Implementing a Reliable Leak Detection System on a Crude Oil Pipeline

Similar documents
Real Time Pipeline Leak Detection on Shell s North Western Ethylene Pipeline

Pipeline Leak Detection: The Esso Experience

6 th Pipeline Technology Conference 2011

SYNERGY IN LEAK DETECTION: COMBINING LEAK DETECTION TECHNOLOGIES THAT USE DIFFERENT PHYSICAL PRINCIPLES

RLDS - Remote LEAK DETECTION SYSTEM

SITRANS F. SITRANS FUG1010 Clamp-on Gas Flowmeters. Answers for industry.

ON-LINE SENSOR CALIBRATION MONITORING AND FAULT DETECTION FOR CHEMICAL PROCESSES

This paper will discuss the leak detection technologies that have been adapted to detect thefts and secure accurate tapping point locations.

Session Seven: Leak Detection and Fiscal Metering for Multi Product Pipelines A Case Study

USER APPROVAL OF SAFETY INSTRUMENTED SYSTEM DEVICES

Compression of Fins pipe and simple Heat pipe Using CFD

ENSC 388: Engineering Thermodynamics and Heat Transfer

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room

Architectural and Engineering Specification for a Fiber Optic Pipeline Integrity Monitoring System. FiberPatrol FP7000

Leak Detection. Ron Threlfall Manager, Leak Detection, Maintenance and Integration

Presented at 6 th Pipeline Technology Conference Hannover, Germany April 4-5, 2011

The New DUSTTRAK II and DRX Aerosol Monitors

Battery Performance Alert

Temperature Data Logging

The New DUSTTRAK II and DRX Aerosol Monitors

Audit/Twinning Report

Battery Performance Alert: A TOOL FOR IMPROVED PATIENT MANAGEMENT FOR DEVICES UNDER BATTERY ADVISORY

Improving Pipeline Integrity and Performance

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION

Optimizing Strategy for Boiler Drum Level Control

Certification Report of the ST3000 Pressure Transmitter

Failure Modes, Effects and Diagnostic Analysis

Certification Report of the ST 3000 Pressure Transmitter with HART 6

AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY

Substation Monitoring System

CHAPTER 2 EXPERIMENTAL APPARATUS AND PROCEDURES

D Implementation of a DEMO system related to Smart Fault Management in LV network (normal/storm conditions)

1 Introduction - The rating level. 3 Subjective or objective analysis? 2 Determination of the adjustment for annoying tones

How to Use Fire Risk Assessment Tools to Evaluate Performance Based Designs

Contamination Control for Electronic and Semiconductor Applications

Modeling and Simulation of Axial Fan Using CFD Hemant Kumawat

CFD Analysis of temperature dissipation from a hollow metallic pipe through circular fins using Ansys 14.5

Field Products. Experion LX. Proven DCS for a wide range of industrial applications

AN ANALYSIS OF THE PERFORMANCE OF RESIDENTIAL SMOKE DETECTION TECHNOLOGIES UTILIZING THE CONCEPT OF RELATIVE TIME

Session Ten Achieving Compliance in Hardware Fault Tolerance

Dryer Controller M720

AVOID CATASTROPHIC SITUATIONS: EXPERT FIRE AND GAS CONSULTANCY OPTIMIZES SAFETY

TESTS OF ADSIL COATING

Speed and Frequency Seite 1 von 7

EAT 212 SOIL MECHANICS

Improved Dryer Control

Substation Monitoring System

TSI AEROTRAK PORTABLE PARTICLE COUNTER MODEL 9110

FIRE & SAFETY SPRING 2016 EDITION

Module Features are-configurable, no module jumpers to set

HENRY GOMES Metering Consultant SGS Kuwait

Fiber Optic Pipeline Monitoring System Preventing and detecting leaks in real time

Theft Net. Already curtailing product theft on pipelines all over the world. Theft Net

Training Fees 4,000 US$ per participant for Public Training includes Materials/Handouts, tea/coffee breaks, refreshments & Buffet Lunch.

Important Considerations When Selecting a Fan for Forced Air Cooling. By: Jeff Smoot, CUI Inc

Safety Instrumented Systems

Standard ECMA th Edition - December Declared Noise Emission Values of Information Technology and Telecommunications Equipment

Practical Distributed Control Systems (DCS) for Engineers & Technicians. Contents

AUTROSAFE 4 A new level in interactive fire detection systems

OVEN INDUSTRIES, INC.

Off Design Operation of Hybrid Noncondensable Gas Removal Systems for Flash Steam Cycle Geothermal Power Plants

ClampOn DSP Corrosion- Erosion Monitor

Leak Detection & Pipeline Management Solutions

ICS Regent. Fire Detector Input Modules PD-6032 (T3419)

Connected Industrial. EC 350 PTZ GAS VOLUME CORRECTORS ENABLING PRECISION GAS MEASUREMENT Proven Technology. Superior Performance.

Final Report for work performed from July 1, 2008 to June 30, 2009

4th International Conference on Sensors, Measurement and Intelligent Materials (ICSMIM 2015)

DTW Master Specification Section EMCS: Start Up, Verification and Commissioning

Exercise 8. Controlling a Batch Mixing Process EXERCISE OBJECTIVE

PAMA PRODUCT PASTEURIZATION, HEATING AND COOLING SYSTEMS

A SURVEY OF OCCUPANT RESPONSE TOWARDS AN AUDIBLE FIRE ALARM

UL268 7 th challenge with single infrared smoke detector

MHC Series Sensors

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

Interfacing with the ADAM Module

Fiber Optic Cable Fence Disturbance Sensor

Advance Warning Flasher System at High Speed

DFE T ECHNOLOGY. At Conceptronic, the design and management process for reflow soldering systems is called Dynamic Flow Engineering, or DFE.

A Cost Effective Multi-Spectral Scanner for Natural Gas Detection

Centaur TM II Cube Slave Alarm Signalling Equipment INSTALLATION GUIDE

Functional Safety: the Next Edition of IEC 61511

PRODUCT CONFORMITY CERTIFICATE

Sensor Placement Algorithm for Rapid Theatre Assessment (SPARTA)

THE NEXT GENERATION IN VISIBILITY SENSORS OUTPERFORM BOTH TRADITIONAL TRANSMISSOMETERS AND FORWARD SCATTER SENSORS

EC 350 PTZ Gas Volume Correctors Enabling Precision Gas Measurement

TS400. Operating Manual. Test Station for Microtector II Series (G450/G460)

RaySense. Fiber Optic Distributed Vibration Sensing (DVS) for Pipeline Security and Leak Detection

Stability of Inclined Strip Anchors in Purely Cohesive Soil

Digitization For Long-Distance Oil Pipeline Leakage Detection. Liang Wei China University of Petroleum, Beijing

TECHNICAL SPECIFICATION

Benefits of Enhanced Event Analysis in. Mark Miller

Lesson 25 Analysis Of Complete Vapour Compression Refrigeration Systems

Smart Combiners Installation Guide. For Obvius A89DC-08 sensor modules

EC PARTS CERTIFICATE GB-1432

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

Application Note. Application Note for BAYEX

Study of Hot-air Recirculation around Off-road Tier-4 Diesel Engine Unit Using CFD Abbreviations Keywords Abstract Introduction and Background

Omnisens DITEST TM FIBER OPTIC DISTRIBUTED TEMPERATURE & STRAIN SENSING TECHNIQUE

Session Four Functional safety: the next edition of IEC Mirek Generowicz Engineering Manager, I&E Systems Pty Ltd

Transcription:

Implementing a Reliable Leak Detection System on a Crude Oil Pipeline By Dr Jun Zhang & Dr Enea Di Mauro* 1. Introduction Pipeline leak detection or integrity monitoring (PIM) systems have been applied to various operational pipelines. While most of the systems can meet the requirements for detecting leaks within a specified time period, they generate false alarms during normal pipeline operating conditions (API 1995, Mears 1993). Such false alarms reduce the confidence of pipeline operators in these systems and increase their maintenance costs. The operational experience of the statistical pipeline leak detection system in Shell (Zhang 1993, Zhang 1997) has demonstrated that the system can detect leaks quickly and it does not give nuisance alarms. This statistical system is trade marked as ATMOS PIPE by REL Instrumentation Limited. To overcome the difficulties of running a dynamic model-based leak detection system, Shell UK Limited has decided to have ATMOS PIPE installed for its crude oil pipeline. After giving some background of the pipeline (Section 2), the implementation of the system will be discussed in Section 3. Section 4 describes the principle of ATMOS PIPE and conclusions are given in Section 5. 2. Pipeline Description The pipeline is 23 Kilometres in length including chainage and has an average internal diameter of 24. Variations in diameter occur as the wall thickness changes with geographical location. Most sections of the pipeline are underground with one section in a tunnel under locks and three sections above ground (Figure 1). The pipeline is not insulated and it runs from a tank farm to a refinery. The pipeline is designed for bi-directional operation and all plant I/O is bi-directional. Crude oil is pumped in either direction in batches. The length of a batch varies between 4 and 20 hours depending on the delivery available. Between the batch transfers, sometimes there are long periods of shut-in when the pipeline is filled with the last batch of crude. Four pumps are used at the inlet and they are started in sequence. The crude density changes significantly from heavy Arabic crude to the light North Sea oil. In order to facilitate the heavy crude pumping, the oil is heated to reduce viscous friction or it is mixed with lighter crude. * REL Instrumentation Limited Armstrong House, Brancaster Road, Manchester M1 7 ED, UK Tel. 44-161-236 8001/228 3210 Fax 228 3211

Tank farm boundary Refinery boundary Tank Tunnel under lock Above ground Railway cutting (above ground) Canal (above ground) FIGURE 1 A SCHEMATIC DIAGRAM OF THE PIPELINE PROFILE The following measurements are available at the inlet and outlet of the pipeline: Volumetric flow, Pressure, Temperature and Density. A valve open/close indicator is also provided together with a flow direction indicator at each end. The field data are collected by dual DEC MicroVAX Computers, through a number of Remote Terminal Units (RTU) and a Microwave communication system. Since the instrumentation system was set up for the application of a dynamic model-based system to pipeline integrity monitoring (PIM) in 1991, the data were collected at 2 second intervals. Over the period 1995 and 1996, Shell experienced a lot of operational problems with the existing PIM system. For example, frequent false alarms were generated during pump start/stop and other transient periods. The VAX Computer also crashed sometimes. After trouble shooting with the existing PIM for several months, no satisfactory result has been achieved. Therefore Shell decided to have an additional PIM system installed and ATMOS PIPE was chosen in 1997. 3. Implementation of ATMOS PIPE 3.1 System Installation As shown in Figure 2, ATMOS PIPE can be installed in a Personal Computer (PC), which communicates with the existing VAX machine. Since the instrumentation system was already in place, the only additional hardware required was a PC and the cost to Shell was minimal. REL Instrumentation Limited Page 2

pressure flow flow pressure VAX ATMOS Pipe FIGURE 2 INSTALLATION REQUIREMENTS ATMOS PIPE was installed without any disruption to the pipeline operation or instrumentation system. A software interface was designed to allow ATMOS to read data from the VAX computer. Although data was available at 2-second intervals, a scan rate of 5 seconds was chosen for ATMOS. It was not necessary to sample at the faster rate since the pipeline dynamics were slow. Figure 3 shows the layout of the system. Since the existing equipment was already a few years old and it did not have any spare capacity for additional trending or alarm, new facilities would be provided together with ATMOS PIPE. SCADA Instruments RTUs VAX Alarm Port FIGURE 3 THE INTERFACE BETWEEN ATMOS AND OTHER SYSTEMS ATMOS PIPE runs in a PC with Windows NT operating system and a SCADA system and a digital card have been installed in the same PC. The SCADA is used for trends and user interface and the digital card for generating audible alarms in the control room. REL Instrumentation Limited Page 3

In trying to reduce the cost to the client and install ATMOS within the existing instrumentation environment, ATMOS had to interface with three separate systems: G VAX computer, G PC SCADA and G Alarm port. These interfaces were written based on the information provided by the individual suppliers. Significant project time has been consumed in making them work due to the following reasons: 1. Both the SCADA and the digital card suppliers have recently changed from Windows 3.1 to Windlows NT. The products were experiencing teething problems. 2. The SCADA software was not robust and it had quite a few outstanding bugs. 3. The software supplied for the digital card was not the correct version. 4. The VAX computer was loaded heavily, hence the communication between the PC and the VAX takes longer than expected. Note that interfacing with different software and equipment is a common practice in the oil and gas industry as most of them were installed for a long working life and upgrading frequently is costly and unnecessary. Unfortunately the continuous change in the PC and software does make it difficult for system integrators to bring all the data together. The time and effort involved for such integration are often underestimated. 3.2 Parameter Tuning To achieve a reliable and sensitive leak detection system, the statistical parameters are tuned based on normal operational data over a one year period. The tuning criteria used are as follows: 4. ATMOS will detect leaks of given sizes within the specified time limits. 5. No false alarm should be generated during the one year operation period. The main tuning parameters include: G Filter length and threshold values for data validation, G Leak sizes to be detected and the corresponding variance values, G Conditions for detecting pipeline transients automatically and setting the operating mode to steady state, medium transient and large transient. Since the system is designed and tuned for this particular pipeline, it learns about its pipeline operation and instrument performance specifically. No assumption has been made about the pipeline and once installed the system continues to learn about the pipeline e.g. an increase in the friction. This on-line learning capability is very important as pipeline operation always changes and instrument drift could occur over a long time period. The data validation function of ATMOS is an essential part of the system because in the real world the data collected by the instrumentation system is rarely perfect. For example, Figure 4 and Figure 5 show the inlet and outlet flow measurements over a period of REL Instrumentation Limited Page 4

FIGURE 4 INLET FLOW CHANGES AS THE PUMPS ARE SWITCHED ON AND OFF FIGURE 5 OUTLET FLOW FOLLOWS INLET FLOW CHANGES WITH MORE NOISES REL Instrumentation Limited Page 5

about 17 hours. Towards the end of this data collection period, the outlet flow readings become erratic. Such behaviour has been observed frequently during this period. After reporting this data fault to the client, further investigations have been carried out and the client found out that the electronics inside the outlet flow meter was not changed after the inlet flow meter electronics was updated. In general typical data faults detected are: G out of range data, G excessively noisy data, G outliers (sudden increase in the rate of change), G frozen data (no change at all for a certain time period) G inconsistent data (one measurement is within a different window from the others). When ATMOS identifies any of the above data faults, it will inform the operators of the fault type so that corrective actions can be taken. In the meantime, it continues the monitoring of the pipeline. However the leak detection response time is expected to increase as the system will be running in the degraded mode. For this crude oil pipeline, the expected detection time for sizes between 1% and 50% are given in Table 1. TABLE 1 THE AVERAGE LEAK DETECTION TIME ON THE CRUDE OIL LINE Leak size Average detection time 1% 7 min 2% 5 min 5% 3 min 10% 2 min 20% 2 min 30% 2 min 50% 2 min 3.3 Batch Tracking In addition to leak detection, a batch tracking function has been implemented for this pipeline. In order to discriminate different batches the crude average density has been used (Figure 6). The operator is provided at each scan with an automatic batch serial number, a log of the times of departure and estimated arrival, estimation of the crude volume delivered, calculation of the average density, estimation of the batch velocity and the current batch position within the pipeline. This information is displayed on a pipeline mimic window using a set of colour displays and a table displaying the numerical values (Figure 7). REL Instrumentation Limited Page 6

FIGURE 6 DENSITY CHANGES AS DIFFERENT BATCHES OF CRUDE ARE TRANSPORTED INLET OUTLET FIGURE 7 AN EXAMPLE OF BATCH TRACKING Hardcopy and logging facilities are provided. The algorithm used is a state transition machine whose initial entry stage is a full system flush. Operational conditions are taken REL Instrumentation Limited Page 7

into account to make the system more robust. Problems encountered included temperature variations between inlet and outlet (which affected density) and the width of the interface region between batches which seems to increase as it approaches the outlet, causing different gradients in the outlet density readings. 3.4 System Performance Statistics One added value of ATMOS PIPE is that it stores all the information it gathers and processes. For operator and client information, the following data are provided in the Executive Summary which is available both on line and off-line (using the event log file): G Operational status (steady state, small and large transient), G Line status (stopped, run forward, run reverse), G Data faults detected, G Alarm status (leak warnings, leak alarms), G Estimated pipeline resistance and G Average flow difference after pressure correction. Such information can be valuable to operators as a report on the performance of the pipeline, the instrumentation system and the loss monitoring system (Figure 8). 4. Description of ATMOS Pipe 4.1 Introduction ATMOS PIPE is a Trade Mark of the statistical pipeline integrity management system developed by Shell (Zhang 1993, Zhang 1997). It applies advanced statistical techniques to flow, pressure and temperature measurements of a pipeline. Variations generated by operational changes are registered and thus reliable system performance can be achieved through tuning of statistical parameters. ATMOS PIPE does not solve partial differential equations to calculate flow or pressure in a pipeline but it detects changes in the relationship between flow and pressure using measurement data available. Therefore no error is introduced by ATMOS PIPE itself and the computational requirement of the system is low. As the system monitors a pipeline continuously it learns about continual changes in the line and in the flow, pressure and temperature instruments. As long as the instruments continue to function correctly, variations in fluid properties e.g. composition change, will not present a problem to ATMOS PIPE. This is a major advantage of ATMOS PIPE. ATMOS PIPE has been developed by Shell following several years of research and field tests in pipeline leak detection. After its initial development, field tests have been performed on liquid propylene, ethylene gas and natural gas pipelines. During all of the tests, controlled pipeline leaks were created at different locations and the responses of the system were monitored closely. The minimum leak created was 0.5% and the maximum leak 55%. All leaks created during the field tests were detected and leak size and location estimates were given. REL Instrumentation Limited Page 8

The continuous monitoring of the above pipelines under leak-free operations showed that the system was truly reliable as no false alarm was generated. Having tested the system successfully, Shell decided to commercialise the system through REL Instrumentation Limited. In the following sections, the system design is discussed. EventLogFile.txt 24/08/98 17:00:15 01/10/98 12:00:15 1 0 56.2% 22.7% 21.1% 64.0% 0.0% 36.0% 0.14 10.172 0 0 1 0 0 0 0 10 0 3 0 2 2 0 1 0 0 3 0 0 0 0 1 0 FIGURE 8 AN EXAMPLE OF THE SYSTEM PERFORMANCE STATISTICS REL Instrumentation Limited Page 9

4.2 The Leak Detection Algorithm ATMOS PIPE applies statistical techniques to detect changes in the overall behaviour of flow and pressure at the ingress and egress points. Although the control and operation may vary from one pipeline to another, the relationship between the pipeline pressure and flow will always change after a leak develops in a pipeline. For example, a leak could cause the pipeline pressure to decrease and introduce a discrepancy between the ingress and egress flow-rate. The leak detection system is designed to detect such changes i.e. pattern recognition. Leak determination is based on probability calculations at regular sample intervals. The basic principle used for the probability calculations is mass conservation and hypothesis testing: leak against no-leak. Although the flow and pressure in a pipeline fluctuate due to operational changes, statistically the total mass entering and leaving a network must be balanced by the inventory variation inside the network. Such a balance cannot be maintained if a leak occurs in a network. The deviation from the established balance is detected by an optimal statistical test method - Sequential Probability Ratio Test (SPRT). The combination of the probability calculations and pattern recognition provides ATMOS with a very high level of system reliability i.e. minimum spurious alarm rate. Under leak-free operations, the mass balance principle determines that the difference between the ingress and egress flow-rate should be equal to the inventory variation in a pipeline. Therefore the following term is calculated: M N L i o 1 1 1 τ ( t) = Q() t Q () t Q () t (1) where τ(t) is called the corrected flow difference term at time t. In practice τ(t) usually fluctuates around a non-zero value due both to the inherent differences in the instruments and fluid compressibility. Q i (t) represents the flow measurement at the ingress points and Q o (t) at the egress points. M is the number of ingress points, N the number of egress points and L is the number of pipeline sections. Q j (t) is a correction term for the inventory variation over the sample period of t-1 to t. Q j (t) is a function of pressure and temperature in the pipeline. Different product types in the network will introduce changes in the inventory calculations. The mean value of the above process τ(t) remains unchanged unless a leak develops in a pipeline or an instrument error occurs. The distinction between these two failure modes has to be made by further analysis, e.g. instrument change pattern identification. ATMOS PIPE can identify typical instrument faults thus informing operators of possible faulty instruments. To detect leaks efficiently with a low false alarm rate, SPRT will be used to decide between the leak-free and leak-present hypotheses, e.g. j REL Instrumentation Limited Page 10

H 0 : τ(t) is gaussian with mean m and variance σ 2 H 1 : τ(t) is gaussian with mean m+ m and variance σ 2 where m represents the mean value of τ(t) under normal (leak-free) operations and m is a parameter determined by the leak size to be detected. To take into account of instrument drifts over time, m is tuned slowly using measurements available during no leak alarm period. The value σ 2 depends on the fluctuations of the flow and pressure signals in a pipeline. For changing operating conditions in the pipeline, different values of σ 2 will be used. Usually three operating modes are identified automatically in a pipeline: Steady state operation, operating status = 0, Medium operational change, operating status = 1, Large operational change, operating status = 2. After a large operational change, it will take longer for ATMOS to detect a leak than during steady state operations. The choice of the different σ 2 values is determined to achieve maximum system reliability, without loss of leak detection functionality. The SPRT for testing hypothesis H 1 against H 0 is transformed to the calculation of the following cumulative sum: m m λ( t) = λ( t 1) + ( τ( t ) m ) 2 σ 2 (2) By comparing the on-line calculated value λ(t) with a pre-set threshold value, a leak alarm can be generated. After a leak is detected, the leak rate is estimated by subtracting the on-line updated value m from the average value of τ(t) shown in equation (1). One key feature of ATMOS PIPE is that it has learning capability, e.g. operational changes introduced after the installation will be used to further tune the system and gradual instrument drift is incorporated for eliminating false alarms. The reliability of the system will improve after it has the opportunity to experience different operational changes: start up, shut down, valve opening. 4.3 Factors Affecting ATMOS Pipe Performance Note that the quality of field instruments for flow, pressure, temperature measurements is very important for pipeline integrity monitoring. According to the definitions given by the Scientific Apparatus Makers Association Standard, instrument accuracy determines the maximum measurement error, repeatability represents the consistency of measurement results and resolution determines the minimum change an instrument can sense. For pipeline monitoring the above three qualities are of varying importance for ATMOS PIPE: REL Instrumentation Limited Page 11

Instrument resolution determines the minimum leak detectable by any system based on field measurements. If the resolution of flow and pressure meters is 0.1%, for example, it is impossible to use these meters to detect a leak smaller than 0.1%. Instrument repeatability is critical in determining leak detection reliability. If it is required to detect a leak of a magnitude equal to or smaller than the instrument repeatability, then false alarms will be generated. Since ATMOS PIPE detects relative changes in the mean value of the corrected flow difference term, known instrument errors are accepted as normal discrepancy between the instruments assuming no leak is present when the system is first installed. Therefore it is possible for ATMOS PIPE to detect a leak smaller than the instrument errors. Previous field tests have shown that ATMOS PIPE detected a leak of 0.5% while the flow accuracy was 1%. Note that SCADA (Supervisory Control And Data Acquisition) systems can reduce measurement resolutions if the Analogue to Digital (AD) converters are not selected properly. To maintain a high resolution level, it is recommended to use 16 bit AD converters. 5. Conclusions The application of ATMOS PIPE to the crude oil pipeline illustrates that it can detect leaks quickly while remaining reliable during normal operating conditions. Reverse flow, batch start and stop, changes in the crude grade and pump on/off switches have presented no problem to ATMOS. Since ATMOS PIPE has been installed within the existing instrumentation and data collection system, the only cost incurred is for the software design and a Personal Computer. However interfacing with different systems has proven to be a time consuming exercise because the SCADA system and digital card specified by the client were having teething problems after upgrading to Windows NT Operating System. Where possible, REL Instrumentation Limited strongly recommends the use of mature systems particularly as computer hardware and software changes take place so quickly that they are not always tested fully before their release to end users. Acknowledgement This paper is published with the kind permission of Shell UK Limited, which is greatly appreciated. References API, 1995. Evaluation Methodology for Software Based Leak Detection Systems, API Publication 1155. M.N. Mears, 1993. Real World Applications of Pipeline Leak Detection, Pipeline Infrastructure II, Proc. Int. Conf. ASCE. X.J. Zhang, 1993. Statistical Leak Detection in Gas and Liquid Pipelines. Pipes & Pipelines International, July-August, p26-29. X.J. Zhang, 1997. Designing a Cost-effective and Reliable Pipeline Leak Detection System, Pipes & Pipelines International, January-February, p20-26. REL Instrumentation Limited Page 12