APPLICATION OF CFD SIMULATIONS FOR LOCATING OUTDOOR UNITS ON HIGH RISE TOWER Basant Kumar Gupta 1, Anand Patil 2

Similar documents
CFD Analysis of a 24 Hour Operating Solar Refrigeration Absorption Technology

Modeling and Simulation of Axial Fan Using CFD Hemant Kumawat

Effect of Flow Distortion in Inlet Duct on the Performance of Centrifugal Blower

[Eswaran, 3(3): March, 2014] ISSN: Impact Factor: 1.852

Heat Transfer Enhancement using Herringbone wavy & Smooth Wavy fin Heat Exchanger for Hydraulic Oil Cooling

OPTIMIZATION OF VENTILATION MODE OF SMOKE CONTROL SYSTEM IN HIGH-RISE BUILDING FIRE

Air Flow Study inside the Supermarket Refrigeration System

Simulation of Evacuation Process in a Supermarket with Cellular Automata

Study of Hot-air Recirculation around Off-road Tier-4 Diesel Engine Unit Using CFD Abbreviations Keywords Abstract Introduction and Background

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION

AIRFLOW STUDY OF A SPILT-TYPE OUTDOOR UNIT SUBJECTED TO NEAR WALL EFFECT USING COMPUTATIONAL FLUID DYNAMIC (CFD) SIMULATION

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

Experimental Analysis of Open, Simple and Modified Greenhouse Dryers for Drying Potato Flakes under Forced Convection

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Analysis of Evaporative Cooler and Tube in Tube Heat Exchanger in Intercooling of Gas Turbine

Solar Drying Techniques And Performance Analysis: A Review

The Research of Performance Comparison of Displacement and Mixing Ventilation System in Catering Kitchen *

Numerical Simulation of Thermal Comfort Degree in Radiant Floor Cooling Room. Architecture, Beijing , China

Equipment Layout Manual. For Cooling Towers, Evaporative Condensers & Closed Circuit Coolers

EqUIPMENT LAYOUT MANUAL

Study of air circulation inside the oven by computational fluid dynamics.

Performance Enhancement of Refrigeration Cycle by Employing a Heat Exchanger

Analysis of a Condenser in a Thermal Power Plant for Possible Augmentation in its Heat Transfer Performance

Emergency Ventilation System Design - Preliminary Report Shishir Gupta

FREQUENCY ENHANCEMENT OF DUAL-JUNCTION THERMOCOUPLE PROBES

Indoor Air of a Double-Storey Residential House in Malaysia

How to ensure Thermal Comfort in buildings with CFD

A Numerical study of the Fire-extinguishing Performance of Water Mist in an Opening Machinery Space

ENERGY SAVING IN A DOMESTIC SPLIT-TYPE AIR CONDITIONER WITH EVAPORATIVE COOLING SYSTEMS

CHAM Case Study Numerical Simulation of a Air-to-air Cross-flow Heat Exchanger

Performance Analysis of Electronic Expansion Valve in 1 TR Window Air Conditioner using Various Refrigerants

Numerical study of heat pipe application in heat recovery systems

Heat transfer and heating rate of food stuffs in commercial shop ovens

The Role of Computational Fluid Dynamic and Aeroacoustic Simulations in Reducing the Noise of a Forward-Curved Blade Radial Fan

Available online Journal of Scientific and Engineering Research, 2017, 4(12): Research Article

NUMERICAL SIMULATION OF THE NEW SOUTH WALES FIRE BRIGADE COMPARTMENT FIRE BEHAVIOUR TRAINING TEST CELL

RESPONSE OF ANCHOR IN TWO-PHASE MATERIAL UNDER UPLIFT

CHAPTER I INTRODUCTION. In the modern life, electronic equipments have made their way

Pressure drop analysis of evaporator using refrigerants R-22, R-404A and R-407C

CASE HISTORY: RETROFIT OF COAL MILL EXHAUST FAN STUDY OF FAN PERFORMANCE AND EROSION

Experimental Study And CFD Based Simulation of Closed Loop Pulsating Heat Pipe Using of Refrigerants (R-134a)

Drying Parawood with Superheated Steam

Sandeep V. Lutade 1, Krunal Mudafale 2, Ranjan Kishore Mallick 3 1, 2

power-saving period in summer, in which one of the indoor units was forced to change from a cooling mode to a fan mode, was introduced, and the effect

Refining and Petrochemical Heater trouble shooting

PERFORMANCE ANALYSIS AND CALCULATION OF DIFFERENT PARAMETERS OF CONDENSER USING ANSYS FLUENT SOFTWARE

Mallikarjun 1, Anandkumar S Malipatil 2

Investigating the Effects of Sprinkler Sprays on Fire-Induced Doorway Flows: A Two-Part Study. Jeremiah Crocker and Dr. Bin Xiao New Technology Team

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

Open Cooling Tower. Equipment Layout Guide

Low Profile Layout Guidelines

Enhancement of COP in Vapour Compression Refrigeration System

ANALYSIS ON EFFECT OF TEMPERATURE ON MOISTURE SEPARATION IN AIR COMPRESSOR

Performance investigation of Air-conditioning system using ejector as expansion device

Tunnel Fire Dynamics and Evacuation Simulations

AIR CURTAIN GUIDE WHAT IS AN AIR CURTAIN?

TRANSACTIONS ON ADVANCEMENTS IN SCIENCE AND TECHNOLOGY (TASTONLINE)

Numerical Studies On The Performance Of Methanol Based Air To Air Heat Pipe Heat Exchanger

Energy Conservation with PARAG Energy Efficient Axial Flow FRP Fans

Design Optimization of Evaporator Clip by FEA (ANSYS)

Shuzo Murakami, Shinsuke Kato, and Taeyeon Kim Institute of Industrial Science, University of Tokyo Tokyo, Japan

ijcrr Vol 04 issue 07 Category: Research Received on:06/02/12 Revised on:17/02/12 Accepted on:02/03/12

An Analysis of Compartment Fire and Induced Smoke Movement in Adjacent Corridor

Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark

Design, Development and Experimental Investigation of Volumetric Air Receiver

Technical college/ Baghdad 4th Year Week No. :- 11. The objectives of this lesson are to: Introduction:

Numerical investigation on the effect of channelled and unchannelled screens on smoke contamination in atriums upper balconies with open upstand

Subscripts 1-4 States of the given system Comp Compressor Cond Condenser E Evaporator vol Volumetric G Gas L Liquid

Improving Single-Sided Room Ventilation by Using a Ceiling Fan

International Forum on Energy, Environment Science and Materials (IFEESM 2015)

TITLE: Improvement in Heat Transfer Rate and Dynamics of Shrouded Fanned Radiator System

Study on Performance Evaluation of Forced Convection Solar Dryer for Turmeric (Curcuma Longa L.)

Basic Input Data Needed to Develop a High Performance Fan/Blower with Low Noise, Energy Saving and High Efficiency

Experimental Investigations of Different Types of Condensers on the Performance of Household Refrigerators

INTERNATIONAL JOURNAL OF APPLIED ENGINEERING RESEARCH, DINDIGUL Volume 1, No 4, 2011

ENERGY UTILIZATION IN CERAMIC TILES INDUSTRIES

Compression of Fins pipe and simple Heat pipe Using CFD

Application of a hybrid control of expansion valves to a 3-ton large room cooling system

POSSIBILITY TO USE SOLAR INDUCED VENTILATION STRATEGIES IN TROPICAL CONDITIONS BY COMPUTATIONAL FLUID DYNAMIC SIMULATION

Analysis and Evaluation of a Passive Evaporative Cool Tower in conjunction with a Solar Chimney

A Novel Heat Recovery System for High Temperature and High Humidity Gas Qing Hao1, a, Meng Si2, b

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

Control of temperature and humidity surrounding the stone chamber of Takamatsuzuka tumulus during its dismantlement

Heat Transfer in Evacuated Tubular Solar Collectors

American International Journal of Research in Science, Technology, Engineering & Mathematics

Sprinklers Modeling for Tunnel Road Fire Fighting

Optimized Finned Heat Sinks for Natural Convection Cooling of Outdoor Electronics

Numerical Analysis of Water Temperature Distribution in the Tank of. ASHPWH with a Cylindrical Condenser

Layout. Guidelines11. Chapter 11: Layout Introduction

Performance Study of Triple Concentric Pipe Heat Exchanger

Series V Layout Guidelines

Fire and smoke management in a uni-directional road tunnel for a congested traffic condition

Development of a Compact High Efficiency Cooling Device for the PA8000 Processor*

Challenges and Methods of Estimating a Conceptual HVAC Design

Jülich Solar Power Tower System Behavior During Downtime

EXPERIMENTAL STUDY OF CENTRIFUGAL HUMIDIFIER FITTED IN AN INDUSTRIAL SHED LOCATED IN TROPICAL CLIMATES

APPLICATION OF MINI HEAT PIPES FOR THERMAL MANAGEMENT OF OPTO-ELECTRONIC INSTRUMENTS

INVESTIGATION FINDINGS III IMPACT OF INADEQUATE VENTILATION AND DISCHARGE SYSTEMS

Case Study 1 Underground Car Park

Transcription:

APPLICATION OF CFD SIMULATIONS FOR LOCATING OUTDOOR UNITS ON HIGH RISE TOWER Basant Kumar Gupta 1, Anand Patil 2 1 Zeus Numerix Private Limited, Pune, India 2 Pankaj Dharkar & Associates, Mumbai, India ABSTRACT The efficiency of an air conditioning system depends on the ability of ODU (Outdoor Unit) to deliver the required air flow rate that is needed for cooling the refrigerant. The case described in this paper involves solving an actual case wherein the occupants of a high rise building were facing an issue with ineffective cooling from their air conditioning system. The issue was traced back to ODUs (Outdoor Units) which were not able to provide sufficient air flow rate since it was located facing high winds. Different ODUs (Outdoor Units) were simulated for their efficiency under known conditions to arrive at the most suitable unit to provide sufficient air flow. CFD simulations were used to locate an appropriate location for the placement of ODUs. Focus during analysis of results was on the pressure distribution around the candidate ODU location. The suction and exhaust side of the ODU was identified and pressure difference between the exhaust and suction surface was quantified. By comparing the additional pressure head against design pressure head, magnitude of deterioration of fan performance was understood and these results helped in locating the ideal location for placing the ODUs (Outdoor Units). INTRODUCTION This study is based on an actual scenario wherein the occupants of high-rise building complained of ineffective cooling from the air conditioning system. The primary reason for ineffective cooling was traced back to the outdoor units (ODU) which was placed outside facing high winds. It was noticed that when wind direction is South-West as during peak summers, ODU fans are not able to deliver the required air flow rate for cooling the refrigerant. The current location of the ODU fans is such that the wind induced pressure difference between exhaust and fresh air side of the ODU is much more or comparable to the fan design head thereby decreasing the fan efficiency. Incompressible flow solver with k-epsilon turbulence model was used for the simulation. Focus during the analysis of results was the pressure distribution around the candidate ODU location. The suction and exhaust side of the ODU will be identified and pressure difference between exhaust and suction surface will be quantified. By comparing the additional pressure head against design pressure head, it was possible to understand the magnitude of deterioration of fan performance. BRIEF ABOUT THE PROBLEM STATEMENT The builder proposed to use a different layout for the ODU as compared to the layout that was used in their previous project. In their previous project, each flat had four 3 HP front discharge ODU which had suction from behind and fan located at the front for exhausting hot air outside. The ODUs were placed on service slabs, which were covered using louvers. The louvers were designed in such a way that the lower half of the louver allowed fresh air in and the upper half was designed for discharge of exhaust air. During high winds, it was found that the fan would just stop rotating due to low delivery head of the front discharge ODU unit. Hence, the builder decided to switch to top discharge ODU with one 14 HP and one 6 HP with both units having a top discharge. Since the new up-rated ODUs are located behind louvers, a cowl piece was attached to direct the exhaust air out of the slab area. Therefore the objectives of CFD study are Assess the advantages of using high static top discharge units against previously used low static front discharge units under high wind conditions Arrive at the most optimum service slab location for ODU installation with recommendation for the orientation of units for suction and discharge based on the local wind conditions The methodology employed in the study involves modelling a single floor of the high-rise building considering only the external features of the building. Though the prevalent wind direction is South-West during summer, the study was carried out taking into consideration at least five different wind directions i.e. S, SSW, SW, WSW and W to ensure that the choice of ODU location is favourable for reasonable variations in wind direction. - 2448 -

Figure 1 Typical floor plan of the high-rise building with area of interest for CFD simulation shown in dark circles. Focus of CFD analysis is to quantify the pressure at the suction side and the discharge side and compare it with pressure jump claimed by ODU manufacturer. ODU PERFORMANCE IN HIGH WINDS Performance of top discharge ODU under wind Figure 4 Pressure and Velocity profile of top discharge ODU Quantitatively, the average suction pressure is 198.4 Pa and average discharge pressure is 214.4 Pa. Hence, we note that ODU fans needs to overcome 16 Pa pressure difference which it claims to be capable of. Performance of front discharge ODU under wind Figure 2 Simulation domain of top discharge ODU with pressure plot The service area houses a top discharge ODU with 6 HP capacity with suction through the front and the side panels. The top discharge with cowl is also modelled. Figure 5 Simulation domain of front discharge ODU with pressure plot The same service area now houses the front discharge ODU with 3 HP capacity with suction side located behind the ODU and exhaust side in the front. Figure 3 Flow pattern from top discharge ODU From Fig 3 the flow pattern for ODU exhaust and suction air is shown. It was observed that due to the location of the cowl, exhaust air gets completely diluted with ambient air and fresh air is available for suction. Figure 6 Flow pattern from front discharge ODU From the flow pattern of the ODU, it was noticed that some of the exhaust air gets sucked up by ODU due to very low discharge speed and low static discharge. - 2449 -

It is estimated that 35% of the suction air is from the ODU discharge, which in turn causes heating up of service slab area. Effect of grill on top discharge ODU Figure 9 Pressure distribution in the presence of grill in top discharge ODU Figure 7 Pressure and Velocity profile of front discharge ODU Quantitatively the average suction pressure is 207.1 Pa and average discharge pressure is 208.6 Pa hence it was noted that the ODU fans needs to overcome 1.5 Pa which the fan is able to but not enough to push the heated air out of the service slab. Modelling and simulation of the grill A representative stack of 10 grills is modelled and meshed with the objective to estimate the pressure drop across the grill for a typical flow rate of 5 m/s. The pressure drop was to be non-dimensionalized for discharge coefficient C D, so that pressure drop at any velocity can be estimated. Value of C D is then used in simulation of typical service slab to observe the effect of grill on ODU performance. From the pressure distribution plot generated, it is observed that a high pressure region exist ahead of the grill and the pressure inside the service slab also increases. It was also found that pressure on the suction panels of ODU was 214.1 Pa whereas pressure on discharge surface of ODU was 270 Pa. Thus, under high winds, ODU fans need to generate 55.9 Pa pressure rise which the fan is capable of. Therefore, we can conclude that the presence of grill reduces the margin on static pressure that was earlier available to us. Additionally, it was also found that hot exhaust air is vented out to ambient air and it does not get sucked in by the ODU itself. Effect of grill on the front discharge ODU Figure 10 Pressure distribution in the presence of grill in front discharge ODU Figure 8 Velocity and Pressure plot for the grill From the Fig above, the pressure drop of 105 Pa for 5 m/s is computed with C D calculated as 7.33. The grill region is modelled as porous zone and corresponding porosity value is assigned for generating grill effect. From the pressure distribution plot, it is seen that the grill creates a higher pressure line upstream with pressure inside the service slab increased by about 7 Pa. Pressure on the suction surface of ODU is 218.8 Pa whereas pressure on the discharge surface of ODU is 221.8 Pa. Like top discharge ODU, in the presence of grill front discharge ODU needs to overcome more pressure drop than without any grills. As noted earlier, the issue of recirculation of hot ODU exhaust existed and this issue gets further aggravated due to the presence of grill because it acts as a resistance to exhaust flow from ODU and does not allow it to mix with ambient air. Therefore, almost 65% of air sucked in is from the discharge of the ODU itself. - 2450 -

SELECTING OPTIMUM ODU LOCATION From the flow pattern generated around the building, it is evident that a stagnation region is formed just ahead of the building and a wake region is formed which extends far behind it. Additionally, it was observed that at the corners of the building, the wind speeds increases up to 100 kmph. Figure 11 Mesh generated around the typical floor of the building Flow around typical floor is analyzed using 2D CFD simulation. Triangulation was made and extruded for one layer. The mesh generated had around 38,000 cells with good quality triangles with gradual increase in size. The simulations were carried out for a floor located at a height of 150 m from the ground. A total of 5 simulations were carried out for different wind direction which was prevalent during summer. Based on the Indian Meteorological data, average wind speed at 10 m height during summer was found to be 5 m/s and this was used to extrapolate the wind speed at a height of 150 m/s using log law for atmospheric boundary layer and the same was found to be 18 m/s. Figure 13 Pressure distribution around the building at a height of 150 meters The pressure distribution around the building is shown for different wind directions. Pressure distribution is the primary factor that would affect the performance of the ODU fan. It is seen that upstream pressure is about 200 Pa with pockets of low pressure zones. The performance of ODU fans depend not only on the dynamic pressure existing on the exit plane but also on the suction side pressure. Analysis of candidate location Figure 12 Flow pattern around the building at a height of 150 meters Figure 14 ODU location and pressure distribution for various locations on the left wing of the building - 2451 -

service slab leading to deterioration of ODU performance. Therefore, it was proposed that high static top discharge ODU is better suited for high wind conditions. This recommendation has been proven from CFD simulations where the hot exhaust air is thrown out into the ambient air and it does not re circulate back. Figure 15 ODU location and pressure distribution for various locations on the right wing of the building From Fig 14 & 15, the pressure distribution experienced by 6 HP ODU is simulated under various wind directions and the results are tabulated above. From the data computed, it was concluded that it is beneficial to have the suction from side A and the exhaust directed towards side B. Analysis of stagnation zones From the simulation it was found that 14 HP ODU always remain under the wake region since the building layout is such that it forms a small volume cavity in which hot ODU exhaust air is being discharged. If the ODU exhaust air does not have enough momentum/static head then the entire cavity may go hot further deteriorating the ODU performance. Hence, further simulation was performed to check whether the ODU exhaust air overcomes the cavity and mixes with the ambient air. Figure 16 Modified direction for ODU discharge From the simulation it was found that the ODU discharge hits the corner of the building and splits into two streams which is not favourable. It was suggested to change the direction of the ODU in order the vent the hot exhaust air in the easterly direction in order to minimise the stacking effect. CONCLUSION From the various simulations carried out for this study, it was concluded that the 3 HP front discharge ODU suffer from recirculation of exhaust air inside the service area because of their low static head. This condition further increases the temperature inside the Further, it was seen that the presence of louvers deteriorate the performance of both front discharge ODU (by recirculation of hot discharge air) and top discharge ODU (by increasing the adverse head by 40 Pa) as it increases the static pressure needed to overcome by ODU (Outdoor Units). The study has been able to identify the physics that was behind the ODU non-performance in building 1 and the study recommends the use of 6 HP and 14 HP units of 78.4 Pa for building 2. Additionally, all the ODU locations for ODU have been investigated based on prevailing wind direction in the summer and the suitable orientation of the ODU are also recommended. Also, re-orientation in the exhaust direction of the ODU was suggested in order to minimize the effect of thermal stacking. REFERENCES 1. Q. Chen, "Using computational tools to factor wind into architectural environment design," Energy and Buildings, vol. 36, pp. 1197-1209, 2004. 2. Ma Jian, Shu Xin, Yang Youdong. Numerical Simulation of Wind Environment Around Buildings. Computer simulation, 2008,25(6):296-298,307 3. Jiang Yujun, Sang Jianguo, Zhang Boyin. An Evaluation on Wind Environment Around Skyscrapers. Acta Scientiarum Naturalium Universitatis Pekinensis, 2006, 42(1):68-73 (Pubitemid 43322637) 4. G. Ziskind, V. Dubovsky, R. Letan, "Ventilation by natural convection of a one-story building," Energy and Buildings, vol. 34, pp. 91-101, 2002 5. Du Xiaohui, Gao Hui. Analysis of the Wind Environment of High Rise Building Residential Quarter in Tianjin Area. Architectural Journal, 2008 (4):42-45. - 2452 -