Appendix 1 Reference HOB and boiler efficiency

Similar documents
Upgrading and Installation of. PP from Japan: Suuri Keikaku

Joint Crediting Mechanism Project Design Document Form

Additional Information for the Proposed Methodology Energy Saving by Introduction of High Efficiency Once-through Boiler

Methodologies for efficiency improvement of HOB and CHP through JCM scheme. Advisory committee on 7 th October in 2013.

Continuous Commissioning: A Valuable Partner to Retrofit Projects

2.4 Air Pollution Control and Energy Conservation Measures (Output 4)

Sivu 2/8 Rate data Description Suomi Shut off times total 0.0 h/day Weekends with shut off times yes Daytime rate of heat pump Time for daytime rate 5

COST REDUCTION BY REPLACING STEAM WITH COKE OVEN GAS FOR HOT AIR DRYER UNIT IN THE ELECTROLYTE CLEANING LINE

Countywide Recycling and Disposal Facility Weekly Progress Report 08/22/08

Analogue to Digital Telecare. Technical Advisory Board. 21 st June 2017 Work Stream 3 Procurement

MONGOLIAN ENVIRONMENTAL IMPACT ASSESSMENT SITUATION

4/8/2015 Item #10D Page 1

Indoor Thermal Environment of Residential Buildings in Three Cities of China

Cork County Energy Agency

Certification Report of the ST 3000 Pressure Transmitter with HART 6

Acknowledgement: Ralph Prahl, Prahl & Associates, contributed critical review and analysis

Air Conditioning Inspections for Buildings Efficiency of Air Conditioning Systems

DETERMINATION REPORT GLOBAL CARBON BV

DISTRICT HEATING SCHEME FEASIBILITY STUDY FRANKTON FLATS QUEENSTOWN

ENERGY CONSUMPTION OF HOUSES AND LIFESTYLE IN COLD CLIMATIC AREA OF JAPAN

Buxton Town Team Artisan Market Footfall Analysis July 2015

MEASURED PERFORMANCE DATA FOR

National Grid Residential Active Demand Reduction Demonstration Project. MA EEAC Demand Reduction Sub-Committee February 23, 2017

Westinghouse UK AP1000 GENERIC DESIGN ASSESSMENT Resolution Plan for GI-AP1000-IH-01 Internal Fire Safety Case Substantiation.

PG18.2 REPORT FOR ACTION. Eco-Roof Incentive Program application: 50 Drummond Street SUMMARY

Heat Consumption Assessment of the Domestic Hot Water Systems in the Apartment Buildings

Response to request for review Destruction of HFC-23 at Refrigerant (HCFC-22) Manufacturing Facility of Chemplast Ltd. (0499)

Partner Agency: Ministry of Construction and Urban Development Funding Agency: UNDP

APPENDIX 112D. PERCHLOROETHYLENE DRY CLEANING NESHAP (40 CFR 63 Subpart M) CAA SECTION 112 NESHAP

WHITE PAPER. ANSI/AHRI Standard for Fan and Coil Evaporators - Benefits and Costs

National Grid Residential & C&I Active Demand Reduction Demonstration Projects. MA EEAC March 15, 2017

URBAN DESIGN LONDON TRAINING PROGRAMME UDL are pleased to present our programme for April 2013 to March 2014.

New Westminster Downtown Parking Strategy Public Open House #1 September 13, 2012

AHRI Releases November 2011 U.S. Heating and Cooling Equipment Shipment Data

NEN, the knowledge network for standardization in the Netherlands. Annual Report 2015

R4 Ventures LLC White Paper

Remodeling Market. Kermit Baker. Remodeling Futures Conference November 9, Harvard University JOINT CENTER FOR HOUSING STUDIES

Radon Measurement Survey Report. Rollins Elementary School 950 Kane Street Aurora, Illinois Prepared For:

Radon Measurement Survey Report. Oak Park Elementary School 1200 Front Street Aurora, Illinois Prepared For:

Hot Water a Hot Commodity Better Buildings by Design, February 2012 Burlington, VT

Carbon footprint of products ISO 14067

Laboratory Evaluation of Hybrid and Advanced Water Heaters: Performance Overview in Hot Humid Climate

MASTER PLAN KICK-OFF Open House #1A, April 28, 2015

Technical Note. Noise emission from Dehumidifier Type C65E TC Project no.: I Page 1 of July 2016

Daikin Altherma Selection Report

HEAT LOAD AND SOLAR GAIN PREDICTION FOR SOLID WALL DWELLINGS RETROFITTED WITH TRIPLE VACUUM GLAZING FOR SELECTED WINDOW TO WALL AREA RATIOS

Radon Measurement Survey Report. McKnight School Service Center 417 Fifth Street Aurora, Illinois Prepared For:

Unvented Roof Summary Article

<<Date>> <<Recipient>> <<Address>>

Copyright 2003 IBACOS, Inc. All rights reserved.

On Balance: Heat Rejection Control a Packaged Solution

Solar Plant Performance Monitoring

Nothing lasts forever planning for successful mine closure

September 11, 2012 Ministry of Economy, Trade and Industry

Residential Structure Match or Lighter Ignited Fires

Can Short Term ARRA Stimulus Funding Achieve Long Term Market Transformation? 1

Certification Report of the ST3000 Pressure Transmitter

Radiation. Pekka Vuorinen. Finnish Association of Construction Product Industries RTT

Final Report Polymer Bead Laundry

GENERAL SUMMARY FOR PUBLIC ULAANBAATAR 2020 MASTER PLAN AND DEVELOPMENT APPROACHES FOR 2030

Biosolids Dewatering, Monitoring, and Disposal Programs

Carmel Bud Failure. HAL Project AL Dr Prue McMichael Dr Kate Delaporte ABA & Trial Co-operators

Eco-Roof Incentive Program application: 77 Glen Rush Boulevard

FUEL TYPE relating to UK deaths from unintentional carbon monoxide poisoning from to

Identification of Aberrant Railroad Wayside WILD and THD Detectors: Using Industry-wide Railroad Data. June 10, 2014

Cooling Options for Geothermal and Concentrating Solar Power Plants

Countywide Recycling and Disposal Facility Weekly Progress Report 12/26/08

Lifestyle Electric Thermal Radiator

Lifestyle Electric Thermal Radiator

Heating and Hot Water

Buran. Cycling Refrigerated Compressed Air Dryer With Ultrapulse Control. Intelligent Energy Management

Comparison of Heating Efficiency of a Heat Pump to Electric Heating Panels

House Efficiency Survey Report

Mechanical System Redesign. Dedicated Outdoor Air System. Design Criteria

Soil and Plant Methods List for Automated Ion Analyzers. Flow Injection Analysis

ENERGY STAR Unit Shipment and Market Penetration Report Calendar Year 2016 Summary

Calculated Energy Savings for Disabling Anti- Sweat Door Heat on Glass Display Case Doors

HALON FLIGHTLINE EXTINGUISHER EVALUATION: DATA SUPPORTING STANDARD DEVELOPMENT [INCLUDES NOVEMBER 2007 ADDENDUM]

Radon Measurement Survey Report. Krug Elementary School 240 Melrose Avenue Aurora, Illinois Prepared For:

UNITED STATES OF AMERICA BEFORE THE FEDERAL ENERGY REGULATORY COMMISSION. North American Electric Reliability ) Docket No. RC Corporation )

LECETURE 2. Performance Characteristics of Sensors

Monthly Report for January 2016

REMOTE VERIFICATION OF THE CARBON FOOTPRINT CALCULATION TOOL OF MAESPA FOR REFERENCE PRODUCTS

INTEGRATION OF DEMAND RESPONSE INTO TITLE 20 FOR HOT FOOD HOLDING CABINETS

Heat Exchanger Earny Type

Monthly Report for October 2015

Technical Document Condensing hot water boilers

Kimberly Rollins, Professor, Department of Economics, University of Nevada, Reno

Eco-Roof Incentive Program application: 6 Curity Avenue

Tysons-Old Meadow Road Bike/Ped Improvements

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems

Monthly Report for October 2015

Lignite fired power station in Romania fits FGD with Wet Booster Fans and Pennguard lined Concrete Chimneys for maximum Efficiency

FINAL REPORT ON THE 4 TH JOINT CROSS-BORDER EMC MARKET SURVEILLANCE CAMPAIGN (2011) LED LIGHTING PRODUCTS

The blank report forms are enclosed. If additional blank forms are needed you may contact my office at (210) and ask for Maria Castoreno.

Failure Modes, Effects and Diagnostic Analysis

Appendix A. Reference Evapotranspiration (ETo) Table.

WLAC Facilities Committee Meeting. September 18, 2017

Financial Results for First Quarter of Fiscal 2013, ending March 31, August 3, 2012

Estimating the Level of Free Riders in the Refrigerator Buy-Back Program

Transcription:

Appendix 1 Reference HOB and boiler efficiency 1. Methods and summary of researches Research on boilers has been conducted to identify reference HOB and set default values of energy efficiency for reference HOB and project HOB in Mongolia. 1.1 Identification of reference HOB Vertical type heat only boiler is determined as a reference HOB in Mongolia based on the following researches. Research on published information (see 2.1.1 for details) Interview with experts (see 2.1.2 for details) Field survey (see 2.1.3 for details) 1.2 Energy efficiency for reference HOB and project HOB 0.533 is set for reference HOB and 0.610 is set for project HOB as boiler efficiency based on the following researches. Research on published information (see 2.2.1 for details) Actual measurement of boiler efficiency (see 2.2.2 for details) 2. Detailed results of researches 2.1 Identification of reference HOB 2.1.1 Research on published information Based on National general registration of air pollutant emission sources in 2011 (АГААР БОХИРДУУЛАХ ЭХ ҮҮСВЭРИЙН 2011 ОНЫ УЛСЫН НЭГДСЭН ТОО БҮРТГЭЛ) provided by Government Implementing Agency for Meteorology & Environmental Monitoring, it is found that the vertical type HOB has the top market share of about 21%, and the old prevailing type HOB (brick boiler) also has a high share of 19% in central six districts of Ulaanbaatar city where almost half of the entire Mongolian population live. The central six districts are Khan-Uul district, Bayhanzurkh district, Somginkohairkhan district, Sukhbaatar district, Chingeltei district and Bayngol district. It is also found that boilers with energy efficiency higher than the vertical type and old prevailing type HOB have been installed in Ulaanbaatar, namely CARBOROBOT and EKOEFFECT (15%), DZL (8.0%), MDZ (5.3%) and so on. However, those high efficient boilers have been installed with financial assistance from foreign countries and international agencies. 1

[source] National general registration of air pollutant emission sources in 2011, Government Implementing Agency for Meteorology & Environmental Monitoring 2.1.2 Interview with experts Interviews with four experts of HOBs in Mongolia have been conducted. It is indicated by the experts that vertical type HOBs such as "CLSG" and "HP10/60Ж" are commonly used at the present day and will be continuously used in the near future. Head of Heat Exchange and Thermodynamics Professor team, Director of Experiment and research center for boiler, Mongolian consulting engineer The boiler which coal is manually loaded into a fixed fire grate by manual operation is suggested as a reference HOB. Since there are many types of HOBs in Mongolia, it is difficult to set the reference HOB as the type of HOB. However, it may be said that the vertical HOBs such as "CLSG" and "HP10/60Ж" are commonly used under the present circumstances of Mongolia. Senior officer of Environmental Monitoring of Government Implementing Agency for Meteorology & Environmental Monitoring Boilers made by bricks willl decrease in the future. CLSG which is made in China and HP10/60Ж which is made in Mongolia are not expensive and are easily introduced. 2

Director of Millennium Challenge Account-Mongolia Energy and Environment Project Old HOBs will be used continuously, or low price HOBs will be introduced easily without assistances of the foreign donor. Since there are many types of HOBs in Mongolia, it is difficult to identify them as reference HOB. Meanwhile, the concept, the vertical HOB is a reference HOB, is agreed. Chairman of Consulting engineer of Mongolia Master of Technical science of Authority of partial engineering supply of Ulaanbaatar city BUZI100 which is made by bricks can be the candidate of reference HOB. However, a new construction of BUZI100 is prohibited in Ulaanbaatar city. It is expected that the low price HOBs such as the vertical type will be used commonly. 2.1.3 Field survey The field survey of HOB was implemented in Lun soum, Bornuur soum, Erdene soum and Altanbulag soum in Tuv aimag. It was found in this field survey that more than half of HOBs were the vertical type HOBs and all of the newly purchased boilers were also vertical type HOBs. Table 1 Results of Field Survey of Operating Boilers in Local Areas of Mongolia Type of HOB Quantity Remarks Vertical Type Boiler 12 Example: НР10/60Ж, CLSG, etc. The newly purchased boiler was the vertical type boiler. <Information on new Installation > 2011 (Erdene soum): НР30Ж 2012 (Lun soum): НР30Ж 2013 (Bornuur soum): LSH Brick Boiler 3 There is no new boiler installation. Small Capacity Boiler 7 The quantity of this type of boiler is many in the supply to the small building. There is no new boiler installation. Total 22 2.2 Energy efficiency for reference HOB and project HOB Further researches to determine the default value of reference and project boiler efficiency have been 3

conducted. 2.2.1 Results of the research on published information The following is the result of the research on the published documents regarding boiler efficiency of HOBs in Mongolia. The range of boiler efficiency varies from 20% to 63% for the existing classic designed HOBs and from 75% to 85% for the project (high efficient) HOBs in Mongolia in those documents. Proposed CDM new methodology:nm0144-rev Title of the NM144-rev: Energy efficiency improvements carried out by an Energy Service Company (ESCO) in Ulaanbaatar, Mongolia to replace old boilers with new ones (the Project) Title of the project activity: Energy improvements carried out by an Energy Service Company (ESCO) in Ulaanbaatar, Mongolia to replace old boilers with new ones (the Project) Source: http://cdm.unfccc.int/methodologies/pamethodologies/pnm/byref/nm0144-rev Boiler efficiency of 16 sample boilers was measured during 2003 to 2005 in Ulaanbaatar. 13 out of 16 samples fall into the capacity of HOB in Mongolian standard, which is between 0.10 to 3.15 MW. 1) Boiler Efficiency of Baseline (existing classic design HOB) 42% - 63% (range of 16 sample) 2) Boiler Efficiency of Project (new design HOB) 82.5% (predicted Project Boiler data) Registered CDM project activity: Ref.0295 Title of the small-scale project activity: A retrofit programme for decentralized heating station in Mongolia Source: http://cdm.unfccc.int/projects/db/rwtuv1150300431.15/view Boiler efficiency of the existing decentralized heating stations in Ulaanbaatar was measured by TÜV Hanover in 2003. Further study on HOB boiler (810 kw and 1,200kW capacity) efficiency and the CDM project boiler was carried out by the Technical University of Ulaanbaatar. 1) Boiler Efficiency of Baseline (existing classic design HOB) [From TÜV Hanover report] 40 % 4

[From study by the Technical University of Ulaanbaatar] BZUI 100 (operating in eighty percent of Mongolia s heating stations) 34.04% DTH 34.20% 2) Boiler Efficiency of Project (new design HOB) [From study by the Technical University of Ulaanbaatar] MZ 1500 84.80% CARBON FINANCE in MONGOLIA 2011 Source: http://www.cdm-mongolia.com/files/final_carbon%20finance%20in%20mongolia_2011.pdf#searc h=%27carbon+finance+in+mongolia+2011%27 The document states that the average efficiencies of the baseline boilers are 40-50%, however, whether such values are based on the actual measurements or not is not stated. 1) Boiler Efficiency of Baseline (existing classic design HOB) Average efficiency: 40-50 % 2) Boiler Efficiency of Project (new design HOB) N/A Preliminary Market Assessment for Heat-Only Boilers in Mongolia Source: http://pdf.usaid.gov/pdf_docs/pnadc231.pdf The document states that the baseline boiler efficiencies as follows, however, whether such values are based on the actual measurements or not is not stated. 1) Boiler Efficiency of Baseline (existing classic design HOB) (< 100 kw) :20 40 % (100 500 kw) :35 50% (500 3 MW) :45 60 % (3 30 MW) :55 60 % 2) Boiler Efficiency of Project (new design HOB) New HOB (Mongolia) :55% (different type from the project HOB) 5

New HOB (Czech Republic) :75% New HOB (Austria) :85% 2.2.2 Results of the actual measurement of boiler efficiency Measurement of boiler efficiency was carried out to support the result of the research on the published documents to determine the default values of HOB boiler efficiencies. 1) Number of samples Measurement was conducted on five project type HOBs and five reference type HOBs. 1 In total, sample numbers are 16 for the project type HOBs and 20 for the reference type HOBs. The average monthly high/low temperature when HOB usually operates is shown in the table below. Since ambient temperature might be a factor to determine boiler efficiency, representative months have been chosen to measure boiler efficiency, which is October, November and December. It is anticipated that colder temperature will result in higher boiler efficiency, therefore, January is excluded from measurement samples. Table 2 Average Monthly Temperature in Ulaanbaatar Oct Nov Dec Jan Feb Mar Apr Average High Temp C 8.1-3.4-11.9-14.1-8.9-0.8 8.7 Average Low Temp C -4.6-14.4-21.6-25.0-21.6-13.8-5.2 [Source: World Meteorological Organization web site] 2) Measurement methods Theoretically, boiler efficiency can be derived from quantity of heat output divided by calorific input value. Thus, measurement was carried out on heat input and heat output of both project and reference type HOB. The value of heat input which is the total amount of heat supply is calculated by multiplying the amount of coal put into the HOBs and net calorific value of coal. The amount of coal put into the HOBs was measured using a certified spring scale, and net calorific value of coal was measured in the coal analysis. For the heat output which is the total amount of heat absorption in outlet hot water, the amount of heat supply was measured by verified heat meter or thermocouple and ultrasonic flow meter. 3) Measurement results of the project type HOB Table 3 shows measurement results of the project HOB, in which catalog value of the boiler 1 Feasibility/Demonstration Studies for New Mechanisms Project/Activities, Global Environment Centre Foundation http://gec.jp/main.nsf/en/activities-climate_change_mitigation-nmfsrepdb-list 6

efficiency is 80% or higher. Standard deviation has been analyzed for 12 measurement samples with a capacity of 0.10 MW 1.00 MW, which is the scope of the proposed methodology, and then 11 data are found to be within the range of two times of standard deviation (μ ± 2σ). The average value is calculated to be 61.0% by averaging those 11 data. Table 3 Actual measurement of boiler efficiency for the project HOB Boiler Measurement Measurement Boiler Type of Boiler Site No. Day equipment efficiency (%) P1 CARBOROBOT 180kW Oct. 30, 2012 60.7 P2 CARBOROBOT 180kW Oct. 31, 2012 63.1 79th school Heatmeter P3 CARBOROBOT 180kW Dec. 6, 2012 69.1 P4 CARBOROBOT 180kW Dec. 7, 2012 67.5 P5 CARBOROBOT 300kW Dec. 4, 2012 Thermocouple-type 64.5 P6 thermometer + 35th school CARBOROBOT 300kW Dec. 5, 2012 Ultrasonic Flowmeter 61.2 (TUF) P7 CARBOROBOT 180kW 79th school Nov. 18,2013 56.2 P8 CARBOROBOT 180kW 79th school Nov. 19,2013 57.0 P9 CARBOROBOT 180kW 79th school Nov. 27,2013 81.1 * Heatmeter P10 CARBOROBOT 180kW 79th school Nov. 28,2013 56.8 P11 CARBOROBOT 180kW 79th school Dec. 16, 2013 56.8 P12 CARBOROBOT 180kW 79th school Dec. 20, 2013 58.2 The average value of all data 62.6 The average value of data excluding one value (P9) which is not within the range of two times of standard deviation (μ ± 2σ) 61.0 * 81.1% is found to be not within the range of two times of standard deviation (μ ± 2σ). 4) Measurement results of reference HOBs Table 4 shows measurement results of the reference HOBs. Although the capacities of boilers measured are unknown because model numbers describing their specifications were missing for old type boilers, they are assumed to be below a capacity of 1 MW from sizes of their bodies and load of facilities which heat is supplied. It is also common in Mongolia that small capacity boilers are installed in parallel to cover large heat capacity and to continue to supply heat in case of emergency. 17 samples have been taken and those sample values fall into the range of 37.1% to 63.8%. To assess dispersion of 17 sample data, standard deviation has been analyzed, and then 16 data are found to be within the range of twice the standard deviation (μ ± 2σ). 7

Table 4 Actual measurement of boiler efficiency for the reference HOBs Boiler Type of Measurement Measurement Boiler Site No. Boiler Day equipment efficiency (%) R1 CLSG Dec. 11, 2012 53.4 Heatmeter R2 CLSG Dec. 19, 2012 42.8 TAVAN GAN TRADE LLC R3 CLSG Nov. 1, 2012 40.1 Thermocouple-type R4 CLSG Nov. 2, 2012 40.6 thermometer + R5 HP 87th school Dec. 7, 2012 49.6 Ultrasonic R6 HP Dec. 4, 2012 40.7 SEN-1 residence flowmeter (TUF) R7 HP Dec. 10, 2012 43.6 R8 HP 79th school Nov. 20, 2013 60.0 R9 HP 79th school Nov. 26, 2013 63.8 R10 HP 79th school Nov. 27, 2013 37.1 R11 HP 79th school Nov. 28, 2013 43.2 R12 HP 79th school Dec. 16, 2013 51.4 Heatmeter R13 HP 79th school Dec. 19, 2013 53.2 R14 HP 79th school Dec. 20, 2013 45.0 R15 CLSG TAVAN GAN TRADE LLC Nov. 28, 2013 54.0 R16 CLSG TAVAN GAN TRADE LLC Dec. 18, 2013 44.0 R17 CLSG TAVAN GAN TRADE LLC Dec. 23, 2013 50.9 The average value of all data 47.8 The average value of data excluding one value (R9) which is not within the range of two times of standard deviation (μ ± 2σ) The average value of data excluding one value (R9) which is not within the range of two times of standard deviation (μ ± 2σ), and excluding nine value (R2, R3, R4, R6, R7, R10, R11, R14, R16) which is less than the abovementioned average value (46.9) 46.9 53.3 2.2.3. Conclusion on energy efficiencies of HOB from the researches 1) Boiler efficiency for the reference type HOB It should be emphasized that catalog efficiency of boiler whose capacity ranges from 0.10 MW to 3.15 MW is no less than 75% since 2001, which is required by the Mongolian national standard, MNS 5043:2001, which implies; The existing old type boilers which may have lower boiler efficiency can be used continuously, however, Only boilers with catalog efficiency of no less than 75% can be newly installed. 8

Therefore, the vertical type HOB with catalog efficiency of no less than 75% is defined as the reference HOB. Although there are some published research results regarding boiler efficiency of HOBs in Mongolia, it is not clearly stated in those documents that sample boilers have catalog efficiency of no less than 75%, and whether the values are actually measured or taken from manufacturer s specification. Therefore, actual measurement of vertical type HOBs with catalog efficiency of no less than 75% shown in Table 4 are used to determine a default value of the boiler efficiency for reference HOBs. The average value is calculated excluding one data (63.8%) which is not within the range of two times of standard deviation. Accordingly, the average value is calculated to be 46.9% by averaging 16 data. Then, another average value is calculated excluding nine more data which is less than the average value calculated above to ensure conservativeness. The obtained value of 53.3% is regarded as a default value of the boiler efficiency for reference HOBs set in a conservative manner. The measured sample data from Proposed CDM new methodology:nm0144-rev can also be reliable since the data has been validated by DOE under the Kyoto Mechanism before being published on UNFCCC CDM website. 7 out of 16 samples shown in Table 5 meets the condition of HOB capacity scoped in the proposed methodology which is below 1.0 MW. The average value of those 7 samples is 51.0%. It should be noted that all sample boilers were installed before MNS 5043:2001 became effective, and catalog efficiency is not obtained, implying that these samples cannot be used as the boiler efficiency for reference HOBs according to its definition. Another reliable data can be derived from boiler efficiency values assumed in the registered CDM project, Ref.0295. The values fall into the range of 34.04% - 40.0% and are validated by DOE under the Kyoto Mechanism. As a result of comparing these data from there different sources, it is concluded that it is conservative to determine the boiler efficiency for reference HOBs as 53.3%, the highest value obtained in actual measurement and research on published information. Table 5 Measured data of baseline boiler efficiency under CDM Boiler No. Capacity of Baseline boiler (kw) Location Baseline boiler efficiency (%) 1 884 Ulaanbaatar 42.0 2 1,768 Ulaanbaatar 44.0 3 872 Ulaanbaatar 43.0 4 4,885 Ulaanbaatar 53.0 5 884 Ulaanbaatar 58.0 6 884 Ulaanbaatar 57.0 7 884 Ulaanbaatar 60.0 9

8 3,536 Ulaanbaatar 55.0 9 884 Ulaanbaatar 43.0 10 1,768 Ulaanbaatar 59.0 11 1,326 Ulaanbaatar 50.0 12 884 Ulaanbaatar 49.0 13 1,326 Ulaanbaatar 47.0 14 5,164 Ulaanbaatar 57.0 15 1,768 Ulaanbaatar 63.0 16 1,768 Ulaanbaatar 48.0 2) Boiler efficiency for the project type HOBs In addition to the fact that there is not enough data from published information to determine boiler efficiency for the project type HOBs, those values might as well be manufactures specification values which tend to be higher than actual performance of the boilers. Therefore, for the purpose of securing conservativeness of the methodology, the actual measured values are selected as the default value for project type HOB, which is, as explained in section 2.2.2, 61.0%. As such, the default value of the project type HOB is estimated to be much less than the values in the published documents. 10