FIRE PROTECTION FOR NON-STORAGE OCCUPANCIES WITH HIGH CEILING CLEARANCES

Similar documents
High Ceiling Protection

Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings

The Effect of Large Orifice Sprinklers on High-Challenge Fires

Evaluation of Protection for Plastic Containers Using Sprinkler Systems with 1.0% AFFF and Plain Water

RESEARCH TECHNICAL REPORT. SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale Fire Tests in Rack Storage

The Loss prevention Council. Phase 1 report

Factors Affecting Efficiency of Water Mist Suppression of Solid Combustible Fires in Open Environment

Significant Advancements in Water Based Fire Suppression for Storage Occupancies

Storage Protection Using Horizontal Barriers and Large K-Factor, Extended Coverage In-Rack Sprinklers

Today's Topics & Sustainability Themes

SPRINKLER TECHNOLOGY:

Warehouse Protection of Exposed Expanded Group-A Plastics with Electronic Sprinkler Technology

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS

Impact of a High Volume Low Speed Fan on Sprinkler Performance in Rack Storage Fires

J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441

Thermal Sensitivity Evaluation of Recessed, Flush and Concealed Sprinklers

IMO. 4 June 1999 GUIDELINES FOR THE APPROVAL OF ALTERNATIVE FIXED WATER-BASED FIRE-FIGHTING SYSTEMS FOR SPECIAL CATEGORY SPACES

An experimental study of the impact of tunnel suppression on tunnel ventilation

RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN

Obstructions and ESFR Sprinklers Phase 2 FINAL REPORT

Table EXIT ACCESS TRAVEL DISTANCE a OCCUPANCY SYSTEM SYSTEM. A, E, F-1, I-1, M, b,d R, S-1. B c. F-2, S-2, U c

COSTCO, SAN FRANCISCO A PRESCRIPTIVE AND PERFORMANCE BASED ANALYSIS OF FIRE PROTECTION SYSTEMS AND DESIGN

David P. Nugent Schirmer Engineering Corporation 707 Lake Cook Road Deerfield, Illinois SUMMARY

Spray sprinkler system

International Water Mist Conference, Istanbul October 22-23, 2014 The background and development of the guidelines in IMO Resolution A.

ASSESSMENT OF FIRE BEHAVIOUR OF TIMBER PARTITION MATERIALS WITH A ROOM CALORIMETER

RESOLUTION MSC.265(84) (adopted on 9 May 2008) AMENDMENTS TO THE REVISED GUIDELINES FOR APPROVAL OF SPRINKLER SYSTEMS EQUIVALENT TO THAT REFERRED TO

RESEARCH TECHNICAL REPORT. SMART Sprinkler Protection for Highly Challenging Fires Phase 1: System Design and Function Evaluation

Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers

Series ELO K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage General Description

ESFR sprinkler system

Storage Sprinkler U.S. Quick Reference Guide

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL /

Considerations in the Design of Smoke Management Systems for Atriums

TECHNICAL DATA. * Refer the Approval Chart on page 120c and Design Criteria on page 120d for culus and FM approval requirements that must be followed.

TECHNICAL DATA OBSOLETE

Sprinkler Solutions for Storage Applications

Chapter 17, Initiating Devices

Large-scale fire sprinkler tests with the AutoStore compact storage system

standard response elo upright and pendent sprinklers (storage-density/area)

Requirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011

Model ESFR K-factor Pendent Sprinkler Early Suppression, Fast Response General Description. Sprinkler Identification Number (SIN)

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL /

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL /

Protection of Storage Under Sloped Ceilings Phase 2 Full Scale Test Matrix

RESEARCH TECHNICAL REPORT. Development of Protection Recommendations for Li-ion Battery Bulk Storage: Sprinklered Fire Test

Fire Spread in Large Industrial Premises and Warehouses

TECHNICAL DATA OBSOLETE. * Refer the Approval Chart on page 121c and Design Criteria on page 121d for FM approval requirements that must be followed.

RESEARCH TECHNICAL REPORT. Numerical Simulations of Sprinkler Activations and Spray Transport under Obstructed, Sloped Ceilings

NFPA 30 FLC-SWC Public Comment Report

Using FDS Modelling to Establish Performance Criteria for Water Mist Systems on Very Large Fires in Tunnels

REVISED GUIDELINES FOR THE DESIGN AND APPROVAL OF FIXED WATER-BASED FIRE-FIGHTING SYSTEMS FOR RO-RO SPACES AND SPECIAL CATEGORY SPACES

High challenge warehouse case study Summary

PRELIMINARY STUDIES ON MECHANICAL SMOKE EXHAUSTS IN LARGE SPACE BUILDING FIRES

Early Suppression Fast Response Sprinklers and Obstructions

Storage Sprinkler. Model LP-46 (SIN) V4603, K25, Standard Response Storage Upright Sprinkler, Patent Pending

E x t E N d e d Co v e r ag e S p r i n k l e r s. Office Buildings Hotels Hospitals Libraries. High-Piled Storage Big-Box Retailing

Model JL-14 (SIN RA1812) K14.0 (200 metric) Early Suppression Fast Response Sprinkler

esfr pendent sprinkler vk510 (k25.2)

ASHRAE JOURNAL ON REHEAT

Box-in-Box Cold Storage Fire Protection Options

Obstructions and ESFR Sprinklers Phase 1

Indicative hoarding fire experiment. Prepared for: London Fire Brigade. 21 May 2014 Client report number

Experiments to Validate the NRCC Smoke Movement Model for Fire Risk-Cost Assessment

Construction Warehouse. FPE 596 Culminating Experience In Fire Protection Engineering Final Project (Spring 2014) By Ben Johnson

TECHNICAL DATA. * Refer the Approval Charts and Design Criteria on pages 3-5 for culus Listing and FM Approval requirements that must be followed.

Series ELO-231 Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

The Situation. Modeling Storage Occupancies Under Sloped Ceilings. Concerns (Elevation View) The Concerns 4/29/ NFPA Conference & Expo

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

Hazardous Material Safety Program

5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea

ESFR PENDENT SPRINKLER VK510 (K25.2) TECHNICAL DATA

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

Sprinklers Modeling for Tunnel Road Fire Fighting

ESFR PENDENT SPRINKLER VK500 (K14.0) TECHNICAL DATA

NEW CD WARP CONTROL SYSTEM FOR THE CORRUGATING INDUSTRY

STORAGE FIRE PROTECTION SPRINKLERS

ESCUTCHEON PLATE SEATING 3/4" NPT SURFACE. 1-1/2" (38,1 mm) CROSS SECTION PENDENT RECESSED PENDENT

Explosion Protection of an Armoured Vehicle Crew Compartment with Water Mist. Andrew Kim and George Crampton

A Monte Carlo Approach for the Design of Thermal Fire Detection System

esfr pendent sprinkler vk510 (k25.2)

A sprinkler operates automatically when the heat-actuated element is heated to, or above, its thermal rating.

Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers

Smoldering Propagation Characteristics of Flexible Polyurethane Foam under Different Air Flow Rates

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Flat-Plate Concealed Pendent Wet Pipe and Dry Pipe Systems General Description

WRENCH FLATS NPT 1/2" 7/16" (11,1 mm) NOMINAL MAKE-IN. 1-1/2" (38,1 mm) 2-3/16" (55,6 mm) WRENCH NPT. (12,7 mm) NOMINAL MAKE-IN.

Standard response. elo sprinklers

Brine Generation Study

Series ELO-231B 11.2 K-factor Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

TECHNICAL DATA NOTICE

Reported Fires in High-Rise Structures in Selected Occupancies with and without Automatic Extinguishing Systems by Extent of Smoke Damage

Conductive Heating Technologies for Medical Diagnostic Equipment. Russell Strehlow, Manager of Research and Development, Minco

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright and Pendent Extended Coverage Light and Ordinary Hazard General Description

How to know if a residential or domestic water mist system is performance compliant to BS 8458:2015?

Modeling of Sprinkler, Vent and Draft Curtain Interaction

Case Study 1 Underground Car Park

RAPID RESPONSE Series LFII Residential Sprinklers 5.8 K-factor Horizontal Sidewall, NFPA 13 Optimized Wet Pipe Systems

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT UPRIGHT SPRINKLER VK535 (K11.2) TECHNICAL DATA

Non-Storage / Special Protection / Storage Sprinklers

Transcription:

FIRE PROTECTIO FOR O-STORAGE OCCUPACIES WITH HIGH CEILIG CLEARACES SOOIL AM, ATOIO BRAGA, HSIAG-CHEG KUG, and JOA M. A. TROUP FM Global Research, 1151 Boston-Providence Turnpike, orwood, Massachusetts 02062, U. S. A. ABSTRACT Five large-scale fire tests were conducted to determine sprinkler protection requirements for non-storage occupancies with floor-to-ceiling clearance up to 18.3 m. Examples of high-ceiling, non-storage occupancies are atrium spaces, movie theaters/studios, auditoriums, and some selected manufacturing facilities. The fire tests were conducted at a 18.3-m high test site using fuel arrays that were designed to simulate ordinary hazard fire scenarios. Sprinkler protection parameters and fuel arrangements were varied in the tests. The tests showed that:1) the sprinklers would provide adequate protection for these occupancies despite a clearance as high as 16.6 m from the top of the fuel stacks to the ceiling, 2) protection based on a 12-mm/min discharge density over a 465-m 2 demand area was judged adequate for fire hazards equivalent to a FMRC Class 3 Commodity, 3) protection based on a 6-mm/min discharge density over a 232-m 2 demand area was adequate for fire hazards up to a Class 2 Commodity, 4) protection based on QR-ELO sprinklers delivering a 18-mm/min discharge density over a 232-m 2 demand area would provide adequate protection for high-ceiling occupancies exposed to a limited amount of plastic materials. Sprinkler skipping, extended sprinkler spacing, and protection of an occupancy with a ceiling higher than 18.3 m remain as subjects needing further study. KEY WORDS: high ceiling clearance, non-storage occupancies, sprinkler protection 1. ITRODUCTIO on-storage occupancies are defined here as occupancies containing potential fuel stacks that are lower than 3 m. The ceiling clearance is defined as the distance between the top of the fuel stacks and ceiling. Examples of non-storage occupancies with high ceiling clearance are atrium spaces, movie sound stages/studios, exhibit halls, auditorium and sports areas, and various manufacturing facilities. There was a concern for whether or not the automatic sprinklers, which were installed on such a high ceiling, would actuate early enough to affect fire control. Some even doubted if the sprinklers would ever actuate. Since there are no clear guidelines pertaining to protection for this type of occupancy, a few untested protection schemes have been widely applied without knowledge of their adequacy. Thus, research was needed to develop guidelines for automatic sprinkler protection for non-storage occupancies with high ceiling clearances. Five full-scale fire tests were conducted at the 18.3-m high test site in the FM Global Test Center, West Glocester, Rhode Island, USA. The Test Center had a 61 m by 76 m test area under a continuous flat horizontal ceiling. All the doors and windows were closed FIRE SAFETY SCIECE--PROCEEDIGS OF THE SEVETH ITERATIOAL SYMPOSIUM, pp. 493-504 493 Copyright International Association for Fire Safety Science

during the tests and no forced ventilation was provided. The tests were designed to provide guidelines for protection of high ceiling clearance, non-storage occupancies that may contain fire hazards equivalent to those ranging from the Factory Mutual Research Corporation (FMRC) Class 2 Test Commodity through the FMRC Cartoned Unexpanded Group A Plastic Test Commodity. The fuel arrays were designed to simulate ordinary hazard fire scenarios. Sprinkler protection parameters that are commonly found at FM Global insured high-clearance, non-storage occupancies were used as the baseline conditions in the tests[1]. 2. FIRE TEST PARAMETERS 2.1 Test Fuels The FMRC Standard Class 2 Commodity served as the fuel in Tests 1 and 2. The commodity consists of a 1.07-m cube, double, triwall corrugated paper carton containing an open bottom sheet metal liner. The cartons have a combined nominal 25 mm thickness. Each fuel stack consisted of two double-up cartons (each x x high) supported on a wood pallet. The FMRC Standard Plastic Test Commodity served as the fuel in Tests 3, 4 and 5. The Cartoned Unexpanded Group A Plastic Commodity consists of 125 empty polystyrene cups packaged in compartmented, single wall, corrugated paper cartons. Each fuel stack consisted of twelve cartons (each 0.53 m x 0.53 m x 0.53 m high) placed on a wood pallet. (See Fig. 1.) (ot to scale) Wood Pallet (0.13 m high) 2.13 m Elevated Platform (0.69 m high) 1.6 m Tests 1 and 2 Tests 3, 4 and 5 (no platform in Tests 4 and 5) Fig. 1 Side views of fuel arrays used in the tests. 2.2 Fuel Array Arrangements The height of the fuel stacks in Tests 1 and 2 was 2.26 m and that in Tests 3, 4 and 5 was 1.73 m. Since the fuel stacks were placed on a 0.69 m high platform in Tests 1 through 3, the clearance from the top of the fuel arrays to the ceiling was 15.4 m in Tests 1 and 2 and 15.9 m in Test 3; Without the platforms, the clearance was 16.6 m in Tests 4 and 5. The top view of the fuel array, 64 stacks of commodity arranged 8 by 8, used in Tests 1 and 2 is given in Fig. 2. Stacks were separated by 0.15 m flues. Tests 3 and 4 used a different fuel array configuration. The top view of the three-row array is given in Fig. 3. Sixteen stacks of the plastic commodity, arranged 2 by 8, comprised the main fuel array. There were two target arrays, each single six-stack row, 1.5 m apart from the main fuel 494

array. Adjacent stacks were separated by 0.15-m flues. Test 5 used the same fuel array as in Tests 3 and 4, but different sprinkler locations; the top view is shown in Fig. 4. 0.15 m (ot to scale) 0.15 m 9.6 m E 9.6 m Sprinkler Location Ignition Location Fig. 2 Plan view of fuel array used in Tests 1 and 2. 2.3 Sprinkler Protection Automatic sprinkler protection in all the tests was provided by upright sprinklers installed 165 mm below the ceiling. The temperature rating of the sprinklers used in Tests 1 through 3 was 74 o C and the Response Time Index (RTI) was 138 (m-s) 1/2. The temperature rating of the sprinklers used in Test 4 was 68 o C and RTI was 28 (m-s) 1/2. The temperature rating of the sprinklers used in Test 5 was 74 o C, and RTI was 28 (ms) 1/2. In Tests 1 and 3, nominal 13.5 mm orifice sprinklers supplying a 12-mm/min discharge density were used. In Test 2, nominal 12.7 mm orifice sprinklers supplied a 6-mm/min discharge density. In Test 4, nominal 16.3 mm orifice Quick Response, Extra Large Orifice (QR-ELO) sprinklers supplied a 18-mm/min discharge density. In Test 5, nominal 25.4 mm orifice Quick Response, Extended-Coverage Control-Mode sprinklers supplied a 18-mm/min discharge density. The sprinkler spacing in Tests 1 through 4 was 3 m by 3 m, and that in Test 5 was 6.1 m by 6.1m. 495

2.4 Ignition Method Two FMRC standard full igniters, 76-mm dia. x 152-mm long cellucotton rolls, each soaked in 236 ml of gasoline and enclosed in a plastic bag, served as the ignition source. The igniters were located in the center flue of each fuel array along the east-west direction. The ignition location was centered below a single ceiling sprinkler as shown in Figs. 2, 3 and 4. As the test program progressed, the sprinkler skipping turned out to be one of the most dominant parameters determining the efficacy of sprinkler protection. As the ignition directly under one sprinkler tends produce a more severe skipping than the other ignition locations do, it was rationalized that ignition directly under one sprinkler would provide a more conservative fire scenario than other ignition locations. (ot to scale) 0.15 m 0.15 m 7.16 m 9.6 m 1.5 m 1.5 m E Sprinkler Location Ignition Location Fig 3 Plan view of fuel array used in Tests 3 and 4 2.5 Instrumentation Sixty-four ceiling sprinklers in an 8 by 8 pattern were installed with timing mechanisms to monitor their opening sequence. Additionally in Tests 1 through 3, three fast response sprinkler links were attached to uncharged sprinklers. One fast response link, denoted as QR1, was adjacent to the center sprinkler. Another, denoted as QR2, was adjacent to the sprinkler located 3 m east of the center sprinkler and the other, denoted as QR3, was adjacent to the sprinkler located 6 m east of the center sprinkler. The response time index 496

(RTI) of the fast response links was 28 (m-s) 1/2. They were installed to just show time responses without delivering any water. 0.15 m 0.15 m 9.6 m 7.16 m 1.5 m 1.5 m E Sprinkler Location (ot to scale). Ignition Location Fig. 4 Plan view of the fuel array used in Test 5. Twenty-three thermocouples were installed 165 mm below the ceiling to measure near ceiling gas temperatures in Tests 1 and 2. They covered up to 26-m distances in the north, east, south and west directions from the ignition location. In Tests 3, 4 and 5, the measurement locations for ceiling gas temperature were increased to 42. Thermocouple trees were installed to measure gas temperatures at six elevations from the floor---3 m, 6 m, 9.1 m, 12.2 m, 15.2 m, and 17.3 m. Tree A was placed at the center of the main fuel array over the ignition location. The data from Tree A would indicate the flame intensity before and after the sprinkler actuation. In Test 1, Trees B and C were placed, respectively, 1.2 m east and 1.2 m north of Tree A. In Tests 2 and 3, Trees B and C were placed 1.8 m east and 1.8 m north, respectively, of Tree A. In Tests 4 and 5, the locations of Trees B and C were moved to 3.2 m east and 3.2 m north, respectively, of Tree A. The temperature data recorded at Trees B and C 497

would provide indications of whether or not fire spread into fuel stacks beyond the center four ignition stacks. Five bi-directional differential flow probes were installed to measure the upward and the horizontal gas velocities generated by the fire plume. Two measuring locations were at Tree A at the 3-m and 9.1-m elevations above ignition. The other three locations were 0.15 m below the ceiling: one in the center flue aligned with Tree A; another 1.5 m south and 1.5 m east from the center; and the other 1.5 m south and 4.6 m east from the center. The mass loss history of the center four fuel stacks (2 by 2) was recorded by placing the stacks on a plate that was equipped with a load cell. 3. TEST HIGHLIGHTS AD RESULTS 3.1 Test 1 About 30 seconds after ignition, flames reached the tops of the fuel stacks. Flames reached at least 3 m above the top of the fuel array by 2 min. The quick response sprinkler link over ignition, QR1, actuated at 2 min 26 s and the first sprinkler actuated at 2 min 58 s. Quick response sprinkler link QR3, which was adjacent to the sprinkler located 6 m east from the first actuated sprinkler, responded at 4 min 51 s. The response of quick response link QR2, which was closer to the ignition source than QR3, was not recorded during the test. The second sprinkler actuated at 5 min 30 s, a considerably long time after the first one. Thirteen more sprinklers operated during the next 1½ minutes; and, the last, the fifteenth sprinkler, actuated at 7 min 3 s. The sprinkler opening sequence and the corresponding time of each actuation after ignition are given in Fig. 5. The dotted box represents the area covered by the fuel array. It should be noted that there was skipping of the entire second ring of sprinklers. Even with 15 operating sprinklers, temperatures measured at Tree A, which are shown in Fig. 6, indicated that the fire maintained the same intensity for a while. The first sign of diminishing flames was evident at 9 min. By then, the center four fuel stacks that were already engulfed in flames were being consumed, while pre-wetted fuel boxes hindered further fire spread. During the next few minutes, the fire continued to diminish and the test was terminated at 17 min. 3.2 Test 2 QR1 actuated at 1 min 46 s. The first sprinkler actuated at 2 min 28 s. QR3 actuated at 5 min. As in Test 1, the response of QR2 was not recorded. The second sprinkler actuated at 5 min 21 s, almost 3 minutes after the first actuation. Then, fifteen more sprinklers actuated within two minutes. A total of 17 sprinklers operated; the last one actuated at 7 min 20 s (see Fig. 7). Even with 17 operating sprinklers, the temperatures measured at Tree A seemed to suggest that the fire remained at the same intensity for quite a while. The first sign of diminishing flames was evident by 13 min. By then, the four center fuel stacks that were engulfed in flames were mostly consumed, while further flame spread was hampered because potential fuel was wetted. During the next 9 min, the fire gradually diminished and the test was terminated at 22 min. 498

3.3 Test 3 For many existing occupancies that are exposed to a limited amount of plastic materials, the previously used close stacking of the fuel stacks was deemed too conservative an arrangement. The fuel arrangement was thus modified as shown in Figs. 3 and 4. A double row of Plastic Commodity, 1.73 m high stacks, was used as the main fuel array. 13 12 5 15 11 3 10 1 14 2 9 6 8 7 4 Fuel Array Outline Sprinkler positions (3-m by 3-m spacing) Operated sprinklers: Total of 15. umbers correspond to opening sequence. Ignition location at base of array. Fig. 5 Plan view of sprinkler operations in Test 1. Operating Sequence Time (min:s) 1 2:58 2 5:30 3 5:31 4 5:41 5 5:43 6 5:45 7 5:46 8 5:53 9 5:54 10 5:55 11 6:00 12 6:10 13 6:24 14 6:54 15 7:03 Temperature ( o C) 1100 1000 900 800 700 600 500 400 300 200 100 0 0 100 200 300 400 500 600 700 800 900 1000 Time (s) Z=2.97 m Z=6.02 m Z=9.07 m Fig. 6 Temperature measurements at Tree A in Test 1. 499

13 9 15 12 10 11 14 8 1 7 17 3 16 2 6 4 5 Fuel Array Outline Sprinkler positions (3 m by 3 m spacing). Operated sprinklers: Total of 17. umbers correspond to opening sequence. Ignition location at base of array. Fig. 7 Plan view of sprinkler operations in Test 2. Operating Time Sequence (min: s) 1 2:28 2 5:21 3 5:29 4 5:34 5 5:49 6 5:58 7 6:01 8 6:12 9 6:13 10 6:20 11 6:26 12 6:29 13 6:38 14 6:47 15 6:48 16 6:58 17 7:20 About 22 seconds after ignition, flames reached the tops of the fuel stacks. At 2 min 5 s, the four center stacks were mostly engulfed in flame. Flames spread into stacks south and north of the center ignition stacks at 1 min 50 s and 2 min 55 s, respectively. The fire spread, by radiative ignition, to the west target at 3 min 44 s and to the east target at 4 min 2 s. The west target fuel array became more involved in the fire than the east target. QR1 responded at 1 min 46 s and QR2 responded at 1 min 59 s. The first sprinkler actuated at 2 min 21 s. QR3 responded at 3 min 15 s. After the first sprinkler operation, there was a considerable delay, 1 min 24 s, before the second sprinkler actuated. Thereafter, there were continuous openings of sprinklers for a total of 26 operating sprinklers by 7½ minutes as shown in Fig. 8. The test was terminated at 9 min due to environmental regulations limiting the amount of smoke generation in a test. By then, the center four stacks in the main fuel array appeared almost completely consumed and the overall fire intensity appeared significantly diminished. However, it could not be verified conclusively with the data collected up to that point whether or not the fire would have been controlled. Other parts of fuel array, including the target arrays, were still involved in fire. Sprinkler skipping played a very significant role. For the first time in the test series, sprinklers in the fourth ring actuated. The more open fuel arrangement in the test could have been one of the contributing factors. The fire spread farther out, compared with the previous fuel arrangement, within the same period of time. It is very likely that there would have been more open sprinklers, if the test had been allowed to continue. 500

3.4 Test 4 The fuel arrangement was identical to that of the previous test; however, protection was changed to QR-ELO sprinklers supplying 18-mm/min discharge density. The quick response links, QR1 through QR3, were no longer installed. 25 23 21 26 Operating Time Sequence (min: s) 22 17 3 15 20 2 19 11 6 5 18 1 7 4 16 12 10 9 14 8 13 Sprinkler positions (3-m by 3-m spacing) Operated sprinklers: Total of 26. umbers correspond to opening sequence. The test was terminated at 9 min. Ignition location at base of array. Fig. 8 Plan view of sprinkler operations in Test 3. 24 Fuel Array Outline 1 2:21 2 3:45 3 3:52 4 3:52 5 3:54 6 3:58 7 3:59 8 4:01 9 4:03 10 4:05 11 4:06 12 4:07 13 4:07 14 4:07 15 4:07 16 4:07 17 4:08 18 4:10 19 4:14 20 4:46 21 5:54 22 6:30 23 6:56 24 6:58 25 7:16 26 7:23 Flames reached the top of the fuel stacks, 1.73 m high, 28 seconds after ignition. The first sprinkler actuated was not the one directly above the ignition point, but was the one located 3 m south of the ignition point (see Fig. 9). As the fuel stacks located south of the four center stacks started to receive the water spray from the operating sprinkler, the fire seemed to spread in the other three directions. At 2 min 33 s, the north fuel stack adjacent to the center four stacks was involved in fire. At 3 min 41 s and 3 min 43 s, two additional sprinklers actuated. The fire was still quite intense and showed no sign of diminishing. At 6 min, many more sprinklers started to actuate. At 6 min 35 s, the fire started to show signs of diminishing intensity. The last sprinkler, the 16 th, actuated at 7 min 13 s. The test was terminated at 15 min. As in all the previous tests, sprinkler skipping seemed to play an important role in the effectiveness of the sprinkler performance with respect to fire control. The degree of 501

skipping was severe. one of the sprinklers immediately east of the center four fuel stacks actuated. The sprinklers immediately west of the center fuel stacks also skipped, but then actuated in a quite late stage of the test. Two of these sprinklers actuated last, even though they were located closer to ignition compared to some other sprinklers that actuated earlier. Operating Time Sequence (min: s) 10 9 5 6 16 3 14 8 15 2 4 11 7 1 12 13 Fuel Array Outline Sprinkler positions (3-m by 3-m spacing) Operated sprinklers: Total of 16. umbers correspond to opening sequence. Ignition location at base of array. Fig. 9 Plan view of sprinkler operations in Test 4. 1 1:41 2 3:41 3 3:43 4 5:55 5 6:07 6 6:12 7 6:12 8 6:12 9 6:15 10 6:16 11 6:18 12 6:40 13 6:48 14 6:53 15 6:53 16 7:13 The test showed that the protection scheme used in the test would provide adequate protection against the fire hazard represented by the fuel arrangement. Fig. 10 shows the temperature measurements at Tree A in the test. If the sprinkler directly above the ignition point had actuated properly, the sprinkler opening pattern would have been different and the number of operating sprinklers could have been reduced. The ceiling gas temperature measurements showed that the ceiling gas temperature steadily decreased after the last sprinkler actuation at t=433 s, which was another indication that the protection scheme used in the test was adequate. 3.5 Test 5 Test 5 was intended to explore using 6.1-m by 6.1-m spacing for the protection of nonstorage, high ceiling clearance occupancies. Since it became clear from the previous tests that 3-m by 3-m spacing would be subjected to sprinkler skipping, protection based on a larger sprinkler spacing had been proposed to possibly avoid sprinkler skipping. The sprinkler chosen for the test was the K-factor 25 Control-mode (Density/Area) Extended- Coverage upright sprinkler, following the work of Heskestad[2]. Since a single test would be insufficient to evaluate the protection effectiveness of using the extended 502

spacing, the test was intended to provide a reference point for future work. The test arrangement was identical to that of Test 4, except for the sprinklers and their locations (see Fig. 4). At 2 min from ignition, the sprinkler over ignition actuated and discharged approximately 681 l/min onto the center four (2 x 2) ignition stacks. The fire started to lose intensity at 2 min 10 s. At 4 min, the view was completely obscured by smoke. It appeared that the fire had been confined to the four ignition stacks during the test. Test was terminated at 30 min. Only one sprinkler operated. 1100 1000 900 Z=3.0 m Z=6.1 m Z=9.1 m Temperature ( o C) 800 700 600 500 400 300 200 100 0 0 100 200 300 400 500 600 Time (s) Fig. 10 Temperature measurements at Tree A in Test 4. 4. SUMMARY AD COCLUSIOS Five full-scale fire tests were conducted at the 18.3-m high ceiling site of the FM Global Test Center to determine adequate sprinkler protection for non-storage occupancies with high ceiling clearance. Test data such as the burning rate of the center fuel stacks, which was estimated through the load-cell data, flame/plume temperatures, ceiling gas temperatures, and sprinkler operating sequence were analyzed. Results of these tests showed that sprinklers installed at such a high ceiling clearance would indeed operate and that fire control would be achieved. Tests 1 and 2 were conducted with 2.3-m high stacks of the FMRC Class 2 test commodity. Sixty-four stacks were placed in an 8 by 8 pattern forming a solid pile fuel arrangement. In Test 1, the adequacy of a 12-mm/min discharge density supplied over a 465-m 2 demand area was assessed. Results were very favorable and all test evaluation criteria were met: only 15 sprinklers operated; ceiling level temperatures remained well within acceptable limits; and, the fire was well confined to the ignition fuel array. Because of the excellent results, it was concluded that the same level of protection can be extended to cover fire hazards equivalent to those involving a Class 3 commodity. 503

In Test 2, the adequacy of a 6-mm/min discharge density supplied over a 232-m 2 demand area was assessed. Results were nearly favorable: 17 sprinklers operated; ceiling level temperatures remained well within acceptable limits; and, the fire was confined to the ignition fuel array. Based on the results of the test, the provided protection was considered adequate for fire hazards up to the Class 2 commodity level. However, the number of the operated sprinklers was marginally within the number that can be regarded adequate for the given design area. A sufficient safety factor for the design area must be provided to prevent overtaxing of the water supply if too many sprinklers were to open. Test 3 was conducted with slightly lower, 1.74-m high, stacks of a higher fire hazard commodity, the FMRC Cartoned Group A Unexpanded Plastic. Twenty-eight fuel stacks were spread out in three rows. Sixteen stacks, arranged in two by eight configuration, comprised the main fuel array. There were two single-row targets located across 1.5-m aisle spaces on either side of the main array. The fuel arrangement was assumed to reflect the typical fire load that can be found at some manufacturing facilities or exhibit halls engaged in boat shows. For protection, nominal 13.5-mm orifice sprinklers supplied a 12-mm/min discharge density. After 7½ minutes from ignition, 26 sprinklers had operated. The test had to be terminated at 9 minutes before it yielded conclusive results. Test 4 used the same fuel package as Test 3. For protection, an 18-mm/min discharge density was provided by nominal 16.3-mm orifice Quick Response, Extra Large Orifice sprinklers. Results were favorable with all test evaluation criteria being satisfied. The results of the test showed that the provided sprinkler protection was effective against the fire hazard equivalent to the limited amount of FMRC Standard Plastic Commodity represented in the test. Test 5 explored 6.1-m by 6.1-m sprinkler spacing. The fuel arrangement was identical to that of Test 3 or 4. Protection was provided by nominal 25.4-mm orifice Quick Response, Extended-Coverage sprinklers supplying a 18-mm/min discharge density. The test results were favorable: only one sprinkler actuated; the fire was well confined within the four ignition stacks. However, additional tests are needed to verify the protection scheme before it can be recommended for specific installations. Sprinkler skipping, which has not been a significant parameter in ordinary-clearance occupancies, played a very important role in the tests. Additional work is needed to study the effects on fire control due to both temporary and permanent sprinkler skipping in high ceiling clearance situations. Also, additional work is needed to determine protection recommendations for non-storage occupancies with even higher ceiling clearance. REFERECES 1. Fire Protection Water Demand for onstorage Sprinklered Properties, FM Global Property Loss Prevention Data Sheet, 3-26, Factory Mutual Insurance Company, Johnston, Rhode Island, USA, 2001. 2. Heskestad, G., Scaling of Water-Spray/Flame Interactions, Technical Report J. I. 0X1J4.RU, Factory Mutual Research Corporation, orwood, Massachusetts, USA, 1999. 504