TENDER NOTICE. Kolhapur Zilla Sahakari Dudh Utpadak Sangh Ltd. B-1, M.I.D.C., Gokul Shirgaon, Tal. Karveer, Dist. Kolhapur

Similar documents
PRICE BID. UNIT QTY Rate in Figure Rate in words Amount DESCRIPTION OF ITEM D: FIRE PROTECTION SYSTEM

ENGINEERING PROJECTS (INDIA) LTD. (A Govt. of India Enterprise) Signature of Bidder 1 of 11 EPI

Supply & Installation of Fire Protection System at STPI- Nashik. Tender No. STPI/P/PUR/07/14-15 Date Signature of Bidder

SUPPLY,INSTALLATION,TESTING AND COMMISSIONING OF SPRINKLER SYSTEM AND FIRE ALARM SYSTEM FOR AIR INDIA LIMITED AT SHAMSHABAD, HYDERABAD.

CENTRAL BOARD OF SECONDARY EDUCATION SHIKSHA KENDRA, 2, COMMUNITY CENTRE, PREET VIHAR, DELHI

EE/ / To, Dear Sir,

Purchase: (Fire Fighting) May 26, Sub: Quotation for AMC of Fire Fighting Systems

BOQ FOR FIRE HYDRANT & FIRE ALARM SYSTEM AT T.I.E

TENDER DOCUMENT FOR CHECKING, TESTING AND REPAIRING OF FIRE HYDRANT AND SPRINKLER SYSTEM AT Bank Of India, STC Building, B-32, Sector-62 Noida

BANK OF BARODA BARODA CORPORATE CENTRE MUMBAI

CENTRAL BOARD OF SECONDARY EDUCATION, 2, COMMUNITY CENTRE, PREET VIHAR, DELHI-92

INDUSTRIAL EXTENSION BUREAU

Date of Start and downloading the tender 12 sep 2018

LIFE INSURANCE CORPORATION OF INDIA DIVISIONAL OFFICE 16/275, CIVIL LINES, KANPUR

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements.

SBI INFRA MANAGEMENT SOLUTIONS PVT.LTD. HEAD OFFICE-GROUND FLOOR RAHEJA CHAMBERS, FREE PRESS JOURNAL MARG, NARIMAN POINT, MUMBAI-21

Tender document for Supply/ Installation of New Fire extinguishers & Refilling TENDER NOTICE

UNIVERSITY OF MISSOURI Fire Protection System Design 2016 Q1

NATIONAL BANKING GROUP WEST-1

DEPARTMENT OF FIRE & EMERGENCY SERVICES DNH.

CubeSmart Gulf Breeze Storage AUTOMATIC FIRE SPRINKLER SYSTEM

BANK OF BARODA BIHAR REGIONAL OFFICE, 4 TH FLOOR, ANAND VIHAR, West Boring Canal Road, Patna TENDER NOTICE

* To be remitted only through DD/Banker Cheque, in favour of Bank of Baroda, payable at Bhopal.

Following are the systems proposed as per NBC & Local Fire Authority:

TR CASSETTE AC 1 NOS TR CASSETTE AC 1 NOS. Rate in words : TR HIGH WALL (3 star rated) 2 NOS.

SECTION WET-PIPE SPRINKLER SYSTEMS

NIT NO. BSRDCL-2039/ TENDER DOCUMENT INSTALLATION, CONFIGURATION, TESTING, COMMISSIONING AND TRAINING OF SMOKE DETECTION FIRE ALARM SYSTEM

Reliance Fire Protection Systems

ENGINEERING PROJECTS (INDIA) LTD. (A Govt. of India Enterprise) PRICED BILL OF QUANTITIES

B. Product Data: Provide manufacturers catalogue information. Indicate valve data and ratings.

BANK OF BARODA ZONAL OFFICE, MP & CG ZONE BHOPAL TENDER NOTICE

TENDER NOTICE FOR SUPPLY, INSTALLATION AND MAINTENANCE OF FIRE EXTINGUISHERS AT BRANCHES / OFFICES IN KARNATAKA & ANDHRA PRADESH ZONE

TENDER NOTICE FOR DESIGNING, SUPPLY, INSTALLATION, TESTING, COMISSIONING AND MAINTENANCE OF FIRE ALARM SYSTEM AT APROX.

TENDER NOTICE FOR SUPPLY, INSTALLATION AND MAINTENANCE OF FIRE EXTINGUISHERS AT BRANCHES / OFFICES IN NCR AND ADJOINING AREAS

Design and Supply of Fire Equipments. External Fire Fighting Systems.


TENDER No /NIT NO. BECIL/FF/2014/55 RECTIFICATION / MODIFICATION OF EXISTING FIRE FIGHTING & FIRE ALARM SYSTEM WORKS

TENDER NOTICE FOR RATE CONTRACT FOR SUPPLY, INSTALLATION AND REFILLING OF FIRE EXTINGUISHERS AT BRANCHES / OFFICES IN NCR AND ADJOINING AREAS

Ravi Malik General Manager

SECTION WET AUTOMATIC FIRE SPRINKLER SYSTEMS

BILL OF QUANTITY OF AIR CONDITIONING WORK FOR SBI JASDAN BRANCH, RAJKOT

C. All components of the systems described shall meet the requirements as stated herein and shall be approved by the Architect and Consultant.

COBB COUNTY SCHOOLS /S&A % BID DOCUMENTS 2/18/11 SECTION SPRINKLER SYSTEM

NOTICE INVITING TENDER

STAR HOUSE BANK OF INDIA NATIONAL BANKING GROUP NORTH-I H-2 CONNAUGHT CIRCUS Middle/Outer Circle, Phone No

DIVISION 21 FIRE SUPPRESSION SECTION FIRE PROTECTION SPECIALTIES

GAS FLOODING SYSTEM FOR CIFF AT BASEMENT


Department of Biochemistry University of Lucknow Lucknow

SUPREME COURT OF INDIA ADMN. MATERIAL BRANCH NOTICE INVITING TENDER FOR COMPREHENSIVE ANNUAL MAINTENANCE CONTRACT FOR RE-FILLING OF FIRE EXTINGUISHERS

Technical write-up on Fire safety services

Bold items are particular to the City of Euless

Model AV Alarm Valve With and Without Model RC-1 Retard Chamber European Conformity Valve Trim General Description

Indian National Trust for Art and Cultural Heritage (INTACH, 71, KK Birla Lane, Lodhi Estate, New Delhi , Ph. No.

ODISHA POWER TRANSMISSION CORPORATION LIMITED OFFICE OF THE GENERAL MANAGER EHT (O&M) CIRCLE, BIDYUTPURI COLONY, BERHAMPUR

INSTALLATION OF DURAVENT POLYPRO SINGLE WALL POLYPROPYLENE VENTING SYSTEMS

B. Related Sections: The following Sections contain requirements that relate to this Section.

The following are the terms and conditions for the firms for submission of bids:

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

ADDENDUM NO. 3 March 19, 2018

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN

Relationship beyond banking

ESTATE DEPARTMENT RAJBHAVAN COMPLEX, BANER ROAD, PUNE Phone No. (020) & , Fax No. (020)

A. This section includes design and performance information for fire protection and suppression systems.

BANK OF BARODA, ZONAL OFFICE, EASTERN U.P ZONE, BARODA HOUSE, V-23, VIBHITI KHAND, GOMTI NAGAR, LUCKNOW, TEL: , TENDER NOTICE FOR

Newport City Council Bettws High School Fire Fighting Performance Specification CONTRACT C1

TENDER FOR EMPANELMENT OF VENDORS FOR REFILLING AND SUPPLY OF NEW FIRE EXTINGUISHERS FOR BRANCHES AND OFFICES IN ZONE UNDER

International Fire Code 2006 Requirements for Construction Plan Reviews of Commercial and Multi-Family Structures

RISK ASSESSMENT & EMERGENCY PREPAREDNESS PLAN

TENDER NOTICE FOR DESIGNING, SUPPLY, INSTALLATION, TESTING, COMISSIONING AND MAINTENANCE OF FIRE ALARM SYSTEM AT APROX.

TENDER DOCUMENT FOR RATE CONTRACT FOR REFILLING AND SUPPLY OF NEW FIRE EXTINGUISHERS FOR BRANCHES AND OFFICES

PROFESSIONAL SUPPLIER

In the year 1988, Amit Industrial Corporation is a reputed name in the industry for Manufacturing and

KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

Owner/Operator Guide for Successful Sprinkler and Fire Pump Systems

CENTRAL BOARD OF SECONDARY EDUCATION, 2, COMMUNITY CENTRE, PREET VIHAR, DELHI-92 TENDER NOTICE

Request for quotation (RFQ) for goods/services

SECTION FIRE PROTECTION

SBI INFRA MANAGEMENT SOLUTIONS PVT. LTD., CIRCLE OFFICE, BHOPAL PART B : PRICE BID

WET AUTOMATIC FIRE SPRINKLER SYSTEMS

DEPARTMENT OF FIRE & EMERGENCY SERVICES DNH.

Enclosure 4- RISK ASSESSMENT

Solutions at every turn.

Division 21: FIRE SUPRESSION WET-PIPE SPRINKLER PROTECTION SYSTEM. The Academy Sept Table of Contents 1 Division 21

Servicing, refilling & maintenance of Fire Extinguishers for RBPH W - 36

highline SVCS-1 INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10

Appendix B. Symbols for Drawings. Table B.1. Air moving devices and ductwork symbols. Air Movement. Fans. Axial flow fan.

Govt. of West Bengal Online Clearance for Fire Safety Certificate and Renewal (Application for Fire Safety Recommendations)

TRIMAX ASIA ENGINEERING & CONSTRUCTION (PG U )

TENDER FOR EMPANELMENT OF VENDORS

SECTION FIRE-SUPPRESSION STANDPIPES

EXPRESSION OF INTEREST (EOI) FOR. Fire Fighting System (FFS)

Bhubaneswar for an over viewing related documents/drawings/plans/etc in any working days during above period.

BANK OF BARODA, ZONAL OFFICE, EASTERN U.P ZONE, BARODA HOUSE, V-23, VIBHITI KHAND, GOMTI NAGAR, LUCKNOW, TEL: , TENDER NOTICE FOR

TN-25 Tunnel Fire Protection System. Safer. Smarter. Tyco.

Appendix - F BANK OF BARODA, GREATER MUMBAI ZONE, MUMBAI PRICE BID TENDER FOR SUPPLY / INSTALLATION OF CCTV SYSTEM. Bill of quantity Price Bid

Bank of Baroda Zonal Office, Tamil Nadu and Kerala Zone, Baroda Pride, New No.-41, Luz Church Road, Mylapore, Chennai

model NO. LSS GALLON SKID MOUNTED HIGH PRESSURE SPRAYER ASSEMBLY / OPERATION INSTRUCTIONS / PARTS

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description

Transcription:

TENDER NOTICE Sealed Tender offers are invited for supply, installation & commissioning of Fire Hydrant System at our Gokul Dairy Project Complex at Gokul Shirgaon Kolhapur. Only contractors having valid Licence issued by Director of Maharashtra Fire Services, Mumbai are eligible to submit Tender offer. Tender details including details of material/equipment required for fire hydrant system, scope of work and Terms & Conditions of Tender are available at our Gokul Shirgaon office from 3.2.208 during office hours. Tender details are also availabe on our web site www.gokulmilk.coop. Sealed Tender offers duly marked as " Tender for Hydrant System" alongwith D/D towards EMD of Rs. 50,000/- should be submitted at our head office at Gokul Shirgaon, Kolhapur on or before 4.2.208. Right to accept or reject any or all Tenders is reserved. Managing Director Chairman Kolhapur Zilla Sahakari Dudh Utpadak Sangh Ltd. B-, M.I.D.C., Gokul Shirgaon, Tal. Karveer, Dist. Kolhapur 4 6234

TENDER DETAILS

KOLHAPUR ZILLA SAHAKARI DUDH UTPADAK SANGH LTD., KOLHAPUR GENERAL TERMS & CONDITIONS OF TENDER ( FIRE HYDRANT SYSTEM TENDER). Tenderer must be a Licensed contractor having Licence issued by Director of Maharashtra Fire Services, Mumbai. Copy of valid Licence should be attached with the Tender. 2. This contract will be a Turn Key Job. Final NOC is to be arranged by contractor. 3. Tender offer is to be given on the Letter head of the Tenderer in the precribed format given by us. 4. Tenderers may visit the site to get idea about this work before sumitting their Tender offer. 5. Material details their specifications and quantities of required material for Fire Hydrant System are given the Tender documents. Rate offered should be inclusive of GST and transport charges. 6. Earnest Money Deposit of Rs. 50,000/- is to be given alongwith the Tender by D/D issued in the name of Kolhapur Zilla Sahakari Dudh Utpadak Sangh Ltd., Kolhapur. Tender without EMD will not be considered. 7. Payment - a) 40% amount of total contract price will be given as an advance against Bank Guarantee of equivalent amount. b) Remaining payment will be released after satisfactory installation and succesful trials of Hydrant System within one month. This payment will be released only after getting NOC from concerned Goverment authority. 8. Sealed Tender offer duly marked as "TENDER FOR FIRE HYDRANT SYSTEM" alongwith requisite EMD should be submitted at our Head office at B-, M.I.D.C., Gokul Shirgaon, Kolhapur on or before 4.2.208. 9. Right to accept or reject any Tender without assigning any reason is reserved. 0.Subject to Kolhapur Jurisdiction. Managing Director

KOLHAPUR JILHA SAHAKARI DUDH UTPADAK SANGH LTD., KOLHAPUR SCOPE OF WORK - We are inviting sealed Tender offers for supply,installation & commissioning of Fire Hydrant System for our New expanded dairy (Processing Area, Refrigeration section, milk packing section) and new boiler House. This would be a ' Turn Key Job', Supply of required equipment / material, installation and commissioning of Hydrant System in specified areas is the scope of work. Obtaining No Objection Certificate (NOC) from Fire department is in the scope of contractor. Entire details of required equipment/ material, their specifications, make and quantities are given in the prescribed Tender format.

TENDER OFFER FORMAT (To be given on the Letterhead of Tenderer) To, The Managing Director, Kolhapur Zilla Sahakari Dudh Utpadak Sangh Ltd. B-, M.I.D.C., Gokul Shirgaon, Tal. Karveer, Dist. Kolhapur - 46 234 Dear Sir, Sub - Tender offer for Fire Hydrant System In continuation to your Tender Notice published in Daily Lokmat, Kolhapur on 3.2.208, I / we submit our Tender offer for Fire Hydrant System for your Dairy Project at Gokul Shirgaon, Kolhapur. We have gone through Terms & conditions of the Tender. We are aware of the scope of work. We agree upon the Terms & Condions of the Tender. Our Contract price for supply, installation and commissioning of Fire Hydrant System is Rs. (In words Rs. ) This price in all inclusive contract price which is inclusive of Transport charges, installation-commissioning charges and applicable GST. Note- Price details sheet in the format given by you is attached herewith. Yours faithfully Seal & Signature of Tenderer Date - Encl. ) Price Details Sheet 2) Copy of Licence from Director, Fire Services, Mumbai 3) D/D towards EMD

PRICE DETAILS PART st - NEW BOILER HOUSE FIRE HYDRANT SYSTEM A) FIRE HYDRANT WORK FOR NEW BOILER HOUSE. No. Details Of Work Qty. Supply. Supply and Installing, testing, perfect alignment and proper leveling and commissioning of fire service Main Electrical Fire Pump of 2850 at 70 mtr. Head coupled type installed by auto system with all accessories.. {KIRLOSKAR MAKE} 2. Supply and Installing, testing, and commissioning of Diesel engine driven Pump 2850 LPM including exhaust piping, heat exchanger, residential silencer, rubber pad, starting arrangement, starting battery set, diesel oil tank mounted on suitable structural support etc. complete in all respect. {KIRLOSKAR MAKE} 3. Supply and Installing, testing, perfect alignment and proper leveling and commissioning of Jokey Pump of 900 LPM at 70 mtr. Head installed by auto system with all accessories. {KIRLOSKAR MAKE} 4. Supplying and installing, testing and commissioning of Pipeline Jindal / Zenith Birla Make. M.S.round C Class ISI Mark with welded joints to correct grade / alignment including cutting the pipes to correct length providing and welding pipes jointing by means of welding, providing and fixing with heavy MS brackets/ hangers anchor fastener. Design, testing, rectifying the leakages if any along with painting the pipes in 2 coats of enamel paints on cote of red oxide primer complete as per specification with painting {I} Installation {II}

4. suitable type of supports, anchor fasteners, nut bolts, clamps, U bolts malleable specials such as reducers, tees, elbows, flanges including cutting, welding, fixing in/ on walls, ceiling by using suitable supports etc as per drawings. The quoted rates shall also include for chasing/ chipping walls, making bore holes in wall/ floor and making them good with filler material and finished in cement mortar etc complete. 50 mm 54 mtr. 00 mm 80 mm 5. Butterfly Valve Supply and Installation of cast iron double flange Butterfly valve {H.SARKAR/KIRLOSKAR/ ZOLOTO/ LEADER} ISI MARK 50 mm 00 mm 6. Non Return Valve Supply and Installation of cast iron double flange Butterfly valve {H.SARKAR/KIRLOSKAR/ ZOLOTO/ LEADER} ISI MARK 00 mm 80 mm 7. Foot Valve Supply and Installation of cast iron foot valve 00 mm 80 mm 8. Strainer Supplying and Installing 00 mm dia end line strainer for + ve suction as per specification No. FF-VL/ELS 9. Portable Fire Extinguisher {SAFEPRO/Minimax/Ceasefire/ Firex BRAND}ISI 6 Kg. A.B.C. Type 4.5 KG CO 2 Type 26 mtr. 8 mtr. 2 2 6 2

0. Fire Bridge Connection Supplying and Installing Fire Service inlet with 2 way connection for supplying water in fire tank.{radheya/arihant Make }. Courtyard Hydrant Valve Supplying and Installing Gun Metal 63 mm Single outlet fire hydrant valve ISI, {Radheya/Arihant/Minimax/ Radiant Make} 2. Hose pipe Supplying Fire Fighting RRL Hose Pipe 63mm die with male/ female coupling Gun Metal (5mtr) ISI Premier Brand - A class. {Jayashree/Newage/Tulasi} 3. M.S.Hose Box Supplying and Installing 6 Gauges Single Door with Glass in front with Lock & Key. 4. Branch Pipe Supplying and Installing Gun Metal detachable hexagonal nozzle ISI 8 8 8 8 5. Hose Reel Providing & Fixing Fire Hose Reel, Wall Mounting Swining Type Fitted with 30 mm die. 30 mtr.long. 5 TOTAL PRICE OF 'A' i.e. TOTAL OF COLOUMN {I} & {II} RS.

B) SPRINKLER SYSTEM FOR NEW BOILER HOUSE - No. Details Of Work Qty. Supply. Supplying and installing, testing and commissioning of Pipeline Jindal / Zenith Birla Make. M.S.round C Class ISI Mark with welded joints to correct grade / alignment including cutting the pipes to correct length providing and welding pipes jointing by means of welding, providing and fixing with heavy MS brackets/ hangers anchor fastener. Design, testing, rectifying the leakages if any along with painting the pipes in 2 coats of enamel paints on cote of red oxide primer complete as per specification with painting suitable type of supports, anchor fasteners, nut bolts, clamps, U bolts malleable specials such as reducers, tees, elbows, flanges including cutting, welding, fixing in/ on walls, ceiling by using suitable supports etc as per drawings. The quoted rates shall also include for chasing/ chipping walls, making bore holes in wall/ floor and making them good with filler material and finished in cement mortar etc complete. {I} Installation {II} 80 mm 40 mm 2. Sprinkler Head Supply and Installing of sprinkler head pendant type. {KIRLOSKAR MAKE} 30 MTR 300 MTR 00 TOTAL PRICE OF 'B' i.e. TOTAL OF COLOUMN {I} & {II} RS. C) FIRE ALARM SYSTEM AND SMOKE DETECTOR FOR NEW BOILER

HOUSE No. Details Of Work Qty. Supply. Fire alarm panel Supply and Installation, testing and commissioning of 2 loop networkable type Fire Alarm / detection control panel {expandable}. The panel should be able to give location of all fire / fault condition of addressable units via the address code. The panel should be able to automatically switch ON / OFF respective control module whenever any alarm is triggered.{simence/ Tyco/ Honewell/ {I} Installation {II} 2. Addressable Hooter SITC OF addressable type loop powered hooter complete with mounting base as required confirming to BS 5839 4 3. Repeater Panel SITC OF analog addressable type active repeater fire alarm panel with backlight LCD display having controls for reset, mute, accept, silence, alarms and self test confirming to BS 5839 standards and duly approved by EN54/ LPCB/ VDS/ UL/ BSA. {Simence/ Tyco/ Honewell/ 4 Addressable Manual Call Point SITC OF analog addressable type Manual Call Point having surface or flush mounting option fully complete to EN54 having rotary decade switches for addressing complete with back box for mounting as required confirming to BS 5839 5

5. Addressable Smoke Detector SITC of intelligent analog addressable type photoelectric type smoke detector complete with DUAL LED hard addressable having rotary decade address switches complete with mounting base complete as required confirming to BS 5839 6. Heat Detector SITC OF intelligent analog addressable type rate of rise / fixed heat detector complete with dual led heat addressable having rotary decade address switches complete with mounting base complete as required confirming to BS 5839 7. Cable Supply and Installation, testing and commissioning of 2 core.5 sq. mm armored cable shedding{red color} {Finolex/ RPG/ Nicco/ Polycab/ Siemence MAKE} Supply and Installation, testing and commissioning of 4 core.5 sq. mm armored cable shedding{red color}for repeater panel {Finolex/ RPG/ Nicco/ Polycab/ Siemence MAKE} TOTAL PRICE OF 'C' i.e. TOTAL OF COLOUMN {I} & {II} RS. 20 4 25 MTR 5 MTR TOTAL OF PART st (A+B+C ) RS. price of New Boiler House Fire Hydrant System i.e PART st ( In words Rs. )

PART 2 nd FIRE HYDRANT SYSTEM FOR NEW DAIRY (Fire Hydrant System for new Processing plant, Refrigeration area & packing section) A) FIRE HYDRANT WORK FOR MILK PROCESSING PLANT. No. Details Of Work Qty. Supply. Supply and Installing, testing, perfect alignment and proper leveling and commissioning of fire service Main Electrical Fire Pump of 2850 at 70 mtr. Head coupled type installed by auto system with all accessories.. {KIRLOSKAR MAKE} 2. Supply and Installing, testing, and commissioning of Diesel engine driven Pump 2850 LPM including exhaust piping, heat exchanger, residencial silencer, rubber pad, starting arrangement, starting battery set, diesel oil tank mounted on suitable structural support etc. complete in all respect. {KIRLOSKAR MAKE} 3. Supply and Installing, testing, perfect alignment and proper leveling and commissioning of Jokey Pump of 80 LPM at 70 mtr. Head installed by auto system with all accessories.. {KIRLOSKAR MAKE} 4. Supplying and installing, testing and commissioning of Pipeline Jindal / Zenith Birla Make. M.S.round C Class ISI Mark with welded joints to correct grade / alignment including cutting the pipes to correct length providing and welding pipes jointing by means of welding, providing and fixing with heavy MS brackets/ hangers anchor fastener. Design, testing, rectifying the leakages if any along with painting the pipes in 2 coats of enamel paints on cote of red oxide primer complete as per specification with painting suitable type of supports, anchor fasteners, nut bolts, {I} Installation {II}

clamps, U bolts malleable specials such as reducers, tees, elbows, flanges including cutting, welding, fixing in/ on walls, ceiling by using suitable supports etc as per drawings. The quoted rates shall also include for chasing/ chipping walls, making bore holes in wall/ floor and making them good with filler material and finished in cement mortar etc complete. 00 mm 80 mm 5. Butterfly Valve Supply and Installation of cast iron double flange Butterfly valve {H.SARKAR/KIRLOSKAR/ ZOLOTO/ LEADER} ISI MARK 00 mm 80 mm 6. Non Return Valve Supply and Installation of cast iron double flange Butterfly valve {H.SARKAR/KIRLOSKAR/ ZOLOTO/ LEADER} ISI MARK 00 mm 80 mm 7. Foot Valve Supply and Installation of cast iron foot valve 00 mm 80 mm 8. Strainer Supplying and Installing 00 mm dia end line strainer for + ve suction as per specification No. FF-VL/ELS 9. Portable Fire Extinguisher {SAFEPRO/Minimax/Ceasefire/ Firex BRAND}ISI 6 Kg. A.B.C. Type 4.5 KG CO 2 Type 0. Fire Bridge Connection Supplying and Installing Fire Service inlet with 2 way connection for supplying water in fire tank.{radheya/arihant Make } 255 mtr. 2 mtr. 2 2 20 08. Courtyard Hydrant Valve Supplying and Installing Gun

Metal 63 mm Single outlet fire hydrant valve ISI, {Radheya/ Arihant/Minimax/ Radiant Make} 2. Hose pipe Supplying Fire Fighting RRL Hose Pipe 63mm die with male/ female coupling Gun Metal (5mtr) ISI Premier Brand - A class. {Jayashree/Newage/Tulasi} 3. M.S.Hose Box Supplying and Installing 6 Gauges Double Door with Glass in front with Lock & Key. 4. Branch Pipe Supplying and Installing Gun Metal detachable hexagonal nozzle ISI 5. Hose Reel Providing & Fixing Fire Hose Reel, Wall Mounting Swining Type Fitted with 30 mm die. 30 mtr.long. 2 24 2 2 4 TOTAL PRICE OF 'A' i.e. TOTAL OF COLUMN {I & II} RS.

B) FIRE HYDRANT WORK FOR POUCH FILLING PLANT. No. Details Of Work Qty. Supply Amoun t {I} Installation {II}. Supply and Installing, testing, perfect alignment and proper leveling and commissioning of fire service Main Electrical Fire Pump of 620 LPM at 70 mtr. Head coupled type installed by auto system with all accessories..{kirloskar MAKE} 2. Supply and Installing, testing, perfect alignment and proper leveling and commissioning of Jokey Pump of 80 LPM at 70 mtr. Head installed by auto system with all accessories.. {KIRLOSKAR MAKE} 3. Supplying and installing, testing and commissioning of Pipeline Jindal / Zenith Birla Make. M.S.round C Class ISI Mark with welded joints to correct grade / alignment including cutting the pipes to correct length providing and welding pipes jointing by means of welding, providing and fixing with heavy MS brackets/ hangers anchor fastener. Design, testing, rectifying the leakages if any along with painting the pipes in 2 coats of enamel paints on cote of red oxide primer complete as per specification with painting suitable type of supports, anchor fasteners, nut bolts, clamps, U bolts malleable specials such as reducers, tees, elbows, flanges including cutting, welding, fixing in/ on walls, ceiling by using suitable supports etc as per drawings. The quoted rates shall also include for chasing/ chipping walls, making bore holes in wall/ floor and making them good with filler material and finished in cement mortar etc complete.

00 mm 96 mtr. 80mm 06 mtr. 4. Butterfly Valve Supply and Installation of cast iron double flange Butterfly valve {H.SARKAR/KIRLOSKAR/ ZOLOTO/ LEADER} ISI MARK 00 mm 6. Non Return Valve Supply and Installation of cast iron double flange Butterfly valve {H.SARKAR/KIRLOSKAR/ ZOLOTO/ LEADER} ISI MARK 00 mm 80 mm 7. Foot Valve Supply and Installation of cast iron foot valve 00 mm 80 mm 8. Strainer Supplying and Installing 00 mm dia end line strainer for + ve suction as per specification No. FF-VL/ELS 9. Portable Fire Extinguisher {SAFEPRO/Minimax/Ceasefire/ Firex BRAND}ISI 6 Kg. A.B.C. Type 4.5 KG CO 2 Type 0. Fire Bridge Connection Supplying and Installing Fire Service inlet with 2 way connection for supplying water in fire tank.{radheya/arihant Make } 8 2. Courtyard Hydrant Valve Supplying and Installing Gun Metal 63 mm Single outlet fire hydrant valve ISI, {Radheya/Arihant/Minimax/ Radiant Make} 2. Hose pipe Supplying Fire Fighting RRL Hose Pipe 63mm die with male/ female coupling Gun Metal (5mtr) ISI Premier Brand - A class. {Jayashree/Newage/Tulasi} 4 4

3. M.S.Hose Box Supplying and Installing 6 Gauges Sngle Door with Glass in front with Lock & Key. 4. Branch Pipe Supplying and Installing Gun Metal detachable hexagonal nozzle ISI 5. Hose Reel Providing & Fixing Fire Hose Reel, Wall Mounting Swining Type Fitted with 30 mm die. 30 mtr.long. TOTAL PRICE OF 'B' i.e. TOTAL OF COLUMN {I & II} RS. 4 4 4

C) FIRE ALARM SYSTEM AND SMOKE DETECTOR FOR MILK PROCESSING PLANT No. Details Of Work Qty. Supply. Fire alarm panel Supply and Installation, testing and commissioning of 2 loop networkable type Fire Alarm / detection control panel {expandable}. The panel should be able to give location of all fire / fault condition of addressable units via the address code. The panel should be able to automatically switch ON / OFF respective control module whenever any alarm is triggered.{simence/ Tyco/ Honewell/ 2. Addressable Hooter SITC OF addressable type loop powered hooter complete with mounting base as required confirming to BS 5839 3. Repeater Panel SITC OF analog addressable type active repeater fire alarm panel with backlight LCD display having controls for reset, mute, accept, silence, alarms and self test confirming to BS 5839 standards and duly approved by EN54/ LPCB/ VDS/ UL/ BSA. {Simence/ Tyco/ Honewell/ 4. Addressable Manual Call Point SITC OF analog addressable type Manual Call Point having surface or flush mounting option fully complete to EN54 having rotary decade switches for addressing complete with back box for mounting as required confirming to BS 5839 2 2 {I} Installation {II}

5. Addressable Smoke Detector SITC of intelligent analog addressable type photoelectric type smoke detector complete with DUAL LED hard addressable having rotary decade address switches complete with mounting base complete as required confirming to BS 5839 6. Heat Detector SITC OF intelligent analog addressable type rate of rise / fixed heat detector complete with dual led heat addressable having rotary decade address switches complete with mounting base complete as required confirming to BS 5839 7. Cable Supply and Installation, testing and commissioning of 2 core.5 sq. mm armored cable shedding{red color} {Finolex/ RPG/ Nicco/ Polycab/ Siemence MAKE} Supply and Installation, testing and commissioning of 4 core.5 sq. mm armored cable shedding{red color}for repeater panel {Finolex/ RPG/ Nicco/ Polycab/ Siemence MAKE} TOTAL PRICE OF 'C' i.e. TOTAL OF COLUMN {I & II} RS. 40 6 350 MT R 55 MT R

D) FIRE ALARM SYSTEM AND SMOKE DETECTOR FOR POUCH FILLING PLANT. No. Details Of Work Qty. Supply. Fire alarm panel Supply and Installation, testing and commissioning of 2 loop networkable type Fire Alarm / detection control panel {expandable}. The panel should be able to give location of all fire / fault condition of addressable units via the address code. The panel should be able to automatically switch ON / OFF respective control module whenever any alarm is triggered. {Simence/Tyco/ Honewell/ 2. Addressable Hooter SITC OF addressable type loop powered hooter complete with mounting base as required confirming to BS 5839 3. Repeater Panel SITC OF analog addressable type active repeater fire alarm panel with backlight LCD display having controls for reset, mute, accept, silence, alarms and self test confirming to BS 5839 standards and duly approved by EN54/ LPCB/ VDS/ UL/ BSA. {Simence/ Tyco/ Honewell/ 4. Addressable Manual Call Point SITC OF analog addressable type Manual Call Point having surface or flush mounting option fully complete to EN54 having rotary decade switches for addressing complete with back box for mounting as required confirming to BS 5839 2 6 Amoun t {I} Installation {II}

5. Addressable Smoke Detector SITC of intelligent analog addressable type photoelectric type smoke detector complete with DUAL LED hard addressable having rotary decade address switches complete with mounting base complete as required confirming to BS 5839 6. Heat Detector SITC OF intelligent analog addressable type rate of rise / fixed heat detector complete with dual led heat addressable having rotary decade address switches complete with mounting base complete as required confirming to BS 5839 7. Cable Supply and Installation, testing and commissioning of 2 core.5 sq. mm armored cable shedding{red color} {Finolex/ RPG/ Nicco/ Polycab/ Siemence MAKE} Supply and Installation, testing and commissioning of 4 core.5 sq. mm armored cable shedding{red color}for repeater panel {Finolex/ RPG/ Nicco/ Polycab/ Siemence MAKE} TOTAL PRICE OF 'D' i.e. TOTAL OF COLUMN {I & II} RS. TOTAL OF PART 2 nd (A+B+C+ D ) Rs. 20 3 00 MT R 75 MT R price of Fire Hydrant System for New Dairy i.e. PART 2 nd ( In words Rs. ) TOTAL CONTRACT PRICE (i.e, Part st + Part 2 nd ) = Rs. ( Contract price In words Rs. ) Signature of Tenderer