Installation Methods for HBX Sensors

Similar documents
Optimization of key processes in a refrigeration system. For maximum cooling load there was an EER increase of 18,6% (EER = Energy efficiency Ratio).

Technical Paper New Refrigerant Quality Measurement and Demand Defrost Methods

Air-Cooling Evaporators

APPLICATION and INSTALLATION

for Valve Types P-H-M-V-W-D-A

Phillips. HORIZONTAL AND VERTICAL ASSEMBLIES For Ammonia (R-717) and Halocarbon Refrigerants

Midea VFD Centrifugal Chiller Technology

PURGER INSTALLATION AND OPERATION BULLETIN PUR-SB17-02 SERVICE BULLETIN

Experimental and Numerical Study on the Performance of R410A Liquid Recirculation Cycles with and without Ejectors

REDUCING AMMONIA REFRIGERANT CHARGE IN SKATING RINK REFRIGERATION SYSTEMS

COLD STORAGE WAREHOUSE, USING DIRECT EXPANSION AMMONIA REFRIGERANT Ray Clarke ISECO Consulting Services Pty Ltd

Thermostatic expansion valves for ammonia Type TEA

Zero Superheat Control

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

Best Practices for DX Piping. Greg Drensky Jacco & Associates

Back to basics. Setting HEVs for Liquid Overfed Evaporators. 13 th Annual IRC R&T Forum May 8-9, 2013

CO 2 EVAPORATOR DESIGN

Intermediate Refrigeration Systems for Operators

Suction Accumulators. Introduction. Suction Accumulators

Refrigeration System Overview. ASTI 32 Hour Managing Ammonia Course September 27 30, 2016

Bulletin , March Electric Hot Gas Bypass Valves

AIC Brazed Plate Heat Exchanger Operating and Instruction Manual

Environmentally friendly refrigeration systems for industrial use

November 2006 / BULLETIN ELECTRIC DISCHARGE BYPASS VALVES

Suction Line Accumulators

RDT Refrigeration Book


SIGMAWIG ALL WELDED PLATE HEAT EXCHANGERS

SB Series Brazed Plate Heat Exchanger Installation Manual

REFRIGERANT PIPING

Air Conditioning Clinic. Refrigerant Piping One of the Fundamental Series TRG-TRC006-EN

INSTANT CHILLER. Chester-Jensen Co., Inc. Unit Construction and Short Gas Flow

XSTREAM Valve System With A.R.M.E.D. Technology Service & Installation Instructions Page 1

Evaporators. Direct Expansion Flooded Recirculated Over Feed

Incident Summary #II (#9286) (FINAL)

Salinas Valley Ammonia Safety Day. May 26, 2011 Salinas, CA

STC Series Twin Unit Coolers (E329630_A)

A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems.

Selection and Operational Considerations. Harold Streicher, Vice President Sales Hansen Technologies, Inc.

Warm Case Troubleshooting Guide 9/18/2014

THERMOSTATIC EXPANSION VALVES Part 1

HEAT EXCHANGERS Maximize Thermal Efficiency with LaZerWeld Plate Heat Exchangers. For Industrial Refrigeration

Analysis of Constant Pressure and Constant Area Mixing Ejector Expansion Refrigeration System using R-1270 as Refrigerant

Low Charge ADX Ammonia. Presented by: Bruce Nelson, President, Colmac Coil Manufacturing Rick Watters, Vice President, AMS Mechanical Systems

COOLING / HEATING COILS

IQF freezers FLOFREEZ A Our newest member of the Frigoscandia freezer product line

Brazed Plate Heat Exchanger

CO2 TRANSCRITICAL BOOSTER SYSTEMS

ICEU 36 SPARE PARTS LIST REV. 07/2016

Installation, Operation, and Maintenance Information

LOW RECIRCULATION RATE EVAPORATORS

Applying the Frick Low Charge Central System to a New Freezer/Cooler Facility

Series 11, Ceiling Units

Ratio Architects, Inc. Section Refrigerant Piping

Refrigeration System with a Capillary Tube and a Thermostat

GEM TRAP FITTING & MAINTENANCE INSTRUCTIONS

Condensing Unit Installation and Operating Instructions

Technical Paper #2. Refrigeration Piping: A Simplified Guide to a Modern Approach

MYSTICOOL Max Valve System with Xstream and A.R.M.E.D. Technology Service & Installation Instructions Page 1

Industrial Refrigeration Defrost Solutions TM Package. Brochure R-222

Typical Piping Diagram

SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES 3/22/2012 REFRIGERATION

Spare Parts Catalogue AC176

REFRIGERANT PIPING INTRODUCTION

REFRIGERATION SUPPLY. A company of Bayer and LANXESS

TURBOIL (welded) / TURBOIL-F (flanged)

InterSeptor Centrifugal Separators Operating & Maintenance Manual

Instructors: Contact information. Don Reynolds Doug McGee Factory Tech Support

Service Step by Step Trouble-Shooting Check-List

INSTRUCTIONS FOR USE PORTABLE VACUUM SYSTEM LEI Part # s / , , , IMPORTANT INFORMATION

D-11 OUTLINE SPECIFICATION FOR HTHW (ABOVE GRADE) HYDRONIC PIPING

Investigation of Evaporator Performance with and without Liquid Overfeeding

Operating Instructions for Fristam Powder Mixer

280 SERIES STEAM CONVERTING VALVE SIZING AND SELECTION. 1. Introduction Design Properties Sizing and Selection Criteria...

Refrigeration and Air Conditioning Mechanic (Residential) Level 2

Commercial Refrigeration

Brazed Plate Heat Exchanger

ParaWeld Plate Heat Exchangers

Development of Gas-Liquid Two-Phase Flow Distributor for Improving Energy Efficiency in Air-Conditioners

Performance Comparison of Ejector Expansion Refrigeration Cycle with Throttled Expansion Cycle Using R-170 as Refrigerant

4201 Lien Rd Madison, WI Owner s Manual Therma-Stor III Heat Recovery System. Installation, Operation & Service Instructions

Refrigeration Systems

Steam Injection Humidifiers for use with steam boilers PR0DUCT CATALOG

Optimization of Cooling Systems

Experiment 2: Test on Domestic Refrigerator for evaluation of EER.

Emerging Technologies: VFDs for Condensers. Douglas T. Reindl Director, IRC University of Wisconsin-Madison. University of Wisconsin-Madison

Refrigerants Type Expensive Coefficient of Performance Toxic

SECTION (15530) - REFRIGERANT PIPING

UNIT PANELS 6/25/2014 9:02:04 AM Page 2 of 23

Troubleshooting(TC32G)

Thermodynamics I. Refrigeration and Heat Pump Cycles

OIL MIGRATION IN R-12 & R-22 SYSTEMS By: Norman Sharpe Professor, Air Conditioning & Refrigeration Dept., California State Polytechni College

Brazed Plate Heat Exchangers TTP s Series

ParaWeld Plate Heat Exchangers

Chapter-8 Capacity Control of Refrigeration Systems

OPEN TYPE MILK COOLING TANKS

NABTEB Past Questions and Answers - Uploaded online

Condensing Unit Installation and Operating Instructions

PRICE CHOPPER SARATOGA, NY. First cascade supermarket system in North America Installed and Started March of 2008

MDX² INSTALLATION MANUAL

Transcription:

Installation Methods for HBX Sensors New Sensor Technologies Control Phase of Refrigerant, which make Ammonia more Safe and Optimize all Types of Refrigeration Systems Works with NH3, CO2, Propan & HFC/HFO Refrigerant Next Generation of HBX Vapor Quality Sensors with both Integrated Sensor-, Evaporator- and Remote Control Feature are now ready to Optimize all Types of Evaporators Patent No.: US 9,587,866 B2 Optimization of key processes in a refrigeration system HBX installation methods_03 240518 page 1

Recommended installation methods DX-Evaporator Control OVC- Recirkulation Control Compressor Protection Recommended for DX Control: HBX-DX-R, 3/4, L160 & L300 Sensor length acc. To the pipe size < DN 80, L160 > DN 80, L300 Recommended for Overfed Control: HBX-OVC, R 1,L300, pipe size >DN100 HBX-OVC, 3/4, L160, pipe size <DN80 HBX-OVC, 3/4, L300, pipe size >DN80 FLOW Slope min. 1grd. NOTE: Slope the piping to ensure the liquid can flow freely. This reduces the risk of submerging (drowning) the sensor in liquid. Flow pattern in two-phase flow varies depending on the evaporator load, type of refrigerant, tube diameter, Vapor Quality, mass flux and flow orientation. All refrigerant types will usually have a stratified two phase flow pattern in horizontal pipes and in part load often slug or plug flow in rising pipes. Installation: 1. The sensitivity of the sensor depends on several parameters. Most important is that the sensor is installed in a position where it can catch the liquid and drops at any two-phase flow regime and gas velocity. Especially at DX regulation we recommend that the HBDX-rod style sensor is installed in countercurrent flow direction, with gas velocity range from 10 to 30m/s. 2. Inline type, we recommend that the sensor is installed in horizontal pipes, alternative downwards. (Sensor in the same size as the suction line). 3. Rod style, we recommend that the sensor is installed in horizontal pipes with the position at the bottom of the inside walls to ensure that the liquid is flowing into the sensor in the bottom of the pipe. Counter Flow direction is recommended for DX evaporator Control Flow direction is recommended for Recirkulation/Overfed Control 4. Compressor Protection sensors can be installed in any directions, with optimum location in accordance to the liquid and gas flow. 5. The sensor must be installed so that the active sensor part is inside the suction pipe/line, the threaded bush/socket must not be longer than the blind part of the sensor. For longer welded sockets, the sensor part should be installed with additional PTFE bushing. HBX installation methods_03 240518 page 2

DX-evaporator/aircooler Installation of HBX in a strainer The pipe should be designed with a P-trap/drop-leg to avoid liquid accumulation around the sensor Installation of HBX in a strainer Plate-heat exchanger The pipe should be designed with a P-trap/drop-leg to avoid liquid accumulation around the sensor HBX installation methods_03 240518 page 3

HBX Installation methods Installation of HBX- OVC sensor in a Tee Slope piping Riser Riser Freezer Liquid fed valve Vapor Quality Sensor installed in the outlet of an evaporator optimizes the entire system and makes it possible to control and limit the amount of refrigerant in the system under all conditions. In particular, it is important to control the refrigerant feed during part load operation to obtain an optimal flow pattern with homogeneous vapor Quality during evaporation. Reduced pipe size DX evaporator HBX installation methods_03 240518 page 4

HBX Installation methods Recommended sensor type: DX Control: Installation in strainer HBX-DX-R, 3/4, L160 pipe size <DN80 HBX-DX-R, 3/4, L300 pipe size > DN80 Overfeed Control, OVC: HBX-OVC-R 1,L300, pipe size >DN100 HBX-OVC-R-3/4, L160, pipe size <DN80 Must flush the pipe bottom HBX-OVC-R-3/4, L300, pipe size >DN80 Note: R-1" sensor should be used for the circulation rate > 1.5. Flow from the evaporator outlet The riser pipe should be designed with a P-trap to avoid liquid accumulation around the sensor Slope piping to ensure that the liquid flows freely and the risk of submerging (drowning) the sensor in liquid is minimized. Flow from the evaporator outlet Vapor Quality Sensor installed in the outlet of an evaporator optimizes the entire system and makes it possible to control and limit the amount of refrigerant in the system under all conditions. In particular, it is important to control the refrigerant feed during part load operation to obtain an optimal flow pattern with homogeneous vapor Quality during evaporation. HBX installation methods_03 240518 page 5

Flow from the evaporator outlet HBX Installation methods Recommended sensor type: DX Control: HBX-DX-R, 3/4, L160 pipe size <DN80 HBX-DX-R, 3/4, L300 pipe size > DN80 Overfeed Control, OVC: HBX-OVC-R 1,L300, pipe size >DN100 Installation of HBX- DX/OVC-R sensor HBX-OVC-R-3/4, L160, pipe size <DN80 HBX-OVC-R-3/4, L300, pipe size >DN80 Note: R-1" sensor should be used for the circulation rate > 1.5. Slope piping to ensure that the liquid flows freely and the risk of submerging (drowning) the sensor in liquid is minimized. Min. 100mm Must flush with the pipe bottom Threaded Elbolet socket and welding instructions can be delivered to all pipe sizes. Note: With longer welded socket should the sensor part be installed with additional PTFE bushing. HBX installation methods_03 240518 page 6

ROD STYLE IN-LINE HBX installation methods_03 240518 page 7