Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Similar documents
Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Performance characteristics of low global warming potential R134a alternative refrigerants in ejector-expansion refrigeration system

International Journal of Engineering Research (IJOER) [Vol-1, Issue-3, June- 2015]

Performance investigation of Air-conditioning system using ejector as expansion device

THE ANALYSIS AND EXPERIMENTAL INVESTIGATION OF HEAT PUMP SYSTEM USING THERMOBANK AND COS EJECTOR CYCLE

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

WORK STUDY ON LOW TEMPERATURE (CASCADE) REFRIGERATION SYSTEM

Thermodynamic Analysis of Cascade Refrigeration System Using R12-R13, R290-R23 and R404A-R23

Analysis of Evaporative Cooler and Tube in Tube Heat Exchanger in Intercooling of Gas Turbine

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

Performance analysis of ejector refrigeration system with environment friendly refrigerant driven by exhaust emission of automobile

International Journal Of Core Engineering & Management (IJCEM) Volume 2, Issue 9, December 2015

Performance analysis of a vapour compression refrigeration system with a diffuser for theeco-friendly refrigerants R-134a, R-600a and R-152a

CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

Role of Nano-technology for improving of thermal performances of vapour compression refrigeration system (VCRS): An Overview

EXERGY ANALYSIS OF DOMESTIC REFRIGERATOR WITH DIFFERENT REFRIGERANTS

International Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 04 Issue: 05 May p-issn:

Thermodynamic Analysis of Ammonia-Water Absorption Refrigeration System with Ejector

CHAPTER 7 PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM IN HYBRID REFRIGERATION SYSTEM

EXPERIMENTAL INVESTIGATION OF COMPARISION OF AIR COOLED AND WATER COOLED CONDENSER ATTACHED WITH COOLING TOWER

Energy and Exergy Analysis of an Ejector-Absorption Refrigeration Cycle with Using NH3-H2O as the Working Fluids

EVALUATION OF REFRIGERANT R290 AS A REPLACEMENT TO R22

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

Numerical Analysis of a Refrigeration System Using Different Nano Fluids by CFD

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

Comparative Study of Transcritical CO 2 Cycle with and Without Suction Line Heat Exchanger at High Ambienttemperature

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

International Journal of Engineering & Technology Sciences Volume 03, Issue 01, Pages 55-64, 2015

(Refer Slide Time: 00:00:40 min)

ME 410 MECHA ICAL E GI EERI G SYSTEMS LABORATORY

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR Siddharth Nagar, Narayanavanam Road AUTONOMOUS QUESTION BANK (DESCRIPTIVE) UNIT I

COMPARATIVE ANALYSIS OF SINGLE AND DOUBLE EFFECT LiBr-WATER ABSORPTION SYSTEM

Modelling the Performance of a Diffusion Absorption Refrigeration System

ENSC 388. Assignment #6

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

Numerical Study on Improvement of COP of Vapour Compression Refrigeration System

Waste Heat Utilization of Vapor Compression Cycle for Operation of Vapor Absorption System

ABSTRACT. Research Professor Yunho Hwang, Ph.D. Department of Mechanical Engineering

Vapour Compression-Absorption Cascade Refrigeration System- Thermodynamic Analysis

Experimental Analysis Of Vapour Compression Refrigeration System With Superheating By Using R-134a, R-12, R-717 Refrigerant

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

An Experiment of Heat Exchanger Produces Hot Water Using Waste Heat Recovery from Air Conditioning

Thermodynamic Calculations of Two-Stage Vapor Compression Refrigeration Cycle with Flash Chamber and Separate Vapor Mixing Intercooler

Performance of an Improved Household Refrigerator/Freezer

Implementation and testing of a model for the calculation of equilibrium between components of a refrigeration installation

Performance and exergy analysis of vapour compression refrigeration system using various alternative of R134a.

Thermodynamic analysis of air cycle refrigeration system for Chinese train air conditioning

Thermal Design of Condenser Using Ecofriendly Refrigerants R404A-R508B for Cascade Refrigeration System

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

ADVANCES in NATURAL and APPLIED SCIENCES

Dynamic Simulation of Liquid Chillers

Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Compression of Fins pipe and simple Heat pipe Using CFD

SAMPLE STUDY MATERIAL

Chapter 10. Refrigeration and Heat Pump Systems

International Journal of Research in Engineering and Innovation Vol-1, Issue-5 (2017), 68-72

NUMERICAL SIMULATION OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING REFRIGERANT R152A, R404A AND R600A

IJISET - International Journal of Innovative Science, Engineering & Technology, Vol. 2 Issue 12, December

A Review on Analysis of Vapour Compression Refrigeration System Using Matrix Heat Exchanger

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump ABSTRACT 1. INTRODUCTION

International Journal of Research in Engineering and Innovation Vol-3, Issue-1 (2019), 1-5

HEFAT th International Conference on Heat Transfer, Fluid Mechanics and Thermodynamics Sun City, South Africa Paper number:pp1

Performance Testing of Unitary Split-System Heat Pump with an Energy Recovery Expansion Device

EXPERIMENTAL INVESTIGATIONS ON AL 2 O 3 NANO REFRIGERANT WITH DIFFUSER AT CONDENSER INLET IN A VCR SYSTEM

Enhancement of COP by Using Spiral and Microchannel Condenser instead of conventional Condenser of VCR System

Performance Evaluation and Design Optimization of Refrigerated Display Cabinets Through Fluid Dynamic Analysis

Effect of the Use Pattern on Performance of Heat Pump Water Heater

Thermodynamic Analysis of Combined Vapor Compression and Vapor Absorption Refrigeration System ABSTRACT

Experimental Study Of An Ejector Refrigeration System

Numerical Simulation of Window Air Conditioner

Modeling and Simulation of Axial Fan Using CFD Hemant Kumawat

[Eswaran, 3(3): March, 2014] ISSN: Impact Factor: 1.852

An Investigation Into The Influence Of Improved Refrigeration Cycle And Refrigerants On An Energy Efficient Domestic Refrigerator

International Engineering Research Journal Performance Analysis of Ejector Based Solar Air Conditioning System

Heat Transfer Enhancement using Herringbone wavy & Smooth Wavy fin Heat Exchanger for Hydraulic Oil Cooling

Performance Analysis of Solar Assisted Cascade Refrigeration System of Cold Storage System

Analysis of a Condenser in a Thermal Power Plant for Possible Augmentation in its Heat Transfer Performance

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

SSC-JE STAFF SELECTION COMMISSION MECHANICAL ENGINEERING STUDY MATERIAL REFRIGERATION CYCLES REFRIGERATION CYCLES REFRIGERATION CYCLES

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Scientific Principals and Analytical Model. Charcoal Cooler. Lisa Crofoot MECH 425, Queens University

Volume 3, Issue 4 (2015) ISSN International Journal of Advance Research and Innovation

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

II. OBJECTIVE OF RESEARCH

ISSN Vol.08,Issue.21, November-2016, Pages:

Numerical study of heat pipe application in heat recovery systems

Performance of a Transcritical CO 2 Heat Pump for Simultaneous Water Cooling and Heating

STUDY OF VAPOUR COMPRESSION REFRIGERATION SYSTEM USING DOUBLE PIPE HEAT EXCHANGER

Performance of CO2 Cycles with a Two-Stage Compressor

PERFORMANCE OF DEEP FREEZER BY USING HYDROCARBON BLENDS AS REFRIGERANTS

LECTURE-17. Multi-Stage Vapour Compression Refrigeration. 1. Introduction

PERFORMANCE OF REFRIGERATOR USING R-600A AS REFRIGERANT

Low GWP Refrigerants for Air Conditioning Applications

η second law = Second law efficiency

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION THERMOELECTRIC REFRIGERATION SYSTEM WITH NOZZLE AND DIFFUSER THROUGH INCORPORATION OF PHASE CHANGE MATERIAL

Enhancement of COP in Vapour Compression Refrigeration System

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Performance Optimization of the Evaporative Condenser Design

Fig.: macroscopic kinetic energy is an organized form of energy and is much more useful

Transcription:

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant Ravi Verma 1, Sharad Chaudhary 2 1, 2 Department of Mechanical Engineering, IET DAVV Indore, India ---------------------------------------------------------------------***--------------------------------------------------------------------- Abstract - It is established that the Ejector Expansion Refrigeration system achieves the significant improvement in constant pressure ejector found that R1270 yields a maximum COP improvement of 42.85%. coefficient of performance as compared to other system. Use of an ejector as expansion device is one of the alternative ways. Nomenclature The performance of a vapour compression system that uses an ejector as an expansion device is investigated. Ejector Expansion Refrigeration systems are analysed in this article using constant pressure and constant area mixing ejector as an expansion device. This paper provides a comparison between constant pressure and constant area model using R- 1270 as a refrigerant. In the analysis, a two-phase constant area and constant pressure ejector flow model was used. Pressure variation along the length of the ejector is obtained for constant area model. The pressure variation is found to be higher for constant area ejector model compared to constant pressure model. V COP h P q e t w c x η μ Ø fluid velocity (m/s) coefficient of performance specific enthalpy (kj/kg) pressure (kpa) specific cooling effect (kj/kg) temperature ( o C) specific work (kj/kg) vapor quality isentropic efficiency entrainment ratio ejector area ratio Key words: Ejector, vapour compression cycle, R-1270 refrigerant, Coefficient of Performance 1. INTRODUCTION Use of ejector as an expansion device by replacing the throttling valve in the vapour compression refrigeration cycle seems to be one of the efficient ways to reduce the throttling loss or the expansion irreversibility in the refrigeration cycle. Ejector also reduces the compressor work by raising the suction pressure to a level higher than that in the evaporator leading to the improvement of Coefficient of Performance (COP). Kornhauser [1] analysed the thermodynamic performance of the ejector-expansion refrigeration cycle using R-12 as a refrigerant based on constant mixing pressure model and found a COP improvement of up to 21% over the standard Cycle under standard operating conditions. Ejector operation relies on the principle of interaction between two fluid streams at different energy levels, in order to provide compression work. The stream with high total energy is the primary stream or motive stream while the other, with the lowest total energy, is the secondary or induced stream. There is a mechanical energy transfer from the primary stream to the secondary stream; imposing on it a compression effect. Ejector reduces the compressor work by raising the suction pressure to a level higher than that of Evaporator, which in turn improves COP of the system. It also enables to reduce size of the evaporator. Ejector Expansion Refrigeration system is much more efficient than conventional VCR system. Raman in their work, using heat exchanger in the 2017, IRJET Impact Factor value: 5.181 ISO 9001:2008 Certified Journal Page 897 PLR pressure Lift Ratio Subscripts b basic cycle c compressor ej ejector II Literature Review Kornhauser [1] analysed the thermodynamic performance of the ejector expansion refrigeration cycle using R-12 as a refrigerant based on a constant mixing pressure model. Sarkar[3] has carried out thermodynamic analyses and comparison of three natural refrigerants based on compression refrigeration cycle(ammonia, isobutene, and propane) and found that the effect of using internal heat exchanger in ejector expansion refrigeration cycle is not profitable. Sarkar[4] analysed and compared the ammonia, propane and isobutene based vapour compression refrigeration cycle using constant area mixing ejector as an expansion device. Sarkar[5] analysed a two phase ejector and their applications in vapour compression refrigeration system. Chaudhary and Singh[6] did the work on the performance improvement in ejector expansion refrigeration system by using liquid vapour heat exchanger in constant mixing chamber

III. Model Description In Ejector Expansion Refrigeration System there are two models. 1. Constant Pressure Mixing Model 2. Constant area Model Constant Pressure Model: The constant pressure mixing ejector-expansion vapour compression Refrigeration cycle is shown in Figure 1 along with the Corresponding P h diagram in Figure 2. The primary stream from the condenser (state 3) and the secondary fluid from the evaporator (state 8) are flowing through primary and the secondary nozzles, respectively, 3-4 and 8-9 to mixing chamber at constant pressure. after the mixing of the flow is discharged to diffuser (10 5) section of the ejector and then separated in forms of vapour (state 1) and liquid (state 6) so that this ratio should be matched with the inlet ratio of primary and secondary flows. Then, the liquid circulates through expansion valve (6 7) and evaporator (7 8), whereas the vapour circulates through compressor (1 2) and condenser (2 3). Three ejector parameters, entrainment ratio (secondary mass flow to primary mass flow), pressure lift ratio (diffuser exit pressure to secondary nozzle inlet Pressure) and geometric area ratio (mixing chamber area to primary nozzle exit area) significantly influence the system performance with an optimum ratio. The ejector-expansion vapour compression refrigeration cycle has been modelled based on the mass, momentum and the energy conservations in each component. To simplify the theoretical model and setup the equations per unit total ejector flow, the following assumptions have been made: (i) Neglect the pressure drop in the condenser, evaporator, separator and the connection tubes. (ii) No heat transfer with the environment for the System except in condenser. (iii) The refrigerant conditions at the evaporator and condenser outlets are saturated. (iv) The vapour stream from the separator is saturated vapour and the liquid stream from the separator is saturated liquid. (v) The flow across the expansion valve or the throttle valves is isenthalpic. (vi) Both the motive stream and the suction stream reach the same pressure at the inlet of the constant area mixing section of the ejector. There is no mixing between the two streams before the inlet of the constant area mixing section. (vii) The expansion efficiencies of the motive stream and suction stream are given constants. The diffuser of the ejector also has a given efficiency. (viii) Kinetic energies of the refrigerant at the Ejector inlet and outlet are negligible Constant Area Ejector Expansion Refrigeration System:- The Schematic diagram of constant area ejector-expansion vapours compression Refrigeration cycle is shown in Figure 3 along with the corresponding P h diagram as shown in Figure 4. The primary flow from the condenser (state 3) and the secondary flow from the Figure1 Schematic Diagram of Constant Pressure Mixing Ejector expansion Refrigeration cycle Figure2 P-h Diagram of Constant pressure Refrigeration cycle Figure3 Schematic Diagram of Constant Area Mixing Ejector expansion Refrigeration cycle 2017, IRJET Impact Factor value: 5.181 ISO 9001:2008 Certified Journal Page 898

Compressor work: It is the amount of high grade energy which is required to run the compressor. Refrigeration Effect: It is the amount of heat which is to be taken from the evaporator. Figure4 P-h Diagram for Constant Area Ejector Expansion Refrigeration evaporator (state 8) are going through primary and secondary nozzles, respectively, constant area mixing and diffuser (10 5) sections of the ejector and then separated in forms of vapour (state 1) and liquid (state 6) so that this ratio should matched with the inlet ratio of primary and secondary flows. Then, the liquid circulates through expansion valve (6 7) and evaporator (7 8), whereas the vapour circulates through Compressor (1 2) and condenser (2 3). Three ejector parameters, entrainment ratio (secondary mass flow to primary mass flow), pressure lift ratio (diffuser exit pressure to secondary nozzle inlet pressure) and geometric area ratio (mixing chamber area to primary nozzle exit area) significantly influence the system performance with an optimum ratio. The Parameters used in expansion refrigeration cycle are as follows. Entrainment Ratio (µ): It is the ratio of secondary mass flow rate of refrigerant coming out from the evaporator (Vapor) to the primary mass flow rate of refrigerant coming out from the condense (liquid). µ= m v/m l Geometric area ratio(ø): It is the ratio of mixing chamber area (a 4+a 9) to primary nozzle exit area (a 4). Coefficient OF Performance: it is the ratio of refrigeration effect to work required. IV. METHODOLOGY For the analysis of Ejector expansion Model, Computational Fluid Dynamics (CFD) Software is used and Procedure was as given below: 1. Design the ejector as per proposed calculations [6]. 2. Design a boundary model of the ejector. 3. Import the geometry in Ansys flow dynamics. 4. Start the fluent flow solver. 5. Set the inlet conditions as pressure inlet, set inlet pressures in Pa and temperature in k. 6. Set outlet conditions as pressure outlet and define outlet pressure and temperature. 7. Define walls and allot material to it (aluminium). 8. Define the flowing fluid (in this case propylene). 9. Define no. of iteration to be run. 10. Specify ambient conditions. 11. Run the solver. 12. Open the result window. 13. Define the type of result display (i.e. pressure, temperature, velocity). 14. Set the number of contours required in the display graph. 15. Display and interpret the results. V. Results and Analysis Study for the analysis was carried out based on the following two bases. 1. Analysis based on COP 2. Analysis based on position of the primary nozzle 2017, IRJET Impact Factor value: 5.181 ISO 9001:2008 Certified Journal Page 899

Based on coefficient of Performance: COP of constant pressure ejector expansion refrigeration cycle was evaluated by developing thermodynamic model, and found that COP of Constant pressure EERS as compared to conventional VCRS. The COP of EER with constant pressure mixing ejector was 6.80 where as in case of VCRS it was 4.90. So % increase in COP is 38.7. Pressure variation with 5mm advancement of the nozzle For 10mm- Based on the position of primary nozzle: Changing the position of primary nozzle, different pressure Contours has been developed and the Following observations has been made. - From figure 5 to 8 are the pressure contours which show the pressure variation along the length of ejector. - As the primary nozzle position varies, there is change in the pressure for different segments. - In Fig.5 primary nozzle is advanced by 5mm towards the mixing chamber and found that the pressure at the exit of primary nozzle reaches to 1.30 10 5 [Pa] when exit pressure of diffuser is 5.41 10 5 [Pa]. - In Fig 6 there is 10mm advancement and pressure at the exit of primary nozzle is found to be less as compared to previous case. - Fig7 shows the pressure variation for 15 mm advancement of the primary nozzle. In this case the Pressure increases at the exit of primary nozzle with respect to the case of 10mm. - In Fig 8 it is found that the pressure variation is almost negligible when primary nozzle is advanced with 20mm. - By this analysis obtained results it is clear that after 20mm advancement of the primary nozzle there is no significant change in the pressure which results no more change in the performance of the cycle. Fig:-6 Pressure variation with 10mm advancement of the nozzle For 15 mm For 5mm: Fig:-7 Pressure variation with 15mm advancement of the nozzle Fig:-5 2017, IRJET Impact Factor value: 5.181 ISO 9001:2008 Certified Journal Page 900

For 20mm refrigerants. International Journal of Energy Research 2010; 34:84-94. 5. J.Sarkar. Renewable and Sustainable Energy Reviews 16,Issue 5 October 2012 6. Raman S, Chaudhary S. Methods to Improve the Performance of VCR Cycles using R-1270 as Refrigerant ; International Journal of Scientific and Research Publications, Volume 3, Issue 5, July 2015. Fig:-8 Pressure variation with 20mm advancement of the nozzle VI. Conclusion This paper provides the thermodynamic and CFD analysis of ejector expansion refrigeration cycle. Thermodynamic analysis for Constant pressure model using R-1270 as refrigerant is carried out whereas for constant area mixing ejector model, different pressure contours are developed using CFD software. In the analysis of Constant pressure model it is found that there is a significant improvement of COP as compared to conventional Vapor compression refrigeration system. In case of constant area mixing model, developed pressure contours gives the idea of pressure variation and mixing pattern of primary and secondary fluid streams when the primary nozzle is advanced at different positions. This pressure variation is justified with the previous work carried out by researchers. By the analysis and obtained results it is found that there is no significant change in the pressure after 20mm advancement of the primary nozzle, which results no more change in the performance of the constant area mixing ejector expansion cycle. REFERENCES 1. Kornhauser AA. The use of an ejector as a refrigerant expander. Proceedings of the 1990 USNC/IIR-Purdue Refrigeration Conference, West Lafayette, IN, U.S.A.,1990; 10 19. 2. Li Daqing, Groll E.A. Transcritical CO2 refrigeration cycle with ejector- expansion device. International Journal of Refrigeration 28 (2005); 766 773. 3. J.Sarkar, Performance characteristics of natural refrigerants based ejector expansion refrigeration cycles, Proceedings of the IMechE, Part A: Journal of Power and Energy 2009,223, pp. 543 50. 4. Sarkar J. Geometric parameter optimization of ejector-expansion refrigeration cycle with natural 2017, IRJET Impact Factor value: 5.181 ISO 9001:2008 Certified Journal Page 901