Installer manual AG-AA10. Air/air heat pump IHB GB AG-AA10-30 AG-AA10-40/50

Similar documents
Installer manual AG-WL10

User manual AG-WT10. Indoor unit air/air heat pump UHB GB

INSTALLATION INSTRUCTIONS

Installer manual ELK 213 Immersion heater

User manual AG-WT10. Indoor unit air/air heat pump UHB GB LEK

INSTALLATION AND USER S MANUAL COOKER HOOD RS-600/A-S

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Outdoor Unit UQB09JJWC UQB12JJWC. Indoor Unit AQB09JJWC AQB12JJWC

OPERATION MANUAL. System Inverter Air Conditioners FXNQ20A2VEB FXNQ25A2VEB FXNQ32A2VEB FXNQ40A2VEB FXNQ50A2VEB FXNQ63A2VEB

Ductless Split Air Conditioner

NIBE SPLIT ACVM 270 Air/water heat pump

INSTALLATION MANUAL. Split-type Air Conditioner (Cooling and Heating) Indoor Unit AQB18J6WC AQB24J2WC. Outdoor Unit UQB18J6WC UQB24J2WC

General safety precautions English

General safety precautions English

AIR CONDITIONER OWNER S MANUAL. Please read this manual carefully before operating your set and retain it for future reference.

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT: AW22AL AW28AL AW38AL AW42AL AW22AL AW28AL AW38AL

Operating Instructions Air Conditioner

User and maintenance manual

Model Modèle Modell Modello Modelo Malli:

DC INVERTER MULTI-SYSTEM AIR CONDITIONER

TECHNICAL DATA & SERVICE MANUAL

TECHNICAL DATA & SERVICE MANUAL SPLIT SYSTEM AIR CONDITIONER OUTDOOR UNIT: AE22AC/ACL/AH AE28AC/ACL/AH AE38AC/ACL/AH AE42AC/ACL/AH

TECHNICAL DATA & SERVICE MANUAL

General safety precautions English

AOYG18LFC OUTDOOR UNIT INSTALLATION MANUAL INSTALLATION MANUAL. For authorized service personnel only. PART NO

TECHNICAL DATA & SERVICE MANUAL

Installation manual for room air conditioner

Bar Fridge USER MANUAL MB46W

R32. Installation Manual Split Type Wall Mounted Air Conditioner. This appliance shall be installed in accordance with: REFRIGERANT

42PHW / 42PHQ 42PHQ...K

SINGLE - ZONE Ductless Split System Heat Pumps Installation, Operation & Maintenance Manual

Vacuum Pack Machine Instruction Manual Model GF439-A

Heat Shade. Instruction manual. Model Modèle Modell Modello Modelo Malli: DR573/DR574/DR575/DR576/DR577/DR578/DR579/ DL492/DL493/GC882/GC883

User manual NIBE F2026

EH0533 Indoor Climate Control

AC-12200E Portable Air Conditioner

Operating Instructions Air Conditioner

Soup Kettle. Instruction manual. Model: L714-A/L715-A/CP851-A CP851-A L715-A L714-A

AUTOMATIC ICE-CUBE MAKER - INSTRUCTIONS AND WARNINGS

TECHNICAL DATA & SERVICE MANUAL

Portable Air Conditioner. Instruction Manual

Installation Instructions

OPERATING INSTRUCTIONS

TECHNICAL DATA & SERVICE MANUAL

DUCTED AIR CONDITIONER. Owner s Manual. KD Series KD24. Kaden Owner s Manual 1

Electric Hand dryer. Installation and operating manual

PORTABLE AIR CONDITIONER (LOCAL)

Cooker Hood Instruction Manual

Refrigerator BRFB1920SS BRFB1900FBI BRFB1920FBI

AUTO COOL DRY FAN SPEED AIR SWING OFF ON TIMER TIMER OFF/ON FAN SPEED MODE TEMP AIR SWING TIMER ON SET OFF CANCEL AC RC SET CHECK CLOCK RESET

General safety precautions English

Original instructions AR

GDDEM10 DEHUMIDIFIER

Food Steamer. Instruction manual. Model: CL205-A

USER MANUAL TPS-M5/M55/M555

Portable Air Conditioner

Local air conditioner

51AKS I S O OWNER S MANUAL

Cabinet Refrigerators/Freezers Instruction manual

Stainless Steel Counter Refrigerators Instruction manual

Installation and Operation Manual. CMA12SB-0 Series. Horizontal/Side Discharge Condensing Units

Installation Operation Maintenance. Ductable water unit FWD FWD-SVX01D-E4

DD12E DEHUMIDIFIER USER'S MANUAL CONTENTS. VOLTAGE: V~50Hz

DAIKIN ROOM AIR CONDITIONER. Operation Manual. English. Deutsch. Français. Nederlands. Español. Italiano. Ελληνικά. Portugues. Русский.

Inverter Air Source Heat Pump Split system

Moisture inside the drum is due to final testing.

WARNING/SAFETY PRECAUTIONS

FR120RC/FR120RM FR120RR/FR120RB FN-153/FN-153C

General safety precautions English

Inverter Air Source Heat Pump Monobloc system

Installation Instructions

Contents. 1. Instructions for safety and use 20

Operating Instructions Air Conditioner

OPERATING INSTRUCTIONS

Split Portable Air Conditioner

Flow Factor ~

Split Air Conditioner. Model: WMI09MH16S WMI12MH16S WMI18MH16S

ZEST HOOD. Instructions Manual.

Blender. Instruction manual. Model Modèle Modell Modello Modelo Malli: CR836/DR825

EH0554 Indoor Climate Control

Installation Instructions

Centrif Duo & Centrif Duo Plus

INSTALLATION GUIDE NZ AU C

General safety precautions English

1. Take the hoses and elbow out of the holders, depending on model. max. 100 cm. min. * cm

INSTALLATION MANUAL COMFORT...BUILT TO LAST. 9,000, 12,000 and 18,000 BTU SINGLE-ZONE DUCTLESS MINI-SPLIT SYSTEM Heat Pump

600 / 400 / 150 litre series Refrigerators/Freezers Instruction manual

INSTALLATION INSTRUCTIONS

INVERTER SPLIT - TYPE

Ductless S plit Air Conditioner

Installation Instructions

Progress plus Instruction manual

WINDOW TYPE ROOM AIR CONDITIONER OPERATION AND INSTALLATION MANUAL

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

SHORT WAVE INFRARED PANEL DRYER

Operating Instructions

CA-707. Manual. Read these instructions carefully before you start using the dehumidifier and keep the manual for later usage.

Operating Instructions

QUICK CONNECT INSTALLATION MANUAL DUCTLESS MINI-SPLIT SYSTEM FOR MODELS: 2PAMSHQC12 2PAMSHQC18 2PAMSHQC24 2PAMSHQC36

WCD-200W Water Dispenser

GENERAL INFORMATION CONTENTS

Transcription:

-30 Installer manual Air/air heat pump -40/50 IHB GB 1516-1 331554

Table of Contents 1 Important information 2 5 Installation 7 Safety information 2 Model combinations 7 Read before starting the installation 3 Installation instructions 7 Electrical requirements 3 Pump down 11 2 Delivery and handling 4 6 The main functions of the valves 12 Transport Assembly Supplied components 4 4 4 7 Disturbances in comfort Troubleshooting 13 13 3 Pipe connections 5 8 Accessories 14 General Connecting the cooling circuit 4 Electrical connections General Connecting indoor and outdoor unit 5 5 6 6 6 9 Technical data Dimensions Technical specifications Index 15 15 16 18 Connecting accessories 6 Table of Contents 1

1 Important information Safety information This manual describes installation and service procedures for implementation by specialists. This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision. Rights to make any design or technical modifications are reserved. NIBE 2015. Symbols NOTE This symbol indicates danger to machine or person. Caution This symbol indicates important information about what you should observe when maintaining your installation. TIP This symbol indicates tips on how to facilitate using the product. Environmental information This unit contains a fluorinated greenhouse gas that is covered by the Kyoto agreement. F-Gas Regulation (EU) No. 517/2014 The equipment contains R410A, a fluorinated greenhouse gas with a GWP value (Global Warming Potential) of 2087.50. DO not release R410A into the atmosphere. Safety precautions NOTE Avoid the use and storage of flammable liquids near the climate unit. Never install electric equipment that does not have IPX1 protection (protection against vertical water drops), under the unit. The manufacturer assumes no liability, if safety the standards or protection preventive measures are not complied with. Special safety measures During installation the cooling circuit must be connected first and then the electrical circuit. Perform in reverse order when removing the unit. During repair Disconnect the voltage (via the main switch) before opening the unit to check or repair the electrical parts. Keep hands and clothing away from moving parts. Clean after completing the work, and check that no metal residue or cable parts have been left inside the unit. Vent the premises during the installation and the cooling circuit test. Ensure that no refrigerant gas has leaked out during the installation, as contact with naked flames or heat sources can be toxic or dangerous. Marking is CE marked and fulfills IPX4. The CE marking means that NIBE ensures that the product meets all regulations that are placed on it based on relevant EU directives. The CE mark is obligatory for most products sold in the EU, regardless where they are made. IPX4 means that the product is protected against drops of water from all angles. 2 Chapter 1 Important information

Read before starting the installation This heat pump complies with strict safety and function standards. It is very important that the installer or the service technicians install or repair the system so that it works safely and efficiently. For a safe installation and good function the following is required: Read this instruction manual carefully before starting installation. Follow the installation and safety instructions exactly as described and shown. Comply with local and national electrical regulations. Note all the warning and safety messages indicated in this manual. The unit must be connected to a separate supply. These instructions are sufficient for installation and maintenance. If assistance is required for a particular problem, contact our dealer for further information. NIBE does not accept any responsibility for damage that occurs in the event of incorrect installation or improper maintenance. Electrical requirements NOTE The electrical discharge can cause serious personal injury or death. Only qualified electricians may handle the electrical system. Before installation ensure that the mains supply for the power supply is the same as that indicated on the climate unit's rating plate. Each unit must be connected with approved grounded cable. The electrical connections must be performed by a specially trained and qualified electrician. Ensure a ground connection before the unit is powered. Hazardous electrical voltage is used in this electrical circuit. See electrical wiring diagram and its instructions below the connection. Incorrect connections or unsuitable ground connection can cause accidents or death. The yellow/green cable must not be used for connections other than ground. Tighten the cables securely. Incorrect connections can cause overheating and fire. Electrical cables must not come into contact with the cooling pipes, the compressor or fan's moving parts. Use separate cables for each type of cable. Chapter 1 Important information 3

2 Delivery and handling Transport Take care when lifting and moving the indoor and outdoor unit. We recommend that you ask for assistance and bend your knees when you lift to avoid injuring your back. There is a risk of cutting yourself on the sharp edges of the climate unit. Assembly We recommend that this climate unit be installed by an authorised technician in accordance with the supplied installation instructions. NOTE Do not install this climate unit where there are flue gases, flammable gases or a lot of moisture, e.g. in a greenhouse. Do not install this climate unit where there is equipment that generates too much heat. Do not install the unit in premises where it may be subjected to water splashes (e.g. laundry rooms). To protect the climate unit from corrosion, the unit must not be installed where it can be directly exposed to seawater splashes or sulphur fumes. Selection of installation location for outdoor unit During installation......in damp or uneven locations: Use a base that is stable and raised above the ground to prevent damage and abnormal vibrations....in locations exposed to strong winds: Secure the unit with bolts and metal frame. Ensure that there is suitable wind protection....in locations susceptible to snowfall (for climate units with heat pump): The concrete foundation or slabs must be positioned so that the lower edge of the evaporator is at the level of the average local snow depth, however a minimum of 300 mm. Prevent the following: proximity to heat sources or to areas where hot air is blown out. Installation on wooden wall, because there is a risk of resonance. damp areas or easily flooded areas and uneven surfaces. to drill holes in the areas where there are electrical parts or units. The following is recommended: If possible, select well-ventilated, shaded areas. Secure the unit securely at the base to prevent vibrations. Installation area Minimum working and maintenance range (measured in mm): 2000 2000 2000 2000 100 100 500 100 100 500 400 400 300 100 Supplied components -30/40/50: 1 x Communication cable (8.5 m) 4 Chapter 2 Delivery and handling

3 Pipe connections General Pipe installation must be carried out in accordance with current norms and directives. Only use refrigerant pipes that are seamless, degreased, deoxidized and suitable for a pressure of at least 42 bar. The pipes must be supplied with at least 8 mm vapour-proof insulation. Pipe length The refrigerant pipes' minimum length The refrigerant pipes' total length with standard filling The refrigerant pipes' total length with additional filling 1 1.5 m 7.5 m 15 m Max 10 m Max 10 m 1 1. Additional filling of refrigerant can be done when the unit runs in cooling operation: For refrigerant pipe 1/4" - 3/8" = 15 g/m For refrigerant pipe 1/4" - 1/2" = 20 g/m For information about pipe dimensions, see section "Technical Specifications" on page 16. Condensation drain For condensation removal, the AG-CH10 accessory of suffient length is required to transport the condensation to an external drain. See section "Accessories" on page 14 for further information about AG-CH10. Connecting the cooling circuit Use the flare method to connect the pipes. Lubricate the contact surfaces and hand tighten, then tighten the connections using a torque wrench to obtain a good and secure connection, see installation instructions on page 8. Check carefully that there is no risk of any leakage prior to the function test. Chapter 3 Pipe connections 5

4 Electrical connections General A heat pump must not be connected without the permission of the electricity supplier and must be connected under the supervision of a qualified electrician. Electrical installation and wiring must be carried out in accordance with the stipulations in force. If a miniature circuit-breaker is used this should have motor characteristic C (compressor operation). For other fuse sizes, see section "Technical Specifications" on page 16. does not include an omnipolar circuit breaker on the incoming power supply. The heat pump s supply cable must be connected to a circuit breaker with a breaking gap of at least 3 mm. When the building is equipped with an earth-fault breaker the heat pump should be equipped with a separate one. Incoming supply must be 230 V ~ 50 Hz via electrical distribution units with fuses. If an insulation test is to be carried out in the building, disconnect the heat pump. Connecting indoor and outdoor unit Connecting accessories The outdoor unit is equipped for connection of a condensation water pipe (AG-CH10).. Connect the power supply to AG-CH10 as illustrated: GREY WHITE GREEN/YELLOW AG-CH10 Indoor unit Rated voltage 230V ~ 50Hz A Outdoor unit L N Caution Also see the Installer manual for AG-CH10. N C L L C2 B N C1 C1 C2 Explanation A Power supply cable B Communication cable 1 C Connection cable 1 The communication cable must always be screened. 8.5 m screened cable supplied. 6 Chapter 4 Electrical connections

5 Installation Model combinations See product catalogue for further information about model combinations. Installation instructions 1. Place the outdoor unit on a stable base raised above the ground and secure it. Outdoor unit -30-40 -50 Indoor unit AG-WT10-4 AG-WT10-4 AG-WT10-7 TIP When installing stand, install screws downward to facilitate removal of the front panel. 300 mm 400 mm 100 mm 2. Hole for connecting the accessory AG-CH10. Chapter 5 Installation 7

3. Remove the side panel, then connect the supply and communication cables to the outdoor unit and secure them with load relief. 5. Remove burrs from the pipe ends. Turn the pipe ends downwards to prevent residue entering the pipe. 6. Thread the flange nuts (which are removed from the outdoor unit) on the pipes and bend up the ends of the pipes. N.O NOTE Only use tools intended for R410A 4. Use insulated copper cooling pipes. Cut a length of 30 50 cm in addition to the distance between the units. min. 8 mm min. 8 mm Insulation 8 Chapter 5 Installation

7. A good upward bend must have the following properties: a smooth and even inner surface a uniform and even outer edge a conical upward bend of uniform length. Lubricate the contact surfaces with compressor oil before connecting the pipes. 9. Insulate the pipes thoroughly and keep the pipe connections free for leak testing. Before vacuuming, leak trace the system. Fill with nitrogen to approx. 3 bar. Leak trace all connections using leak spray (soapy water) to ensure that the system is sealed. Lubricate! 3 mm 45 10. For vacuuming of the indoor unit and refrigerant pipe, connect the vacuum pump to the outdoor unit as illustrated. NOTE Remaining air or damp affects the heat pump's function negatively and can damage the product. 8. Tighten the connections using a wrench and torque wrench according to the tightening torque values in the table. Pipe diameter 6.35 mm (1/4") 9.52 mm (3/8") 12.7 mm (1/2") 15.88 mm (5/8") Tightening torque Approx. 15 20 Nm Approx. 30 40 Nm Approx. 50 55 Nm Approx. 60 65 Nm Chapter 5 Installation 9

11. Remove the valve caps from both valves. Now start the vacuum pump. If damp air has entered the cooling pipes, flush through with dry nitrogen. 13. Open the service valves fully (anti-clockwise direction). Disconnect the vacuum pump. Reinstall the caps on the valves, tighten to a torque of 20 Nm. Leak trace caps and connections using a sniffer or leak spray. See page 12 for the valves' main functions. High pressure Low pressure 12. With the vacuum pump in operation, close the tap on the manometer unit when you have reached a vacuum less than 2 mbar (absolute pressure, standing vacuum min. 30 minutes). Stop the vacuum pump. 14. Complete insulation, protect against mechanical impacts, secure and hang up. If necessary, seal the valve opening in the wall. 10 Chapter 5 Installation

Pump down Pump down means retrieving all refrigerant in the outdoor unit without losing the system's filling. This is done when the climate unit is to be moved or during repair of the cooling circuit. Procedure for "Pump down": 1. Connect a manometer assembly to the low pressure valve, open partially (1/4 turns). Extract air from the manometer. Then close the high pressure valve fully. 2. Start the climate unit in cooling mode. When the pressure that is read out from the manometer has dropped to a value less than 0.6 bar (absolute pressure), the low pressure valve must be closed fully and the climate unit switched off. 1 0 0,5 3. Remove the manometer assembly. The action "Pump down" is now complete and all refrigerant has been collected in the outdoor unit. Chapter 5 Installation 11

6 The main functions of the valves Action 2-way valve (service valve) 3-way valve (service valve) Delivery CLOSED O-ring Valve cap Cone Function and test of the climate unit OPEN Pressure measurement and gas filling OPEN * Vacuuming with vacuum pump CLOSED * * The service valve on the outdoor unit that gives access to the refrigerant system is of the "Schrader" type. Use hoses that have a Schrader opener in the connection. 12 Chapter 6 The main functions of the valves

7 Disturbances in comfort Troubleshooting NOTE Work behind covers secured by screws may only be carried out by, or under the supervision of, a qualified installation engineer. NOTE As can be connected to several different indoor units, these should also be checked. NOTE In the event of action to rectify malfunctions that require work within screwed hatches the incoming electricity must isolated at the safety switch. Basic actions Start by checking the following possible fault sources: That the climate unit is running or that the supply cable to is connected. Group and main fuses of the accommodation. The property's earth circuit breaker. Fault codes Caution Remove the side panel that protects the terminal blocks to read off the LEDs. See page 8. Key to symbols The LED is off. The LED flashes. DL3 DL4 DL5 DL6 DL7 Cause Compressor sensor defective or not connected. Outdoor temperature sensor defective or not connected. Evaporator sensor defective or not connected. Overcurrent on compressor. The compressor's control electronics have overheated. Overcurrent on fan. The fan's control electronics have overheated. Fault in indoor unit. Communication error. Phase monitor tripped. When the unit functions correctly DL3 lights with a steady light. DL4 lights with a steady light if the indoor unit is running, otherwise the lamp is out. Chapter 7 Disturbances in comfort 13

8 Accessories Condensation water pipe Condensation water pipe for leading condensation to external drain. AG-CH10-10 Length: 1000 mm Part no. 067 466 AG-CH10-30 Length: 3000 mm Part no. 067 467 AG-CH10-60 Length: 6000 mm Part no. 067 468 Ground stand Ground stand AG-GS10-1 Part no. 067 460 Wall mounting Wall mounting AG-WS10-1 Part no. 067 462 14 Chapter 8 Accessories

9 Technical data Dimensions -30 1/4" 3/8" -40/50 1/4" 3/8" (AA10-40) 1/2" (AA10-50) Chapter 9 Technical data 15

Technical specifications -30-40 -50 Output data Cooling capacity +35 C 1) / 27 C 2), min/max 1370/3650 W 1010/4060 W 900/5650 W Heat capacity +7 C 1) / +20 C 2), min/max 930/3880 W 910/4870 W 1030/5290 W Heat capacity -7 C 1) / +20 C 2), max 2650 W 3510 W 3900 W Heat capacity -20 C 1) / +20 C 2), max 2150 W 2980 W 3040 W Pdesignc/SEER/Energy class (cooling +35 C) 3) 2680 W/6.1/A++ 3670 W/6.0/A++ 5215 W/6.7/A++ Pdesignh/SCOP/Energy class (heat -10 C) 3) 3030 W/3.82/A 4020 W/4.01/A+ 4470 W/4.16/A+ Electrical data Rated voltage 230 V ~ 50 Hz Max. specified power/operating current 1550 W/6.90 A 1550 W/6.90 A 1790 W/7.80 A Fuse 10 A Refrigerant circuit Type of refrigerant R410A Type of compressor Single rotary Single rotary Twin rotary Volume 0.81 kg 1.1 kg 1.3 kg Pipe connections Pipe connection (liquid) 6.35 mm (1/4") 6.35 mm (1/4") 6.35 mm (1/4") Pipe connection (gas) 9.52 mm (3/8") 9.52 mm (3/8") 12.77 mm (1/2") Min. thickness refrigerant pipe 0.8 mm 0.8 mm 0.8 mm Dimensions and weight Weight 35 kg 57 kg 57 kg Width 765 mm 895 mm 895 mm Depth 315 mm 345 mm 345 mm Height 544 mm 630 mm 630 mm 16 Chapter 9 Technical data

-30-40 -50 Recommended working range 4) Min/max outdoor temp. during cooling Min/max indoor temp. during cooling Min/max outdoor temp. during heating Min/max indoor temp. during heating -20/50 C 10/32 C -20/24 C 0/27 C Miscellaneous Max. sound pressure level at 2 m, according to ISO 9614 40 db(a) 44 db(a) 41 db(a) Enclosure class IPX4 Part No. 064 061 064 162 064 163 1) Refers to the outdoor temperature. 2) Refers to the indoor temperature. 3) According to EN 14825 4) Access to full capacity is guaranteed within the heat pumps' recommended working range. Operation outside the recommended working range is possible as the internal protective functions ensure that the heat pump will not be damaged. Chapter 9 Technical data 17

10 Item register Item register A Accessories, 14 D Delivery and handling, 4 Assembly, 4 Transport, 4 E Electrical connection, 6 I Important information, 2 Electrical requirements, 3 Safety information, 2 Installation, 7 Installation instructions, 7 Model combinations, 7 Pump down, 11 M Marking, 2 P Pipe connections, 5 Condensation removal, 5 Connecting the cooling circuit, 5 S Safety information Marking, 2 Symbols, 2 Safety precautions, 2 Supplied components, 4 Symbols, 2 T Technical data, 15 Dimensions, 15 Technical specifications, 16 The main function of the valves, 12 18 Chapter 10 Item register

37 4255 128 01 NIBE AB Sweden Hannabadsvägen 5 Box 14 SE-285 21 Markaryd info@nibe.se www.nibe.eu 331554