Table OUT OF SERVICE. Building Fire Video 1/15/ Inspection, testing and maintenance. Standards Further Referenced by FCNYS

Similar documents
Subject: Fire Protection Impairment Program Reference: NFPA (see bottom of page 5) Effective Date: August 2014 Distribution All YC Employees

Fire System Impairment Policy

UNIVERSITY. Facilities Management

Chapter 4: Fire Protection Systems

I. Scope: II. Environmental Health and Safety Fire Alarm System Impairment Program - Guideline Revision Date: April, 2018

Risk Management Services

Date Issued: December 14, 2017 Revision: 2.1

2010 FIRE CODE OF NEW YORK STATE

Iowa State Fire Marshal

Impairments to Fire Protection Equipment

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

UC Irvine Environmental Health & Safety TITLE: FIRE WATCH AND OUT OF SERVICE NOTIFICATION

OXNARD FIRE DEPARTMENT Fire Watch Guidelines

Understanding, Applying and Enforcing NFPA 25. James D. Lake NFSA Director of Training

UNIVERSITY OF ROCHESTER ENVIRONMENTAL HEALTH & SAFETY

B. The Facility Emergency Planners and Alternate Planners will successfully complete the in-house DJJ Fire Prevention course.

Fire Watch Program. Building Administrators Building Administrators will inform building occupants about fire watch events and building evacuations.

Fire Protection System Contractors and Systems. Submission of the Application for a Water-Based Fire Protection Inspector

Written Fire Safety Plans

BUILDING INSPECTION SAFETY PROGRAM MANUAL CHAPTER 5, REFERENCE # 1.4 August 1, 2009 OUT OF SERVICE (OOS) SPRINKLER AND STANDPIPE SYSTEMS

Fire Protection System Contractors and Systems. Submission of the Application for a Water-Based Fire Protection Inspector Permit

DUQUESNE UNIVERSITY. Fire Protection System Impairment Program (Red etag Permit)

CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS

Management Practices: Fire Protection Impairments November 2015

FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION

TEN STEP PROCESS PREPARING FIRE SAFETY PLANS

ICC CODE CORNER 2015 International Fire Code

UNIVERSITY OF TOLEDO

PRINTED: 06/09/2017 FORM APPROVED CENTERS FOR MEDICARE & MEDICAID SERVICES OMB NO (X2) MULTIPLE CONSTRUCTION A. BUILDING 03 - A BUILDING

Interim Life Safety Measures. Healthcare Construction Certificate - Level 1

DEPARTMENTAL GUIDELINES CHAPTER 6 TACTICAL OPERATIONS

National Fire Protection Association. 1 Batterymarch Park, Quincy, MA Phone: Fax:

SURREY FIRE SERVICE. Construction Fire Safety Plan Bulletin

Cedar Hammock Fire Rescue Standard Operational Guidelines FIRE WATCH. General. Requirements for a Fire Watch

Agency for Health Care Administration

EMERGENCY PLANNING AND PREPAREDNESS

EMERGENCY PLANNING AND PREPAREDNESS

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Fire & Life Safety Practices. Hospitals. Revised 7/2010

For additional information please contact the Chesapeake Fire Prevention Office at or at

1301: Fire protection systems.

Center for Life Safety Education

JEFFERSON COUNTY PUBLIC SCHOOLS FIRE WATCH PROGRAM

NY Fire Safety Institute Coordinator of Fire Safety & Alarm Systems F-80

STATE FIRE MARSHAL S REQUIRED FIRE PROTECTION SYSTEMS NARRATIVE REPORT

RULES OF DEPARTMENT OF COMMERCE AND INSURANCE DIVISION OF FIRE PREVENTION CHAPTER FIRE PROTECTION SPRINKLER SYSTEM CONTRACTORS

EC 5.10 FIRE PREVENTION MANAGEMENT

Understanding and Applying NFPA 25

Fire Protection System Impairment Procedure

1301: Fire protection systems. (A) Section 901 General

Report on First Revision June 2014 NFPA 5000

Fire & Life Safety Practices

Public Notice of Amendment to New Shoreham General Ordinances Chapter 5 Fire Prevention and Protection New Article IV Fire Alarm Ordinance

1.2 To ensure the safety of all persons working in or occupying a building where a hot work operation is performed.

A Comprehensive Community Risk Reduction Initiative A COMPREHENSIVE COMMUNITY RISK REDUCTION INITIATIVE

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

Western Michigan University Facilities Management Engineering Division

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

FIRE SAFETY PLAN FOR CONSTRUCTION, RENOVATION AND DEMOLITION SITES

1301: Fire protection systems. Section 901 General

Austin Independent School District Police Department Policy and Procedure Manual

SACRAMENTO FIRE DEPARTMENT FIRE PREVENTION DIVISION FIRE DEPARTMENT DEVELOPMENT SERVICES UNIT CONTRATOR INFORMATION PACKET

Purpose: To establish procedures for identifying fire hazards and preventing fires. Scope: All Central New Mexico Community College (CNM) Community.

CAMPUS COMMUNITY FIRE AND LIFE SAFETY POLICY

Fire & Life Safety Practices

Safe Operating Procedure

a) Establishment of emergency procedures to be followed at the time of an emergency;

Emergency Planning and Preparedness

Rocky Mountain Fire Protection District 4390 Eldorado Springs Drive Boulder, CO

Alarm. A warning of danger. An indication of the existence of a condition that requires immediate action. (SIG-FUN)

OUTLINE FOR FIRE PREVENTION ACTIVITY

BURN NOTICE: KEEP THE HEAT AWAY!

Black Diamond Fire Department Building Owner s Responsibilities for Fire Safety Equipment


Managing Fire Protection System Impairment

CHAPTER LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE, 2000 EDITION SECTIONS

Other EC and LS documents may be requested by surveyors, as needed, throughout the survey.

RISK ENGINEERING GUIDELINE.

Fire Prevention Plan

Narrative Reports As Regulated by 780 CMR, Section 903.0

GUIDELINES FOR EMERGENCY PLANNING AND PREPAREDNESS. High-Hazard

Nova Scotia Fire Dispatch Minimum Standards (2017)

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

FIRE SAFETY AND EVACUATION PLANNING FOR ASSISTED LIVING FACILITIES AND NURSING HOMES

New Facilities. Minimum Requirements

Training Toolbox Series. ICA11v1.0 Information, Digital Media & Technology

Danilo B. Concepcion, CBNT, CCHT-A Operations Manager St. Joseph Hospital Renal Services

This policy may also be used for routine work orders that are Life Safety in nature and cannot be completed within 45-days.

HAWAII ADMINISTRATIVE RULES TITLE 12 DEPARTMENT OF LABOR AND INDUSTRIAL RELATIONS SUBTITLE 7 BOARDS CHAPTER 45.1 STATE FIRE COUNCIL STATE FIRE CODE

DEPARTMENT OF PUBLIC SAFETY DIVISION OF FIRE PREVENTION AND CONTROL

South Elgin & Countryside Fire Protection District

Onsite Fire Risk Reduction Methods

The Technical Committee on Commissioning and Integrated Testing

CHAPTER 5. FIRE DEPARTMENT AND FIRE PREVENTION (Repealed and Recreated Ordinance # /6/08) SUBCHAPTER I: FIRE DEPARTMENT 5-1

Winnipeg Fire Department Fire Prevention Branch

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

Builders Risk - Fire Prevention Inspection Checklist

MNEC NFPA 72 WHITE PAPER

SECTION SECURITY TESTING AND COMMISSIONING

POLICY NUMBER ISSUE DATE REVISED DATE REVIEW DATE

Transcription:

901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. OUT OF SERVICE Building Fire Video Standards Further Referenced by FCNYS FCNYS 901.6.1 Fire protection systems shall be inspected, tested and maintained in accordance with the referenced standards listed below: Table 901.6.1 Fire Protection System Maintenance Standards SYSTEM STANDARD Portable fire extinguishers NFPA 10 CO2 Extinguishing NFPA 12 Halon 1301 Extinguishing NFPA 12A Dry-chemical Extinguishing NFPA 17 Wet-chemical Extinguishing NFPA 17A Water-based fire protection Fire Alarm System Water-mist system NFPA 750 Clean-agent extinguishing NFPA 2001 5 1

Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems National Fire Alarm Code Fire Alarm System 2007 Edition 2008 Edition F901.7 Systems out of service Where a required fire protection system is out of service, the fire department and the code enforcement official shall be notified immediately and, where required by the code enforcement official, F901.7 Systems out of service the building shall either be evacuated or an approved fire watch shall be provided for all occupants left unprotected by the shut down until the fire protection system has been returned to service. Fire Code of New York State Does not discuss a time period (i.e. after 4 hours) for implementing fire watch or other protective measures. Instead requires fire code official to make decision on what is required (i.e. fire watch) immediately. FIRE WATCH REQUIREMENTS Office Building 2

IFC 901.7 2006 Fire Code Commentary The protection afforded by a required fire protection system must not be diminished in any existing building except for the purpose of conducting tests, maintenance or repairs. The length of service interruptions must be kept to a minimum. The fire department and the fire code official must be notified of any service interruptions. IFC 901.7 2006 Fire Code Commentary They must carefully evaluate the continued operation or occupancy of buildings and structures where protection is interrupted. Whenever possible, all unaffected portions of the system should be kept in service. Until protection is restored, hazardous processes or operations should be suspended and alternative special protection should be considered in addition to an approved fire watch. IFC 901.7 2006 Fire Code Commentary The code text only addresses when a required system is placed out of service. However, if a system is in place, even though it is not required by the code or the IBC, it would be an appropriate courtesy to the fire department to inform it of the discontinuance or temporarily taking out of service of any fire protection system. IFC 901.7 2006 Fire Code Commentary If the nonrequired system is to be placed out of service for an extended period of time, the fire code official has the authority to address the condition under Section 901.4.4 and require that the system be either placed back into operation or removed so as not to create a false impression of protection. F901.7 Systems out of service Where utilized, fire watches shall be provided with at least one approved means for notification of the fire department and their only duty shall be to perform constant patrols of the protected premises and keep watch for fires. Exception: F901.7 Systems out of service The code enforcement official is permitted to waive the requirement for evacuation or a fire watch where there is not a substantial risk to life safety or where alternatives to maintain an equivalent level of safety are prescribed. 3

F901.7.1 Impairment coordinator The building owner shall assign an impairment coordinator to comply with the requirements of this section. Impairment Coordinator Impairment Coordinator is the person who manages the impairment while system work is being performed. In the absence of a specific designee, the owner shall be considered the impairment coordinator. Chapter 4 General Requirements 4.1 Responsibility of the Property Owner or Occupant. 4.1.3 Notification of System Shutdown. The property owner or occupant shall notify the authority having jurisdiction, the fire department, if required, and the alarm-receiving facility before testing or shutting down a system or its supply. 4.1.3.1 The notification of system shutdown shall include the purpose for the shutdown, the system or component involved, and the estimated time of shutdown. 4.1.3.2 The authority having jurisdiction, the fire department, and the alarm-receiving facility shall be notified when the system, supply, or component is returned to service. 4.1.4* Corrections and Repairs. The property owner or occupant shall promptly correct or repair deficiencies, damaged parts, or impairments found while performing the inspection, test, and maintenance requirements of this standard. 4.1.4.1* Corrections and repairs shall be performed by qualified maintenance personnel or a qualified contractor. qualified maintenance personnel or a qualified contractor. Qualified Having knowledge of the installation, construction, or operation of apparatus and the hazards involved. 4

15.4 Impaired Equipment. 15.4.1 The impaired equipment shall be considered to be the water-based fire protection system, or part thereof, that is removed from service. 15.4.2 The impaired equipment shall include, but shall not be limited to, the following: (1) Sprinkler systems (2) Standpipe systems (3) Fire hose systems (4) Underground fire service mains (5) Fire pumps (6) Water storage tanks (7) Water spray fixed systems (8) Foam-water systems (9) Fire service control valves 15.5.2 Before authorization is given, the impairment coordinator shall be responsible for verifying that the following procedures have been implemented: (1) The extent and expected duration of the impairment have been determined. (2) The areas or buildings involved have been inspected and the increased risks determined. (3) Recommendations have been submitted to management or the property owner/manager. Where a required fire protection system is out of service for more than 10 hours in a 24-hour period, the impairment coordinator shall arrange for one of the following: (a) Evacuation of the building or portion of the building affected by the system out of service (b)* An approved fire watch (c)* Establishment of a temporary water supply (d)* Establishment and implementation of an approved program to eliminate potential ignition sources and limit the amount of fuel available to the fire. National Fire Alarm Code 2007 edition 5

Code Section 4.6.1 requires the contractor to notify the system owner or representative when a fire alarm is impaired. And impairments include out-of-service events. Another important code requirement that contractors must address with owners is that an impairment record must be maintained by the system owner or their designated representative for a period of one year from the correction date. When a fire alarm system is out of service, -2007, section 4.6.3 requires mitigating measures acceptable to the AHJ be implemented for the period that the system is impaired. The AHJ typically determines the need for mitigating measures on a case-by-case basis. The Life Safety Code Section 9.6.1.6 Where a required fire alarm system is out of service for more than four hours in a 24-hour period, the authority having jurisdiction [AHJ] shall be notified, and the building shall be evacuated or an approved fire watch shall be provided for all parties left unprotected by the shutdown until the fire alarm system has been returned to service. F901.7.2 Tag required A tag shall be used to indicate that a system, or portion thereof, has been removed from service. F901.7.2 Tag required A tag shall be used to indicate that a system, or portion thereof, has been removed from service. connection, system control valve, fire alarm control unit, fire alarm annunciator and fire command center, indicating which system, or part thereof, has been removed from service. The code enforcement official shall specify where the tag is to be placed. 6

connection, connection, system control valve, connection, system control valve, fire alarm control unit, connection, system control valve, fire alarm control unit, fire alarm annunciator connection, system control valve, fire alarm control unit, fire alarm annunciator and fire command center, connection, system control valve, fire alarm control unit, fire alarm annunciator and fire command center, indicating which system, or part thereof, has been removed from service. The code enforcement official shall specify where the tag is to be placed. 7

F901.7.4 Preplanned impairment programs Preplanned impairments shall be authorized by the impairment coordinator. Before authorization is given, a designated individual shall be responsible for verifying that all of the following procedures have been implemented: Planned impairment When a fire protection system is out of service due to work that has been planned in advance, such as revisions to the water supply or sprinkler piping system. F901.7.4 Preplanned impairment programs 1. The extent and expected duration of the impairment have been determined. 2. The areas or buildings involved have been inspected and the increased risks determined. 3. Recommendations have been submitted to management or building owner/manager. 4. The fire department has been notified. F901.7.4 Preplanned impairment programs 5. The insurance carrier, the alarm company, building owner/manager, and other authorities having jurisdiction have been notified. 6. The supervisors in the areas to be affected have been notified. 7. A tag impairment system has been implemented. F901.7.5 Emergency impairments When unplanned impairments occur, appropriate emergency action shall be taken to minimize potential injury and damage. The impairment coordinator shall implement the steps outlined in F901.7.4. 8. Necessary tools and materials have been assembled on the impairment site. 8

An emergency impairment is a condition in which the water-based fire protection system or a portion thereof is out of service due to an unexpected occurrence. Such an impairment may also be necessary following a successful system operation during a fire. Following a fire, sprinklers that have operated must be replaced and the system returned to service. The replacement of sprinklers illustrates the importance of the sprinkler cabinet inspections required by Chapter 5, since the impairment time can be substantially reduced if replacement sprinklers are on site. When impaired equipment is restored to normal working order, the impairment coordinator shall verify that all of the following procedures have been implemented: 1. Necessary inspections and tests have been conducted to verify that affected systems are operational. 2. Supervisors have been advised that protection is restored. 3. The fire department has been advised that protection is restored. 4. The building owner/manager, insurance carrier, alarm company and other involved parties have been advised that protection is restored. 5. The impairment tag has been removed. 1. Necessary inspections and tests have been conducted to verify that affected systems are operational. 2. Supervisors have been advised that protection is restored. 9

3. The fire department has been advised that protection is restored. 4. The building owner/manager, insurance carrier, alarm company and other involved parties have been advised that protection is restored. 5. The impairment tag has been removed. Section 10.2.1.2.2 of the code also requires system defects and malfunctions be corrected. Although that may seem like a nonsensical requirement, some owners will put off repairs until a later time, often until the defect or malfunction has been reported a number of times. It is extremely important that contractors document any defects or malfunctions found and put their findings in writing to the owner. In fact, Section 10.2.1.2.3 requires: If a defect or malfunction is not corrected at the conclusion of system inspection, testing or maintenance, the system owner or the owner s designated representative shall be informed of the impairment in writing within 24 hours. This requirement is as much for the protection of the contractor as it is for the owner. 10

11