CENTRIFUGAL LIQUID CHILLERS YMC 2 MODEL A WITH OPTIVIEW CONTROL CENTER. R-134a. INSTALLATION Supersedes: N1 (611) Form N1 (512) LD14000

Similar documents
CENTRIFUGAL LIQUID CHILLERS MODEL YD (STYLE A) R-134A (COOLING ONLY) WITH OPTIVIEW CONTROL CENTER AND ELECTRO-MECHANICAL STARTER R-134A

FIELD RE-ASSEMBLY FOR FORM 3 AND FORM 7 SHIPMENT MODEL YD CHILLERS - MOD A AND B WITH GRAPHIC CONTROL CENTER AND ELECTRO-MECHANICAL STARTER

MODEL YK M3 M3 G4 THRU YK S6 S4 J2 (STYLE C) R-22 (COOLING ONLY) MODEL YK LB LB G4 THRU YK SE SC J4 (STYLE C) R-134a (COOLING ONLY)

CENTRIFUGAL LIQUID CHILLERS YMC 2 MODEL A WITH OPTIVIEW CONTROL CENTER. R-134a in

MODELS STEAM YIA-ST-1A1 THRU YIA-ST-14F3 HOT WATER YIA-HW-1A1 THRU YIA-HW-14F3

MODEL YST UNITS MANUFACTURED AFTER DECEMBER 2006

Water-Cooled Dual Compressor Screw Chiller

INSTALLATION, OPERATION, MAINTENANCE Supersedes: ICOM2 (1216) Form ICOM2 (318)

WATER-COOLED SCREW LIQUID CHILLERS. MODEL YVWA Dual Compressor 50 Hz and 60 Hz Tons kw. R-134a. Issue Date: April 30, 2015

MODEL YK (STYLE G) R-134a or R-531A WITH OPTIVIEW CONTROL CENTER FOR ELECTRO-MECHANICAL STARTER, SOLID STATE STARTER AND VARIABLE SPEED DRIVE

Installation Manual IM

PARALLEL RACK SYSTEM INSTALLATION & OPERATIONS MANUAL With Master Rack Compressor Sequencer

Installation Instructions

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

SECTION STEAM CONDENSATE PUMPS

Water-Cooled Scroll Compressor Chillers

MODEL YVAA EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST CUSTOMER: LOCATION: ADDRESS: CUSTOMER ORDER NO: PHONE: JCI CONTRACT NO: JOB NAME:

Guide Specifications

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS

Installation Instructions

BuildingName The Description of the Project P DOCUMENTS

Installation Operation Maintenance

TABLE OF CONTENTS. NOTE: Read the entire instruction manual before starting the installation. TROUBLESHOOTING... 13

Model REAC / SEAC Self Contained Cooling / Electric Heating Units

Installation Operation Maintenance

EQUIPMENT PRE-STARTUP AND STARTUP CHECKLIST TEL NO: ORDER NO: CONTRACT NO:

Water-Cooled Scroll Compressor Chillers

IOM Installation, Operation, and Maintenance Manual. Magnitude Magnetic Bearing Centrifugal Chillers

Installation Instructions

TITAN FLOW CONTROL, INC.

IOM Installation, Operation, and Maintenance Manual. Magnitude Magnetic Bearing Centrifugal Chillers

.2 Section Waste Management and Disposal.

Installation Instructions Part No , Part No Part No

4 route 147, C.P.33 Coaticook, Qc J1A 2S8

SECTION CENTRIFUGAL WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower

Single Package Vertical R-410A A/C & H.P. UNIT MODELS VPC-B, VPP-B, & VPH-B INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 (50 Hz) PROVEN PERFORMANCE GENERAL FEATURING

Installation, Start-Up and Service Instructions

Installation, Operation, and Maintenance

Installation, Operation, and Maintenance

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions.

Single Package Vertical R-22 A/C & HP UNIT MODELS VPC, VPP, & VPH INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

Installation Instructions

TECHNICAL GUIDE. Description SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS YD360, 480 & THRU 50 NOMINAL TONS YTG-B-0811

User s Information and Installation Instructions

This label warns for risk of electrical shock when failing to observe.

Installation, Start-Up and Service Instructions

Installation, Operation and Maintenance LOK-FLANGE Multitube Heat Exchangers

ENGINEERING GUIDE YORK YZ Centrifugal Chiller Form: EG1-EN(1217)

YCIV Hz & Hz

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

568X, 587X, 588X Series

APPLICATION DATA SHEET

SECTION CHILLERS

DLCLRA. INSTALLATION INSTRUCTIONS Outdoor Unit Single Zone Ductless System Sizes 36 to 58 TABLE OF CONTENTS

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions.

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards

Installation Instructions

Patterson/AMT Inline Circulator Pump Refer to pump manual for General Operating and Safety Instructions.

CONTENTS. B. System Design and Performance Requirements

Installation, Operation, and Maintenance

MACH N-407 Heat Pump Air-Cooled Chiller

Installation Instructions

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

INSTALLER: PLEASE LEAVE THIS MANUAL FOR THE OWNER S USE. Condensate Return Systems General Installation, Operation, & Service Instructions !

Chapter-8 Capacity Control of Refrigeration Systems

CELDEK Evaporative Cooler Module Installation, Operation, and Maintenance Manual. CELDEK Evaporative Cooler

COLMAC COIL. Installation, Operation, and Maintenance ENG Rev A. Air Cooled Fluid Coolers. Contents. When you want Quality, specify COLMAC!

PS SERIES PARALLEL RACK SYSTEM GLYCOL CHILLER START UP GUIDE. Master Rack Compressor Sequencer 7/21/2017

KR Series Air Defrost Unit Coolers Operating and Installation Manual

PhiloWilke Partnership Addendum No. 2 A/E Project No April 2016

IM Installation and Maintenance Manual. Templifier Heat Recovery Water Heaters

INFINITY FLUIDS CORPORATION

GeneSys Air-Cooled Screw Compressor Chiller

INTRODUCTION. NOTE: Read the entire instruction manual before starting the installation. FIRE, EXPLOSION, ELECTRICAL SHOCK HAZARD

IOM Installation, Operation, and Maintenance Manual. Magnitude Magnetic Bearing Centrifugal Chillers

SECTION ROTARY-SCREW WATER CHILLERS

INSTALLATION INSTRUCTIONS

Installation Instructions Dual Fuel Ranges

Air-Cooled Fluid Cooling Units (P/N E R2)

Installation Instructions

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW

Installation Operation Maintenance

Contour TM Screw Compressors

ISOLATED DIRECT DRIVE PLENUM FAN (IDDP)

RCF Closed Circuit Cooling Towers RCC Evaporative Condensers

Installation Instructions

Installation and operating instructions. E.2 Series high efficiency circulator

Product Data. Features/Benefits. 19XB Positive Pressure Storage System

TECHNICAL GUIDE SPLIT-SYSTEM AIR-COOLED EVAPORATOR BLOWER 25, 30, 40 & 50 TON LA300, LB360, 480 & 600 PROVEN PERFORMANCE GENERAL FEATURING

Direct Drive Fluid Coolers

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

INSTRUCTION AND REPAIR MANUAL

LONGONI ENGINEERING SRL

CHILLER. Model CH3000. Operator s & Installation Manual

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS. HA300, HB360, HB480 & HB thru 50 NOMINAL TONS (50 Hz)

Installation, Operation, and Maintenance Information

40LM Hz INSTALLATION, START-UP AND SERVICE INSTRUCTIONS CHILLED WATER FAN COIL UNIT

Transcription:

CENTRIFUGAL LIQUID CHILLERS INSTALLATION Supersedes: 160.78-N1 (611) Form 160.78-N1 (512) YMC 2 MODEL A WITH OPTIVIEW CONTROL CENTER LD14000 R-134a Issue Date: May 30, 2012

IMPORTANT! READ BEFORE PROCEEDING! GENERAL SAFETY GUIDELINES FORM 160.78-N1 This equipment is a relatively complicated apparatus. During installation, operation maintenance or service, individuals may be exposed to certain components or conditions including, but not limited to: refrigerants, materials under pressure, rotating components, and both high and low voltage. Each of these items has the potential, if misused or handled improperly, to cause bodily injury or death. It is the obligation and responsibility of operating/service personnel to identify and recognize these inherent hazards, protect themselves, and proceed safely in completing their tasks. Failure to comply with any of these requirements could result in serious damage to the equipment and the property in which it is situated, as well as severe personal injury or death to themselves and people at the site. This document is intended for use by owner-authorized operating/service personnel. It is expected that these individuals possess independent training that will enable them to perform their assigned tasks properly and safely. It is essential that, prior to performing any task on this equipment, this individual shall have read and understood this document and any referenced materials. This individual shall also be familiar with and comply with all applicable governmental standards and regulations pertaining to the task in question. SAFETY SYMBOLS The following symbols are used in this document to alert the reader to specific situations: Indicates a possible hazardous situation which will result in death or serious injury if proper care is not taken. Identifies a hazard which could lead to damage to the machine, damage to other equipment and/or environmental pollution if proper care is not taken or instructions and are not followed. Indicates a potentially hazardous situation which will result in possible injuries or damage to equipment if proper care is not taken. Highlights additional information useful to the technician in completing the work being performed properly. External wiring, unless specified as an optional connection in the manufacturer s product line, is not to be connected inside the OptiView TM cabinet. Devices such as relays, switches, transducers and controls and any external wiring must not be installed inside the micro panel. All wiring must be in accordance with Johnson Controls published specifications and must be performed only by a qualified electrician. Johnson Controls will NOT be responsible for damage/problems resulting from improper connections to the controls or application of improper control signals. Failure to follow this warning will void the manufacturer s warranty and cause serious damage to property or personal injury. 2 JOHNSON CONTROLS

CHANGEABILITY OF THIS DOCUMENT In complying with Johnson Controls policy for continuous product improvement, the information contained in this document is subject to change without notice. Johnson Controls makes no commitment to update or provide current information automatically to the manual owner. Updated manuals, if applicable, can be obtained by contacting the nearest Johnson Controls Service office. Operating/service personnel maintain responsibility for the applicability of these documents to the equipment. If there is any question regarding the applicability of these documents, the technician should verify whether the equipment has been modified and if current literature is available from the owner of the equipment prior to performing any work on the chiller. CHANGE BARS Revisions made to this document are indicated with a line along the left or right hand column in the area the revision was made. These revisions are to technical information and any other changes in spelling, grammar or formatting are not included. ASSOCIATED LITERATURE MANUAL DESCRIPTION YMC 2 Operations & Maintenance YMC 2 Unit Re-assembly YMC 2 Centrifugal Chiller Long Term Storage YMC 2 Field Connections YMC 2 Unit Wiring and Field Control Modifications YMC 2 Unit Renewal Parts YMC 2 OptiView TM Operation OptiSpeed TM VSD Model HYP744 Renewal Parts FORM NUMBER 160.78-O1 160.78-N2 50.20-NM5 160.78-PW1 160.78-PW2 160.78-RP1 160.78-O2 160.78-RP3 JOHNSON CONTROLS 3

SYSTEM NOMENCLATURE Y M C 2 - S 0756 A A YORK Magnetic Bearing Centrifugal Chiller S = Single Stage T = Two Stage Mod Level Refrigerant R-134a Capacity in KW COMPRESSOR NOMENCLATURE M1 B - 197 F A A Motor Motor Design Level Impeller Tip Diameter (mm) Rotation F = Forward R = Reverse Gas Path Revision Level Impeller Design Revision Level VESSEL NOMENCLATURE E A 25 14 271 B R 1 1 F C R Vessel E = Evaporator C = Condenser Heat Exchanger Mod Level Nominal Inside Diameter (Inches) Nominal Length (Feet) Marketing Tube Number Tube Code B = 3/4" Code 1 C = 3/4" Code 2 D = 3/4" Code 3 E = 3/4" Code 4 2 = 1" Code 1 3 = 1" Code 2 4 = 1" Code 3 5 = 1" Code 4 Vessel Refrigerant Pressure Code R = Code 180 S = Code 235 T = Code 300 U = Code 350 V = Code 400 Inlet from Front View R = Right L = Left Waterbox Type C = Compact M = Marine Water Connection Type F = Flanges G = Grooved Standard A = Victaulic AGS Number of Passes Water Side Pressure Code 1 = 150 psi 3 = 300 psi VARIABLE SPEED DRIVE NOMENCLATURE HYP 744 X H 15 D - 40 Hyper Amps X = Factory Mount R = Retrofit Model H = YMC 2 Chiller 40 = 380V 60Hz 50 = 400V 50Hz 46 = 460V 60Hz 68 = 415V 50Hz D = Disconnect Switch B = Circuit Breaker Liquid DWP 15 = 150 psi 30 = 300 psi 4 JOHNSON CONTROLS

TABLE OF CONTENTS SECTION 1 - SHIPPING...7 General...7 Component Combinations...7 Field Assembled Units Only...8 YMC 2 Shipment Forms...8 Form 1...8 Form 2...9 Form 3...9 Form 7...10 Form 9...10 Form 10... 11 Form 11... 11 Inspection Damage Shortage...12 Chiller Data Plate...12 SECTION 2 - INSTALLATION...13 Overview...13 Rig Chiller Unit...13 Determine Location...14 Foundation Requirements...14 Clearance Requirements...14 Rig Unit To Final Location...14 Install Isolators...14 Neoprene Isolator Pads...14 Install Optional Spring Isolators...17 Make Connections...19 Piping Connections...19 Refrigerant Relief Piping...21 Unit Piping...21 Control Wiring...21 Power Wiring...21 Supplied Variable Speed Drive...21 Apply Insulation...24 Installation Check Request For Start-Up Service...24 SECTION 3 - DIMENSIONS, NOZZLE ARRANGEMENTS AND WEIGHTS...25 Compressor Unit Dimensions...25 Evaporator Nozzle Arrangements (150 Psi Compact Water Boxes)...26 Condenser Nozzle Arrangements (150 Psi Compact Water Boxes)...28 Evaporator Nozzle Arrangements (150 PSI Marine Water Boxes)...30 Condenser Nozzle Arrangements (150 Psi Marine Water Boxes)...32 Weights...34 150 PSI Compact And Marine Water Boxes Lbs (Kgs)...34 Temperature...35 JOHNSON CONTROLS 5

LIST OF FIGURES FIGURE 1 - YMC 2 Chiller Components...7 FIGURE 2 - Rigging...13 FIGURE 3 - Neoprene Isolators...15 FIGURE 4 - Neoprene Isolators...16 FIGURE 5 - Spring Isolators...17 FIGURE 6 - Spring Isolators...18 FIGURE 7 - Typical Refrigerant Vent Piping...19 FIGURE 8 - Schematic Of A Typical Piping Arrangement...20 FIGURE 9 - FAA Unit Insulation...22 FIGURE 10 - FAB Unit Insulation...23 FIGURE 11 - Dimensions 197 & 205 Compressor Units Ft-In (Mm)...25 FIGURE 12 - Evaporators - Compact Water Boxes (1-Pass Nozzle Arrangements)...26 FIGURE 13 - Evaporators - Compact Water Boxes (2-Pass Nozzle Arrangements)...26 FIGURE 14 - Evaporators - Compact Water Boxes (3-Pass Nozzle Arrangements)...26 FIGURE 15 - Evaporators - 150 Psi Compact Water Boxes...27 FIGURE 16 - Condensers - Compact Water Boxes (1-Pass Nozzle Arrangements)...28 FIGURE 17 - Condensers - Compact Water Boxes (3-Pass Nozzle Arrangements)...28 FIGURE 18 - Condensers - Compact Water Boxes (2-Pass Nozzle Arrangements)...28 FIGURE 19 - Condensers - 150 Psi Compact Water Boxes...29 FIGURE 20 - Evaporators - Marine Water Boxes (1-Pass Nozzle Arrangements)...30 FIGURE 21 - Evaporators - Marine Water Boxes (2-Pass Nozzle Arrangements)...30 FIGURE 22 - Evaporators - Marine Water Boxes (3-Pass Nozzle Arrangements)...30 FIGURE 23 - Evaporators - 150 Psi Marine Water Boxes...31 FIGURE 24 - Condensers - Marine Water Boxes (1-Pass Nozzle Arrangements)...32 FIGURE 25 - Condensers - Marine Water Boxes (2-Pass Nozzle Arrangements)...32 FIGURE 26 - Condensers - Marine Water Boxes (3-Pass Nozzle Arrangements)...32 FIGURE 27 - Condensers - 150 Psi Marine Water Boxes...33 LIST OF TABLES TABLE 1 - Allowable Motor / Compressor / Evaporator / Condenser Combinations...7 TABLE 2 - Approximate Unit Weight* (Max Tube Count Using 150 Psi Compact Waterboxes)...34 TABLE 3 - Evaporator Marine Water Box Weights (To Be Added To Standard Unit Weights Shown On Table 2)...34 TABLE 4 - Condenser Marine Water Box Weights (To Be Added To Standard Unit Weights Shown On Table 2)...34 TABLE 5 - SI Metric Conversion...35 6 JOHNSON CONTROLS

SECTION 1 - SHIPPING 1 GENERAL This manual provides instructions for rigging and installing a YMC 2 Liquid Chilling Unit. Chillers can be shipped as a single factory assembled, piped, wired package, requiring a minimum of field labor to make chilled water connections, condenser water connections, refrigerant atmospheric relief connections, and electrical power connections. (Refrigerant charges shipped separately unless optional condenser isolation valves are ordered.) They can also be shipped dismantled when required by rigging conditions, but it is generally more economical to enlarge access openings to accommodate the factory assembled unit. Chillers that are shipped dismantled MUST be field-assembled under the supervision of a Johnson Controls representative, but otherwise installation will be as described in this manual. COMPONENT COMBINATIONS Figure 1 identifies the major components of the YMC 2 Chiller. The chiller is customized based on the selected combination of Motor, Compressor, Evaporator, and Condenser. Table 1 lists all of the allowable combinations. Table 1 - ALLOWABLE MOTOR / COMPRESSOR / EVAPORATOR / CONDENSER COMBINATIONS Motor Codes Compressor Codes YMC2 Evaporator Codes Condenser Codes M1 197DFAA EA2510 CA2110 M1 197DFAA EA2510 CA2510 M1 197DFAA EA2514 CA2514 M1 205DFAA EA2510 CA2110 M1 205DFAA EA2510 CA2510 M1 205DFAA EA2514 CA2514 LD14022 Figure 1 - YMC 2 CHILLER COMPONENTS JOHNSON CONTROLS 7

Section 1 - Shipping FIELD ASSEMBLED UNITS ONLY If the chiller was not shipped complete (as shown in Form 1 or 2 below), use the YMC 2 Unit Re-assembly Manual (Form 160.78-N2) in conjunction with this installation manual. This manual is furnished with all units that are to be field assembled. The services of a Johnson Controls representative will be furnished to check the installation, supervise the initial start-up and operation of all chillers installed within the Continental United States. The Johnson Controls Warranty may be voided if the following restrictions are not adhered to. 1. No valves or connections should be opened under any circumstances because such action will result in loss of the factory nitrogen charge. 2. Do not dismantle or open the chiller for any reason except under the supervision of a Johnson Controls representative. 3. When units are shipped dismantled, notify the nearest Johnson Controls office in ample time for a Johnson Controls representative to supervise rigging the unit to its operating position and the assembly of components. 4. Do not make final power supply connections to the compressor motor drive or control center. 5. Do not charge the unit with refrigerant. 6. Do not attempt to start the system. 7. Do not run hot water (110 F / 43 C max) or steam through the evaporator or condenser at any time. YMC 2 SHIPMENT FORMS The chiller may be ordered and shipped in any of the following forms: Form 1 (shipped complete) Form 2 (shipped complete) Form 3 (shipped in three assemblies) Form 7 (shipped in four assemblies) Form 9 (shipped in two assemblies) Form 10 (shipped in two assemblies) Form 11 (shipped in two assemblies) Form 1 FORM 160.78-N1 Units that are shipped dismantled MUST be re-assembled by, or under the supervision of a Johnson Controls representative. Refer to YMC 2 Unit Re-assembly Manual (Form 160.78-N2) for detailed re-assembly instructions. When more than one chiller is involved, the major parts of each unit will be marked to prevent mixing of assemblies. Piping and wiring drawings to be furnished by Johnson Controls. The chiller is shipped complete with miscellaneous loose items shipped together. Chiller Unit Refrigerant charges are included. The unit is completely assembled at the factory. The driveline (compressor/motor assembly) is mounted and all the necessary interconnecting piping is assembled. The complete unit is factory leak-tested, evacuated, and shipped charged with R-134A refrigerant. The OptiView Control Center is mounted on the unit. The Variable Speed Drive (VSD) is mounted, wired, and shipped with glycol. Miscellaneous Items The following items are shipped together: Four (4) vibration isolation pads (or optional spring isolators and brackets). 8 JOHNSON CONTROLS

Section 1 - Shipping VSD Inhibitor Other shipped loose items, including piping, water temperature controls, wiring, etc. Form 2 The chiller is shipped complete; miscellaneous loose items are shipped together. Chiller Unit Refrigerant charges are shipped separately. Arrangements with the local service office must be made to ensure refrigerant is onsite when the unit is ready to be charged. The unit is completely assembled at the factory. The driveline (compressor/motor assembly) is mounted and all the necessary interconnecting piping is assembled. The complete unit is factory leak-tested, evacuated, and shipped charged with a 2 to 3 PSIG (115.122 kpa) holding charge of dry nitrogen. The OptiView Control Center is mounted on the unit. The Variable Speed Drive (VSD) is mounted, wired, and shipped with Glycol. Miscellaneous Items The following items are shipped together: Four (4) vibration isolation pads (or optional spring isolators and brackets). Other shipped loose items, including piping, water temperature controls, wiring, etc. Inhibitor (VSD) Form 3 The chiller is shipped in three assemblies: 1. The driveline (compressor/motor assembly) 2. The evaporator/condenser shell assembly 3. The Variable Speed Drive (VSD) 4. Miscellaneous shipped loose items Refrigerant charges are shipped separately. Arrangements with the local service office must be made to ensure refrigerant is onsite when the unit is ready to be charged. Prior to shipping, the unit is completely assembled at the factory. Interconnecting piping is assembled and the complete unit is wired and leak-tested. The unit is then dismantled and shipped as follows: Driveline The driveline (compressor/motor assembly) is removed from the shells and skidded. All integral wiring is left on the compressor. All openings on the compressor are closed and shipped charged with a 2 to 3 PSIG (115.122 kpa) holding charge of dry nitrogen. Shells The evaporator and condenser are assembled prepared for shipping but not skidded. All conduit is left on the shells. All openings the shells are closed and charged with a 2 to 3 PSIG (115.122 kpa) holding charge of dry nitrogen. Variable Speed Drive (Vsd) The VSD is skidded and shipped separately from the assembled chiller. The VSD is filled with glycol for shipping. The VSD Inhibitor is shipped with the other loose items. Miscellaneous Material The following assemblies and items are shipped together: OptiView Control Center Magnetic Bearing Controller (MBC) Four (4) vibration isolation pads (or optional spring isolators and brackets). 1 JOHNSON CONTROLS 9

Section 1 - Shipping Other shipped loose items, including piping, water temperature controls, wiring, etc. Inhibitor (VSD) Form 7 The chiller is shipped in four assemblies: 1. The driveline (compressor/motor assembly) 2. The evaporator 3. The condenser 4. The Variable Speed Drive (VSD) 5. Miscellaneous shipped loose items Refrigerant charges are shipped separately. Arrangements with the local service office must be made to ensure refrigerant is on-site when unit is ready to be charged. Prior to shipping, the unit is completely assembled at the factory. Interconnecting piping is assembled and the complete unit is wired and leak-tested. The unit is then dismantled and shipped as follows: Driveline The driveline (compressor/motor assembly) is removed from shells and skidded. All integral wiring is left on the compressor. All wiring harnesses on shells are removed. All openings on the compressor are closed and shipped charged with a 2 to 3 PSIG (115.122 kpa) holding charge of dry nitrogen. Shells The evaporator and condenser are separated at the tube sheets and prepared for shipping separately but not skidded. All conduit is left on the shells. Refrigerant lines between shells are flanged and capped, requiring no welding. FORM 160.78-N1 All openings the shells are closed and charged with a 2 to 3 PSIG (115.122 kpa) holding charge of dry nitrogen. Variable Speed Drive (Vsd) The VSD is skidded and shipped separately from the assembled chiller. The VSD is filled with glycol for shipping. The VSD Inhibitor ia shipped with the other loose items. Miscellaneous Items The following assemblies and items are shipped together: OptiView Control Center Magnetic Bearing Controller (MBC) Four (4) vibration isolation pads (or optional spring isolators and brackets). VSD Inhibitor Other shipped loose items, including piping, water temperature controls, wiring, isolators, etc. Form 9 The chiller is shipped in two assemblies: 1. The chiller unit (less the VSD) 2. The VSD 3. Miscellaneous shipped loose items. Chiller Unit Refrigerant charges are shipped separately. Arrangements with the local service office must be made to ensure refrigerant is on-site when unit is ready to be charged. The unit is first completely assembled at the factory: The driveline (compressor/motor assembly) is mounted, with all necessary interconnecting piping assembled. 10 JOHNSON CONTROLS

Section 1 - Shipping Interconnecting piping is assembled and the complete unit is factory leak-tested then evacuated and shipped charged with a 2 to 3 PSIG (115.122 kpa) holding charge of dry nitrogen. The Motor Terminal Box adapter remains attached to the chiller unit. Variable Speed Drive (VSD) The VSD is skidded and shipped separately from the assembled chiller. The VSD is filled with glycol for shipping. The VSD Inhibitor is shipped with the other loose items. Miscellaneous Material The following assemblies and items are shipped together: Four (4) vibration isolation pads (or optional spring isolators and brackets). Other shipped loose items, including piping, water temperature controls, wiring, etc. VSD Inhibitor Form 10 The chiller is shipped in two assemblies: 1. The assembled chiller unit (less the VSD) 2. The VSD 3. Miscellaneous shipped loose items. Refrigerant charges are included. The complete unit is factory leak-tested, evacuated, and shipped charged with R-134A refrigerant. The Motor Terminal Box adapter remains attached to the chiller unit. Variable Speed Drive (VSD) The VSD is skidded and shipped separately from the assembled chiller. The VSD is filled with glycol for shipping. The VSD Inhibitor is shipped with the other loose items. Miscellaneous Material The following assemblies and items are shipped together: Four (4) vibration isolation pads (or optional spring isolators and brackets). Other shipped loose items, including piping, water temperature controls, wiring, etc. VSD Inhibitor Form 11 The chiller is split down the middle and shipped in two assemblies: 1. The condenser-side assembly 2. The evaporator-side assembly 3. Miscellaneous shipped loose items Refrigerant charges are shipped separately. Arrangements with the local service office must be made to ensure refrigerant is on-site when unit is ready to be charged. 1 Chiller Unit The unit is first completely assembled at the factory: The driveline (compressor/motor assembly) is mounted, with all necessary interconnecting piping assembled. Prior to shipping, the unit is completely assembled at the factory. Interconnecting piping is assembled, and the complete unit is wired and leak-tested. The unit is then dismantled into two assemblies and shipped as follows: JOHNSON CONTROLS 11

Section 1 - Shipping Condenser-Side Assembly (Condenser / Optiview Control Center / Variable Speed Drive) The Condenser-side assembly consists of the Condenser, the OptiView Control Center and the Variable Speed Drive. All conduit is left on the condenser shell. Interconnecting piping between shells are flanged and capped, requiring no welding. All openings on the condenser shell are closed and shipped charged with a 2 to 3 PSIG (115.122 kpa) holding charge of dry nitrogen. Evaporator-Side Assembly (Evaporator / Driveline / Magnetic Bearing Controller) The evaporator-side assembly consists of the evaporator, the driveline (compressor/motor assembly), and the Magnetic Bearing Controller. All conduit is left on the evaporator shell. Interconnecting piping between shells are flanged and capped, requiring no welding. All integral wiring is left on the compressor. All openings on the evaporator shell and driveline are closed and shipped charged with a 2 to 3 PSIG (115.122 kpa) holding charge of dry nitrogen. The unit shipment should be checked on arrival to see that all major pieces, boxes and crates are received. Each unit should be checked on the trailer or rail car when received, before unloading, for any visible signs of damage. Any damage or signs of possible damage must be reported to the transportation company immediately for their inspection. FORM 160.78-N1 JOHNSON CONTROLS WILL NOT BE RESPON- SIBLE FOR ANY DAMAGE IN SHIPMENT OR AT JOB SITE OR LOSS OF PARTS. (Refer to Shipping Damage Claims Form (Form 50.15-NM). When received at the job site all containers should be opened and contents checked against the packing list. Any material shortage should be reported to Johnson Controls immediately. (Refer to Shipping Damage Claims Form (Form 50.15-NM). CHILLER DATA PLATE A unit data plate is mounted on the control center assembly of each unit, giving unit model number; design working pressure; water passes; refrigerant charge; serial numbers; and motor power characteristics and connection diagrams. Additional information may be found on the motor data plate. This information should be included when contacting the factory on any problem relating to the motor. Miscellaneous Material The following items are shipped together: Four (4) vibration isolation pads (or optional spring isolators and brackets) Other shipped loose items, including piping, water temperature controls, wiring, etc. VSD Inhibitor INSPECTION DAMAGE SHORTAGE 12 JOHNSON CONTROLS

SECTION 2 - INSTALLATION OVERVIEW The installation process consists of the following steps: 1. Rig Chiller Unit 2. Determine Location Foundation Requirements Clearance Requirements 3. Rig Chiller to Final Location 4. Install Isolators Locate and place Isolator Pads, or Install optional Spring Isolaters 5. Level Chiller 6. Make Connections Piping Wiring 7. Apply Insulation RIG CHILLER UNIT The complete standard chiller is shipped without skids. (When optional skids are used it may be necessary to remove the skids so riggers skates can be used under the unit end sheets to reduce overall height.) Each unit has four lifting holes (two in each end sheet). Lift the unit using these holes only, as shown in Figure 2. Care should be taken at all times during rigging and handling of the chiller to avoid damage to the unit and its external connections. Do not lift the unit with slings around the driveline (compressor/motor assembly) or by means of eyebolts in the tapped holes of the compressor motor assembly. Do not turn a unit on its side for rigging. Do not rig vertically. 2 LD03864 Figure 2 - RIGGING JOHNSON CONTROLS 13

Section 2 - Installation The rigging, operating weights, and overall dimensions are provided in Section 3 - Unit Weights and Measurements to help you determine the clearances required for rigging. Add 6" (15 cm) to overall height for optional skidded unit. DETERMINE LOCATION YMC 2 Chillers are furnished with vibration isolator mounts for basement or ground level installations. Units may be located on upper floor levels providing the floor is capable of supporting the total unit operating weight and optional spring isolators are used. Sufficient clearance to facilitate normal service and maintenance work must be provided around and above the unit and particularly space provided at either end to permit cleaning or replacement of evaporator and condenser tubes see Clearance. A doorway or other sufficiently large opening properly located may be used. The chiller should be located in an indoor location where temperatures range from 40 F to 110 F (4.4 C to 43.3 C). Foundation Requirements A level floor, mounting pad or foundation must be provided by others, capable of supporting the operating weight of the unit. Clearance Requirements Clearances should be adhered to as follows: Rear and Above Unit Front of Unit Tube Removal * 10' (3m): 2110 & 2510 Shell Codes 14' (4.3m): 2514 Shell Codes 2 ft (61 cm) 3 ft (91 cm) RIG UNIT TO FINAL LOCATION 14 ft* (4.3 m) either end FORM 160.78-N1 Rig the unit to its final location on the floor or mounting pad, lift the unit (or shell assembly) by means of an overhead lift and lower the unit to its mounting position. (If optional shipping skids are used, remove them before lowering the chiller to its mounting position.) At this point units shipped dismantled should be assembled under the supervision of a Johnson Controls representative. If evaporator is to be field insulated, the insulation should be applied to the evaporator before the unit is placed in position while the unit is in the lift position. Be sure unit is properly supported. (Refer to Insulation in this section and Figure 9 for further information.) INSTALL ISOLATORS Neoprene Isolator Pads Locate And Place Isolator Pads The isolator pad mounts are to be located and placed rubber-side down as shown in Figures 3 and 4. After the isolator pads have been placed into position on the floor, lower the chiller onto the pads. When the unit is in place, remove the rigging equipment and check that the unit is level. Level The Unit The longitudinal alignment of the unit should be checked by placing a level on the top center of the evaporator shell under the compressor/motor assembly. Transverse alignment should be checked by placing a level on top of the shell end sheets. The unit should be level within 1/4" (6 mm) from one end to the other end and from front to the rear. If the chiller is not level within the amount specified, lift it and place shims between the isolation pad and the chiller tube sheets. (Shims are furnished by the installer.) Lower unit again and recheck to see that it is level Checking The Isolation Pad Deflection All isolation pads should be checked for the proper deflection while checking to see if the unit is level. Each pad should be deflected approximately 0.10 inches (2.5 mm) to 0.20 inches (5 mm). If an isolation pad is under-deflected, shims should be placed between the unit tube sheet and the top of the pad to equally deflect all pads. 14 JOHNSON CONTROLS

Section 2 - Installation 2 LD12638 UNIT WEIGHT UP TO 5,500 Lbs (2,494 Kgs) LD12639 UNIT WEIGHT 5,501-8,000 Lbs (2,495-3,628 Kgs) LD12640 LD12641 UNIT WEIGHT 8,001-15,000 Lbs (3,629-6,804 Kgs) UNIT WEIGHT 15,001-29,000 Lbs (6,805-13,154 Kgs) NOTE: Dimensions are shown in Inches (mm) Figure 3 - NEOPRENE ISOLATORS JOHNSON CONTROLS 15

Section 2 - Installation FORM 160.78-N1 D D D B C A D E LD12642 OPERATING UNIT WEIGHT DIM "A" DIM "B" DIM "C" DIM "D" DIM "E" 15,001-29,000 Lbs (6,805-13,154 Kgs) 62" (1575) 31" (787) 31" (787) 10" (254) 8" (203) NOTE: Dimensions are shown in Inches (mm) Figure 4 - NEOPRENE ISOLATORS 16 JOHNSON CONTROLS

Section 2 - Installation Install Optional Spring Isolators Bolt Isolators To The Unit If ordered, spring type isolator assemblies are furnished with the unit. The four assemblies are identical and can be placed at any of the four corners of the unit. While the unit is still suspended by the rigging, the isolators should be bolted to the unit by inserting the cap screw(s) through the hole(s) in the mounting bracket into the tapped hole in the top of the isolator leveling bolt(s). Then the unit can be lowered onto the floor. Level The Unit The longitudinal alignment of the unit should be checked by placing a level on the top center of the evaporator shell under the compressor/motor assembly. Transverse alignment should be checked by placing a level on top of the shell end sheets. Rotate the leveling bolts one turn at a time, in sequence, until the unit end sheets are clear of the floor by the dimension shown in Figures 5 and 6 and the unit is level. If the leveling bolts are not long enough to level unit due to an uneven or sloping floor or foundation, steel shims (grouted, if necessary) must be added beneath the isolator assemblies as necessary. 2 LD126544 UNIT WEIGHT Up To 35,009 Lbs (15,880 Kgs) Figure 5 - SPRING ISOLATORS JOHNSON CONTROLS 17

Section 2 - Installation FORM 160.78-N1 F B C A F D E LD12643 OPERATING UNIT WEIGHT DIM "A" DIM "B" DIM "C" DIM "D" DIM "E" DIM "F" Up to 35,000 Lbs (15,880 Kgs) 62" (1575) 31" (787) 31" (787) 6" (152) 6-7/8" (175) 5-1/2" (140) NOTE: Dimensions are shown in Inches (mm) Figure 6 - SPRING ISOLATORS 18 JOHNSON CONTROLS

Section 2 - Installation MAKE CONNECTIONS After the unit is leveled, place wedges and/or shims under each corner to solidly support the unit in this position while connecting and hanging the piping, adjusting the connections, and checking for proper alignment. After the connections are made and insulation is applied, the unit can be filled with water and checked for leaks. If spring isolators were installed, final adjustments can be made to the leveling bolts until the wedges and shims can be removed. The unit should now be in correct level position, clear of the floor or foundation and without any effect from the weight of the piping. The coolant temperature inside any JCI-supplied liquid-cooled motor starter must be maintained above the dewpoint temperature in the equipment room to prevent condensing water vapor inside the starter cabinet. Therefore, an additional temperature-controlled throttle valve is needed in the flow path for the starter heat exchanger to regulate cooling above the equipment room dewpoint for applications using cooling sources other than evaporative air-exchange methods, such as wells, bodies of water, and chilled water. The temperature control valve should be the type to open on increasing drive coolant temperature, fail-closed, and set for a temperature above dewpoint. It can be requested as factory-supplied on a chiller order by special quotation. Piping Connections After the unit is leveled (and wedged in place for optional spring isolators) the piping connections may be made; chilled water, condenser water and refrigerant relief. The piping should be arranged with offsets for flexibility, and adequately supported and braced independently of the unit to avoid strain on the unit and vibration transmission (refer to Figure 7). Hangers must allow for alignment of pipe. Isolators (by others) in the piping and hangers are highly desirable, and may be required by specifications, in order to effectively utilize the vibration isolation characteristics of the vibration isolation mounts of the unit. Check for piping alignment Upon completion of piping, a connection in each line as close to the unit as possible should be opened, by removing the flange bolts or coupling and checked for piping alignment. If any of the bolts are bound in their holes, or if the connection springs are out of alignment, the misalignment must be corrected by properly supporting the piping or by applying heat to anneal the pipe. If the piping is annealed to relieve stress, the inside of the pipe must be cleaned of scale before it is finally bolted in place. 2 LD03863 Figure 7 - TYPICAL REFRIGERANT VENT PIPING JOHNSON CONTROLS 19

Section 2 - Installation FORM 160.78-N1 LD08529 Figure 8 - SCHEMATIC OF A TYPICAL PIPING ARRANGEMENT Evaporator And Condenser Water Piping The evaporator and condenser liquid heads of chiller have nozzles which are grooved, suitable for welding 150 psig DWP flanges or the use of flexible couplings. Factory mounted flanges are optional. If welding is done on the nozzles, flow switches, condenser level sensor, and water temperature thermistors should be disconnected and the welding ground MUST be good contact located at the head to prevent current damage to the devices. The nozzles and water pass arrangements are furnished in accordance with the job requirements (see Product Drawings) furnished with the job. Standard units are designed for 150 psig DWP on the water side. If job requirements are for greater than 150 psig DWP, check the unit data plate before applying pressure to evaporator or condenser to determine if the chiller has provisions for the required DWP. Inlet and outlet connections are identified by labels placed adjacent to each nozzle. Chilled Water Foreign objects which could lodge in, or block flow through, the evaporator and condenser tubes must be kept out of the water circuit. All water piping must be cleaned or flushed before being connected to the chiller pumps, or other equipment. Permanent strainers (supplied by others) are required in both the evaporator and condenser water circuits to protect the chiller as well as the pumps, tower spray nozzles, chilled water coils and controls, etc. The strainer must be installed in the entering chilled water and condenser liquid line, directly upstream of the chiller. Water piping circuits should be arranged so that the pumps discharge through the chiller, and should be controlled as necessary to maintain essentially constant chilled and condenser water flows through the unit at all load conditions. If pumps discharge through the chiller, the strainer may be located upstream from pumps to protect both pump and chiller. (Piping between strainer, pump and chiller must be very carefully cleaned before start-up.) If pumps are remotely installed from chiller, strainers should be located directly upstream of the chiller. Condenser Water Circuit For proper operation of the unit, condenser refrigerant pressure must be maintained above evaporator pressure. If operating conditions will fulfill this requirement, no attempt should be made to control condenser water temperature by means of automatic valves, cycling of the cooling tower fan, or other means, since chillers are designed to function satisfactorily and efficiently when condenser water is allowed to seek its own temperature level at reduced loads and off-peak seasons of the year. However, if it is possible for the entering condenser water temperature to go below the required minimum, condenser water temperature must be maintained equal to or slightly higher than the required minimum. Refer to the YMC 2 Engineer- 20 JOHNSON CONTROLS

Section 2 - Installation ing Guide (Form 160.78-EG1) for required minimum Condenser and Evaporator temperatures. Refer to Figure 8 for typical water piping schematic. Stop Valves Stop valves may be provided (by others) in the evaporator and condenser water piping adjacent to the unit to facilitate maintenance. Thermometer wells and pressure taps should be provided (by others) in the piping as close to the unit as possible to facilitate operating check. Flow Switches Thermal type water flow switches are factory mounted in the chilled and condensed water nozzles and are factory wired to the OptiView Control Panel. These solid-state flow sensors have a small internal heating element and use the cooling effect of the flowing fluid to sense when an adequate flow rate has been established. Waterbox Drain And Vent Valves Drain and vent valves (by others) should be installed in the connections provided in the evaporator and condenser liquid heads. These connections may be piped to drain if desired. Checking Piping Circuits And Venting Air After the water piping is completed, but before any water box insulation is applied. Tighten and torque to maintain between 30 and 60 ft. lbs. (41 and 81 N m) the nuts on the liquid head flanges. Gasket shrinkage and handling during transit cause nuts to loosen. If water pressure is applied before tightening is done, the gaskets may be damaged and have to be replaced. Fill the chilled and condenser water circuits, operate the pumps manually and carefully check the evaporator and condenser water heads and piping for leaks. Repair leaks as necessary. Before initial operation of the unit both water circuits should be thoroughly vented of all air at the high points. Refrigerant Relief Piping Each unit is equipped with pressure relief valves located on the condenser and on the evaporator for the purpose of quickly relieving excess pressure of the refrigerant charge to the atmosphere as a safety precaution in case of an emergency, such as fire. Refrigerant relief vent piping (by others), from the relief valves to the outside of the building, is required by code in most areas and should be installed on all chillers. The vent line should be sized in accordance with the ANSI/ ASHRAE-15, or local code. The vent line must include a dirt trap in the vertical leg to intercept and permit clean out and to trap any vent stack condensation. The piping MUST be arranged to avoid strain on the relief valves, using a flexible connection, if necessary. Unit Piping Compressor refrigerant piping and system external piping are factory installed on all units shipped assembled. On units shipped dismantled, the piping should be completed under the supervision of the Johnson Controls representative. Control Wiring On units shipped disassembled, after installation of the control center, control wiring must be completed between unit components and control center, solid state starter, or variable speed drive, when used, using wiring harness furnished. Refer to YMC 2 Field Connections Manual (Form 160.78-PW1) Field wiring connections for commonly encountered control modifications (by others) if required, are shown in the YMC 2 Unit Wiring and Field Control Modifications Manual (Form 160.78-PW2). Power Wiring No deviations in unit wiring from that shown on drawings furnished shall be made without prior approval of the Johnson Controls representative. DO NOT cut wires to final length or make final connections to starter power input terminals until approved by the Johnson Controls representative. Supplied Variable Speed Drive. The factory mounted Variable Speed Drive does not require wiring to the compressor motor. The motor power wiring is factory connected to the Variable Speed Drive (refer to the YMC 2 Unit Wiring and Field Control Modifications Manual (Form 160.78-PW2)). All wiring to the control panel is completed by the factory. A control transformer is factory furnished with the Variable Speed Drive. 2 JOHNSON CONTROLS 21

Section 2 - Installation FORM 160.78-N1 HOT GAS LINE LIQUID LINE SIGHT GLASS CONDENSER EVAPORATOR CONDENSER EVAPORATOR Tape Insulation around flanges to allow for removal. HOT GAS CONNECTION SIGHT GLASS Bold lines and shaded components represent insulation. LD03827a Figure 9 - FAA UNIT INSULATION 22 JOHNSON CONTROLS

Section 2 - Installation HOT GAS LINE LIQUID LINE 2 SIGHT GLASS CONDENSER EVAPORATOR CONDENSER EVAPORATOR Tape Insulation around flanges to allow for removal. HOT GAS CONNECTION INSULATE LINE Bold lines and shaded components represent insulation. LD03827b Figure 10 - FAB UNIT INSULATION JOHNSON CONTROLS 23

Section 2 - Installation APPLY INSULATION DO NOT field insulate until the unit has been leak tested under the supervision of the Johnson Controls representative. Insulation of the type specified for the job, or minimum thickness to prevent sweating of 30 F (-1 C) surfaces should be furnished (by others) and applied to the evaporator shell, end sheets, liquid feed line to flow chamber, compressor suction connection, and evaporator liquid heads and connections (see Figure 9). The liquid head flange insulation must be removable, to allow head removal for the tube maintenance. FORM 160.78-N1 INSTALLATION CHECK REQUEST FOR START-UP SERVICE The services of a Johnson Controls representative will be furnished to check the installation and supervise the initial start-up and operation on all chillers installed within the Continental United States. After the unit is installed, piped and wired as described in this Instruction, but before any attempt is made to start the unit, the Johnson Controls District Office should be advised so that the start-up service, included in the contract price, can be scheduled. Notify the Johnson Controls office using the Installation Checklist and Request Form (Form 160.78-CL1). Units are furnished factory anti-sweat insulated on order at additional cost. This includes all low temperature surfaces except the two (2) cooler liquid heads. 24 JOHNSON CONTROLS

SECTION 3 - DIMENSIONS, NOZZLE ARRANGEMENTS AND WEIGHTS COMPRESSOR UNIT DIMENSIONS Type Of Chiller Mounting Additional Operating Height Clearance To Floor Ft - In (mm) M 3 Neoprene Pad Isolators 1-3/4" (45) Spring Isolators 1" Deflection 1" (25) Direct Mount 3/4" (19) EVAPORATOR CODE CONDENSER CODE DIMENSIONS - 197 & 205 COMPRESSOR UNITS FT - IN (MM) A B C D E EA2510 CA2110 5-5 (1651) 7-4 (2235) 1-3-1/2 (394) 1-3-1/2 (394) 10-0 (3048) EA2510 CA2510 5-5 (1651) 7-9 (2362) 1-3-1/2 (394) 1-3-1/2 (394) 10-0 (3048) EA2514 CA2514 5-5 (1651) 7-9 (2362) 1-3-1/2 (394) 1-3-1/2 (394) 14-0 (4267) NOTES: 1. All dimensions are approximate. Certified dimensions are available on request. 2. Standard water nozzles are Schedule 40 pipe size, furnished as welding stub-outs with ANSI/AWWA C-606 grooves, allowing the option of welding, flanges, or use of ANSI/AWWA C-606 couplings. Factory-installed, class 150 (ANSI B16.5, round slip-on forged carbon steel with 1/16" raised face), water flanged nozzles are optional (add 1/2" to nozzle length). Companion flanges, nuts, bolts, and gaskets are not furnished. 3. One, two, and three-pass nozzle arrangements are available only in pairs shown for all shell codes. Any pair of evaporator nozzles may be used in combination with any pair of condenser nozzles Compact water boxes on one heat exchanger may be used with Marine Water Boxes on the other heat exchangers. 4. Condenser water must enter the water box through the bottom connection for proper operation of the sub-cooler to achieve rated performance. 5. To determine overall height, add dimension "M" for the appropriate isolator type. VSD VSD CONTROL PANEL COMPRESSOR CONTROL PANEL MOTOR B H J C A D 3-3/8 M F (EVAP.) E G (EVAP.) LD07134 Figure 11 - DIMENSIONS 197 & 205 COMPRESSOR UNITS FT-IN (MM) JOHNSON CONTROLS 25

Section 3 - Dimensions, Nozzle Arrangements And Weights FORM 160.78-N1 EVAPORATOR NOZZLE ARRANGEMENTS (150 PSI COMPACT WATER BOXES) LD14004 1-Pass Evaporator Nozzle Arrangements In Out Left End Right End Right End Left End Figure 12 - EVAPORATORS - COMPACT WATER BOXES (1-PASS NOZZLE ARRANGEMENTS) LD14005 2-Pass Evaporator Nozzle Arrangements In Out Lower Right End Upper Right End Lower Left End Upper Left End Figure 13 - EVAPORATORS - COMPACT WATER BOXES (2-PASS NOZZLE ARRANGEMENTS) LD14006 3-Pass Evaporator Nozzle Arrangements In Out Right End Left End LD14007 3-Pass Evaporator Nozzle Arrangements In Out Left End Right End Figure 14 - EVAPORATORS - COMPACT WATER BOXES (3-PASS NOZZLE ARRANGEMENTS) Evaporator Shell Code EA25 Nozzle Pipe Size Ft-In (mm) COMPACT WATER BOXES-150 PSI Evaporator Nozzle Dimensions Ft-In (mm) No. of Passes 1-Pass 2-Pass 3-Pass C 1 2 3 AA 5 AA 5 BB 5 EE AA 5 BB 5 EE 8" (203) 6" (152) 4" (102) 1' - 3-1/2" (394) 1' - 10" (559) 1' - 5" (432) 2' - 3" (686) 0' - 5" (127) 1' - 5" (432) 2' - 3" (686) 0' - 5" (127) NOTE: Dimensions are shown in Inches (mm) 26 JOHNSON CONTROLS

Section 3 - Dimensions, Nozzle Arrangements And Weights EVAPORATOR NOZZLE ARRANGEMENTS (150 PSI COMPACT WATER BOXES) 3 LD14020 Evaporator Shell Code Dimensions Ft - In (mm) F EA25 1' - 2-1/8" (359) 0' - 6-5/16" (160) G NOTES: 1. All dimensions shown in Ft/In (mm) 2. Standard water nozzles are furnished as welding stub-outs with ANSI/AWWA C-606 grooves, allowing the option of welding, flanges, or use of ANSI/AWWA C-606 couplings. Factory-installed, class 150 (ANSI B16.5, round slip-on, forged carbon steel with 1.6mm raised face), water flanged nozzles are optional (add 13mm to nozzle length). Companion flanges, nuts, bolts, and gaskets are not furnished. 3. One-, Two- and Three-pass nozzle arrangements are available only in pairs shown and for all shell codes. Any pair of evaporator nozzles may be used in combination with any pair of condenser nozzles. 4. Evaporator and condenser water must enter the water box through the bottom connection to achieve rated performance. 5. Connected piping should allow for removal of compact water boxes for tube access and cleaning. 6. Add dimension "M" as shown on the unit dimensions page for the appropriate isolator type. Figure 15 - EVAPORATORS - 150 PSI COMPACT WATER BOXES JOHNSON CONTROLS 27

Section 3 - Dimensions, Nozzle Arrangements And Weights FORM 160.78-N1 CONDENSER NOZZLE ARRANGEMENTS (150 PSI COMPACT WATER BOXES) LD14008 1-Pass Condenser Nozzle Arrangements In Out Left End Right End Right End Left End Figure 16 - CONDENSERS - COMPACT WATER BOXES (1-PASS NOZZLE ARRANGEMENTS) LD14009 2-Pass Condenser Nozzle Arrangements In Out Lower Right End Upper Right End Lower Left End Upper Left End Figure 17 - CONDENSERS - COMPACT WATER BOXES (3-PASS NOZZLE ARRANGEMENTS) LD14010 3-Pass Condenser Nozzle Arrangements In Out Right End Left End LD14011 3-Pass Condenser Nozzle Arrangements In Out Left End Right End Figure 18 - CONDENSERS - COMPACT WATER BOXES (2-PASS NOZZLE ARRANGEMENTS) Condenser Shell Code Nozzle Pipe Size In (mm) COMPACT WATER BOXES-150 PSI Condenser Nozzle Dimensions Ft-In (mm) No. of Passes 1-Pass 2-Pass 3-Pass C 1 2 3 AA 5 AA 5 BB 5 AA 5 BB 5 CA21 10" (254) 6" (152) 6" (152) 1' - 3-1/2" (394) 1' - 11-1/2" (597) 1' - 5" (432) 2' - 6" (762) 1' - 5" (432) 2' - 6" (762) CA25 12 (305) 8" (203) 6" (152) 1' - 3-1/2" (394) 2' - 1-1/2" (648) 1' - 5-7/8" (454) 2' - 9-1/8" (841) 1' - 5-7/8" (454) 2' - 9-1/8" (841) NOTE: Dimensions are shown in Inches (mm) 28 JOHNSON CONTROLS

Section 3 - Dimensions, Nozzle Arrangements And Weights CONDENSER NOZZLE ARRANGEMENTS (150 PSI COMPACT WATER BOXES) 3 LD14020 Condenser Shell Code Dimensions Ft - In (mm) F CA21 1' - 1-3/4" (349) 0' - 5-13/16" (148) CA25 1' - 1-3/4" (349) 0' - 6-5/16" (160) G NOTES: 1. All dimensions shown in Ft/In (mm) 2. Standard water nozzles are furnished as welding stub-outs with ANSI/AWWA C-606 grooves, allowing the option of welding, flanges, or use of ANSI/AWWA C-606 couplings. Factory-installed, class 150 (ANSI B16.5, round slip-on, forged carbon steel with 1.6mm raised face), water flanged nozzles are optional (add 13mm to nozzle length). Companion flanges, nuts, bolts, and gaskets are not furnished. 3. One-, Two- and Three-pass nozzle arrangements are available only in pairs shown and for all shell codes. Any pair of evaporator nozzles may be used in combination with any pair of condenser nozzles. 4. Evaporator and condenser water must enter the water box through the bottom connection to achieve rated performance. 5. Connected piping should allow for removal of compact water boxes for tube access and cleaning. 6. Add dimension "M" as shown on the unit dimensions page for the appropriate isolator type. Figure 19 - CONDENSERS - 150 PSI COMPACT WATER BOXES JOHNSON CONTROLS 29

Section 3 - Dimensions, Nozzle Arrangements And Weights FORM 160.78-N1 EVAPORATOR NOZZLE ARRANGEMENTS (150 PSI MARINE WATER BOXES) LD14012 1-Pass Evaporator Nozzle Arrangements In Out Left End Right End Right End Left End Figure 20 - EVAPORATORS - MARINE WATER BOXES (1-PASS NOZZLE ARRANGEMENTS) LD14013 2-Pass Evaporator Nozzle Arrangements In Out Lower Right End Upper Right End Lower Left End Upper Left End Figure 21 - EVAPORATORS - MARINE WATER BOXES (2-PASS NOZZLE ARRANGEMENTS) LD14014 3-Pass Evaporator Nozzle Arrangements In Out Right End Left End LD14015 3-Pass Evaporator Nozzle Arrangements In Out Left End Right End Figure 22 - EVAPORATORS - MARINE WATER BOXES (3-PASS NOZZLE ARRANGEMENTS) Evaporator Shell Code EA25 Nozzle Pipe Size Ft-In (mm) MARINE WATER BOXES-150 PSI Evaporator Nozzle Dimensions Ft-In (mm) No. of Passes 1-Pass 2-Pass 3-Pass C 1 2 3 AA 5 AA 5 BB 5 EE AA 5 BB 5 EE 8" (203) 6" (152) 4" (102) 1' - 3-1/2" (394) 3' - 7" (1092) 1' - 2" (356) 3' - 7" (1092) 1' - 5-1/2" (445) 1' - 2" (356) 3' - 7" (1092) 1' - 5-1/2" (445) NOTE: Dimensions are shown in Inches (mm) 30 JOHNSON CONTROLS

Section 3 - Dimensions, Nozzle Arrangements And Weights EVAPORATOR NOZZLE ARRANGEMENTS (150 PSI MARINE WATER BOXES) 3 LD14021 Evaporator Shell Code EA25 1-Pass 2-Pass 3-Pass F I F I G F I 1' - 6-5/8" (473) 0' - 8-11/16" (221) 1' - 4-1/2" (419) 0' - 7-5/8" (194) 0' - 6-5/16" (160) 1' - 4-1/2" (419) 0' - 7-5/8" (194) NOTES: 1. All dimensions shown in Ft/In (mm) 2. All dimensions are approximate. Certified dimensions are available upon request. 3. Standard water nozzles are Schedule 40 pipe size, furnished as welding stub-outs with ANSI/AWWA C-606 grooves, allowing the option of welding, flanges, or use of ANSI/AWWA C-606 couplings. Factory-installed, class 150 (ANSI B16.5, round slip-on, forged carbon steel with 1.6 mm raised face), water flanged nozzles are optional (add 13 mm to nozzle length). Companion flanges, nuts, bolts, and gaskets are not furnished. 4. One-, two-, and three-pass nozzle arrangements are available only in pairs shown and for all shell codes. Any pair of evaporator nozzles may be used in combination with any pair of condenser nozzles. Compact water boxes on one heat exchanger may be used with Marine Water Boxes on the other heat exchanger. 5. Water must enter the water box through the bottom connection to achieve rated performance. Figure 23 - EVAPORATORS - 150 PSI MARINE WATER BOXES JOHNSON CONTROLS 31

Section 3 - Dimensions, Nozzle Arrangements And Weights FORM 160.78-N1 CONDENSER NOZZLE ARRANGEMENTS (150 PSI MARINE WATER BOXES) LD14016 1-Pass Condenser Nozzle Arrangements In Out Left End Right End Right End Left End Figure 24 - CONDENSERS - MARINE WATER BOXES (1-PASS NOZZLE ARRANGEMENTS) LD14017 2-Pass Condenser Nozzle Arrangements In Out Lower Right End Upper Right End Lower Left End Upper Left End Figure 25 - CONDENSERS - MARINE WATER BOXES (2-PASS NOZZLE ARRANGEMENTS) LD14018 3-Pass Condenser Nozzle Arrangements In Out Right End Left End LD14019 3-Pass Condenser Nozzle Arrangements In Out Left End Right End Figure 26 - CONDENSERS - MARINE WATER BOXES (3-PASS NOZZLE ARRANGEMENTS) Condenser Shell Code Nozzle Pipe Size Ft-In (mm) MARINE WATER BOXES-150 PSI Evaporator Nozzle Dimensions Ft-In (mm) No. of Passes 1-Pass 2-Pass 3-Pass C 1 2 3 AA 5 AA 5 BB 5 EE AA 5 BB 5 EE CA21 10" (254) 6" (152) 6" (152) CA25 12 (305) 8" (203) 6" (152) NOTE: Dimensions are shown in Inches (mm) 1' - 3-1/2" (394) 1' - 3-1/2" (394) 3' - 10-1/2" (1181) 4' - 0-1/2" (1232) 1' - 5-1/2" (445) 1' - 5-1/2" (445) 3' - 10-1/2" (1181) 4' - 0-1/2" (1232) 1' - 4-1/2" (419) 1' - 6-1/2" (470) 1' - 5-1/2" (445) 1' - 5-1/2" (445) 3' - 10-1/2" (1181) 4' - 0-1/2" (1232) 1' - 4-1/2" (419) 1' - 6-1/2" (470) 32 JOHNSON CONTROLS