BRAZED INSPECTED PLATE HEAT EXCHANGER SCAMBIATORI DI CALORE SALDOBRASATI ISPEZIONABILI CIESSE

Similar documents
SB Series Brazed Plate Heat Exchanger Installation Manual

HRS Heat Exchangers Instruction Manual

Air Cross 21 Installation and User Manual

AIC Brazed Plate Heat Exchanger Operating and Instruction Manual

LONGONI ENGINEERING SRL

Brazed Plate Heat Exchanger

Installation, Operation and Maintenance Instructions for ThermaFlex Gasketed Plate Heat Exchangers

Rycroft Supapac Plate Heat Exchangers

Instruction and Maintenance Manual. Spiral Heat Exchanger

Operation Manual. Plateheatexchanger. Read and follow the operating instructions and safety information before using for the first time.

Instruction Manual Plate Condenser. AlfaCond 400/600/800. Part number

Operation and Maintenance Manual Sondex All-Welded Heat Exchangers (SAW)

BRAZED PLATE HEAT EXCHANGERS

Brazed Plate Heat Exchanger Operations Manual

Installation and operating instructions. DK energy storage and DK energy buffer

Installation, Operation and Maintenance Instructions ThermaFlex Gasketed Plate Heat Exchanger OM010

Brazed Plate Heat Exchanger

Oil burners fuel unit with solenoid valve

Titanium Plate Heat Exchanger. Installation & Operating Manual

Channel plates Heat is transferred from one medium to the other through the thin channel plates.

Description. Main components. Lifting eyes To used for lifting and transport securing. Carrying bar Carries the cassettes and the pressure plate.

Installation, Operation and Maintenance Instructions for Electric Storage Calorifier

Evaporators. Direct Expansion Flooded Recirculated Over Feed

TRI-PLATE B INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS PART NO EFFECTIVE MARCH 1, 1983 REPRINT APRIL 16, 1999

Oil burners fuel unit with solenoid valve

Brazed Plate Heat Exchangers TTP s Series

M3 M6 M10 TS6 T2 T5 TL3 TL6

MECHANICAL ENGINEERING ME.2017 FUNDAMENTAL OF REFRIGERATION AND AIR CONDITIONING. Sample Questions and Answers

PLATE HEAT EXCHANGERS. Operation and Maintenance Manual

PLATE HEAT EXCHANGERS BETTER BY DESIGN

Empty unit Cover Water Total weight 15 kg 8 kg 10 kg 33 kg

1. Description. 2. Application and Installation Considerations

Installation, Operation and Maintenance Instructions for Thermax Semi-Storage Calorifier

BRAZED PLATE HEAT EXCHANGERS MOUNTING AND OPERATION MANUAL

Brazed heat exchangers

PLATE HEAT EXCHANGERS

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

A AD Oil burners fuel unit. deltapumps.com. DE A-AD_en_0709.pdf Page 1/1

Vertical Stack Fan Coil Units Models: TVA, TVE, TVS

Heat Exchanger. The purpose may be either to remove heat from a fluid or to add heat to a fluid.

4 route 147, C.P.33 Coaticook, Qc J1A 2S8

SERVICE MANUAL. For Service & Parts please call APK THERMAL at or SAFETY INSTRUCTION

UltraHeat Plate and Frame Heat Exchangers. Engineered for Excellence

Installation, Operation and Maintenance Manual

TMCI Padovan Evaporators

Installation, Operation and Maintenance LOK-FLANGE Multitube Heat Exchangers

Quality Heat Exchangers

Heat exchanger plates

OFFICINE MINUTE VILLORBA - TREVISO

WesPlate. Operation, Maintenance & Installation Manual. Heat Exchanger. Models WP & WPDW

TEMSPEC INC. VERTICAL FAN COIL UNIT MODELS TVA, TVE, TVS

Polaris PHEs vs. Shell-and-Tube Exchangers

To who it may concerns. I-Ravenna, March 11 th, 2016 HEAT EXCHANGER MAINTENANCE

How is the heat transfer?

Chapter 6. Do s & Don ts in Refrigeration & Air-Conditioning Servicing

Plate Coil Heat Exchangers

INSTALLATION INSTRUCTIONS TXV Horizontal Slab Coils WLSH

SENJU SPRINKLER CO., LTD.

Exercise 2-4. Heat Exchangers (Optional Exercise) EXERCISE OBJECTIVE DISCUSSION OUTLINE. Description of a brazed plate heat exchanger DISCUSSION

COLMAC COIL. Installation, Operation, and Maintenance ENG Rev A. Air Cooled Fluid Coolers. Contents. When you want Quality, specify COLMAC!

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

Installation Manual. Instrucciones de instalación y manual de usuario 1

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

PLATE HEAT EXCHANGER

CBE BRAZED PLATE HEAT EXCHANGER

UltraHeat Plate and Frame Heat Exchangers. Engineered for Excellence

Forced draught gas burner

Installation, Operation and Maintenance Guide. Steam Coil Installation, Operation and Maintenance. steam coils

Tips & Technology For Bosch business partners

General Maintenance and Operating Instructions for Heat Exchangers

As we discussed early in the first chapter that heat can transfer through materials and the surrounding medium whenever temperature gradient exists

Secure hydraulic system performance. Smart solutions for cooling and cleaning hydraulic oil

INSTALLATION INSTRUCTIONS TXV Horizontal Duct Coils EHD

INSTALLATION INSTRUCTIONS Cased N Coil, Horizontal ENH4X

Heat Exchanger Piping Hook-up

COPYRIGHT Alfa Laval Lund AB, 2012 How to contact Alfa Laval Contact details for all countries are continually updated on our website.

Air-Cooling Evaporators

HANDBOOK REFRIGERATING SYSTEM PROTECTORS. Ed REFRIGERATING SYSTEM PROTECTORS DP-ED 01/ ENG 1

This chapter is devided into two sections:

APPLICATION GUIDELINES FOR COPELAND COMPLIANT SCROLL COMPRESSORS (ZR*1 Models)

Model ESFR-17 Dry Type Pendent Sprinklers Early Suppression Fast Response 16.8 K-factor General Description

Universal fuel unit for oil burners

A. Air Handling Units shall be designed to the specific requirements of the application: Recirculation or 100% Makeup.

AMERICAN EQUIPMENT SYSTEMS A Division Of Trevor-Martin Corporation th Terrace North Clearwater, Florida 33762

Heat Exchangers. Heat Exchangers 1

Installation, Operation and Maintenance Instructions for ThermaFlex Brazed Plate Heat Exchangers

THERMOSTATIC EXPANSION VALVES AND THERMOSTAT CONTROL DEVICES

Instruction Manual - Anti-Siphon Ejector Chlorine & Sulfur Dioxide 500 PPD (10 kg/h) Maximum Capacity

Remeha. Fuel oil/gas boilers P 520. Installation and Service Manual A

Installation Instructions

Installation Instructions

SCHMIDT- BRETTEN GASKETED PLATE HEAT EXCHANGERS

INSTALLATION INSTRUCTIONS TXV Coils for Manufactured Housing EMA

Mechanical Engineering Department Sheet (1)

INSTALLATION MANUAL UN-CASED A COILS UPFLOW FOR COOLING/HEAT PUMPS FLEX COILS FOR FIELD INSTALLED TXV MODELS: UC LIST OF SECTIONS LIST OF FIGURES

Gasketed and brazed plate heat exchangers

Installation Instructions. For the 18 Built-In Dishwasher and Front Color Panels

INSTRUCTION MANUAL HETO CBN 8 / 18 / C Cooling Baths ID: IM.doc Revision 1

Operation of heat exchangers

Dehumidifier. Instruction Manual. Model DH-320/A

Transcription:

SERIE / I BRAZED INSPECTED PLATE HEAT EXCHANGER SCAMBIATORI DI CALORE SALDOBRASATI ISPEZIONABILI CIESSE

Brazed PLATE HEAT EXCHANGER SERIES CIESSE DESCRIPTION The heat exchangers are essential components in air-conditioning installations in civil facilities and in the thermoregulation of industrial installations in which there is an exchange of thermal energy between two fluids at different temperature levels. In general a heat exchanger does not produce energy, but is a means of allowing the transit of thermal energy from one fluid to a temperature level of another that is located at a different level TYPE OF CONSTRUCTION TYPE OF CONSTRUCTION Brazed heat exchangersare a type of heat engine versatile, with highly efficient heat transfer and suitable for every kind of application and need: in cooling systems, chillers and free coolers, industrial applications for pasteurization, heat pumps, food industry, recovery of waste heat, machine tools, lubrication systems for cooling hydraulic oil. They are made up of a pack of corrugated plates without gaskets, welded together by brazing copper in a vacuum furnace. Its advantages are pressures, high temperatures and reduced dimensions.

OPERATION OPERATION They consist of bundles of corrugated metal plates enclosed by a casing; inside the plate pack are created 2 scroll circuits, called primary and secondary circuit, within which the fluids lap in counter current against the opposing faces of each plate.the corrugations of adjacent plates are touching forming fragmentary ducts which are very thick, so that the motions of fluids are extremely turbulent. The four holes on each plate and the perfect alignment of the plate pack, allow the formation of four supply manifolds and collecting the fluids that are removed to the outside through four passages (threaded nozzles or flanged connections) located on the initial plate. The heat exchangers used to transfer the thermal energy from the primary circuit to the secondary circuit will be of the plate type, with high efficiency and 2 primary accesses and 2 secondary, parallel to each other, all on the side of the fixed plate, with flanged or threaded connections.

Sheet for cooler selection / Modulo richiesta dati CIESSE Date / Data : Customer / Cliente: Name of applicant / Nome del richiedente: Phone / Telefono: Total power engine Potenza installata: KW Note Power to be dissipated Potenza da dissipare KW Oil flow rate Portata olio lmp Inlet oil temperature Temperatura ingresso olio C Oil viscosity Viscosità olio cst Water flow rate Portata acqua lmp Inlet water temperature Temperatura ingresso acqua C MAX DIMENSION AVAILABLE INGORMBRI MASSIMI DISPONIBILI A = B = C =

USE AND MAINTENANCE OF THE SERIES BRAZED PLATE HEAT EXCHANGER INSTALLATION The following installation position is recommended: the vertical or in the position shown below, taking care to leave enough space to make maintenance easier. The most suitable position must be chosen in such a manner that the discharge of the fluids from the inside of the exchanger is the most simple and natural as possible. For better heat exchange efficiency, the vertical position is the one most recommended. All other positions may cause a drop in thermal efficiency. In applications of the refrigeration system or in systems where bi-phase fluids may be used, all heat exchangers are to be mounted vertically. Never mount exchangers with connections facing downward. All exchangers should be supported by brackets or supports, never fasten them to the structure of the machine or plant with only connections or rigid piping. ATTENTION check and ensure that no vibrations or pulsations of the system is transmitted to the exchangers, as this would result in mechanical failure of the connections. To avoid this is the surrounding area connections have been reinforced but we recommend installing it between the heat exchanger and the source of the vibration system which can absorb the mechanical stresses. The studies carried out by the most important institution in the field of heating systems and district heating (the Finnish), have shown that the service life of the heat exchangers in brazed plate heat decreases if you hav faulty or inadequate regulation systems. Below are some of the most important factors that have a detrimental effect on the service life of the : Control valves oversized Excessive and sudden changes in pressure The poor quality of the control valves The incorrect calibration of the adjustment system The wrong position of the sensor for temperature control ATTENTION for the installation of new systems or reconditioned ones, before connecting the pipes to the BPHE, it is recommended to clean the pipes and remove any debris, also it is recommend to use a filter with a mesh of 500 µ, as in the case of refrigerating applications, the obstruction of a single channel of the water circuit would lead to the freezing and the subsequent mixing of the water and the gas refrigerates Note: During and after welding on the exchangers there must be no dark colours present. If during welding the flame has a yellow straw colour there is no danger of corrosion. Example: TIG or MIG welding of a connection

ODS brazing connections Clean and degrease the contact surfaces. Apply a solvent-based hydrochloride with a brush. Insert the copper pipe in the connection of the heat exchanger and braze it with 45-55% silver solder. Be careful not to point the flame in the direction of the plate pack, but only at the junction to braze at a maximum temperature of 650 (1200 F). To avoid oxidation, the heat exchanger must be protected from the inside with nitrogen N2. Use a damp cloth around the connection, to avoid excessive heating. During the brazing hold the pipe in a fixed position. TIG or MIG welding techniques. NOTE: Excessive heating during the brazing process can lead to the fusion of copper and consequently to breakage of the heat exchanger! Connections to threaded attachments Mount the brazed exchanger and then connect the pipes of the exchanger via the threaded attachments. Screw the fitting to comply with the limits described in the table in the chapter on the positioning of the heat exchangers. Starting before starting installation, verify that the design data transcribed on the plate exchanger, conform to the required heat. Check that joints between the threaded connections and the pipes of both are well done to allow good sealing. The pumps which feed the BPHE must be equipped with "shut-off" valves. Pumps having an operating pressure higher than that of the system shall be equipped with safety valves. The pump must not suck in air in any way, in order to avoid the "water hammer". To avoid sudden changes in pressure, the pumps have to be started with closed valves. The valves of the feed lines and return lines must be opened slowly and as far as possible simultaneously, until it reaches the desired operating temperature. All variations in pressure must be avoided. During loading, any air in the system piping must be removed via the vent valves located along the pipes. If the air present in the heat exchangers is not discharged completely, the declared yield may deteriorate as not all the sharing surface will be used for the heat exchange. In addition, the residual air increases the risk of corrosion. Just as for the start-up also during close down the flow should be stopped slowly and possibly on both circuits (I and II ). If you cannot stop the flow at the same time, then, the first to be closed is the hottest one. During periods of inactivity of the installations which are more or less long, the exchangers should be completely drained and cleaned inside. This is very common when the exchangers are outside and then subjected to freezing conditions in winter, or in the case where the heat exchange is conducted with aggressive fluids or particularly rich in solids in suspension. Operations After starting the installation make sure that no pressure change has occurred. If the heat exchanger is installed between a control valve and a differential pressure controller, make sure that the simultaneous closing of both devices, will not lead to a "water hammer". In district heating plants, particular attention must be paid to the fact that the pressure of the secondary circuit is the same as that of the primary circuit, connected directly to the main network. Doing so may cause a "water hammer" that would be passed via the back of the heat exchanger. Check the functional efficiency of the control devices (cf).and connections to the pipes The operating conditions must always be the same as those of the project, any change may cause malfunction or damage. Note: the "water hammer" and the sudden pressure changes can cause internal or external losses of BPHE. provide for a grounding of the exchanger in order to avoid the phenomenon of stray currents.

Frost protection freezing is the main cause of breakage of the heat exchangers in brazed plate. To avoid this phenomenon, simple measures are to be adopted such as: the use of anti-freeze such as ethylene glycol % or propylene glycol %, if the operation provides thermal temperatures close to freezing point = 0, fluid can enter from the top and exit from the bottom, the use of a filter to prevent impurities to obstruct the passage of the fluid in the channels of the exchanger, the use of a protection thermostat for temperature control and a flow switch to guarantee a constant flow before, during and after starting the compressor, the use of additional connections for the insertion of the probes inside the heat exchanger, placed on the opposite side of the input and output of the circuit of the fluid to be cooled. Fouling it must conform to DIN concerning the use of drinking water and water for heating, to Vd-TÜV regulations, regulations, to the norms of the GFW, and to the charactistics stated on the page of this manual. There are many factors that can lead to fouling of the heat exchangers to plates, such as for example: the low velocity of the fluid, the high temperature, the erroneous distribution, poor water quality, etc. One of the tools to prevent clogging of the brazed heat exchangers is the installation of simple hydraulic filters with a mesh of between 0.5 and 0.8 mm, in this way all the particles up to 1 mm will be blocked. It is necessary that the velocity of the fluids inside the BPHE's is high, so as to generate high turbulence and decrease the risk of fouling. The formation of calcium on the surface of the plate heat exchangers used for heating or hot water production equipment, can occur at temperatures above 60 C. Therefore, the high turbulence and temperatures below 60 C reduce the risk of lime scale deposits. During the closing phase of the plant, close first the side of the primary circuit (the one further down) and then the side of the secondary circuit. While starting open first the secondary side and then the primary side. These two latter procedures will avoid excessive overheating of the heat exchanger. Note poor water quality leads to and increases the risk of clogging and corrosion. Cleaning: in cases where the heat exchanger is clogged because of poor water quality (high degree of hardness or rich in suspended particles), it is necessary to clean it, by circulating a cleaning liquid by force into the interior.. For this purpose one can use a system consisting of a pump with a high prevalence and a tank containing the light acid (5% phosphoric acid or 5% of oxalic acid diluted in water). For effective cleaning the flow rate of the liquid detergent must be at least 1.5 times the operating heat exchanger and forced circulation should last at least 8-10 hours INSTRUCTIONS FOR CLEANING OF BRAZED PLATE HEAT EXCHANGER FOR CLEANING In some applications, the tendency to fouling can be very strong, for example, when using very hard water. It 'always possible to clean the exchanger by circulating a cleaning liquid (CIP). Use a tank containing light acid, 5% nitric acid, or, if the exchanger is frequently cleaned, 5% oxalic acid. Circulate the detergent inside the exchanger: for effective cleaning the flow rate of the detergent must be at least 1.5 times the normal load. Rinse thoroughly with water to remove all traces of acid before putting the system into operation. Carry out this cleaning at regular intervals.

Heat exchanger Weak acid FILTERS The use of a filter is highly recommendable if it is assumed that particles of magnitude greater than 1 mm are present in the fluid. Sizes smaller than 1 mm do not cause any problem.

Scambiatori di calore a piastre ispezionabili CIESSE A plate heat exchanger is a device with the capacity to retrieve the heat present in a fluid, transferring it to another fluid. The two fluids never mix because they are divided by metal sheets. These sheets, called plates, are very thin and are corrugated to enable transfer of the highest possible quantity of heat for each surface unit. The plate heat exchanger is manufactured so as to guarantee such heat exchange with maximum safety. Description Heat exchangers with screws are made of : - Support column - Support bar (It support grooved plates and pressure plate.) - Pressure plate Mobile steel plate. In some instances pipes can be connected to it (Multi-pass) - Tie rods - Guide bar - Grooved plates Heat is transferred from one medium to another by mean of thin grooved plates. The number of plates determines the overall heat exchange surface. - Connections The holes in the plate of the frame enable the fluid to enter the heat - exchanger. - Fixed plate - Tightening nuts They push grooved plates one against the other.

Operating principles There are three different kinds of heat transmission: irradiation conduction convection The operating principle of the heat exchangers is based on convection and conduction. Let's consider two fluids flowing within two coaxial pipes. Let's assume that the temperature of the fluid contained in the inner pipe is higher than that of the fluid in the outer pipe. Firstly, let's consider the case where both fluids flow in the same direction. The standard formula: Q=KS (ta-tb) is not applicable, because it applies only when temperatures ta and tb are constant. In this case, instead, the temperature of the heating fluid (A) is t1 at the inlet and t2 at the outlet and obviously t1>t2. The temperature of the heated fluid will be t0 at the inlet and t01 at the outlet and t0 must be higher than t01. The above formula is still approximately valid considering the average temperatures of the heating fluid and heated fluid. So: Q=KS((t1+t2)/2)-(t01+t0)/2) In this case of direct flow (equi-flow), heat exchange is very active in the first part of the pipe, where there is a significant difference of temperature between heating fluid and heated fluid, while it is not very active at pipe end, where the difference of these temperatures is limited. To avoid this issue we have fluids flowing in opposite directions (counterflow) so as to maintain a significant temperature gap between the two fluids, ensuring a smoother heat exchange among them. That is why all plate heat exchangers feature counter-flow. The plate heat exchanger includes a variable number of corrugated metallic plates with holes for the passage of the two fluids which exchange heat. They form channels which enable fluids toflow alternately in oppositedirections. The fluids always remain separated by two gaskets. Plates feature a typical fishbone corrugation in the middle, facing alternately in opposite directions. The gaskets have two functions: fluid containment in the plate outer area and fluid deviation alternately inside the exchanger. A fluid entering the primary circuit is allowed to access the passage to the channel between the first two plates, instead it cannot access the second passage. In the secondary circuit, the fluid finds the first passage closed while the second passage is open. This results in two thin layers of fluids divided by a metal sheet. Thus, heat exchange is maximised. Plate undulation facilitates fluid turbulence and enhances plate rigidity. There two main types of circuit: - figure A: single (1-1) - figure B: multi-pass (2-2/3-3/4-4) The first type of circuit is shown in figure A, where both primary and secondary circuit cross the fixed plate; in this kind of circuit the fluid crosses the exchanger and returns back after reaching pressure plate. The second type of circuit is shown in figure B. The presence of an intermediate

plate causes an additional passage, as if two or more plates are connected in series. This kind of flow requires connections on the mobile plate. Caution: different kinds of circuit do not determine the overall dimensions of the exchanger; they simply require different connections. FIGURE A: SINGOLAR FIGURE B: MULTI-PASS Recommends Ciesse s.r.l. recommends as well the installation of drain valves for both supply pipes, so as to be able to drain the exchanger before opening it, avoiding problems to the nearby equipments. It is useful to mount connections for cleaning between the valves and the exchanger. For instance it is possible to perform chemical cleaning without having to disassemble or open the exchanger. Ciesse s.r.l. recommends to observe the following cautions: Caution: Tensions or thermal expansions must not be discharged on the attachments or on the exchanger. The mobile plate must never be connected to a fixed point. Any tension due to thermal expansion may cause leaks. Before connecting any pipe, ensure that there is no extraneous matter inside the equipment. When performing connection, ensure that pipes do not stress the plate heat exchanger. Do not act in rough manner connecting pipes to threaded connections up to 2" 1/2. To avoid water hammers, do not use fast closing valves. The "water hammer" is a short pressure peak which may occur when starting or stopping an hydraulic system; it causes a pressure wave which crosses the pipe at the speed of sound. It may cause serious damages to the equipment (for instance seals may escape from their position and fluids may leak outside). In case inhibiting agents are used, Ciesse s.r.l. suggests to verify that these do not interact with the materials of seals, plates and connecting parts. Multi-pass units (with connections on the fixed plate and on the pressure plate)

It is important that the plate pack is properly tightened, before connecting the pipe. Caution: To facilitate disconnection of heat exchanger and plates, it is necessary to connect a 90 elbow to the connection in the pressure plate, directed upwards or laterally, with another flange located just outside the heat exchanger profile; such connection is necessary to let the pressure plate slide up to the support when opening plate pack.