/C)System with Variable Speed Compressor and Variable Speed Supply Fan

Heat Transfer of R-22 and Alternatives in a Plate- Type Evaporator

Efficiency of Non-Azeotropic Refrigerant Cycle

Development of Performance Test Facility of Positive Displacement CO2 Refrigerant Compressor

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

A Review of Hydroflorocarbons (HFC S) Refrigerants as an Alternative to R134a Refrigerant

Transcription:

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2012 Experimental Investigation of a New High Temperature Heat Pump Using Water as Refrigerant for Industrial Heat Recovery Marwan Chamoun marwan.chamoun@insa-lyon.fr Romuald Rulliere Philippe Haberschill Jean-Louis Peureux Follow this and additional works at: http://docs.lib.purdue.edu/iracc Chamoun, Marwan; Rulliere, Romuald; Haberschill, Philippe; and Peureux, Jean-Louis, "Experimental Investigation of a New High Temperature Heat Pump Using Water as Refrigerant for Industrial Heat Recovery" (2012). International Refrigeration and Air Conditioning Conference. Paper 1165. http://docs.lib.purdue.edu/iracc/1165 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

2108, Page 1 Experimental investigation of a new high temperature heat pump using water as refrigerant for industrial heat recovery Marwan CHAMOUN 1 *, Romuald RULLIERE 2, Philippe HABERSCHILL 3, Jean-Louis PEUREUX 4 1,2,3 Université de Lyon, CNRS, INSA-Lyon, CETHIL, UMR5008, Villeurbanne, F-69621, France, Université Lyon 1, F-69622, France 4 EDF R&D, Eco-efficiency & Industrial Process Department, Moret sur Loing, F-77818, France 1 Phone: +33 4 72 43 84 91, Fax: +33 4 72 43 88 11, E-mail: marwan.chamoun@insa-lyon.fr 2 Phone: +33 4.72.43.79.51, Fax: +33 4 72 43 88 11, E-mail: philippe.haberschill@insa-lyon.fr 3 Phone: +33 4 72.43.63.05, Fax: +33 4 72 43 88 11, E-mail: romuald.rulliere@insa-lyon.fr 4 Phone: +33 1 60 73 74 43, Fax: +33 1 60 73 69 12, E-mail: jean-louis.peureux@edf.fr ABSTRACT Currently, improving energy efficiency becomes a main challenge for all industrial energy systems. This challenge involves an improved recovery of wasted heat generated by several industrial processes. Large energy savings and potential environmental benefits are associated with the use of industrial heat pump mainly at high temperature levels. A laboratory flexible industrial scale heat recovery system is able to reproduce the operating conditions of real case simulating energetic losses and requirements in high temperature industrial applications. The integrated heat pump is an electrically-driven vapor compression using a twin screw compressor. Water vapor has been adopted as a working fluid using a modified screw compressor to carry out a dry compression process at high temperature levels. This heat pump generates vapor using flash evaporation. A purging valve is implemented in order to eliminate non-condensable gases present in system. Experimental simulation of the start-up phase has been presented showing the non-condensable purging process and the evolution of some parameters of the heat pump. Several scenarios of industrial processes for high-temperature heat recovery (heat sources between 80 C and 90 C) and heat upgrading are numerically simulated. The presented results show the global energy savings and the environmental benefits of using water as refrigerant at high temperature levels. 1. INTRODUCTION Currently, improving energy efficiency becomes a main challenge for all energy systems due to the sharp increase of fuel prices (FY, 2010). This challenge involves a reduction of industrial processes fuel consumption by a better recovery of process waste heat and using it to meet heating requirements. In addition to energy savings, the environmental context is introduced by further international and local agreements that involve a stronger awareness of environmental concerns especially by emission reduction. Large energy savings and potential environmental benefits are associated with the use of industrial heat recovery systems mainly at high temperature levels. Several market studies assess a large amount of waste heat rejections in the range 80 C-90 C in different industrial sectors like chemistry, paper drying, cleaning in place, However, several applications need heat at higher range of temperature, typically 120 C-130 C (EDF R&D, 2009, Dupont and Sapora, 2009, US DoE, 2003). A heat pump technology is able to upgrade these wastes to make it useful in higher temperature applications. Presently, implemented heat pumps in industries are limited to heat production at a temperature level of 100 C. Several studies try the development of new high temperature heat pumps using newly developed synthetic

2108, Page 2 refrigerant which still harmful to the environment. Therefore the development of a new industrial high temperature heat pump using a natural refrigerant becomes a step to improve industrial energy efficiency while reducing environmental impact which is the goal of the present work. One of the major problems with the development of this high temperature compression heat pump is the choice of the working fluid and corresponding compressor that can be used for these high ranges of temperatures. In this work, experimental simulations reproducing industrial scale operating conditions are carried out to evaluate the potential of an electrically-driven vapor compression heat pump using water as refrigerant. Technological choices, test bench and experimental simulation results have been presented for the start-up phase of the machine. The calculated performance of this machine shows the global energy savings and the environmental benefits of using water as refrigerant at high temperature levels. 2. TECHNOLOGICAL CHOICES FOR THE HIGH TEMPERATURE HEAT PUMP 2.1 Working fluid The choice of the working fluid for this high temperature heat pump should takes into account several considerations like environmental, economical, safety, efficiency, thermodynamic properties. In general, synthetic refrigerants (R134a, R245fa, R1234yf ) dominate vapor compression refrigeration systems. Calm (2008) breaks history into four refrigerant generations based on defining selection criteria. He discusses the succession of criteria that involved a displacement of earlier working fluids and the renewed interest in natural refrigerants. Several studies (Chamoun et al., 2011, EDF R&D, 2009) selected water vapor as refrigerant for high temperature heat pump applications. In refrigeration applications, the use of water has been limited to absorption systems around a binary fluid. This natural fluid is a very attractive refrigerant, lots of studies compared water to other refrigerants from different point of views (Chamoun et al., 2011, Kilicarslan and Muller, 2005). Others made investigations and discussed the feasibility of a refrigerating machine using water vapor as refrigerant (Van Orshoven, 1991, Lachner et al., 2007, Wight, 2000). Water vapor is an environmental friendly refrigerant with no Ozone Depletion Potential (ODP) and a highly reduced Total Equivalent Warming Impact comparing to synthetic refrigerants. It is non-toxic, non-flammable, chemically inert at high temperature and needs low compressing pressures. Water has a high critical temperature therefore its thermodynamic properties suites high temperature ranges. Otherwise, it is easily available with low costs and presenting high theoretical coefficient of performance (COP) due to its high latent heat of vaporization compared to other traditional refrigerants. Hence, the use of water as refrigerant in this high temperature heat pump offer several potentially significant advantages but involves technical and feasibility difficulties especially related to the compressor technology (Chamoun et al., 2012). 2.2 Compressor Except expensive compression machinery, EDF R&D (2009) shows that currently, water vapor compression at high temperature levels can be performed by several industrial compressors: - blowers allow compression of high mass flow rates but under low compression ratios (corresponding to saturated temperature difference T of 5 to 7 K). - multi-stages blowers allow an increase of T to 10 to 12 K. - lobe compressors are adapted to low flow rates but with higher T to 20 K. These compressors have a poor isentropic efficiency. - classical centrifugal compressors (mechanical bearings) can be used in double stage compression process to attain a maximum T of 40 K. These machines are very expensive and work at high rotational speeds at high compression ratio. At these conditions, high level of maintenance is required. In addition, reduced reliability of these compressors is due to the use of mechanical bearings and imperfect sealing at these conditions. Therefore, the largest obstacle is associated with the compressor technology. Adapted compressor should simultaneously satisfy different requirements at high temperature levels like:

2108, Page 3 - high compression ratio corresponding to T of 40 K - high volumetric flow capacity - high isentropic efficiency To overcome this compression problem, an ANR (Association Nationale de la Recherche) project named PACO launched the development of a new twin screw compressor. This compressor is an air compressor specially adapted to water vapor which could satisfy this heat pump demand with some modifications (water injection, sealing ). This type of volumetric compressor presents high compression ratio (corresponding to 40-50 K), sufficient isentropic and high volumetric efficiencies. This electrically-driven vapor compressor provides a dry compression in the heat pumping application by a single stage compression at variable speed. 2.3 Other components At these temperature levels, water evaporating pressure is below atmospheric pressure which implies high specific volume in the evaporation process. Hence, the heat exchangers should be large enough to allow phase change. To avoid large dimensions of heat exchangers, a coupled liquid-liquid plate heat exchanger with a flash evaporation system is implemented to assure evaporation process. In addition, the condenser is a plate and gasket heat exchanger with reduced pinch. A substantial amount of air will have to be removed upon start-up phase of the machine. An additional amount of incoming air depends on many parameters related to the specifics and the hermeticity of the overall system. The presence of air degrades heat exchanger performance and places an additional load on the compressor. Therefore, a significant amount of non-condensable gas in the refrigerant results in a loss of cycle performance and so the noncondensable gases must be purged. An accumulator with a purging valve is implemented at the end of the condensing process to eliminate non-condensable gases existing at the start-up of the machine. 3. TEST BENCH DESCRIPTION The experimental set-up is composed of two main parts: the heat recovery heat pump system and the hydraulic circuit. The designed heat pump is implemented to be tested in an industrial environment imposed by the hydraulic system which simulates industrial wastes and requirements. 3.4 Heat pump circuit In this refrigerating cycle, the evaporative system generates vapor (state 1) into the inlet of the double screw compressor, this vapor flow is mixed to an injected water flow (state 6) in the suction chamber of the compressor. This injected mass flow rate is necessary to avoid high superheating in the compression process risky for the compressor. The biphasic mixture is compressed and discharged at higher pressure level at state 2 in a superheated state. Afterward, vapor condenses by releasing heat to the external sink via the condenser to be collected as condensate (state 3) at the inlet of the accumulator. Then, water (state 4) flows through a ball float steam trap to be expanded into the flash reservoir (state 5) at low pressure. A re-circulating mass flow rate of water (state 6) leaves the tank to absorb heat through the evaporator and re-enters the tank at state 7 to be flashed generating vapor at state 1. Another mass flow rate at state 6 leaves this tank to be injected in the suction chamber of the compressor. A controlled purging valve is implemented at the top of the accumulator in order to eliminate existing air upon start-up phase and air leakages that will escape to low pressure branch of the machine at normal operating conditions.

2108, Page 4 Flash Tank Condenser Evaporator 1 2 7 Compressor 3 6 5 4 Accumulator Expansion valve Circulation pumps Figure 1. Scheme of the heat pump 3.5 Hydraulic circuit The industrial operating conditions are simulated using the hydraulic circuit (Khattar et al., 2010). This circuit is composed of two separate loops (figure 2), the first one low temperature represents industrial waste which delivers energy to the heat pump evaporator. This loop includes a water tank, a controlled electric heater, and a water pump with adjustable volume flow rate. Including the condenser, the second hydraulic loop high temperature simulates the user s heat requirement that the heat pump has to satisfy. This loop includes a water tank, a variable capacity dry cooler, a controlled electric heater, and a water pump with adjustable volume flow rate. Figure 2. Scheme of the hydraulic loops

Temperature [ C] 2108, Page 5 4. RESULTS AND DISCUSSION 4.1 Test campaign The preliminary test was carried out at EDF R&D - EPI Department Renardières laboratory. The presented experimental test is the start-up phase of the heat pump at partial load conditions. In this heat pump configuration, a substantial amount of air will have to be removed upon start-up phase before attaining steady state conditions. This phase was experimentally simulated imposing a constant motor frequency of 500 RPM. Water flow rates on the hydraulic circuit were set to 61 m 3.h -1 at 85 C at the inlet of the evaporator and 56 m 3.h -1 at 110 C at the inlet of the condenser. These parameters can be adjusted at any desired level by the control features of heat pump and hydraulic circuits. The dynamic evolution of condensing pressure and temperature are disturbed by the presence of non-condensable gases in the machine. Figure 3 shows measured temperature evolution of air and water vapor mixture in the accumulator. The difference between saturated temperature at condensing pressure and condensing temperature is a function of partial added pressure of air in the system. After 6 minutes, this difference tends to disappear while eliminating air through the air purging valve at the top of the accumulator. 110 100 90 80 Measured temperature Saturation temperature 70 60 0 2 4 6 8 10 Time [min] Figure 3. Temperature evolution in high pressure branch of the heat pump In the first part of this start-up phase, the process simulation circuit adds heat to heat pump system via the condenser and absorbs heat in the second part where heat pumping function of the heat pump begins. Figure 4 presents evaporation temperature which stills constant in the flash vessel while the discharge temperature of the compressor increases to attain a constant temperature of 130 C in 35 min. The increase of this temperature is due to the pressure evolution while a constant injected mass flow rate is imposed at the suction of the compressor.

Pressure [bar] Temperature [ C] 2108, Page 6 130 120 110 100 90 Compressor inlet Compressor outlet Condenser outlet 80 0 5 10 15 20 25 30 35 Time [min] Figure 4. Inlet and outlet temperature of the compressor and the condenser at start-up At constant evaporation pressure 0.6 bars, figure 5 presents the condensing pressure evolution in function of time to attain steady state conditions at 1.5 bars which corresponds to an superheating of the compressor outlet of 20K in 35 minutes. In this figure, we observe a lot of sudden pressure drops due to the opening of the ball float steam trap which control the water level in the accumulator. The amplitude of these pressure drops are function of the difference between mass flow rates imposed by the compressor and the expansion valve. These drops disappear at higher rotational speed of the compressor. 1.5 1.4 1.3 1.2 1.1 1 0 5 10 15 20 25 30 35 Time [min] Figure 5. High pressure evolution of the heat pump at start-up phase Furthermore, performances of the present heat pump are presented using the numerical model established by Chamoun et al., (2012). Different high temperature processes were simulated for different waste heat scenarios.

Coefficient of performance [-] Process temperature [ C] Heating power [kw] 2108, Page 7 At full load operating conditions of the compressor (motor frequency of 4700 RPM), process volume flow rate was set to 30 m 3.h -1 at 110 C at the inlet of the condenser. Figure 6 shows the evolution of process temperature and heating power supplied by the heat pump in several process scenarios for waste heat temperature levels varying between 85 C and 95 C, with different waste volume flow rates (VFR). The increase of waste heat temperature or waste volume flow rate increases heating power. This figure shows that increasing waste temperature from 88 C to 92 C at constant waste VFR of 36m 3.h -1 increases heating power from 300 to 335 kw and from 328 to 368 kw while the VFR is doubled. 121.5 121 VFR waste = 36 m 3.h -1 VFR waste = 54 m 3.h -1 VFR waste = 72 m 3.h -1 380 120.5 120 119.5 119 118.5 360 340 320 300 118 86 88 90 92 94 Waste heat temperature [ C] 280 86 88 90 92 94 Waste heat temperature [ C] Figure 6. Condensing temperature and heating power versus VFR and temperature of waste heat Figure 7 shows the heat pump performance in the process scenarios mentioned above. This figure illustrates the sensitivity of the global COP to the waste heat VFR and temperature. We can conclude that the heat pump COP is not heavily affected by the VFR variation (maximum observed increase about 5 %) but an increase of 11% is observed with the rising of the waste heat temperature. 5.6 5.4 5.2 5 4.8 4.6 4.4 VFR waste = 36 m 3.h -1 VFR waste = 54 m 3.h -1 VFR waste = 72 m 3.h -1 4.2 86 87 88 89 90 91 92 93 94 Waste heat temperature [ C] Figure 7. COP of the heat pump versus VFR and temperature of waste heat The present heat pump for industrial heat recovery presents high performance highly depending on waste heat temperature and process temperature to satisfy. The presented heat pump can recover waste heat from 85 C to 95 C to satisfy heat demand at higher temperature level attaining a condensing temperature of 145 C.

2108, Page 8 5. CONCLUSION High temperature heat pumps offer a great potential for recovering waste heat generated by several industrial applications. A high temperature heat pump using water as refrigerant is designed and built to be tested on a laboratory test bench that reproduce the operating conditions of real case industrial applications. This heat pump is an electrically-driven vapor compression closed-cycle type, using a newly developed twin screw compressor. This new heat pump generates vapor by flash evaporation. A purging valve is implemented at the top of the accumulator in order to eliminate noncondensable gases from the installation. Since a substantial amount of air will have to be removed upon start-up phase of the heat pump, preliminary experimental results has been presented showing the uniqueness of using this design of heat pumping specific for water vapor. COP is calculated showing generally good energy performance and high environmental benefits. NOMENCLATURE COP Coefficient of performance (-) T Temperature ( C) T Temperature difference (K) VFR Volume flow rate (m 3.h -1 ) REFERENCES Chamoun, M., Rulliere, R., Haberschill, P., Berail, J.F., 2012. Dynamic model of an industrial heat pump using water as refrigerant, Int. J. Refrig., vol. 35, no. 4: p. 1080-1091. Chamoun, M., Rulliere, R., Haberschill, P., Berail, J.F., 2011. Water Vapor as refrigerant for a new high temperature heat pump. In: Proceedings of the 23th International Congress of refrigeration (Prague), Paper no.178. Dupont, M., Sapora, E., 2009. The heat recovery potential in the French industry: which opportunities for heat pump systems? ECEEE Summer Study, La Colle sur Loup, Côte d'azur, France, p. 1115-1123. EDF R&D, 2009. EDF R&D, EPI Department. Internal data, reports and documents. FY Program, 2010. US Department of Energy, Energy efficiency and Renewable Energy, Industrial technologies program, Save energy now http://www1.eere.energy.gov/industry/saveenergynow/pdfs/sen_fy2010_program_developments. pdf. James M. Calm, 2008. The next generation of refrigerants- Historical review, considerations and outlook, Int. J. Refrig., 31, 1123-1133. Kilicarslan, A., and Müller, N., 2005. A comparative study of water as a refrigerant with some current refrigerants, International Journal of Energy Research, 29, 947-959. Lachner, Brandon., Jr., Gregory, F.Nellis, Douglas T Reindl. 2007. The commercial feasibility of the use of water vapor as a refrigerant, Int. J. Refrig., 30, 699-708. US Department of Energy, 2003. Energy efficiency and Renewable Energy, Industrial heat pumps for steam and fuel saving, http://www1.eere.energy.gov/industry/bestpractices/pdfs/heatpump.pdf Van Orshoven, D, 1991. The use of water as a refrigerant - an exploratory investigation, These MS, by (U of Wisconsin-Madison). Wight, S.E, Yoshinaka, T., Le Drew, B.A., D Orsi N.C., 2000. The efficiency limits of water vapor compressors. Report for air-conditioning and Refrigeration Technology Institute.