Bulletin 018 Rev. H Model JL-14 (SIN RA1812) K14.0 (200 metric) Early Suppression Fast Response Sprinkler Bulletin 018 Rev. H Product Description The Reliable Model JL-14 Early Suppression Fast Response (ESFR) Sprinkler is intended for use against severe fire challenges. This sprinkler is designed to respond quickly to growing fires and will deliver a heavy water discharge to suppress rather than control fires. Note: The Model JL-14 ESFR sprinkler utilizes a levered fusible alloy solder link in either a 165 F (74 C) or a 212 F (100 C) rating. FM Global considers this a Quick Response storage sprinkler for use in Data Sheet 8-9. The sprinkler has a Nominal K Factor of 14.0 (metric 200) and will deliver approximately 100 gpm (378 L/min) of water at 50 psi (3,5 bar). The deflector and frame provide a broad, very symmetrical, hemispherical pattern capable of suppressing fires between sprinklers in high storage height areas and at the same time retaining a high momentum central core to penetrate and suppress fires occurring directly beneath the sprinkler in low storage height areas. Application and Installation The Model JL-14 ESFR sprinkler is intended for installation in accordance with NFPA 13 and FM Loss Prevention Data Sheets 2-0 and 8-9 as well as the Authority Having Jurisdiction. This sprinkler is intended for protection of palletized and solid piled and open frame single row, double row, multiple row and portable rack storage of most common materials including unexpanded and cartoned expanded plastics. The JL-14 ESFR sprinkler was designed to be shorter, and more compact than other ESFR sprinklers. The shorter sprinkler allows piping to be installed further from the ceiling and obstructions. The JL-14 ESFR sprinkler is also less susceptible to damage due to smaller deflector and frame design. The lighter JL-14 ESFR passed rough use and abuse test in the labs without plastic protectors. The Model JL-14 ESFR Sprinkler is FM approved when installed in accordance with Factory Mutual Loss Prevention Data Sheet 8-9 and Data Sheet 2-0 and other FM Installation Standards. The Model JL-14 ESFR Sprinkler is UL Listed and Certified for Canada for installation in accordance with NFPA 13 Standards. Model JL-14 ESFR Sprinkler Design Criteria General guidelines: Orientation: Pendent. Deflector should be parallel with the ceiling or roof. System Type: Wet Pipe Systems Only Maximum area of coverage: 100 ft 2 (9,3m 2 ), greater coverage area are allowable in some cases. Minimum area of coverage: 64 ft 2 (5,8m 2 ) Maximum slope ceiling: 2/12 pitch (9.5 ) Maximum spacing: 12 ft (3,7m) for building heights up to 30 ft (9,1m) and 10 feet (3,1m) for building heights greater than 30 ft (9,1m) Minimum spacing: 8 feet (2,4m) Deflector distance from walls: At least 4 inches (102mm) from walls, and no more than one-half the allowable distance permitted between sprinklers. Deflector to Top of Storage: at least 36in (914mm). Deflector to ceiling Distance: 6-14 in (152-356mm) per NFPA 13. 5-14 in (121-35mm) per FM 2-2. Center Line of Thermal Sensing Element To Ceiling Distance: 4-13 in (102-330mm) per FM Listings and Approvals 1. Listed by Underwriters Laboratories Inc. and UL certified for Canada (culus) 2. FM Approved as a storage sprinkler 3. VdS Schadenverhütung GmbH (VdS) 4. Loss Prevention Certification Board (LPCB) 5. CNBOP-PIB Technical Approval Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Model JL-14 Ratings Classification Ordinary Intermediate Installation Data Sprinkler Type Pendent Only Thread Size Sprinkler Maximum Ceiling Link Frame Color Color F C F C 165 74 Black Uncolored 100 38 212 100 White White 150 66 Nominal K Factor US Metric Maximum Working Pressure Finish ¾ (R¾) 14.0 200 175 psi (12,1 bar) Bronze Maintenance The Model JL-14 ESFR Sprinkler should be inspected and the sprinkler system maintained in accordance with NFPA 25. Do not clean sprinkler with soap and water, ammonia or any other cleaning fluid. Replace any sprinkler that has been painted (other than factory applied) or damaged in any way. A stock of spare sprinklers should be maintained to allow quick replacement of damaged or operated sprinklers. Prior to installation, sprinklers should be maintained in the original cartons and packaging until used, to minimize the potential for damage to sprinklers that would cause improper operation or non-operation. Once operated, automatic sprinklers cannot be reassembled and reused. New sprinklers of the same size, type and temperature rating must be installed. A cabinet of replacement sprinklers should be provided for this purpose. Model JL-14 ESFR Sprinkler Specification Sprinklers shall be Early Suppression Fast Response (ESFR) pendent suppression mode sprinklers specifically tested and [UL Listed] [FM Approved] for commodity storage applications. Sprinkler frame and deflector to be of bronze construction. Fusible link assembly shall utilize the strut and lever principle of operation with approved fast response black-painted or white-painted beryllium-nickel thermal element. Water seal shall consist of a Electroless Nickel PTFE coated Bellville spring washer and brass cap assembly containing no plastic parts. ESFR sprinklers shall have a nominal K-factor of 14.0 with ¾ NPT threaded end connections. Sprinkler temperature rating shall be [Ordinary 165 F (74 C)] [Intermediate 212 F (100 C)]. ESFR pendent sprinklers shall be Reliable Model JL-14 (Bulletin 018). Model J1 Sprinkler Wrench Sprinkler Identification Number (SIN) RA1812 Use only the Model J1 sprinkler wrench for removal and installation. Any other type of wrench may damage the sprinkler. Note: Sprinklers should be tightened between 14-20 ft-lbs (19-27,1 N-m) torque. Sprinklers not tightened to recommended torque may cause leakage or impairment of the sprinklers. Damage sprinklers must be replaced immediately. Ordering Information Specify: 1. rating 2. Thread type 3 /4 NPT or ISO 7-R 3 /4 Note: Grooved sprinkler boss provided to ensure that the sprinkler wrench does not slip during installation. The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for almost 100 years. Manufactured by Reliable Automatic Sprinkler Co., Inc. (800) 431-1588 Sales Offices (800) 848-6051 Sales Fax (914) 829-2042 Corporate Offices www.reliablesprinkler.com Internet Address Recycled Paper Revision lines indicate updated or new data. EG. Printed in U.S.A. 11/17 P/N 9999970378
Features: 1. culus, VdS, and LPCB listed as a nominal K16.8 (240 metric) ESFR sprinkler. 2. FM Approved as a quick-response, storage and non-storage, sprinkler. 3. Fusible link operating element. 4. Compact design allows piping to be installed farther from the ceiling and obstructions compared with larger sprinklers. Listings and Approvals 1. Listed by Underwriters Laboratories Inc. and UL certified for Canada (culus) - Category Code VNWH. 2. FM Approved as a quick-response, storage and nonstorage, sprinkler. 3. VdS Schadenverhütung GmbH (VdS). 4. Loss Prevention Certification Board (LPCB). 5. CNBOP Technical Approval. Bulletin 019 Rev. H Model JL-17 (SIN RA1914) K16.8 (240 metric) Early Suppression Fast Response Sprinkler Model JL-17 ESFR Sprinkler Bulletin 019 Rev. H Product Description The Reliable Model JL-17 Early Suppression Fast Response (ESFR) Sprinkler with a nominal k-factor of 16.8 (240 metric). This sprinkler is designed to respond quickly to growing fires and will deliver a heavy water discharge to suppress rather than control fires. FM Global classifies the Model JL-17 as a quick-response sprinkler, storage and non-storage, when the sprinkler is used in accordance with FM Global Property Loss Prevention Data Sheets. The Model JL-17 ESFR sprinkler utilizes a levered fusible alloy solder link in either a 165 F (74 C) or a 212 F (100 C) rating. Model JL-17 sprinklers are culus Listed for compliance with UL/ULC 1767, including the high clearance test for rack storage. The Model JL-17 ESFR sprinkler was designed to be shorter and more compact than other ESFR sprinklers. The shorter sprinkler allows piping to be installed farther from the ceiling and obstructions. The JL-17 ESFR sprinkler is also less susceptible to damage due to smaller deflector and frame design. The lighter JL-17 ESFR passed rough use and abuse listing tests without plastic protectors. Application and Installation The Model JL-17 ESFR sprinkler is intended for installation in accordance with NFPA 13 and FM Loss Prevention Data Sheets 2-0 and 8-9, as well as the requirements of any Authorities Having Jurisdiction. See Table 1 for information on NFPA and FM Global design criteria for the Model JL-17 sprinkler. Use only the Model J1 sprinkler wrench for removal and installation. Any other type of wrench may damage the sprinkler. A grooved wrench boss is provided on the sprinkler to limit the potential for the wrench to slip during installation. Model J1 Sprinkler Wrench When handling sprinklers, hold sprinklers only on frame arms and do not apply any force on the link assembly. Sprinklers should be tightened between 14-40 ftlbs (19-54 N-m) torque. Sprinklers not tightened to recommended torque may cause leakage or impairment of the sprinkler. Damage sprinklers must be replaced immediately. Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Ratings and Approvals Classification Rating Link Frame Maximum Ambient F C Color Color F C Ordinary 165 74 Black Uncolored 100 38 Intermediate 212 100 White White 150 66 Approvals culus, FM, VdS, LPCB, CNBOP culus, FM, VdS, LPCB, CNBOP Sprinkler Identification Number (SIN) RA1914 Installation Data Sprinkler Type Thread Size Nominal K- Factor US Metric Maximum Working Pressure Finish Pendent ¾ (R¾) 16.8 240 175 psi (12.1 bar) Bronze Installation Criteria The following general guidelines are provided for information only. NFPA and, where applicable, FM Global standards shall be consulted for complete design and installation criteria. Orientation: Pendent, deflector should be parallel with the ceiling or roof. System Type: Wet Pipe Systems Only. Maximum area of coverage: 100 ft 2 (9.3m 2 ), greater coverage areas are allowable in some cases. Minimum area of coverage: 64 ft 2 (5.8m 2 ). Maximum slope ceiling: 2/12 pitch (9.5 ). Maximum spacing: 12 ft (3.7m) for building heights up to 30 ft (9.1m) and 10 feet (3.1m) for building heights greater than 30 ft (9.1m). Minimum spacing: 8 feet (2.4m). Deflector distance from walls: At least 4 inches (102mm) from walls, and no more than one-half the allowable distance permitted between sprinklers. Deflector to Top of Storage: at least 36 in (900mm). Deflector to ceiling Distance: 6-14 in (150-350mm) per NFPA 13. Center Line of Thermal Sensing Element To Ceiling Distance: 2-13 in (50-330mm) for smooth ceilings or 4-13 in (100-330mm) for nonsmooth ceilings per FM Data Sheet 2-0. Maintenance The Model JL-17 ESFR Sprinkler should be inspected and the sprinkler system maintained in accordance with NFPA 25. Do not clean sprinkler with soap and water, ammonia or any other cleaning fluid. Replace any sprinkler that has been painted (other than factory applied) or damaged in any way. A stock of spare sprinklers should be maintained to allow quick replacement of damaged or operated sprinklers. Prior to installation, sprinklers should be maintained in the original cartons and packaging until used, to minimize the potential for damage to sprinklers that would cause improper operation or non-operation. Once operated, automatic sprinklers cannot be reassembled and reused. New sprinklers of the same size, type and temperature rating must be installed. A cabinet of replacement sprinklers should be provided for this purpose. 2. Model JL-17 ESFR Sprinkler Specification Sprinklers shall be Early Suppression Fast Response (ESFR) pendent sprinklers specifically tested and [culus Listed] [FM Approved] [VdS Approved] [LPCB Approved] for commodity storage applications. Sprinkler frame and deflector to be of bronze construction. Fusible link assembly shall utilize the strut and lever principle of operation with approved fast response black-painted or white-painted beryllium-nickel thermal element. Water seal shall consist of a PTFE coated Bellville spring washer and brass cap assembly containing no plastic parts. ESFR sprinklers shall have a nominal K-factor of 16.8 (240 metric) with [¾ NPT] [ISO 7-R¾] threaded end connections. Sprinkler temperature rating shall be [Ordinary 165 F (74 C)] [Intermediate 212 F (100 C)]. ESFR pendent sprinklers shall be Reliable Model JL-17 (Bulletin 019). Ordering Information Specify: 1. Sprinkler: Model JL-17 2. rating: [Ordinary 165 F (74 C)] [Intermediate 212 F (100 C)] 3. Thread type: [ 3 /4 NPT] [ISO 7-R 3 /4]
Storage Type NFPA FM Open Frame (that is, no solid shelves) Single, Double, Multiple-Row, or Portable Rack Storage of Class I-IV and Group A or B Plastics Solid Pile or Palletized Storage of Class I-IV and Group A or B Plastics Idle Pallet Storage Rubber Tire Storage Rolled Paper Storage (Refer to the standard) Chapters 16 and 17. Chapters 14 and 15. Chapter 12. Chapter 18. Chapter 19. Refer to FM 2-0 and FM 8-9. Refer to FM 2-8 and FM 8-9. Refer to FM 2-0 and FM 8-24. Refer to FM 2-0 and FM 2-0 and FM 8-3. Refer to FM 8-21. Flammable Liquid Storage (Refer to standard) Refer to NFPA 30. N/A Aerosol Storage (Refer to the standard) Refer to NFPA 30B. Refer to FM 7-31. Automotive Components In Portable Racks (Control mode only; refer to the standard) Chapters 20. N/A TABLE 1 COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW FOR MODEL ESFR-17 PENDENT SPRINKLERS 3.
Reliable...For Complete Protection Reliable offers a wide selection of sprinkler components. Following are some of the many precision-made Reliable products that guard life and property from fire around the clock. Automatic sprinklers Flush automatic sprinklers Recessed automatic sprinklers Concealed automatic sprinklers Adjustable automatic sprinklers Dry automatic sprinklers Intermediate level sprinklers Open sprinklers Spray nozzles Alarm valves Retarding chambers Dry pipe valves Accelerators for dry pipe valves Mechanical sprinkler alarms Electrical sprinkler alarm switches Water flow detectors Deluge valves Detector check valves Check valves Electrical system Sprinkler emergency cabinets Sprinkler wrenches Sprinkler escutcheons and guards Inspectors test connections Sight drains Ball drips and drum drips Control valve seals Air maintenance devices Air compressors Pressure gauges Identification signs Fire department connection The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for almost 100 years. Manufactured by Reliable Automatic Sprinkler Co., Inc. (800) 431-1588 Sales Offices (800) 848-6051 Sales Fax (914) 829-2042 Corporate Offices www.reliablesprinkler.com Internet Address Recycled Paper Revision lines indicate updated or new data. EG. Printed in U.S.A. 11/17 P/N 9999970379