Hot Water Temperature Maintenance. HWAT System. Product Selection and Design Guide

Similar documents
HOT WATER TEMPERATURE MAINTENANCE HWAT SYSTEM

Design Guide Design Notes Design Examples Technical Data Sheets Expanded Capabilities Specifications Warranty

Hot Water Temperature Maintenance Product Selection and Design Guide

HWAT -ECO. Installation and Operation Manual. Electronic controller for hot water temperature maintenance systems

XL-Trace System Application and Design Guide

Hot water temperature maintenance. Less water volume and less heat loss in the pipe work help prevent bacteriological

Pipe Freeze Protection. Flow Maintenance. Introduction. XL-Trace System

Freezer Frost Heave Prevention

FIRE SPRINKLER SYSTEM FREEZE PROTECTION XL-TRACE SYSTEM

Roof and Gutter De-Icing

CSI Master Format 2012 Guide Specification for: Hot Water Temperature Maintenance (HWAT) Systems

RayClic Connection System

CSI Master Format 2004 Guide Specification for: Flow Maintenance of Aboveground Fuel Oil Lines

CSI Master Format 2004 Guide Specification for: Flow Maintenance of Above Ground Greasy Waste Disposal Lines

THERMAL MANAGEMENT SOLUTIONS

ROOF AND GUTTER DE-ICING ICESTOP SYSTEM

ECW-GF, ECW-GF-DP DIGITAL ELECTRONIC CONTROLLERS AND REMOTE DISPLAY PANEL PRODUCT OVERVIEW

Union County Vocational - Technical Schools Scotch Plains, New Jersey

THERMAL MANAGEMENT SOLUTIONS

Gardian W51. Approvals

DESIGN GUIDELINES. THERMAL building SOLUTIONS

Domestic Hot Water Application manual

Technical Handbook

Commercial and Residential Self-Regulating Heating Products

PLSRR Heat Trace Cable Data Sheet

XL-Trace System. Installation and Operation manual for pipe freeze protection and flow maintenance

HWT-P HWAT POWER CONNECTION KIT WITH END SEAL INSTALLATION INSTRUCTIONS

SMPG3 SNOW MELTING AND DE-ICING POWER DISTRIBUTION AND CONTROL PANEL. For three-phase heating cables PRODUCT OVERVIEW

FreezGard. Self-regulating crankcase heater. Product Overview

COMMERCIAL & RESIDENTIAL SELF-REGULATING HEATING PRODUCTS APPLICATION AND DESIGN GUIDE EUROPE, MIDDLE EAST, AFRICA

JBS-100-ECP-A COMBINATION POWER CONNECTION BOX AND DIGITAL ELECTRONIC CONTROLLER INSTALLATION INSTRUCTIONS

XL-Trace System Installation and Operation Manual

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

CSI Master Format 2004 Guide Specification for: Freezer Frost Heave Prevention (Mineral Insulated)

Fire Sprinkler Freeze Protection Design / Install Guide

SMPG1 SNOW MELTING AND DE-ICING POWER DISTRIBUTION AND CONTROL PANEL FOR SINGLE-PHASE HEATING CABLES PRODUCT OVERVIEW

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

Snow melting for ramps, access ways, and footpaths

C A Heating Cable Gland Kit

NGC-40 Advanced Heat-Tracing Control System

1SC-SSC Splice Connection Kit Installation Instructions

ITC 2000 HEATING CONTROL CABINET. Installation & Operation Manual

920 Series. A dry contact relay is provided for alarm annunciation back to a distributed control system (DCS).

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

ACCS-30. Multipoint commercial heat-tracing control system

SPECIFICATION GUIDELINE FROST PROTECTION FOR PIPES. Tender Specification. Engineering Specification for Pipe Frost Protection. Contents.

Principle of Operation:

Heat Tracing Sales Mt. Airy, Maryland Heating Cable. Cut to Length in Field. Description

Technical handbook. Temperature maintenance and frost protection systems

JBM-100-LBTV2 Power Connection, Powered Splice, Dual Power Connection, or Splice with Junction Box

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT

IceStop System Installation and Operation Manual

JBS-100-EC Electronic controller replacement kit for JBS-100-ECP-A and JBS-100-ECW-A Installation Instructions

Data Sheet. Self regulating process heating tapes RS stock numbers ,

NELSON HEAT TRACING SYSTEMS

ACS-30 MULTIPOINT COMMERCIAL HEAT-TRACING SYSTEM PRODUCT OVERVIEW. ACS-30 System

NELSON HEAT TRACING SYSTEMS INSTALLATION

H908 WinterGard Plug-in Power Connection Kit with End Seal

JB-RTD-STAND RTD PIPE STAND FOR COMBINATION POWER CONNECTION BOX AND ELECTRONIC CONTROLLER INSTALLATION INSTRUCTIONS

PANEL MOUNTED ELECTRONIC MULTI-CIRCUIT HEAT-TRACING CONTROL, MONITORING AND POWER DISTRIBUTION SYSTEM mm. 100 mm

Consignes d installation

Data Sheet. Self regulating heating tapes. RS stock numbers

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

C910 Series. Single-point heat-tracing control system

RAYCHEM NGC-30 COMPONENTS

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

Frost Heave Protection System Installation and Operation Manual

Frequently asked questions: Intelligent Transmitter Series

C Electrical Connection Kit

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3 PRODUCT OVERVIEW

COLD WEATHER SOLUTIONS: ELECTRIC HEAT AND CONTROL PRODUCTS

INSTALLATION INSTRUCTIONS FOR 6532 SERIES PACKAGE HEAT PUMP

SECTION LOW VOLTAGE LIGHTING CONTROLS

FTC-HST WARNING: CAUTION:

Control Relay Modules

TRACENET TM GENESIS CONTROL AND MONITORING SYSTEM SPECIFICATION GUIDE

Heating cable solutions for temperature-related problems

NGC-40 PANEL MOUNTED ADVANCED MODULAR HEAT-TRACING CONTROL SYSTEM HTC HTC3

SECTION AUTOMATIC TRANSFER SWITCHES

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

910 Series Single-point heat-tracing control system

Polymer solutions Heating mat EM2-CM

F1202 TRACE HEATING. Road & Ramp

OPERATING AND INSTALLATION MANUAL

INSTALLATION INSTRUCTIONS AND OWNER S MANUAL FOR

NELSON HEAT TRACING SYSTEMS ALT-BC STANDARD POWER CONNECTION KIT

ACS-30-EU-VIA-DU-20-MOD

IceStop System INSTALLATION AND OPERATION MANUAL FOR ROOF AND GUTTER DE-ICING SYSTEMS

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS

SCM. Micro. Streaming Current Monitor. Analyzer. Sensor/Sampler with light shield removed. The Analyzer. Instrument Overview

Self-regulating Roof Heat and Gutter Trace Cable

BC3250. Blowdown Controller

SECTION RADIANT-HEATING ELECTRIC CABLES PART 1 - GENERAL 1.1 SECTIONS INCLUDES

Drexan Energy Systems Inc.

HTC-915-CONT. Heat-Trace Control system

Oxygen (O2) Single-Point Gas Detection System

isopv and AGH-PV Ground Fault Detector for Ungrounded Solar Arrays up to 1100 V And Isolation Tester Prior to Array Startup (Grounded and Ungrounded)

Self-regulating Roof Heat Cable

NELSON HEAT TRACING SYSTEMS

Transcription:

Hot Water Temperature Maintenance HWAT System Product Selection and Design Guide

A Solutions Company Tyco Thermal Controls provides complete heat tracing and specialty wiring solutions for the industrial, commercial, and residential markets. Employing over one thousand people around the world, Tyco Thermal Controls is the global leader in total solutions. Worldwide Approach With operations in 48 countries and worldwide experience, Tyco Thermal Controls can support your project efforts anywhere, anytime. Whether it is state-of-the-art products or turnkey services, Tyco Thermal Controls has the solution. The Raychem Brand Raychem is the leading brand in electric heat-tracing solutions. In 1971, Raychem Corporation introduced the world s first self-regulating heat-tracing products. By 1980, self-regulating heating cables had become the industry standard worldwide. Today, Raychem brand heating cables continue to be recognized as the leading solution for Hot Water Temperature Maintenance, Pipe Freeze Protection, Snow Melting, Roof & Gutter De-icing, and Floor Warming applications. Raychem HWAT System The HWAT system provides a simple way to keep water at a consistent warm temperature, regardless of how complex the building. Already installed in more than 100,000 hotels, hospitals, apartments, offices, schools, nursing homes, and correctional facilities around the world, the HWAT system offers a simple, reliable alternative to recirculation.

The Optimal Hot Water Temperature Maintenance System Comfortable and energy efficient Today s hot water system requirements focus on users comfort as well as operational and energy savings. With this in mind, the Raychem HWAT System keeps the hot water at the right temperature everywhere in the building while saving energy at the same time. Simple, effective and intelligent The HWAT system ensures an abundant supply of hot water at the same temperature throughout the building while eliminating the need for return piping. The HWAT heating cable is attached to a hot water pipe, keeping the water at the desired temperature. The cable continuously senses the temperature of the pipes, and will modify its heat output accordingly. Combined with the HWAT-ECO controller, HWAT is a sophisticated temperature and energy management system. The HWAT system provides real energy savings and delivers quality hot water. Return piping, balancing valves and pumps required in a recirculation system are eliminated in an HWAT System, branches and risers can be traced easily, as indicated in the above illustration. HWAT systems can be found in a variety of commercial buildings, including hospitals, office and retail buildings and schools.

Intelligent Energy & Cost Saving Less energy consumption The self-regulating technology manages the heat output locally. Heat loss is lower with only 1 pipe as opposed to a recirculation system that requires return piping. Because a recirculation pump is not needed, energy is saved. Water heater efficiency is optimized, therefore, a smaller water heater can be used. Because hot water is maintained along the entire length of supply pipe, there is no need to overheat the supply water at the beginning of the cycle, as with a recirculation system. The HWAT-ECO electronic controller calculates the amount of on time required to maintain the desired temperature. When water usage is low, maintain temperatures can be reduced. When water usage is high and hot water is flowing from the water heater to the point of use without delay, the heating cable can be turned off. Economical in design and installation A Single pipe: no need for complex pressure and balance calculations or drawings which saves design time. Simple Design: The length of pipe corresponds to the length of heating cable that is required. Easy to install: the system uses few components. The cable is attached directly onto the hot water pipe under the thermal insulation. No need for return pipe works, valves or pumps! Fast connection: the RayClic system allows for connections to be made quickly. The lengths of pipe correspond to the lengths of heating cable needed.

The Secret is in the Heating Cable Automatic temperature adjustment The self-regulating heating cable really is the heart of the system. It senses the temperature of the pipes and modifies the heat output accordingly. The self-regulating cable can be installed on all the supply piping to ensure that instant hot water is available at every tap. Optimized for efficient energy usage The easy-to-program HWAT-ECO controller modulates the heating cable in accordance with the specific requirements of your building. It even monitors water heater temperatures to ensure that the system is only used for temperature maintenance; not for heating the water. This minimizes energy consumption. Flexible temperature control: variable temperature maintenance in the range 105-140 F (40 60 C). Building Management System (BMS) compatibility: The HWAT- ECO controller allows connection to a BMS system, enabling remote temperature maintenance and continual feedback through the alarm contacts. Monitors the water heater temperature: activates an alarm and adjusts the maintain temperature setpoint automatically when the water heater temperature falls below the maintain temperature. Nine building specific-programs: make programming of complex buildings easier. Master/slave function: allows one controller to network with up to eight additional controllers for fast programming. Simplified Installation The RayClic connection system cuts installation time considerably. Power, splice and tee connections are made easily and reliably. Tightening two screws is all it takes. No need for special tools. Minimal heating cable stripping. No heat- shrink components. Top: HWAT-R2 heating cable. Center: HWAT-ECO controller. Bottom: RayClic connection kit.

Time to Tap Immediate hot water The HWAT system provides commercial buildings with immediate hot water at the tap without the use of a water recirculation system. Save time and water with the HWAT system. 2 minutes spent waiting per use and 1825 gallons of water wasted per year! Recirculation System Low flow fixtures typically use.5 gallons of water per minute (gpm). In this example, with a recirculation system, it would take 2 minutes for hot water to arrive at the fixture located 50 feet away from the recirculation loop. Water in 10 feet of 1/2 pipe: Water in 40 feet of 3/4 pipe: Water between fixture and recirculation loop: 0.1 gallons 0.9 gallons 1.0 gallons If this fixture were used 5 times per day, the annual water waste would be 1,825 gallons per year! The Raychem HWAT system delivers instant hot water with zero water waste and requires zero waiting.

Raychem HWAT Hot Water Temperature Maintenance System The Raychem HWAT System is a hot water temperature maintenance system that provides immediate hot water without the use of a water recirculation system. This product selection and design guide provides all the information necessary to select and design an HWAT system. For information regarding other products and applications, contact Tyco Thermal Controls at (800) 545-6258. Also, visit our web site at www.tycothermal.com. Contents Raychem HWAT Hot Water Temperature Maintenance System..................... 1 Section 1: Design Guide..................................................... 1 Section 2: Design Examples................................................. 13 Section 3: Technical Data Sheets HWAT Heating Cables.................................................. 17 HWAT -ECO.......................................................... 19 RayClic Connection System.............................................. 22 Section 4: Expanded HWAT -ECO Electronic Controller Capabilities.................. 25 Section 5: Specification..................................................... 29 Section 6: Limited Warranty................................................. 33 9/04 (800) 545-6258 www.tycothermal.com Tyco Thermal Controls

RAYCHEM HWAT HOT WATER TEMPERATURE MAINTENANCE SYSTEM Tyco Thermal Controls www.tycothermal.com(800) 545-6258 9/04

Section 1: Design Guide This step-by-step design guide provides the tools necessary to design a Raychem HWAT Hot Water Temperature Maintenance System. For additional information, contact your Tyco Thermal Controls representative or phone Tyco Thermal Controls at (800) 545-6258. Also, visit our web site at www.tycothermal.com. Section Contents Introduction............................................................. 1 Typical Applications.................................................... 1 Approvals and Code Compliance........................................... 2 Safety Guidelines....................................................... 2 Ground-Fault Protection................................................. 3 Design Requirements................................................... 3 System Overview......................................................... 3 HWAT-ECO Electronic Controller........................................... 4 HWAT Heating Cables................................................... 4 RayClic Connection Kits................................................ 6 Design Guidelines......................................................... 6 Before You Begin....................................................... 7 Introduction The Raychem HWAT System is a hot water temperature maintenance system that utilizes an electronic controller, self-regulating electric heating cables, and an easy-to-install set of connection kits to provide commercial buildings with immediate hot water at the tap without the use of a water recirculation system. Recirculation systems require the water heater temperature to be at least five degrees above the maintain temperature to compensate for the heat that is lost in the recirculation loop. With HWAT systems, the water in the supply pipe is maintained at a constant temperature along the entire length of the supply pipe so heating the water above the maintain temperature is not required. Recirculation systems also require return lines, pumps, and balancing valves, all of which are all unnecessary with HWAT. A key component of the HWAT system is the HWAT-ECO controller. In addition to providing flexible temperature control, the HWAT-ECO provides energy savings; a heat-up cycle that increases the water temperature in stagnant pipes; Building Management System (BMS) interface; alarm relay to signal power, temperature, or communication problems; a water heater sensor function; and nine predefined programs that can be customized by the user. H57510 9/04 (800) 545-6258 www.tycothermal.com Tyco Thermal Controls 1

SECTION 1: DESIGN GUIDE Typical Applications The HWAT system is designed to be installed and operated in commercial buildings. Table 1.1 shows typical HWAT applications, desired maintain temperatures, and the appropriate HWAT heating cable when used in conjunction with the HWAT-ECO controller. Table 1.1 Typical HWAT Applications Application Desired maintain temperature HWAT heating cable Hospitals, nursing homes 105 F (40 C) Y2 or R2 Schools, prisons, some 115 F (45 C) Y2 or R2 hospitals Offices, hotels, apartments 125 F (50 C) Y2* or R2 Kitchens, laundries 140 F (60 C) R2 * Depending on ambient conditions and supply voltage This design guide covers standard HWAT applications which must meet the following conditions: Installed on copper pipes Insulated in accordance with the insulation schedule shown in Table 1.7 Powered at 208 V or 240 V Operated indoors where the ambient temperature is relatively constant and between 60 F (15 C) and 80 F (26 C) If your application does not meet the above conditions, contact your Tyco Thermal Controls representative for custom design assistance. Approvals and Code Compliance The HWAT system, with or without the HWAT-ECO controller, is UL Listed, CSA Certified, and FM Approved in nonhazardous locations. 718K Pipe Heating Cable HWAT is also in compliance with the following international and national codes: International Plumbing Code International Building Code International Energy Conservation Code National Standard Plumbing Code National Electrical Code Canadian Electrical Code Additionally, HWAT has numerous state and local code approvals. Contact your Tyco Thermal Controls representative for further information. Safety Guidelines The safety and reliability of any heat-tracing system depends on the quality of the products selected and on proper design, installation, and maintenance. Incorrect design, handling, installation, or maintenance of any of the system components can cause underheating or overheating of the pipe or damage to the heating cable system and may result in system failure, electric shock, or fire. The guidelines and instructions contained in this guide are important. Follow them carefully to minimize these risks and to ensure that the HWAT system performs reliably. Pay special attention to safety warnings identified as WARNING. 2 Tyco Thermal Controls www.tycothermal.com (800) 545-6258 H57510 9/04

System Overview Ground-Fault Protection To minimize the danger of fire from sustained electrical arcing if the heating cable is damaged or improperly installed, and to comply with Tyco Thermal Controls requirements, agency certifications, and national electrical codes, ground-fault equipment protection must be used on each heating cable branch circuit. Arcing may not be stopped by conventional breakers. Design Requirements To comply with warranty requirements, the design and installation of the HWAT system must be in accordance with this guide and the additional documents listed below: HWAT-ECO Installation and Operations Manual (H57340) HWAT System Installation and Operations Manual (H57548) RayClic Connection Kit Installation Instructions (H55388 and H55092) Installation documents are shipped with the respective products and are also available via the Tyco Thermal Controls web site at www.tycothermal.com. System Overview A complete HWAT system includes one or more HWAT-ECO electronic controllers, HWAT-Y2 or HWAT-R2 heating cables, and RayClic connection kits. Figure 1.1 illustrates a typical HWAT system. The key components of the system will be described in this section. End seal Tee Heating cable Thermal insulation Controller Water heater Splice To power distribution panel Power connection Fig. 1.1 Typical HWAT heating cable system H57510 9/04 (800) 545-6258 www.tycothermal.com Tyco Thermal Controls 3

SECTION 1: DESIGN GUIDE HWAT-ECO Electronic Controller The Raychem HWAT-ECO is an electronic controller designed for use with HWAT-Y2 and HWAT-R2 self-regulating heating cables. The HWAT-ECO provides a variety of features and control options, listed below, for your hot water temperature maintenance system. Fig. 1.2 HWAT-ECO controller Flexible temperature control Selectable temperature control set points across the temperature range of the heating cable Energy savings Lowers the maintain temperature during low water usage hours and turns off the heating cable during peak water usage hours Heat-up cycle Increases the water temperature of a hot water system that is not in use Building Management System (BMS) interface Receives a DC voltage to determine the desired maintain temperature Alarm Signals power, temperature, or communication problems Water heater sensor Lowers the maintain temperature if the hot water supply temperature is too low Master/slave function Allows one HWAT-ECO to control up to eight additional HWAT-ECO controllers Programmable settings Nine predefined programs that can be customized by the user HWAT Heating Cables HWAT-Y2 and HWAT-R2 self-regulating heating cables are installed on hot water supply pipes underneath standard pipe insulation. The heating cable adjusts its power output to reduce the effect of ambient temperature swings. The HWAT system provides continuous hot water temperature maintenance while eliminating the need for a recirculation system. Modified polyolefin outer jacket Tinned-copper braid Polymer-coated aluminum wrap Modified polyolefin inner jacket Self-regulating conductive core Nickel-plated copper bus wires Fig. 1.3 HWAT-Y2 and HWAT-R2 heating cables 4 Tyco Thermal Controls www.tycothermal.com (800) 545-6258 H57510 9/04

Design Guidelines HWAT heating cables provide the following features: Adjust power output to reduce the variations in water temperature Can be cut to length, spliced, teed, and terminated in the field Designed for use with the HWAT-ECO controller RayClic Connection Kits The RayClic connection system is a simple, fast, and reliable set of connection kits developed for use with HWAT self-regulating heating cables. RayClic connection kits reduce installation time, lowering the total installed cost of the HWAT system. RayClic-PC RayClic-S RayClic-PT RayClic-E RayClic-X RayClic-PS RayClic-T Fig. 1.4 RayClic connection kits Design Guidelines This section describes the seven steps necessary to design an HWAT system: 1 Select the heating cable 2 Lay out the heating cable 3 Select connection kits and accessories 4 Finalize circuit length 5 Select control configurations 6 Select thermal insulation 7 Complete Bill of Materials To assist you with the design, we will carry two design examples through this process. The example details are listed below each step in red. Example 1 Example 2 An elementary school where 115 F (46 C) is the desired maintain temperature and no heat-up cycle is required. Piping layout shows approximately 300 ft of pipe with two branches at the same location. A medium security prison where 115 F (46 C) is the desired maintain temperature and a 140 F (60 C) heat-up cycle is required. Piping layout shows approximately 700 ft of pipe with two branches at different locations. H57510 9/04 (800) 545-6258 www.tycothermal.com Tyco Thermal Controls 5

SECTION 1: DESIGN GUIDE Before You Begin Before you begin designing your HWAT system, gather this necessary information: Desired maintain temperature Indoor ambient temperature Supply voltage Piping layout Total pipe length Pipe diameters HWAT System Design 1. Select heating cable 2. Lay out the heating cable 3. Select connection kits and accessories 4. Finalize circuit length 5. Select control configuration 6. Select insulation 7. Complete Bill of Materials Step 1 Select heating cable Use Table 1.2 and Figure 1.5 to select the appropriate heating cable. Whether you desire the capability of heating pipes above the maintain temperature will influence the selection of the heating cable. This capability is called a heat-up cycle. For more information on heat-up cycles, refer to Section 4: Expanded Capabilities of the HWAT-ECO Electronic Controller. If you are not sure if a heat-up cycle is required, or for the most flexibility in design, choose HWAT-R2. Record the following information: Desired maintain temperature ( F/ C) Indoor ambient temperature ( F/ C) Supply voltage (V) Heat-up cycle (Yes/No) Temperature ( F/ C) Example: Heating Cable Selection Example 1 Example 2 Desired maintain temperature 115 F (46 C) 115 F (46 C) Ambient temperature 70 F (21 C) 70 F (21 C) Supply voltage 208 V 208 V Heat-up cycle required No Yes Heat-up cycle temperature n/a 140 F (60 C) Table 1.2 HWAT System Temperature Range HWAT-Y2 HWAT-R2 Minimum maintain temperature 105 F (40 C) 105 F (40 C) Maximum maintain temperature See Fig. 1.5 140 F (60 C) Heat-up cycle* Up to 125 F (50 C) >140 F (60 C) * For additional information on heat-up cycles, refer to Section 4: Expanded HWAT-ECO Electronic Controller Capabilities 6 Tyco Thermal Controls www.tycothermal.com (800) 545-6258 H57510 9/04

Design Guidelines WARNING Burn Hazard Water temperatures above 120 F (50 C) can cause skin damage and pain. Be sure the correct HWAT cable is used and the HWAT-ECO is programmed properly. Avoid exposure to water during heat-up cycles or from water systems with high maintain temperatures during normal operation. Ambient temperature F ( C) 80 (27) 70 (21) 60 (16) 105 (41) HWAT-Y2 208V 110 (43) 115 (46) 120 (49) 125 (52) 130 (54) Maintain temperature F ( C) 135 (57) 140 (60) Ambient temperature F ( C) 80 (27) 70 (21) 60 (16) 105 (41) HWAT-Y2 240V 110 (43) 115 (46) 120 (49) 125 (52) 130 (54) Maintain temperature F ( C) 135 (57) 140 (60) Ambient temperature F ( C) 80 (27) 70 (21) 60 (16) 105 (41) 110 (43) 115 (46) HWAT-R2 208 & 240V 120 (49) 125 (52) 130 (54) Maintain temperature F ( C) 135 (57) 140 (60) Fig. 1.5 Maintain temperature capabilities Example: Heating Cable Selection Example 1 Example 2 Heating cable selected HWAT-Y2* HWAT-R2 * Selected for the longer cable circuit length HWAT System Design 1. Select heating cable 2. Lay out the heating cable 3. Select connection kits and accessories 4. Finalize circuit length 5. Select control configuration 6. Select insulation Step 2 Lay out the heating cable The piping layout of your building may require more than one HWAT circuit. To determine the number of circuits, group your piping by maintain temperature and location for convenience, a step that may require you to consult the plumbing and/or electrical engineer. Calculate the total length of pipe in each group, allowing one foot of heating cable for each foot of pipe. The length of heating cable in each group must not exceed the circuit lengths listed in Table 1.3. In Step 4, you will calculate the additional cable required to install the connection kits. This will increase the total length of heating cable and may require the need for additional circuits. 7. Complete Bill of Materials H57510 9/04 (800) 545-6258 www.tycothermal.com Tyco Thermal Controls 7

SECTION 1: DESIGN GUIDE Table 1.3 Maximum Circuit Lengths Circuit lengths Circuit breaker size (Amps) HWAT-Y2 ft (m) HWAT-R2 ft (m) 15 350 (105) 250 (75) 20 500 (150) 330 (100) 30 800 (240) 500 (150) Notes: Assumes a minimum water temperature of 50 F (10 C) at startup WARNING To minimize the danger of fire from sustained electrical arcing if the heating cable is damaged or improperly installed, and to comply with Tyco Thermal Controls requirements, agency certifications, and national electrical codes, ground-fault equipment protection must be used on each heating cable branch circuit. Arcing may not be stopped by conventional breakers. Example: Lay out circuits Example 1 Example 2 HWAT heating cable selected HWAT-Y2 HWAT-R2 Length of pipe 300 ft 700 ft Number of circuits 1 2 Circuit breaker size 15 Amp 30 Amp HWAT System Design 1. Select heating cable 2. Lay out the heating cable 3. Select connection kits and accessories 4. Finalize circuit length 5. Select control configuration 6. Select insulation 7. Complete Bill of Materials Step 3 Select connection kits and accessories HWAT systems are approved and warranted only as a complete system. The appropriate RayClic connection kits must be used. Use Table 1.4 to select the connection kits and accessories necessary for your HWAT system. Refer to the RayClic Connection System data sheet in the Technical Data section for more information on the products. The appropriate numbers of end seals are included with each connection kit. Table 1.4 RayClic Connection Kits and Accessories Catalog number Description Quantity required No. of end seals included RayClic-PC Power connection kit One -PC, -PS, -PT 1 required per circuit RayClic-PS Powered splice kit One -PC, -PS, -PT 2 required per circuit RayClic-PT Powered tee kit One -PC, -PS, -PT 3 required per circuit RayClic-S Splice kit As required* 0 RayClic-X Cross kit As required 2 RayClic-T Tee kit As required 1 RayClic-E End seal kit As required for spares 1 GT-66 Glass tape 1 roll per 50 ft of pipe n/a ETL Electric traced tape 1 label per 10 ft of pipe n/a * To minimize cable waste, Tyco Thermal Controls recommends that one RayClic-S be ordered for every 500 feet of cable. Example: Select connection kits and accessories Example 1 Example 2 Piping layout determined that the following 1 RayClic-PC 2 RayClic-PC connection kits and accessories are required. 1 RayClic-X 2 RayClic-T 6 GT-66 14 GT-66 30 ETL 70 ETL 8 Tyco Thermal Controls www.tycothermal.com (800) 545-6258 H57510 9/04

Design Guidelines HWAT System Design 1. Select heating cable 2. Lay out the heating cable 3. Select connection kits and accessories 4. Finalize circuit length 5. Select control configuration 6. Select insulation 7. Complete Bill of Materials Step 4 Finalize circuit length Additional cable is required for future access at each connection kit. Add the additional cable, as detailed in Table 1.5, to the estimated circuit lengths from Step 2. Confirm that the maximum lengths shown in Table 1.3 have not been exceeded. If your circuit lengths are greater than those shown, reconfigure your heating cable layout to allow for additional circuits. Table 1.5 Additional Cable Required for Each Connection Kit Connection kit name No. of cable connections/kit Cable length/ connection ft (m) Total cable length (service loop) ft (m) RayClic-PC 1 2.0 (0.6) 2.0 (0.6) RayClic-S 2 1.0 (0.3) 2.0 (0.6) RayClic-T 3 1.0 (0.3) 3.0 (0.9) RayClic-X 4 1.0 (0.3) 4.0 (1.2) RayClic-PS 2 1.5 (0.5) 3.0 (0.9) RayClic-PT 3 1.3 (0.4) 4.0 (1.2) RayClic-E 1 n/a n/a Example: Finalize circuit length Example 1 Example 2 Circuit 1* Circuit 2* Length of heating cable per circuit 300 ft 350 ft 350 ft Additional cable required RayClic-PC 2 ft 2 ft 2 ft RayClic-T n/a 3 ft 3 ft RayClic-X 4 ft n/a n/a Total length of heating cable required 306 ft 355 ft 355 ft * In this example, the circuits were evenly divided. Equal circuit lengths are not required. HWAT System Design 1. Select heating cable 2. Lay out the heating cable 3. Select connection kits and accessories 4. Finalize circuit length 5. Select control configuration 6. Select insulation 7. Complete Bill of Materials Step 5 Select control configuration The HWAT-ECO allows the HWAT system to maintain specific temperatures. The HWAT-ECO can be configured in three different ways, as defined in Table 1.6 and shown in Fig. 1.6. Select the configuration that is most appropriate for your application. For the most flexibility, select the Individual control configuration. Table 1.6 HWAT-ECO Control Configuration Circuits per Configuration controller Programmable settings* Current switching Individual control Single Per circuit Internal 24 A Triac/relay Master/slave control Single Per system Internal 24 A Triac/relay Group control Multiple Per system External contactor * Programmable settings include maintain temperature, voltage, ambient temperature, and power correction H57510 9/04 (800) 545-6258 www.tycothermal.com Tyco Thermal Controls 9

SECTION 1: DESIGN GUIDE Figure A: Individual Control HWAT heating cable Master Slave 1 Slave 2 208/240 V RS-485 Alarm BMS Sensor HWAT heating cable Figure B: Master/Slave Control RS-485 208/240 V HWAT heating cable 208/240 V HWAT heating cable Panel energized light Ground Line voltage 208 V or 240 V ø 1 ø 2 ø 3 N Three-pole main CB C NC Contactor coil (208 or 240 V) Three-pole main contactor HWAT-ECO internal switch Two-pole with 30-mA ground-fault trip (208/240 Vac) Two-pole with 30-mA ground-fault trip (208/240 Vac) Power connection Heating cable End seal HWAT heating cable HWAT heating cable Figure C: Group Control Fig. 1.6 HWAT-ECO control configurations Braid/pipe Example: Select control method Example 1 Example 2 Control method Individual control Master/slave control Number of HWAT-ECO controllers 1 2 HWAT System Design 1. Select heating cable 2. Lay out the heating cable 3. Select connection kits and accessories 4. Finalize circuit length 5. Select control configuration 6. Select insulation Step 6 Select Insulation Select the size of thermal insulation from Table 1.7. You will need to know the length and diameter of each pipe used in your application. For pipes 1 1/4 inches and smaller, use insulation that is oversized by 1/4 inch to allow room for insulating over the heating cables. Table 1.7 specifies IPS (Iron Pipe Size) insulation, which has a greater inner diameter than CTS (Copper Tube Size) insulation. 10 Tyco Thermal Controls www.tycothermal.com (800) 545-6258 H57510 9/04

Design Guidelines For pipes 3 inches and larger, the thickness of insulation can either be equal to the pipe diameter with a single heating cable or 1/3 the pipe diameter with two heating cables. For example, a 6 inch pipe with 6 inches of insulation and one run of heating cable is equivalent to a 6 inch pipe with 2 inches of insulation and two runs of heating cable. Table 1.7 Fiberglass Insulation Selection Copper pipe size (in) IPS insulation size (in) Insulation thickness (in) 1/2 3/4 1/2 3/4 1 1 1 1 1/4 1 1 1/4 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 2 2 2 2 1/2 2 1/2 2 1/2 3 3 3 Note: For pipes 3 inches and larger, the thickness of insulation can be equal to the pipe diameter with one run of heating cable or 1/3 the pipe diameter with two runs of heating cable. Example: Select Insulation Copper pipe size (in) IPS insulation size (in) Insulation thickness (in) Example 1 3/4 1 1 1 1 1/4 1 1 1/2 1 1/2 1 1/2 Example 2 1 1 1/4 1 2 2 2 2 1/2 2 1/2 2 1/2 HWAT System Design 1. Select heating cable 2. Lay out the heating cable 3. Select connection kits and accessories 4. Finalize circuit length 5. Select control configuration 6. Select insulation 7. Complete Bill of Materials Step 7 Complete Bill of Materials You are now ready to compile a Bill of Materials. Using the design results, detail each item as shown in Tables 1.8 and 1.9 below. Fig. 1.7 illustrates a complete typical HWAT system. H57510 9/04 (800) 545-6258 www.tycothermal.com Tyco Thermal Controls 11

SECTION 1: DESIGN GUIDE End seal Glass tape Thermal insulation ETL label Tee Heating cable Hot water heater sensor Controller To BMS Splice To power distribution panel Note: Partial pipe insulation shown here for clarity. All pipes must be fully insulated. Power connection Fig. 1.7 Typical HWAT heating cable system Table 1.8 Bill of Materials (Example 1) Description Catalog number Quantity HWAT heating cable HWAT-Y2 308 ft Power connection kit RayClic-PC 1 Cross connection kit RayClic-X 2 Controller HWAT-ECO 1 Attachment tape GT-66 6 rolls Labels ETL 30 Table 1.9 Bill of Materials (Example 2) Description Catalog number Quantity HWAT heating cable HWAT-R2 706 ft Power connection kit RayClic-PC 2 Tee connection kit RayClic-T 2 Controller HWAT-ECO 2 Attachment tape GT-66 12 rolls Labels ETL 70 12 Tyco Thermal Controls www.tycothermal.com (800) 545-6258 H57510 9/04

Section 2: Design Examples School The plumbing engineer was laying out the piping for the domestic hot water system for a three-story high school. The engineer did not believe it necessary to recirculate the risers and was going to run two recirculation loops, one for each wing, in the ground-floor ceiling space. However, the engineer decided that the return lines would have to take the same route as the supply lines. In this situation, the engineer knew the HWAT system would provide the more economical design. Furthermore, the client had indicated the possibility of extending either wing at some time in the future. The engineer knew that by using HWAT products, the system could be easily expanded if and when the client decided to do so. The high school required a maintain temperature of 115 F. HWAT-R2 and two HWAT-ECO electronic controllers were chosen to maintain 115 F during normal operation and to have the ability during the weekend, when the school is unoccupied, to occasionally elevate the water temperature above 140 F or to maintain a lower temperature for energy savings. The engineer thought it would be useful to be able to isolate either wing for maintenance, so it was decided to run two separate circuits, each to be operated independently with a HWAT-ECO. The plumbing engineer noted the pipes to be traced with HWAT heating cables on the drawings. He then inserted the standard clauses to provide, install, and test the HWAT system, and called out the correct thicknesses of fiberglass insulation, in Division 15 of the specification. The electrical engineer noticed that in the electrical drawings, junction boxes were located near each power connection. It was decided to power both circuits from the same panel. Circuit breaker sizes and steady-state current were calculated and included on a table in the electrical drawings. The need for a ground-fault protection device in each circuit was noted on the electrical drawings. School Plan for ground-floor hot water piping LEGEND Beginning and end of HWAT heat-tracing circuit Water heater Riser up Note All heat-tracing must be HWAT-R2 H57510 9/04 (800) 545-6258 www.tycothermal.com Tyco Thermal Controls 13

SECTION 2: DESIGN EXAMPLES Prison Reviewing the architectural drawings, the plumbing engineer observed that the design consisted of about a dozen two-story pods arranged around an expanse of open space. For security reasons, the County had requested that mechanical equipment and piping, and the associated pipe openings, be kept to an absolute minimum. The layout of the cells in each pod did not allow any shortcut for return piping for a recirculation loop; it would have to follow the same corridor as the supply piping. The plumbing engineer knew from experience that in these kinds of situations, the HWAT system would be more economical than recirculation. For the prison application, HWAT-Y2 and one HWAT-ECO electronic controller were selected to maintain 105 F. Each pod would be provided with a separate water heater and it was not considered necessary to heat trace the risers. Upon measuring the length of the ground-floor piping, the plumbing engineer found it was possible to trace the entire piping in each pod with a single HWAT-Y2 circuit and stay within the capacity of a 15 amp ground-fault circuit breaker. This would allow the heating cable to be conveniently powered from the electrical panel in the mechanical room. Because the mechanical rooms were located in isolated areas, the specification was written to connect the network of HWAT-ECO controllers to the building management system (BMS) using the BMS interface. Temperature set points would be programmed into the BMS with continual feedback provided by the HWAT-ECO through the alarm contacts, including loss of power and water heater monitoring. The plumbing engineer decided that the situation was sufficiently simple to ignore marking on the plumbing drawing the lines to be heat traced. Instead, the extent of the heat tracing could be called out in the notes. The plumbing engineer then inserted the standard clauses to provide, install, and test the HWAT system, and called out the correct thicknesses of fiberglass insulation, in Division 15 of the specification. The electrical engineer confirmed that a 15 amp breaker was adequate, and calculated the steady-state current. A junction box was located adjacent to the beginning of the heating cable circuit, and its number and the number of the electrical panel in the table were noted. A draftsperson copied the table onto the electrical drawings, along with a note calling out the need for a ground-fault protection device in each circuit. H Prison LEGEND Beginning and end of HWAT heat-tracing circuit Water heater Riser up Note Heat-trace all HW distribution piping with HWAT-Y2 heating cable. Do not trace branches or risers. Ground-floor hot water piping diagram 14 Tyco Thermal Controls www.tycothermal.com (800) 545-6258 H57510 9/04

Apartment Building Apartment Building The plumbing engineer was faced with laying out the hot water piping for the 35-story stateof-the-art apartment building. The piping was relatively complex, making it especially important to balance the system adequately. As requested by the developer, the architect had squeezed in the maximum number of residential floors by working to the minimum headroom allowed by code. The plumbing engineer was required by code to divide the building into three pressure zones. However, there would be great difficulty in running the horizontal supply and return lines necessary in each zone, given the very limited space provided above the dropped ceilings. And there was not any room for the booster heaters and pumps for the recirculation system. The plumbing engineer decided that an HWAT system would eliminate the need for horizontal piping and additional heaters or pumps. The risers could run continuously from top to bottom, broken only by pressure reducing valves at the 11th and 23rd floors. The plumbing engineer noted that the need for flow balancing was completely eliminated by using the HWAT system. In order to interface with the Building Management System, the engineer selected the HWAT-ECO electronic controller. Having estimated that a single circuit length on a 20 amp circuit breaker could run the complete height of the building, the engineer marked an HWAT circuit on each of the four risers and sent copies of the plumbing drawing and the design sheet to the electrical engineer. HWAT-Y2 was selected for a maximum circuit length of 500 feet with a 20 amp breaker and to maintain 120 F at a 70 F ambient temperature and a 208 supply voltage. HWAT-R2 was not selected because a high temperature heat-up cycle was not required. Standard clauses to provide, install, and test the HWAT system were included in Division 15 of the specification. To provide pressure relief in the piping during system startup, an expansion tank was indicated on each riser at each pressure reducing valve. The electrical engineer looked at the plumbing drawing and determined that it was most convenient to power all the circuits from the penthouse mechanical room. Junction boxes would be located at the beginning of each circuit and power run from a single panel. The electrical engineer calculated the breaker sizes and the steady-state currents. A finished table was included in the electrical drawings, along with a note calling for a ground-fault protection device in each circuit. Apartment Building LEGEND Beginning and end of HWAT heating cable circuit installed on supply pipe Water heater Pressure-reducing valve Expansion tank Note All heat-tracing must be HWAT-Y2 H57510 9/04 (800) 545-6258 www.tycothermal.com Tyco Thermal Controls 15

SECTION 2: DESIGN EXAMPLES Hotel The plumbing engineer reviewed the architectural drawings for a new hotel. The building consisted of six floors of guest rooms over a commercial area containing a health club, restaurants, conference rooms, shops, offices, and a laundry. The plumbing engineer decided to deliver water from the boiler at 140 F directly to the kitchens and laundry, and to mix to 120 F for domestic hot water. The HWAT system was chosen rather than recirculation because the owner insisted that there be no delay in getting hot water from any fixture, especially for the metered faucets on the first floor. Also, the HWAT system would accommodate all the architectural and construction changes that were bound to occur before the system was operating. HWAT-R2 was selected for the 140 F line running out of the boiler to the kitchens and laundry, and HWAT-Y2 for the 120 F domestic hot water system. After reviewing the circuit length table, it was determined that the entire domestic hot water piping could be traced with only two HWAT-Y2 circuits by utilizing a 30 amp circuit breaker. However, the plumbing engineer decided to lay out the heating cable in smaller discrete zones to facilitate partial shutdown of the system for maintenance. Given the short circuit length for each circuit, 15 amp circuit breakers were specified and the circuits were indicated on the drawing. The electrical engineer looked at the layout of the circuits and assigned junction box and panel locations for each circuit according to the electrical drawings. The engineer calculated the breaker size and the steady-state current for each circuit. A completed table, with a note that the circuit breakers would incorporate 30 ma ground-fault protection, was then transferred to the electrical drawing. Hotel LEGEND Beginning and end of HWAT heating cable circuit installed on suppy pipe Water heater Note All heating cables to be HWAT-Y2 except circuit no. 1 which shall be HWAT-R2 16 Tyco Thermal Controls www.tycothermal.com (800) 545-6258 H57510 9/04

HWAT Heating Cables Self-regulating cables for hot water temperature maintenance Raychem HWAT self-regulating heating cables are installed on hot water supply pipes underneath standard pipe insulation. The heating cable adjusts its power output to compensate for variations in water temperature and ambient temperature. The heating cable replaces supply-pipe heat losses at the point where the heat loss occurs, thereby providing continuous, energy-efficient, hot water temperature maintenance and eliminating the need for a recirculation system. Simplified design Single-pipe HWAT systems eliminate the need for designing complex recirculation systems, with their pumps, piping networks, and complicated flow balancing. Special cases, such as retrofits and multiple pressure zones, are simple to design. Low installed cost Installation of the HWAT system is simple. The heating cable can be cut to length, spliced, tee-branched, and terminated at the job site, reducing installation costs. Fewer plumbing components are needed; recirculation piping, pumps, and balancing valves are all eliminated. Low operating cost The HWAT system continuously maintains hot water temperature at every point along the supply pipe. Unlike conventional recirculation systems, HWAT systems do not require the overheating of supply water to allow for cooling. The HWAT system reduces the energy requirements of typical hot water systems with reduced heat loss from supply piping, no heat loss from recirculation piping, and no pump to run. HWAT-ECO The HWAT-ECO electronic controller is designed for operation with HWAT-Y2 and HWAT-R2 heating cables. The HWAT-ECO provides flexible temperature control, energy savings, heat-up cycle function, BMS interface, and nine predefined programs that can be customized by the user. Modified polyolefin outer jacket Tinned-copper braid Polymer-coated aluminum wrap Modified polyolefin inner jacket Self-regulating conductive core Nickel-plated copper bus wires Specifications Jacket Modified polyolefin Braid Tinned copper Bus wires 16 AWG nickel-plated copper Supply voltage 208 V/240 V Minimum bend radius 0.5 in (12 mm) Product Characteristics (Nominal) Catalog number HWAT-Y2 HWAT-R2 Jacket color Yellow Red Maintain temperature range* 105 F (40 C) to 125 F (50 C) 105 F (40 C) to 140 F (60 C) Weight 200 lbs/1000 ft (0.31 kg/m) 230 lbs/1000 ft (0.35 kg/m) Dimensions Width 0.67 in (17 mm) 0.72 in (18 mm) Thickness 0.38 in (10 mm) 0.38 in (10 mm) * When designed in accordance with the HWAT System Product Selection and Design Guide H57512 9/04 (800) 545-6258 www.tycothermal.com Tyco Thermal Controls 17

HWAT Heating Cables Design and Installation For proper design and installation, use the Design section of the HWAT System Product Selection and Design Guide (H57538) and the HWAT System Installation and Operations Manual (H57548). Maximum Circuit Length ft (m) Ground-Fault Protection Approvals HWAT-Y2 HWAT-R2 Breaker size @208 V @208V 30 amp 800 (240) 500 (150) 20 amp 500 (150) 330 (100) 15 amp 350 (105) 250 (75) To minimize the danger of fire from sustained electrical arcing if the heating cable is damaged or improperly installed, and to comply with Tyco Thermal Controls requirements and national electrical codes, 30 ma ground-fault equipment protection must be used on each heating cable branch circuit. Arcing may not be stopped by conventional circuit protection. 718K Pipe Heating Cable HWAT heating cables are UL Listed, CSA Certified, and FM Approved when used with the appropriate agency-approved Raychem components and accessories 18 Tyco Thermal Controls www.tycothermal.com (800) 545-6258 H57512 9/04

HWAT -ECO Electronic controller for hot water temperature maintenance systems The Raychem HWAT-ECO controller is designed for operation with HWAT-Y2 and HWAT-R2 self-regulating heating cables. The HWAT-ECO controller provides the following features: Flexible temperature control of hot water temperature maintenance systems. Integrated function that lowers the maintain temperature during low use hours to save energy. Heat-up cycle function that increases the water temperature of a hot water system that is not in use. Building Management System (BMS) interface that receives a DC voltage to determine the desired maintain temperature. Alarm relay to signal power, temperature or communication problems. Water heater sensor function that alarms and lowers the maintain temperature if the water heater temperature is too low. Master/slave function that allows one HWAT-ECO to control up to eight additional HWAT-ECO controllers. Nine predefined programs that can be customized by the user. General Area of use Approvals Nonhazardous locations 80BJ Type 12 Energy Management Equipment Maintain temperature setpoint Controller ambient temperature Switching capacity Operating voltage Internal power consumption Circuit protection Internal temperature alarm BMS control voltage Alarm contacts 105 F (40 C) to 140 F (60 C) 40 F (5 C) to 105 F (40 C) 24 A @ 208/240 Vac maximum SPST 208/240 (±10%), 60 Hz 2.5 W Maximum 30 A with 30 ma ground-fault protection 185 F (85 C) 0 10 Vdc Maximum 24 Vdc or 24 Vac, 1 A, SPST, voltage free H57339 9/04 (800) 545-6258 www.tycothermal.com Tyco Thermal Controls 19

HWAT -ECO General Alarm events Power correction factor Water heater sensor Electromagnetic Compatibility (EMC) Real time clock Clock accuracy Loss of power Controller reinitialized Internal controller temperature too high Water heater temperature too high Water heater temperature too low Master/slave error To increase or decrease your actual pipe maintain temperature Thermistor with 13 ft 3 in (4 m) lead Complies to EN 50081-1/2 for emission and EN 50082-1/2 for immunity Automatic daylight savings time and leap year correction ±10 minutes per year Enclosure Enclosure rating Enclosure material Mounting Conduit entries Cable gland NEMA 12 (IP52) indoor use only ABS Wall mount with two screws or optional DIN rail Two each 1/2 in conduit entries 3-hole grommet Maximum cable size: 2-wire: 20 AWG (0.5 mm 2 ) 4-wire: 24 AWG (0.2 mm 2 ) Typical Enclosure Dimensions and Module Layout 02-11-2004 09:30 Maintain * 6.5" (165 mm) A B Power supply (green LED) Power to heating cable (green LED) 3.34" (85 mm) A B C D E F G H C D E F Heat-up cycle (green LED) increased risk of scalding Water heater alarm (requires installed sensor) that lowers maintain temperature if water heater temperature is too low (green LED) Alarm (red LED) Escape, backspace; NO; or display maintain temperature setpoint G Arrow keys: to change menu selection or position the cursor H Confirm selection, new value or YES 2 ea - 1/2" conduit entries To water heater sensor To HWAT-ECO network/alarm entries Programming Default programs Program settings Nine predefined programs that can be customized by the user There are 48 1/2-hour time blocks of the following program settings: Off, Economy, Maintain, and Heat-up cycle 20 Tyco Thermal Controls www.tycothermal.com (800) 545-6258 H57339 9/04

HWAT -ECO Networking Master/slave Master/slave cable Master is selectable in the controller, up to eight slaves can be connected 2-wire, 300 V, minimum 24 AWG twisted pair Memory Parameters stored in memory All parameters are stored in nonvolatile memory, except date and time Clock back-up time Eight hours ±10% Ground-Fault Protection To minimize the danger of fire from sustained electrical arcing if the heating cable is damaged or improperly installed, and to comply with the requirements of Tyco Thermal Controls and national electrical codes, you must use 30 ma ground-fault equipment protection on each heating cable branch circuit. Arcing may not be stopped by conventional circuit protection. The HWAT-ECO does not include ground-fault protection. Ordering Details Catalog number Part number Weight HWAT-ECO P000000121 2 lb (1 kg) H57339 9/04 (800) 545-6258 www.tycothermal.com Tyco Thermal Controls 21

3 1/8" R RayClic 3 1/8" R WARNING: SHOCK HAZARD Do not open while energized LISTED DESIG. 3A, 3B, 3C, 2E RayClic Connection System Connection kits for Raychem self-regulating heating cables The RayClic connection system is a simple, fast and reliable set of connection kits developed for select Raychem self-regulating heating cables. There is no wire stripping needed because the insulation displacement connector makes the electrical connection. The easy-to-install RayClic connection system reduces installation time, lowering the total installed cost of the heating cable system. Simple No need for special tools Three-step installation Reliable Intuitive installation Rugged, waterproof, UV-resistant enclosure Cost-effective Quick installation Powered Connection Kits Catalog number Part number Description RayClic-PC 233053 A RayClic-PC can supply power to one heating cable. Each kit contains one RayClic-PC power connection, one RayClic-E end seal, and one SB-04 pipe mounting bracket. The kit includes 5' power lead wires and conduit fitting; the junction box and flexible conduit required to make a complete connection are not included. Weight: 1.8 lb (0.8 kg) RayClic-PS 861247 A RayClic-PS can be used as a power connection kit for supplying power to two heating cables. Each kit contains one RayClic-PS powered splice connection, two RayClic-E end seals, and one SB-04 pipe mounting bracket. The kit includes 5' power lead wires and conduit fitting; the junction box and flexible conduit required to make a complete connection are not included. Weight: 2.0 lb (0.9 kg) RayClic-PT 804231 A RayClic-PT can be used as a power connection kit for supplying power to three heating cables. Each kit contains one RayClic-PT powered tee connection, three RayClic-E end seals, and one SB-04 pipe mounting bracket. The kit includes 5' power lead wires and conduit fitting; the junction box and flexible conduit required to make a complete connection are not included. Weight: 2.0 lb (0.9 kg) Unpowered Connection Kits Catalog number Part number Description RayClic-S 861247 Splice kits are installed as needed to connect two heating cables together at one point. Each kit contains one RayClic-S splice. Weight: 1.3 lb (0.6 kg) 22 Tyco Thermal Controls www.tycothermal.com (800) 545-6258 H57545 9/04

3 1/8" WARNING: SHOCK HAZARD Do not open while energized R LISTED DESIG. 3A, 3B, 3C, 2E RayClic Connection System Unpowered Connection Kits (Continued) Catalog number Part number Description RayClic-T 014023 Tee kits are installed as needed to connect three heating cables together at one point. Each kit contains one RayClic-T tee connection and one RayClic-E end seal. Weight: 1.9 lb (0.9 kg) RayClic-X 546349 Cross kits are installed as needed to connect four heating cables together at one point. Each kit contains one RayClic-X cross and two RayClic-E end seals. Weight: 2.0 lb (0.9 kg) Accessories Catalog number Part number Description RayClic-E 805979 The RayClic-E is a replacement end seal kit. RayClic-SB-02 852001 The RayClic-SB-02 is a wall mounting bracket for use with any RayClic connection kit. RayClic-SB-04 616809 The RayClic-SB-04 is a pipe mounting bracket for use with any RayClic connection kit. One pipe mounting bracket is included with each powered connection kit. RayClic System Specifications Rated voltage Maximum circuit breaker size Maximum exposure temperature Minimum installation temperature Enclosure rating 120 277 Vac 30 A 150 F (65 C) 0 F ( 18 C) NEMA 4X Applicable Products XL-Trace IceStop HWAT RaySol 5/8 XL-CR/CT GM-1X, GM-2X, GM-1XT, GM-2XT HWAT-Y2, HWAT-R2, HWAT-P1 RaySol-1, RaySol-2 H57545 9/04 (800) 545-6258 www.tycothermal.com Tyco Thermal Controls 23

RayClic Connection System Approvals 718K Pipe Heating Cable 877Z De-Icing and Snow Melting 9J86 Radiant Heating Cable APPROVED For HWAT, IceStop, and XL-Trace only For IceStop (GM-XT) only Hazardous Locations Class I, Div. 2, Groups A,B,C,D Design and Installation Ground-Fault Protection For proper design and installation of a RayClic connection system, use the appropriate product design guide and the installation instructions included with the connection kit. To minimize the danger of fire from sustained electrical arcing if the heating cable is damaged or improperly installed, and to comply with the requirements of Tyco Thermal Controls and national electrical codes, ground-fault equipment protection must be used on each heating cable branch circuit. Arcing may not be stopped by conventional circuit protection. 24 Tyco Thermal Controls www.tycothermal.com (800) 545-6258 H57545 9/04

Section 4: Expanded HWAT -ECO Electronic Controller Capabilities The HWAT -ECO electronic controller has multiple capabilities that help make the HWAT system a superior alternative to recirculation systems. This section expands upon some of these capabilities that were introduced in Section 1: Design Guide, including the heat-up cycle and subsequent cool down, Building Management System (BMS) interface, predefined programs, and the water heater sensor function. For additional information, refer to the HWAT-ECO Installation and Operation Manual (H57340). Heat-Up Cycle and Cool Down The HWAT-ECO includes a heat-up cycle function that allows the HWAT system to increase the water temperature of a hot water system that is not in use. During the heat-up cycle, the HWAT-ECO continuously powers the heating cable for the selected timeframe. Using the heat-up graphs below, program the HWAT-ECO for the amount of time required to reach the desired temperature. To allow sufficient time for the pipes to cool before hot water is used, refer to the cool-down chart to determine the amount of time required in Off mode after the heat-up cycle is complete and program the HWAT-ECO accordingly. Pipe Temperature F ( C) Pipe Temperature F ( C) HWAT-Y2 at 208 V 150 (66) 140 (60) 130 (54) 120 (49) 110 (43) 70 F (21 C) ambient 105 (41) 00 2 4 6 8 10 12 14 16 18 20 22 24 Time (hours) HWAT-Y2 at 240 V 150 (66) 140 (60) 130 (54) 120 (49) 110 (43) 105 (41) 70 F (21 C) ambient 1/2-inch pipe 1-inch pipe 2-inch pipe 1/2-inch pipe 1-inch pipe 2-inch pipe 0 2 4 6 8 10 12 14 16 18 20 22 24 Time (hours) Fig. 4.1 Heat-up cycle graphs Pipe Temperature F ( C) Pipe Temperature F ( C) HWAT-R2 at 208 V 150 (66) 140 (60) 130 (54) 120 (49) 110 (43) 105 (41) HWAT-R2 at 240 V 150 (66) 140 (60) 130 (54) 120 (49) 110 (43) 105 (41) 70 F (21 C) ambient 0 2 4 6 8 10 12 14 16 18 20 22 24 70 F (21 C) ambient Time (hours) 1/2-inch pipe 1-inch pipe 2-inch pipe 1/2-inch pipe 1-inch pipe 2-inch pipe 0 2 4 6 8 10 12 14 16 18 20 22 24 Time (hours) H57510 9/04 (800) 545-6258 www.tycothermal.com Tyco Thermal Controls 25

WARNING Burn Hazard Water temperatures above 120 F (50 C) can cause skin damage and pain. Be sure the correct HWAT cable is used and the HWAT-ECO is programmed properly. Avoid exposure to water during heat-up cycles or from water systems with high maintain temperatures during normal operation. 150 (66) 145 (63) 140 (60) Cool-Down 708 F (21 C) ambient 1/2-inch pipe 1-inch pipe 2-inch pipe Pipe Temperature F ( C) 135 (57) 130 (54) 125 (52) 120 (49) 115 (46) 110 (43) 105 (40) 0 1 2 3 4 5 6 7 8 9 10 11 12 Time (hours) Fig. 4.2 HWAT cool-down graph BMS Interface The HWAT-ECO can be programmed to have a BMS control the temperature setpoints. Under these conditions, the HWAT-ECO converts the voltage received from the BMS to maintain the desired temperature. All modes, including Heat-Up, Maintain, Economy and Off, are controlled by the BMS. Continual feedback is provided to the BMS through the HWAT-ECO alarm contacts, including loss of power, supply water temperature alarms, and communication errors. HWAT-Y2 HWAT-R2 U-BMS/U-GLT (VOLT) Temp F ( C) >147 (>64) X >6.4 147 (64) X 6.4 140 (60) X 6 131 (55) X X 5.5 122 (50) X X 5 113 (45) X X 4.5 106 (41) X X 4.1 Off X X 0 Fig. 4.3 BMS voltage input chart 26 Tyco Thermal Controls www.tycothermal.com (800) 545-6258 H57510 9/04

Predefined Programs The HWAT-ECO has nine predefined programs that can be customized by the user. These programs include time intervals for Maintain, Economy, Heat-Up and Off modes. The economy setting is selected for low water usage periods where a lower maintain temperature is acceptable. The Off setting is selected for cool down after a heat-up cycle or for high usage periods where hot water is flowing from the water heater to the point of use with minimal delay thus not requiring energy from the HWAT system. = Heat-up cycle = Maintain temperature = Economy temperature = Heating off Monday-Friday Heat-up Maintain Economy Apartments Off 00 02 04 06 08 10 12 14 16 18 20 22 24 Heat-up Maintain Saturday-Sunday Economy Off 00 02 04 06 08 10 12 14 16 18 20 22 24 Fig. 4.4 Predefined program example Water Heater Sensor Function The HWAT-ECO ensures that the maintain temperature does not exceed the supply water temperature. When the water heater sensor option is activated, the HWAT-ECO monitors the temperature of the water being supplied to the system. As shown in Fig. 4.5, the water heater sensor can be installed on the outlet of the water heater or after the mixing valve, depending on the configuration of your system. HWAT-Y2 HWAT-R2 A B Hot water out Tempered water out Water heater Mixing valve Cold water in Fig. 4.5 Water heater sensor function example H57510 9/04 (800) 545-6258 www.tycothermal.com Tyco Thermal Controls 27

28 Tyco Thermal Controls www.tycothermal.com (800) 545-6258 H57510 9/04

Section 5: Specification 1 General 2 Materials 1. Furnish and Install a UL Listed, CSA Certified and FM Approved system of electric selfregulating heating cable, connection kits and electronic controller for maintaining the hot water as indicated on the drawings. The cable shall utilize a radiation-crosslinked conductive polymer as the heating element, and the cable shall be specifically designed, manufactured and UL Listed, CSA Certified and FM Approved for hot water temperature maintenance. 2. Submittals i) Copy of UL, CSA and FM file indicating the heating cable is specifically intended to provide supplementary heating to hot water service supply systems utilizing thermally insulated metal or plastic pipe ii) Manufacturer s catalog cuts showing materials and performance data iii) Project list of at least 20 projects, installed for at least five years, with at least 2000 ft (600 m) of heating cable in each project. 1. Construction: The self-regulating heating cable shall consist of two (2) 16 AWG (1.2 mm 2 ) nickel-coated copper bus wires embedded in a radiation-crosslinked conductive polymer core. It shall be covered by a radiation-crosslinked, polyolefin, dielectric jacket surrounded by a polymer-coated aluminum wrap, and enclosed in a tinned copper braid of 14 AWG (2.5 mm 2 ) equivalent wire size. The braid shall be covered with a (nominal) 40 mil (1 mm) polyolefin outer jacket, color coded for easy identification. 2. Mechanical: The cable shall have a minimum cut-through resistance of 100 lb (445 N) per the IEEE 515.1 (4.3.3) and CSA 130-03 (6.28) Resistance to Cutting Tests. The cable shall have a minimum impact resistance of 10 ft-lbs per the IEEE 515.1 (4.2.9) and CSA 130-03 (6.2.10.2) Impact Tests. The cable shall have a minimum abrasion resistance of 2500 cycles per the IEEE 515.1 (4.3.4) Abrasion Test. The cable shall withstand a crush resistance of 225 lbs per the IEEE 515.1 (4.2.8) Deformation Test, and withstand a crush resistance of 345 lbs (1500 N) per the CSA 130-03 (6.2.7) Crush Resistance Test. 3. Connection Kits: All heating cable connection kits shall be UL Listed, CSA Certified and FM Approved for use as part of the system to maintain hot water temperature. Component enclosures shall be rated NEMA 4X to prevent water ingress and corrosion. Installation shall not require the installing contractor to cut into the heating cable core to expose the bus wires. Connection systems requiring the installing contractor strip the bus wires, or which use crimps or terminal blocks, shall not be acceptable. All connection kits except for the power connection shall be installed under the thermal insulation. The end seal shall use silicone gel. 4. Controller: Installed system shall include at least one agency-approved electronic controller. The controller shall not be of line sensing over-limit design. The controller shall be capable of setting different pipe temperatures based on ambient and voltage with 24 hour, 7 day/week programmable options. The controller shall have the energy savings feature of lowering pipe temperature during low use periods and the ability to raise the temperature of the pipes for a programmed interval. The controller shall have BMS interface capabilities to set pipe temperatures and provide alarm relays in loss of power, incorrect water heater temperature and communication failure. The controller shall have flexible wiring configurations to operate individually or control up to eight additional controllers. H57510 9/04 (800) 545-6258 www.tycothermal.com Tyco Thermal Controls 29

3 Performance 1. Maintain Temperatures: The system shall maintain temperatures between 105 F (40 C) and 140 F (60 C) at 208 V or 240 V. Temperature shall be maintained by utilizing an electronic controller with straight runs of heating cable on the pipe. 2. Insulation schedule shall be as follows: Table 5.1 Insulation Thickness Copper pipe size (in) IPS insulation size (in) Insulation thickness (in) 1/2 3/4 1/2 3/4 1 1 1 1 1/4 1 1 1/4 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 2 2 2 2 1/2 2 1/2 2 1/2 3 3 3 Note: For pipe 1 1/4 inches and smaller, use insulation that is oversized by 1/4 inch to allow room for installing over the heating cables. For pipes three inches and larger, the thickness of insulation can be equal to the pipe diameter with one heating cable or 1/3 the pipe diameter with two runs of heating cable. 3. Power control (self-regulating index): The slope of the power/temperature shall be such that the power of the heating cable shall increase with decreasing temperature at a rate of at least 0.028 W/ft- F (0.16W/m- C) from 50 F (10 C) to 100 F (38 C) 4. Long-term thermal stability (as determined by accelerated testing): The power retention of the heating cable shall be at least 90% after 300 cycles between 50 F (10 C) and 212 F (100 C). 5. High temperature withstand: The heater shall not decrease in resistance, overheat, or burn when powered at 208 V or 240 V and exposed to 400 F (205 C) in an oven for 30 minutes. 4 Manufacturer 1. Experience: The manufacturer shall have more than ten years experience with self-regulating heating cables for temperature maintenance of domestic hot water. 2. Acceptable product and manufacturer: Raychem HWAT by Tyco Thermal Controls 5 Execution 1. Installation: The system shall be installed according to the drawings and the manufacturer s instructions. The installer shall be responsible for providing a functional system, installed in accordance with applicable national and local requirements. Each circuit shall be protected with a 30 ma ground-fault protection device. 2. Testing i) Procedure: Measure the heater circuit continuity and the insulation resistance between the braid and the bus wires with a 2500 Vdc megohmmeter (megger). ii) Timing: The tests should be performed after the pipe insulation has been installed and prior to the installation of wall or ceiling panels, and shall be witnessed by the Construction Manager and the manufacturer or the manufacturer s representative. 30 Tyco Thermal Controls www.tycothermal.com (800) 545-6258 H57510 9/04

iii) Acceptable results: The heater circuit shall be continuous and megger readings shall be at least 1000 megohm regardless of the heater length. Circuits yielding unacceptable readings must be repaired or replaced. iv) Submittal of results: Submit records of the test data to the Construction Manager. Self-regulating heating cables and components to have a limited 10-year warranty extension from the date of installation if a properly completed online warranty form is completed within 30 days from the date of installation. Appendix: Installation Alternatives Depending on the local requirements, there are several alternative installation methods that can be used in the specification. 1. Plumber purchases, plumber installs: Plumber shall purchase material, and is responsible for entire system, including testing before and after insulation. Installation, including all splices, tees and end terminations, shall be performed by plumbing contractor, with the exception of any power connections, which shall be installed and connected to power by a qualified electrical contractor. 2. Plumber purchases, electrician installs: Plumber shall purchase material, and is responsible for entire system, including testing before and after insulation. Installation, including all splices, tees and end terminations and power connections shall be performed by qualified electrical contractor. 3. Electrician purchases, electrician installs: Electrician shall purchase material, and is responsible for entire system, including testing before and after insulation. Installation, including all splices, tees and end terminations and power connections shall also be performed by qualified electrical contractor. Electrical contractor shall coordinate with responsible plumbing contractor regarding material requirements and scheduling. H57510 9/04 (800) 545-6258 www.tycothermal.com Tyco Thermal Controls 31

32 Tyco Thermal Controls www.tycothermal.com (800) 545-6258 H57510 9/04

Section 6: Limited Warranty Tyco Thermal Controls warrants all Industrial, Commercial Construction, and Wholesale Distribution Heating Products as well as all Industrial and Commercial Wiring products against faulty workmanship and use of defective materials when such goods are properly installed, operated, and maintained according to product documentation. All documentation regarding proper use and installation can be found on our web site at www.tycothermal.com. Goods subjected to misuse, neglect, alteration or improper installation, operation, maintenance, repair or testing (or such other act or omissions not attributable to Tyco Thermal Controls) are not covered by this Limited Warranty. Tyco Thermal Controls shall in no event be liable for the cost of removal or installation, for loss or damage to or loss of use of facilities or other property, loss of revenue, loss of use of revenue, loss of anticipated profits, or other damages or costs of any kind whatsoever, whether direct, indirect, incidental, or consequential, and in no event shall Tyco Thermal Controls liability exceed an amount equal to the sales price. This warranty remains in force for a period of 18 months from installation or 24 months from the date of shipment, whichever occurs first with respect to Industrial and Commercial Construction Heating and Wiring Products and two (2) years from the date of purchase with respect to Wholesale Distribution Heating Products. Tyco Thermal Controls will examine and confirm that any alleged product issue covered by this Limited Warranty actually exists and occurred in the course of proper and normal use and was not caused by accident, misuse, neglect, alteration or improper installation, operation, maintenance, repair or testing or such other cause outside of the responsibility of Tyco Thermal Controls under this Limited Warranty. Tyco Thermal Controls will repair such goods or supply replacement goods or credit Buyer s account for goods covered by this Limited Warranty whichever Tyco Thermal Controls may elect at its sole discretion. The Buyer should promptly notify Tyco Thermal Controls, or their Tyco Thermal Controls Representative, either by writing or by email within thirty (30) days after discovery of an alleged warranty issue. Detailed warranty claim information will be requested at this time and must be supplied by the Buyer. The Buyer may then be asked to return the goods, postage paid, to the location given by Tyco Thermal Controls. THE FOREGOING WARRANTY IS IN LIEU OF ALL OTHER REPRESENTATIONS, WARRAN- TIES, OR CONDITIONS, EXPRESS OR IMPLIED, INCLUDING WITHOUT LIMITATION ANY IMPLIED WARRANTY OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE OR NONINFRINGEMENT, AND OF ANY OTHER OBLIGATION OR LIABILITY ON THE PART OF TYCO THERMAL CONTROLS, WHETHER BY STATUTE, CONTRACT, STRICT LIABILITY, TORT OR OTHERWISE. An extension of the limited warranty period to ten (10) years from the date of installation is available if a properly completed online warranty form is completed within thirty (30) days from the date of installation. The extension is valid for the HWAT-Y2 and HWAT-R2 heating cables, RayClic connection kits and accessories but not the HWAT-ECO controller. Complete warranty information and the 10-Year warranty extension form can be found at www.tycothermal.com. H57510 9/04 (800) 545-6258 www.tycothermal.com Tyco Thermal Controls 33

NOTES: 34 Tyco Thermal Controls www.tycothermal.com (800) 545-6258 9/04

Worldwide Headquarters Tyco Thermal Controls 300 Constitution Drive Menlo Park, CA 94025-1164 USA Tel: (800) 545-6258 Fax: (800) 596-5004 info@tycothermal.com www.tycothermal.com Canada Tyco Thermal Controls 250 West St. Trenton, Ontario Canada K8V 5S2 Tel: (800) 545-6258 Fax: (800) 596-5004 Important: All information, including illustrations, is believed to be reliable. Users, however, should independently evaluate the suitability of each product for their particular application. Tyco Thermal Controls makes no warranties as to the accuracy or completeness of the information, and disclaims any liability regarding its use. Tyco Thermal Controls' only obligations are those in the Tyco Thermal Controls Standard Terms and Conditions of Sale for this product, and in no case will Tyco Thermal Controls or its distributors be liable for any incidental, indirect, or consequential damages arising from the sale, resale, use, or misuse of the product. Specifications are subject to change without notice. In addition, Tyco Thermal Controls reserves the right to make changes without notification to Buyer to processing or materials that do not affect compliance with any applicable specification. Tyco, HWAT, Raychem and RayClic are trademarks or registered trademarks of Tyco Thermal Controls LLC or its affiliates. 2004 Tyco Thermal Controls LLC Printed in USA H57538 9/04