Significant Advancements in Water Based Fire Suppression for Storage Occupancies

Similar documents
Storage Sprinkler U.S. Quick Reference Guide

Storage Protection Using Horizontal Barriers and Large K-Factor, Extended Coverage In-Rack Sprinklers

SPRINKLER TECHNOLOGY:

ESFR PENDENT SPRINKLER VK510 (K25.2) TECHNICAL DATA

Model ESFR K-factor Pendent Sprinkler Early Suppression, Fast Response General Description. Sprinkler Identification Number (SIN)

esfr pendent sprinkler vk510 (k25.2)

ESFR PENDENT SPRINKLER VK500 (K14.0) TECHNICAL DATA

Box-in-Box Cold Storage Fire Protection Options

TECHNICAL DATA. * Refer the Approval Chart on page 120c and Design Criteria on page 120d for culus and FM approval requirements that must be followed.

TECHNICAL DATA. * Refer the Approval Charts and Design Criteria on pages 3-5 for culus Listing and FM Approval requirements that must be followed.

Storage Sprinkler. Model LP-46 (SIN) V4603, K25, Standard Response Storage Upright Sprinkler, Patent Pending

TECHNICAL DATA NOTICE

TECHNICAL DATA OBSOLETE. * Refer the Approval Chart on page 121c and Design Criteria on page 121d for FM approval requirements that must be followed.

Model ESFR-25 Early Suppression, Fast Response Pendent Sprinklers 25.2 K-factor General Description

Sprinkler Identification Numbers

esfr pendent sprinkler vk510 (k25.2)

STORAGE PRODUCT BROCHURE

Model ESFR-17 Early Suppression, Fast Response Upright Sprinklers 16.8 K-factor General Description

Model JL-14 (SIN RA1812) K14.0 (200 metric) Early Suppression Fast Response Sprinkler

Requirements for the protection of High-Piled Combustible Storage (HPCS) Effective Date: January 2011

Protection of Rack Stored Exposed Expanded Group A Plastics with ESFR Sprinklers and Vertical Barriers

STORAGE FIRE PROTECTION SPRINKLERS

The Effect of Large Orifice Sprinklers on High-Challenge Fires

TECHNICAL DATA OBSOLETE

Today's Topics & Sustainability Themes

High Ceiling Protection

Sprinkler Solutions for Storage Applications

Tire Storage. Michigan Fire Inspectors Society Fall Conference

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

NFPA Edition. NFPA 13 (2016 Edition) Hot Topics and NFPA 13 FAQ s. Highlights of 2016 Changes. Storage Commodity Classification 4/29/2014

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

esfr dry pendent sprinkler Vk502 (k14.0)

First Revision No. 632-NFPA [ Global Input ] Supplemental Information. Submitter Information Verification. Committee Statement

esfr dry pendent sprinkler Vk501 (k14.0)

SANTA ROSA FIRE DEPARTMENT FIRE PREVENTION BUREAU INSPECTION CHECKLIST HIGH PILED STORAGE

TECHNICAL DATA. Refer to the Approval Chart and Design Criteria for UL and FM Listing/Approval requirements that must be followed.

standard response elo upright and pendent sprinklers (storage-density/area)

ec/qrec ordinary hazard upright and pendent sprinklers vk570 and vk572 (k14.0)

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT UPRIGHT SPRINKLER VK535 (K11.2) TECHNICAL DATA

Plan Submittal Checklist

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description

standard/quick response extended coverage light and ordinary hazard elo sprinklers

Model ESFR K-factor Dry Type Pendent Sprinklers Early Suppression, Fast Response General Description

E x t E N d e d Co v e r ag e S p r i n k l e r s. Office Buildings Hotels Hospitals Libraries. High-Piled Storage Big-Box Retailing

NFPA 30 FLC-SWC Public Comment Report

EC/QREC ORDINARY HAZARD PENDENT SPRINKLER VK572 (K14.0) TECHNICAL DATA

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright and Pendent Extended Coverage Light and Ordinary Hazard General Description

Series ELO K-factor Upright and Pendent Sprinklers Standard Response, Standard Coverage General Description

High-Piled Combustible Storage

Obstructions and ESFR Sprinklers Phase 2 FINAL REPORT

Fire Prevention Coffee Break Training. May 2017

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description

ATTIC UPRIGHT SPECIFIC APPLICATION SPRINKLER VK696 TECHNICAL DATA

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright, and Pendent Extended Coverage Light and Ordinary Hazard General Description

Model/Sprinkler Identification Number JULY, 2011 WARNINGS

culus Listed: Category VNIV Refer to the Approval Chart on page 3. VK697 Attic Upright Sprinkler Specifications:

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL /

Series EC K-factor Extended Coverage (Light Hazard) Pendent and Recessed Pendent Sprinklers General Description

High challenge warehouse case study Summary

EC/QREC ORDINARY HAZARD UPRIGHT SPRINKLER VK570 (K14.0) TECHNICAL DATA

STANDARD/QR EXTENDED COVERAGE LIGHT HAZARD TECHNICAL DATA ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK617

Redlands Fire Department Fire Protection Standard

mirage Quick response extended coverage concealed pendent sprinklers (vk632 and vk634)

Sprinkler Standards Proposed Technical Changes

Factors Affecting Efficiency of Water Mist Suppression of Solid Combustible Fires in Open Environment

Early Suppression Fast Response Sprinklers and Obstructions

STANDARD/QUICK RESPONSE ECOH ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK537 (K11.2) TECHNICAL DATA

DISCONTINUED PRODUCT

Sprinkler Identification Numbers

TECHNICAL DATA. Viking Technical Data may be found on Maximum Working Pressure: 175 psi (12 Bar).

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL /

TECHNICAL DATA STANDARD/QUICK RESPONSE EXTENDED COVERAGE PENDENT SPRINKLER VK534 (K11.2)

ESCUTCHEON PLATE SEATING SURFACE. 1-11/16" (42,7 mm) CROSS SECTION

Series EC K-factor Extended Coverage (Light Hazard) Pendent and Recessed Pendent Sprinklers General Description

STANDARD/QR EXTENDED COVERAGE LIGHT HAZARD ELO FUSIBLE ELEMENT PENDENT SPRINKLER VK617 TECHNICAL DATA

FIRE PROTECTION FOR NON-STORAGE OCCUPANCIES WITH HIGH CEILING CLEARANCES

By: Russell Bainbridge March 18th, 2016 FPE 596

FREEDOM RESIDENTIAL PENDENT SPRINKLER VK468 (K4.9) TECHNICAL DATA

ROLL PAPER STORAGE. Table of Contents

Model MBEC-14. Extended Coverage Ordinary & Extra Hazard Horizontal Sidewall Sprinklers for Metal Building Applications. Model MBEC-14 (SIN R6932)

QUICK RESPONSE EXTENDED COVERAGE FUSIBLE ELEMENT PENDENT SPRINKLER VK601 (K5.6) TECHNICAL DATA

STANDARD/QUICK RESPONSE EXTENDED COVERAGE PENDENT SPRINKLER VK602 TECHNICAL DATA

microfast sr/qr extended coverage pendent sprinkler

TECHNICAL DATA OBSOLETE

MODEL V-BB SPECIFIC APPLICATION TECHNICAL DATA

sprinkler vk538 (K11.2)

HORIZON QUICK RESPONSE FLUSH PENDENT SPRINKLERS TECHNICAL DATA

RESEARCH TECHNICAL REPORT. SMART Sprinkler Protection for Highly Challenging Fires - Phase 2: Full-Scale Fire Tests in Rack Storage

microfast quick response extended coverage hsw sprinkler vk606

qr fusible element sprinklers (part nos , 13959, 17535, and 17536) 3. technical data Sprinkler 42h March 14, 2013

Refer to the specific sprinkler or spray nozzle technical data pages for sprinkler listings and approvals.

RAPID RESPONSE Series LFII Residential Sprinklers 4.9 K-factor Recessed Pendent, Dry Type Wet Pipe and Dry Pipe Systems General Description

standard response/ quick response extended coverage

Facilities, 2012 edition.

FREEDOM RESIDENTIAL CONCEALED PENDENT SPRINKLER VK457 (K4.9) TECHNICAL DATA

TECHNICAL DATA STANDARD/QUICK RESPONSE EXTENDED COVERAGE LIGHT HAZARD ELO PENDENT SPRINKLER VK608

HORIZON STANDARD RESPONSE FLUSH PENDENT SPRINKLER VK400 TECHNICAL DATA

Exaggerated for Clarity. Residential Pendent, Recessed Pendent. System No. Submitted By Spec Sect Para Location Date Approved Date

TECHNICAL DATA. Viking Technical Data may be found on Minimum Operating Pressure: Refer to the Approval Chart.

Transcription:

Significant Advancements in Water Based Fire Suppression for Storage Occupancies Presented by: James Golinveaux Sr. Fellow Tyco Fire Protection Products

Higher Faster - Further How high can we go? Ceiling Only? 2

The Challenge Currently NFPA 13 and FM 8-9 limit Ceiling Only protection for some commodities to 45 ft (13.7m). UL Specific Application Sprinklers (Reliable K22 and Tyco K25 ESFR) extend Ceiling Only protection for some commodities to 48 ft (14.6m). K14 (200) ESFR have been limited to 35 ft (10.6m) ceilings from it s original 40 ft (12m) application. When installing in-rack sprinklers, most vertical spacing's are limited to 10 ft (3m) to 12 ft (3.7m) requiring many levels of in-rack sprinklers. At what height is Control Mode not enough for local fire department capability? There are 17 different sprinklers in CMDA, CMSA and ESFR categories to select from for storage applications. 3

4

What is the Big Deal? FM Global and NFPA have made Significant Changes for Storage in 2011 and 2012 FM has eliminated all names of storage sprinklers such as ESFR, CMSA and CMDA, NFPA still uses the names to differentiate the rules FM has banned K5.6 (K80) and K8.0 (K115) from ceiling protection of storage, NFPA restricts the use but not a ban FM has banned 286 degree (high temperature) sprinklers from wet systems FM has eliminated density and area from design considerations, NFPA still highly dependent on density curves FM has eliminated storage height from design consideration of ceiling only protection, storage height and clearance a significant design consideration in NFPA FM and NFPA now recognize ceiling only designs with as few as 6 sprinklers in the hydraulic demand. 5

What s Important? Getting the commodity class correct. Recognizing storage arrangement and shelving definition limitations within design schemes. Picking the best sprinkler orifice and temperature for the ceiling height. Being able to sleep at night knowing that the facility operators know what a flue space is, a plywood shelf is not considered open and storage should be removed from the bottom of the pile to not exceed clearance limitations??? 6

K5.6 Spray 7 psi (0.5 bar) to 100 psi (7 bar) 7

K25EC Droplet Size 7 psi (0.5 bar) to 100 psi (7 bar) 8

Droplets Ability to Penetrate the Fire Plume 22 MPH (45 KPH) 9

Small Drops are Carried Back to Ceiling - May Skip or Prevent Adjacent Sprinklers from Opening Skipping 22 MPH (45 KPH) 10

NFPA 13 K-factor Requirements for Storage Protection NFPA 13, 2013 Edition Density K-factor 12.6.1: densities of 0.20 gpm/ft2 (8.2 mm/min) or less 5.6 (80) & larger 12.6.2: densities of greater than 0.20 gpm/ft 2 (8.2 mm/min) to 0.34 gpm/ft 2 (13.9 mm/min) 8.0 (115) & larger 12.6.3: densities greater than 0.34 gpm/ft 2 (13.9 mm/min) 11.2 (160) & larger FM 8 9 2.3.3.2.1 Use only FM Approved sprinklers listed in the Approval Guide under the heading of Storage Sprinklers (Ceiling Level) for any ceiling level sprinkler options in this data sheet. Currently, FM Approved ceiling level Storage sprinklers have K factor values ranging from 11.2 (160) to 25.2 (360). 11

K8.0 (115).33 gpm/ft 2 / 3000 sq ft (13.44 / 279)

EC-25

CMDA - Pressure is not the Issue PRESSURE (PSI) 100.0 95.0 90.0 85.0 80.0 75.0 70.0 65.0 60.0 55.0 50.0 45.0 40.0 35.0 30.0 25.0 20.0 15.0 10.0 5.0 0.0 0.45 0.5 0.55 0.6 0.65 0.7 0.8 K5.6 K8.0 K11.0 K17-231 K25 EC DENSITY (100 SQ FT) 14

Chapter 14 Example - 30 ft (9.1m) Class IV Palletized Storage under a 35 ft (10.6m) Ceiling Wet System CMSA Sprinkler Demand GPM (LPM) CMDA Figure 14.2.4.2 0.30 gpm/ft 2 (12.2 mm/min) X 190% (Figure 14.2.4.3) =.57 gpm/ft 2 (23.2 mm/min) over 2000 ft 2 (186 m 2 ) Table 14.1.3 - Hose allowance is 500 gpm (1900 L/min) for 150 minutes K11.2 (160) @ 100 ft 2 = 26 psi (1.8 bar) K16.8 (240) @ 100 ft 2 = 11.5 psi (0.8 bar) Hose Demand GPM (LPM) Total Flow GPM (LPM) Duration Minutes Total Gallons (Liters) Sprinkler Demand GPM (LPM) 1,470 (5,476) Table 14.3.1 K19.6 (280) Pendent 15 sprinklers @ 25 psi (1.7 bar) = 15 x 98 gpm = 1470 (5564 L/min) Table 14.3.1 - Hose allowance is 500 gpm (1900 L/min) for 90 minutes Hose Demand GPM (LPM) 500 (1,900) Total Flow GPM (LPM) 1,970 (7,376) Duration Minutes 90 Total Gallons (Liters) 177,300 (663,840) Sprinkler Demand GPM (LPM) ESFR Table 14.4.1 K25.2 (360) Pendent 12 sprinklers @ 20 psi (1.4 bar) = 12 x 113 gpm = 1356 (5112 L/min) Table 14.4.1 - Hose allowance is 250 gpm (946 L/min) for 60 minutes Hose Demand GPM (LPM) 1,356 (5,112) 250 (946) Total Flow GPM (LPM) 1,606 (6,058) Duration Minutes 60 Total Gallons (Liters) 96,360 (363,480) 1,140 (4,315) 500 (1,900) 1,640 (6,215) 150 246,000 (932,250) 15

NFPA 13 2013 New Chapter 21 -Alternative Sprinkler System Designs for Chapters 12 Through 20 - DRAFT Storage Arrangement Commodity Class Maximum Storage Height Maximu m Ceiling/R oof Height ft m ft m 20 6.1 30 9.1 K Factor/ Orientation 25.2 (360) Upright/ Pendent Number of Type of Design system Sprinklers Wet 6 Minimum Operating Pressure 30 psi (2.1 bar) Maximum Coverage Area 12ft x 12ft (3.6m x 3.6m) 144 ft 2 (13.4 m 2 ) Hose Stream Allowance 250 gpm (950 L/ min) Water Supply Duration (hours) 1 SPECIAL Table 21.2 K25.2 EC (360) Upright 8 sprinklers @ 40 psi (2.6 bar) = 8 x 159 gpm = 1272 (4815 L/min) Sprinkler Protection Criteria for Open Frame Rack Storage Class I Through Class IV, encapsulated and unencapsulated, and Cartoned Unexpanded Plastics 20 6.1 30 9.1 25 7.6 30 9.1 25 7.6 30 9.1 25 7.6 35 11 25.2 (360) Upright/ Pendent 25.2 (360) Upright/ Pendent 25.2 (360) Upright/ Pendent 25.2 (360) Upright/ Pendent Wet 6 Wet 6 Wet 6 Wet 8 30 psi (2.1 bar) 30 psi (2.1 bar) 30 psi (2.1 bar) 40 psi (2.6 bar) 14ft x 14ft (4.2m x 4.2m) 196 ft 2 (18.2 m 2 ) 12ft x 12ft (3.6m x 3.6m) 144 ft 2 (13.4 m 2 ) 14ft x 14ft (4.2m x 4.2m) 196 ft 2 (18.2 m 2 ) 12ft x 12ft (3.6m x 3.6m) 144 ft 2 (13.4 m 2 ) 250 gpm (950 L/ min) 250 gpm (950 L/ min) 250 gpm (950 L/ min) 250 gpm (950 L/ min) 1 1 1 1 Table 21.2 - Hose allowance is 250 gpm (946 L/min) for 60 minutes K25.2 EC (280) @ 144 ft 2 (13.4 m 2 ) 25 7.6 35 11 25.2 (360) Upright Wet 8 40 psi (2.6 bar) 14ft x 14ft 500 (4.2m x 4.2m) 196 ft 2 (18.2 m 2 (1800 L/ min) ) 1.5 30 9.1 35 11 30 9.1 35 11 25.2 (360) Upright/ Pendent 25.2 (360) Upright Wet 8 Wet 8 40 psi (2.6 bar) 40 psi (2.6 bar) 12ft x 12ft (3.6m x 3.6m) 144 ft 2 (13.4 m 2 ) 250 gpm (950 L/ min) 14ft x 14ft 500 (4.2m x 4.2m) 196 ft 2 (18.2 m 2 (1800 L/ min) ) 1 1.5 Sprinkler Demand GPM (LPM) Hose Deman d GPM (LPM) Total Flow GPM (LPM) Duratio n Minute s Total Gallons (Liters) Table 21.3.1 Sprinkler Protection Criteria for Open Frame Rack Storage of Class I Through Class IV and Cartoned Unexpanded Plastic Commodities. 1,275 (4,819) 250 (946) 1,525 (5,769) 60 91,500 (346,14 0) 16

NFPA 13 Chapter 14 Example - 30 ft (9.1m) Class IV Palletized Storage under a 35 ft (10.6m) Ceiling Wet System - Summary Sprinkler Type Total Flow GPM (LPM) Total Gallons (Liters) CMDA K11.2 (160) or Greater 1,640 (6,215) 246,000 (932,250) CMSA - K19 (280) Pend 1,970 (7,376) 177,300 (663,840) ESFR - K25 (360) ESFR 1,606 (6,058) 96,360 (363,480) Special - K25 (360) EC 1,525 (5,769) 91,500 (346,140) 17

FM 8-9 Example - 30 ft (9.1m) Class IV Palletized Storage under a 35 ft (10.6m) Ceiling Wet System FM Engineering Bulletin 06 11 90 Minutes error in EB 18

FM 8-9 Example - 30 ft (9.1m) Class IV Palletized Storage under a 35 ft (10.6m) Ceiling Wet System From Table 3 35 ft (10.5m) Ceiling Height Table 3 Sprinkler Demand GPM (LPM) Hose Demand GPM (LPM) K25.2EC (K360EC) Pendent and Upright 12ft x12ft (3.6m) 8 @ 40 psi (2.8 bar) 1,275 (4,819) 1,525 (5,769) K25.2EC (K360EC) Upright 14ft x14ft (4.2m) 8 @ 40 psi (2.8 bar) 1,275 (4,819) 1,775 (6,719) K16.8 QR (K240) Pendent 10ft x 10ft (3.0m) 12 @ 50 psi (3.5 bar) 1426 (5,388) 1676 (6,338) Duration Minutes 60 min 90 min 60 min Total Gallons (Liters) 91,500 (346,140) 159,750 (604,654) 100,560 (380,280) 19

NFPA and FM 8-9 Example - 30 ft (9.1m) Class IV Palletized Storage under a 35 ft (10.6m) Ceiling Wet System Sprinkler Demand GPM (LPM) Hose Demand GPM (LPM) Total Flow GPM (LPM) Duration Minutes CMDA K11.2 (160) or Greater 30 ft (9.1m) Class IV Palletized Storage under a 35 ft (10.6m) Ceiling Wet System CMSA - K19 (280) Pend NFPA 13 FM 8 9 ESFR - K25 (360) ESFR NFPA 13 2013 Special - K25 (360) EC 12ft x12ft (3.6m) 8 @ 40 psi (2.8 bar) K25.2EC (K360EC) Pendent and Upright 12ft x12ft (3.6m) 8 @ 40 psi (2.8 bar) K25.2EC (K360EC) Upright 14ft x14ft (4.2m) 8 @ 40 psi (2.8 bar) K16.8 QR (K240) Pendent 10ft x 10ft (3.0m) 12 @ 50 psi (3.5 bar) 1,140 (4,315) 1,470 (5,476) 1,356 (5,112) 1,275 (4,819) 1,275 (4,819) 1,275 (4,819) 1426 (5,388) 500 (1,900) 500 (1,900) 250 (946) 250 (946) 250 (946) 500 (1,900) 250 (946) 1,640 (6,215) 1,970 (7,376) 1,606 (6,058) 1,525 (5,769) 1,525 (5,769) 1,775 (6,719) 1676 (6,338) 150 90 60 60 min 60 min 90 min 60 min Total Gallons (Liters) 246,000 (932,250) 177,300 (663,840) 96,360 (363,480) 91,500 (346,140) 91,500 (346,140) 159,750 (604,654) 100,560 (380,280) 20

45 ft (13,7 m) Ceiling Recommendation Rack Storage With No In-Rack Sprinklers Model ESFR-25 K-Factor 25.2 (360) NFPA/FM Global Exceptions No Solid Shelves Open-top containers Uncartoned Unexpanded Plastic Cartoned or Uncartoned Expanded Plastic 45 ft (13,7 m) Ceiling Above Finished Floor 21

2 2 Expanded Exposed Plastic

ESFR 25 Exclusives - NFPA Table 15.4.1 The only ESFR recognized to protect Palletized or Solid Piled Exposed Expanded Plastic Table 18.4(d) Rubber Tires The only ESFR to protect laced tire storage up to 25 ft (7.6m) under a 40 ft (12.1m) ceiling Table 18.4(d) Rubber Tires The only ESFR to protect up to 30 ft (9.1m) storage under a 40 ft (12.1m) ceiling Table 18.4(d) Rubber Tires The only ESFR to protect up to 30 ft (9.1m) palletized portable rack storage under a 40 ft (12.1m) ceiling Table 20.2 Automotive Components The only ESFR to protect Automotive Components to 25 ft (7.6m) storage under a 35 ft (10.7m) ceiling Section 20.3.7 Big Box Retail Plastics in Display Shelving The only ESFR for Storage to 20 (6.1m) under a 30 ft (9.1m) ceiling. Only ESFR in the Retail section. Section 20.7.3 High Bay Record Storage the only ESFR recognized for High Bay Record Storage up to 34 ft (10.4m) high. 23

ESFR 25 (Pend QR) Exclusives FM 8-9 Table 4 Protection of Cartoned Expanded Plastic Commodities in Solid-Piled, Palletized, Shelf, and Bin-Box Arrangements The only ESFR (Pend QR) to protect 35 ft (10.7m) and 40 ft (12.1m) high ceilings Table 6 Protection of Uncartoned Expanded Plastic Commodities in Solid- Piled, Palletized, Shelf, and Bin-Box Arrangements The only ESFR (Pend QR) to protect 35 ft (10.7m) and 40 ft (12.1m) high ceilings Table 9 Protection of Cartoned Expanded Plastic Commodities in Open- Frame Storage Racks The only ESFR (Pend QR) to protect 35 ft (10.7m) and 40 ft (12.1m) high ceilings Table 10 Protection of Uncartoned Unexpanded Plastic Commodities in Open-Frame Storage Racks; The only ESFR (Pend QR) to protect 35 ft (10.7m) and 40 ft (12.1m) high ceilings Table 11 Protection of Uncartoned Expanded Plastic Commodities in Open- Frame Storage Racks - The only ESFR (Pend QR) to protect 35 ft (10.7m) and 40 ft (12.1m) high ceilings 24

EC-25 Pendent In-Rack (Reliable) Performance Based Protection FSC7JY

EC-25 Pendent (Reliable) Performance Based Protection

EC-25 Pendent (Reliable) Performance Based Protection N252 EC Sprinklers Centered in Longitudinal Flue and Centered Between Rack Uprights = 8-3 on center.

Testing with a Continuous Barrier Across the Uprights Tests 1, 2, & 3 Tests 4 & 5

EC-25 Pendent (Reliable) Performance Based Protection

EC-25 Pendent (Reliable) Performance Based Protection For storage of exposed expanded plastics in double row, open framed racks: By installing a horizontal barrier at the 20 level with the Model N252 EC Pendent, used as in-rack sprinklers, buildings up to 40 high will have lower water demands than using ceiling-only sprinkler protection. By installing continuous horizontal barriers at 20 to 30 levels with the Model N252 EC Pendent, used as inrack sprinklers, buildings over 48 high may be protected while reducing the number of sprinklers required by current in-rack schemes. Fires may be contained between barriers with no horizontal spread.

ESFR- Dry-Type K14 (200) & K17 (240) Ambient Temperature of Discharge End of Sprinkler Exposure Length of Sprinkler inches (mm) in Heated Area Temperature of Heated Area 40 F (4 C) 40 F (4 C) 0 30 F ( 1 C) 0 20 F ( 7 C) 4 (100) 10 F ( 12 C) 8 (200) 0 F ( 18 C) 12 (305) 10 F ( 23 C) 14 (355) 20 F ( 29 C) 14 (255) 30 F ( 34 C) 16 (405) 40 F ( 40 C) 18 (455) 50 F ( 46 C) 20 (510) 60 F ( 51 C) 20 (510) Do not attempt to add additional insulation around the barrel in the heated area as a method to minimize condensation. This will reduce the calculated Exposure Length. 31

UL Specific Application Listing K22 & K25 ESFR Provide ceiling-only protection up to and including: 48 ft (14.6 m) Ceiling 43 ft (13.1 m) Storage Eliminates need for in-rack sprinklers for storage arrangements beyond NFPA 13 Lower pressure provides flexibility when sizing system piping when compared to other listed sprinklers 10-Year Limited Warranty 3 2

Specific Application Listing ESFR-25 Key Design Criteria Temperature rating: 212 F (100 C) Deflector to top of storage: 36 in (914 mm) Deflector to ceiling distance 6 14 in (152 356 mm) Sprinkler system design: NFPA 13 for ESFR Sprinkler based on 45 PSI (3.1 bar) Minimum aisle width: 8 ft (2,4 m) 33

Where In-Racks Become Mandatory Based on Type of Sprinkler and Storage or Ceiling Height NFPA 13 Chapter Commodity Storage Height Building Height CMDA CMSA ESFR Class IV >22 ft (6.7 m) NA x Class I - III >25 ft (7.6 m) NA x 16 Class I - IV >35 ft (10.6) >40 ft (12.1 m) x Class I - IV >40 ft (12.1 m) >45 ft (13.7 m) x 17 Group A plastic commodities in cartons, encapsulated or nonencapsulated Group A plastic Cartoned Unexpanded Group A plastic Cartoned Unexpanded Group A plastic Exposed Unexpanded 20 ft (6.1 m) >25 ft (7.6 m) x >20 ft (6.1 m) NA x >35 ft (10.6) >40 ft (12.1 m) x >40 ft (12.1 m) >45 ft (13.7 m) x >35 ft (10.6) >40 ft (12.1 m) x 34

Where In-Racks Become Mandatory Based on Type of Sprinkler and Storage or Ceiling Height FM 8-9 Where In Racks Become Mandatory Based on Ceiling Height FM 8 9 Chapter Commodity Building Height Class I IV and Cartoned Unexpanded Plastic >45 ft (13.7 m) Tables 7 11 Cartoned and Uncartoned Expanded Plastic >40 ft (12.1 m) 35

3 6 ESFR Obstructed

Summary We are approaching the maximum one shot protection scheme (ceiling only). In-rack sprinklers may need to perform closer to suppression sprinklers when heights exceed local fire brigade operations. The faster the sprinklers activate the better (now that the orifice sizes are regulated). Allowing adjustments based on storage heights may cause future concerns. 37