R32 Compressor for Air conditioning and Refrigeration applications in China

Similar documents
Study of R161 Refrigerant for Residential Airconditioning

Low GWP Refrigerants for Air Conditioning Applications

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Purdue e-pubs. Purdue University

Control Method Of Circulating Refrigerant Amount For Heat Pump System

Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Performance Comparison of R32, R410A and R290 Refrigerant in Inverter Heat Pumps Application

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Experimental Investigation on the Performance of Ground-source Heat Pump with the Refrigerant R410A

Development of R744 Two Stage Compressor for Commercial Heat Pump Water Heater

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

Experimental Study of Fouling Performance of Air Conditioning System with Microchannel Heat Exchanger

Development of an Open Drive Scroll Compressor for Transportation Refrigeration

Evaluation and Optimization of System Performance using HFO-mix Refrigerants for VRF and Mini-split Air-Conditioner

Performance Evaluation of Heat pump System using R32 and HFO-mixed Refrigerant in High Ambient Temperature.

TEST REPORT #14. System Drop-In Test of Refrigerant Blend ARM-42a in an Air-Cooled Screw Chiller

TEST REPORT #65. Compressor Calorimeter Test of Refrigerant L-41-2 (R-447A) in a R-410A Scroll Compressor

Design and Research of the Commercial Digital VRV Multi-Connected Units With Sub-Cooled Ice Storage System

TEST REPORT #4. Travis Crawford Dutch Uselton. Lennox Industries Inc Metrocrest Drive Carrollton, TX 75006

Comparison Of Hermetic Scroll And Reciprocating Compressors Operating Under Varying Refrigerant Charge And Load

The Design Of A New Generation Of Twin Screw Refrigeration Compressors

A study of high efficiency CO2 refrigerant VRF air conditioning system adopting multi-stage compression cycle

Higher Efficiency, Lower Sound, and Lower Cost Air Conditioning Compressors: Part 1 Efficiency

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

TEST REPORT #47. System Drop-in Test of R-32 and Refrigerant Blends ARM-71a, HPR2A, L-41-2 and DR-5A in a Five-Ton R-410A Rooftop Packaged Unit

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid

Evaluation of HCFC Alternative Refrigerants

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Application Engineering

TEST REPORT #34. Compressor Calorimeter Test of Refrigerant DR-7 in a R-404A Scroll Compressor

Efficiency of Non-Azeotropic Refrigerant Cycle

Scroll Compressor for Mobile HVAC/R Application

Sub-Critical Operation of the CO2 Expander/ Compressor

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Effect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Airconditioning

Performance Measurement of R32 Vapor Injection Heat Pump System

TEST REPORT #53. System Drop-in Test of Refrigerant Blend DR-55 in a Five-Ton R-410A Rooftop Packaged Unit

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

TEST REPORT #43. System Drop-in Tests of Refrigerants L-41-1, L-41-2, and R-32 in Water-to- Water Heat Pump

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

TEST REPORT #32. System Soft-Optimized Test of Refrigerant D2Y60 in Air Source Heat Pump

Systematic Study of the Solution Properties of Low Global Warming Potential R-404A Replacement Refrigerant Blends with Various Polyol Ester Lubricants

Air-Cooled Heat Exchanger Performance for R410A

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

Low GWP Refrigerants for Air Conditioning and Chiller Applications

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Executive Summary. Number of Low Number of High Number of Faults , Number of OK

Purdue e-pubs. Purdue University. T. Hamada Mitsubishi Heavy Industries Ltd. N. Nishiura Mitsubishi Heavy Industries Ltd.

High Efficiency R-134a Compressor for Domestic Refrigerator

Development Of 2-Cylinder Rotary Compressor Series For Light Commercial Use With R410A

Enhancement of the Separate Sensible and Latent Cooling Air-Conditioning Systems

Experimental Investigation of a New High Temperature Heat Pump Using Water as Refrigerant for Industrial Heat Recovery

Performance of CO2 Cycles with a Two-Stage Compressor

The Innovative Green Technology for Refrigerators Development of Innovative Linear Compressor

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Modelling of an Integrated Supermarket Refrigeration and Heating System Using Natural Refrigerants

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Selection of a refrigeration oil for the R32 refrigerant and evaluation of the compressor reliability

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

Dynamic Simulation of Liquid Chillers

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Alternative Refrigerants For Household Refrigerators

Comparison of the High Side vs

Oil Return Measurements In A Unitary Split System Air Conditioner Using Different Refrigerant Mixtures

2016 Annual Conference

Load Sharing Strategies in Multiple Compressor Refrigeration Systems

Development of HFC-134a Compressor for Domestic Refrigerator

New High Performance, Low GWP Refrigerants for Stationary AC and Refrigeration

Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION

EXPERIMENTAL STUDY ON R1234YF HEAT PUMP AT LOW AMBIENT TEMPERATURE AND COMPARISON WITH OTHER REFRIGERANTS

Figure 1: Schematic of internal heat exchanger vapor-injection cycle

System Modeling of Gas Engine Driven Heat Pump

Comparison of Energy Efficiencies of Commercial Refrigeration Direct and Indirect Systems

System Using Exhaust Heat from Residential GHPs

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

ASSESSMENT OF R430A REFRIGERANT AS A POSSIBLE SUBSTITUTE TO R134A REFRIGERANT IN LARGE CAPACITY FREEZER

R-404A Alternative with Low Compressor Discharge Temperature

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

A Performance-Enhancing Additive for Vapor- Compression Heat Pumps: Additional Test Results

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

A Comparison Between Refrigerants Used In Air Conditioning

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

Experimental Study on Compact Heat Pump System for Clothes Drying Using CO 2 as a Refrigerant. Abstract

Simulation of the Working Process of an Oil Flooded Helical Screw Compressor with Liquid Refrigerant Injection

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Study of R-161 refrigerant as an Alternate Refrigerant to various other refrigerants

Analysis of Oil Pumping in the Hermetic Reciprocating Compressor for Household Refrigerators

Transcription:

Purdue University Purdue e-pubs International Compressor Engineering Conference School of Mechanical Engineering 2012 R32 Compressor for Air conditioning and Refrigeration applications in China Weihua Guo warner.guo@emerson.com GaoFeng Ji Honghong Zhan Dan Wang Follow this and additional works at: http://docs.lib.purdue.edu/icec Guo, Weihua; Ji, GaoFeng; Zhan, Honghong; and Wang, Dan, "R32 Compressor for Air conditioning and Refrigeration applications in China" (2012). International Compressor Engineering Conference. Paper 2204. http://docs.lib.purdue.edu/icec/2204 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

R32 Compressor Development for Air Conditioning Applications in China Weihua Guo, Gaofeng Ji, Honghong Zhan, Dan Wang Emerson Climate Technologies (Suzhou) R&D Center Emerson Building, International Science Park 1355 Jinjihu Avenue, Suzhou Industrial Park Jiangsu 215021, P.R.China ABSTRACT This paper evaluates the compressor performance and reliability impact by using R32 refrigerant for air conditioning (residential and commercial system); Performance and reliability impacts are compared with different popular refrigerants used in China, for example, R410A & R22 for AC. The design improvement on the scroll compressor will be discussed in order to reach required efficiency and reliability; these improvements include lubrication, internal heat management, motor design, and vapor injection technologies, etc. Key words: Refrigerant, R32, Oil, Vapor Injection, Performance, Reliability 1. INTRODUCTION HCFCs refrigerant R22 as the representative of its damage to the ozone layer has been identified, and there is restrictions on the use and required to be eliminated within a certain period. In China, a lot of efforts have been put to make R32 a substitute for R22. The theoretical volume cooling capacity of R32 is higher than R410A, and its price is low. R32 is with good prospects of application; its lower cost in China provides incentive for investing development time for mitigating its disadvantages through compressor and system design optimization. Because R32 and R410A have very similar thermal property, R410A compressor is taken as a baseline. Through theoretical calculation and initial drop-in test, it seems R32 offers more advantage than disadvantage over R410A, for example, lower liquid density results in lower system charge; lower system mass flow leads to lower pressure drop; higher liquid thermal conductivity leads to higher heat transfer coefficient; etc. Meanwhile, the compressor development mainly focus on solving the higher discharge temperature issue as well as developing new POE oil for R32 application. By far the effective results have been achieved. This paper will review future R32 compressor design with improved performance and enhanced reliability. In this paper, a real China R32 system test has been introduced, and the further system design improvement is discussed. 2. Scroll Compressor Performance Comparison - R32 v.s. R410A R410A is taken as a baseline for all the analysis and comparison for R32 in this discussion. 2.1 Theoretical Performance Analysis Figure 1 shows respectively the comparisons between theoretical volumetric capacity and energy efficiency ratio (TEER) of R32 over R410A at ARI condition. The testing set up is based upon standard 20Ksuperheat and 15K subcooling per AHRI 540 standard, while assuming equal volumetric and equal overall isentropic efficiency at ARI. All the properties of R32 and R410A are cited from the NIST software REFPROP7. 1

Figure 1: PH Diagram Comparison R32 v.s. R410A at ARI Condition As the diagram shows, in theory, R32 has 11% higher capacity and 3% higher efficiency at ARI rated condition. The relative gains will be increased when the Te (Saturated Evaporating Temperature) and the Tc (Saturated Condensing Temperature) is getting higher. Figure2 and Figure3 show the theoretical capacity and EER under the different operating conditions. As the diagram shows, the capacity and EER ratio of R32/R410A increases when the condensing temperature increase. It indicates the gains on both capacity and EER at high condensing temperature conditions for R32 compressor is more than R410A compressor. Figure 2: Comparison of Theoretical EER Figure 3: Comparison of Theoretical Performance 2.2 Compressor Drop in Test Comparison - R32 v.s.r410a Considering the working pressure of R32 and R410A is comparable, a R410A optimized compressor was employed to do the drop in test at ARI condition. The test result is shown in table 1. 2

Table1: Compressor drop-in test At ARI condition Model Refrigeration Capacity Power EER DLT Unit kw kw W/W C/ K R410A 6.5 2.2 3.0 94 3HP R32 6.9 2.3 3.0 119 R32/R410A 5.7% 7.2% 0.0% 25 R410A 12.7 4.0 3.2 93 5HP R32 13.5 4.3 3.2 115 R32/R410A 6.3% 7.5% 0.0% 22 R410A 35.1 10.8 3.3 93 12HP R32 36.9 11.5 3.2 115 R32/R410A 4.8% 6.4% -3.0% 22 As the diagram shows, on average, the tested R32 compressor capacity is 6% lower than the theoretical calculation. It is mainly because of higher suction super heat. The higher polytrophic exponent and the lower mass flow are the major two facts to cause higher suction superheat, therefore results in volumetric efficiency reduction. 31% lower mass flow has been observed during the testing, which is believed to be the primary reason why the discharge line temperature is higher than R410A. Correspondingly, on average, the tested compressor EER is about 3-4% lowers than theoretical calculation due to lower overall isentropic efficiency. It is expected that the compressor capacity and efficiency will get worse at higher compression ratio conditions. 2.3 Design Improvement Opportunity for Performance Enhancement 2.3.1 EVI Technology Enhance Vapor Injection (EVI) is an effective approach for R32 compressor performance improvement. As shown in Table 2, the actual capacity and EER for a 10-ton scroll compressor at have 15% capacity gain at cooling condition, and 20% capacity gain at heat pump condition, respectively, while 7-9% efficiency gain at both conditions. Table 2: EVI On/Off Comparison Test 2.3.2 Scroll Element Optimization DLT: Discharge Line Temperature Refrigerant ET/CT C/ C EVI Capacity Power EER DLT Capacity EER kw kw W/W C Gain Gain R32 7/54 Off 33.9 11.0 3.1 118 R32 7/54 On 39.1 11.8 3.3 102 15% 7% R32-12/32 Off 21.3 6.4 3.3 103 R32-12/32 On 25.6 7.0 3.6 92 20% 9% ET: Evaporating Temperature, CT: Condensing Temperature, DLT: Discharge Line Temperature Considering different thermodynamic properties of R32 and R410A, the design optimizations for R32 scroll sets are needed. Firstly, the scroll suction inlet is to be optimized to get lower suction superheat. Secondly, scroll wrap is to be designed to take care of higher R32 running temperature. Drop-in test shows those two improvements are effective. 3

3. R32 Scroll Compressor Reliability Higher loads have been observed in a R32 scroll compressor. Meanwhile, the high discharge line temperature is a concern to compressor reliability. New technologies and design improvements have been assessed as show below. 3.1 Lubricant Many POE oils are widely used in R410A applications. However, it is not suitable for R32 application due to the miscibility issue as shows in Figure 4. Clearly, the POE oil A does not meet the needed miscibility requirements for R32 applications. Figure 4: Oil Miscibility Diagram POE Oil B is a newly-developed oil for R32. It has passed all the bench tests and compressor reliability tests (Table 3). The new POE oil B significantly reduces the wear at the inner wrap of the scroll sets in the compressor. With the vapor injection technology, the new oil performs the best in terms of wear resistance characteristics. Table 3: R32 Compressor Reliability Result with Different Oil 4

3.2 Discharge Line Temperature Control As discussed previously, the R32 compressor has higher compressor discharge temperature compared to other refrigerants. This challenge is to be addressed before launch R32 product to market. Several design changes has been deployed to lower the discharge temperature; however, there are trade-offs between compressor efficiency and reliability. As Table 2 shows, Enhanced Vapor Injection is an effective approach to control discharge temperature. An acceptable discharge temperature could be set by controlling vapor injection flow rate. Liquid injections into the scroll pockets or compressor suction line are alternatives to control discharge temperature; however, by using liquid injection, the performance penalty will be anticipated, as power consumption will increase and efficiency will decrease. A big part of the increased discharge temperature in a R32 compressor v.s. a R410A compressor is due to the increased suction superheat. Because of lower mass flow, R32 suction gas is easier to be heated up by motor inside, especially in a low-side compressor. As one of the solutions, a design change is deployed to shorten the distance between the compressor suction line and scroll set suction inlet, which results in the superheat reduction by 20-30K. When testing on different working conditions, more reduction on suction superheat at lower mass flow condition has been observed. Meanwhile, R32 scroll set is to be designed at a higher build-in volume ratio in order to reduce the recompression heat and lower discharge temperature under high compression ratio condictions. Table 4 is shown, with better internal heat management and higher volume ratio design scroll, more than 25K discharge temperature reduction is observed. It is expected to get more benefits at higher compression ratio conditions. Table 4: Discharge Temperature Reduction with Different System Pressure Compression Ratio Due to lower mass flow in R32 compressor and system, at any low mass flow condition, for example, low ambient heating application, the compressor is easily getting higher discharge line temperature and it put risk on compressor reliability. At such condition, the lubricant oil quantity sucked by scroll set becomes not enough for sealing and lubrication. One technology developed by Emerson Climate Inc. is deployed to increase oil quantity in scroll set to reduce scroll internal leakage, therefore reduce discharge temperature and improve compressor performance as well. In Table 5, with more oil put into the scroll set, more than 8K discharge temperature reduction is observed and also with 5% performance gain in low mass flow condition. Table 5: Discharge Temperature Reduction & EER Improve With More Oil Circulation Rate in Scroll Set 5

4. R32 System Performance with Enhanced Vapor Injection Technology Although many different compressor technologies have been discussed in above chapters, EVI (Enhanced Vapor Injection) has magnificent advantage over rest of the technologies, in terms of system capacity as we as EER/COPs. Hereby we will discuss a typical Chinese 65kw chiller system test with two10hp EVI compressors. 4.1 System Configuration Normally, a typical chiller system includes an EVI compressor, a water heat exchanger and an air heat exchanger, a TXV or an EXV,an accumulator and a receiver. What s more, for EVI system, an economizer heat exchanger is deployed to inject vapor. Schematic is showed as Figue5. Figure5: Vapor Injection System Schematic 4.2 System Test Data This is a drop-in test to a typical Chinese R410A system with some modifications made according to R32 compressor. Two pieces of R410A compressors were replaced by two pieces 10HP R32 EVI scroll compressors with EVI function. And an economizer was added which includes a heat exchanger and an EXV. System refrigerant charge amount is optimized. The comparison tests between EVI on and EVI off were done in an enthalpy test lab. The test condition follows GB18430.1-2007 standard and it showed in table 6. Figure 6 and 7 show capacity and EER comparison respectively, in different conditions. 6

Table 6: Chiller system test conditions T indoor Temp. T outdoor Temp. Test Condition T water_out T outdoor_dry T outdoor_wet ( C) ( C) ( C) Rated Cooling 7 35 - Max Cooling 15 43 - Rated Heating 45 7 6 Max Heating 50 21 16 Figure6: Capacity Comparison Figure7: EER Comparison Figure 6 shows capacities increased by 11% with EVI on in cooling condition and 16%~19% gain in heating condition. In other words, with EVI technology, a smaller compressor can be used. Figure 7 shows EER with EVI on is 0.6% lower than EVI off in cooling condition. Because condenser Temperature for EVI on is about 1 K higher than EVI off, it caused more power. However, in heating condition, 2.5%-7.5% EER gain observed. In summary, EVI Compressor showed more Benefits on cooling and heating capacity and heating EER. 4.3 System Design Optimization R32 EVI system design could be based upon a similar R410A system. To obtain a better performance and system reliability, some system design changes are needed. For example, heat exchanger of water side and air side are both needed to be optimized for EVI system. The R32 system charging amount also needs to be optimized which should be smaller than original R410A system charging. The economizer EXV control should be set to maintain a safety discharging temperature. Wet injection could be needed under high system compression ratio. Besides, the design of key system components, such as compressor and expansion device, should be modified or re-designed according to R32. 7

5. Conclusions Base upon above studies, R32 could be a cost-effective, Low-GWP/Low-LCCP refrigerant solution for China s air conditioning applications. Among all different R32 compressor technologies, vapor injection technology has inherent advantages on both efficiency and reliability. It provides 7~9% efficiency gain at rated heating, while comparable efficiency at rated cooling condition, comparing to non-injection technology. Through EVI technology, the ability to controlled discharge temperature has been enhanced. However, considering diversity of China s air conditioning systems and the sensitivity on system cost, managing discharge temperature without injection is attractive for R32 system builders. As third alternative, liquid injection is another solution. Although liquid injection has less cost adder to EVI system, it potentially has performance penalty. REFERENCES 1. The Air Conditioning, Heating and Refrigeration Institute (AHRI) Alternative Refrigerants Evaluation Program, CD Volumes I & II reports (1992-1997), report 196 2. Leck T., Property and Performance Measurements of Low GWP Fluids for AC and Heat Pump Applications, 23rd IIR Congress of refrigeration, Prague Czech Republic, Aug. 2011 3. Zhou Yingtao, Liu Zhongshang, Application experimental study of R32 refrigeration compressor for airconditioning, Refrigeration and Air-conditioning, April 2011 4. Mei Kui, Li Ming, Liang Lujun, Comparative research on the cycle performance of R32 and R410A, Refrigerantion and Air-conditioning, April 2011 5. Ruzaburo Yajima, Atushi Yoshimi, Chuncheng Piao, measures to reduce the discharge temperature of R32 compressor, Refrigeration and Air-conditioning, April 2011 6. GB18430 1-2007 8