SECTION : MEPS IDENTIFICATION & LABELING

Similar documents
A. Shop Drawing submittals shall include, but not be limited to, the following:

SECTION ELECTRICAL IDENTIFICATION

SECTION (16075) - IDENTIFICATION FOR ELECTRICAL SYSTEMS

Brown University Revised June 29, 2012 Facilities Design & Construction Standards SECTION ELECTRICAL DESIGN CRITERIA

IDENTIFICATION FOR ELECTRICAL SYSTEMS July Electrical Systems

A. Product Data: For each electrical identification product indicated. B. Comply with 29 CFR and 29 CFR

An Owner s Guide to Maintaining a Mobile / Manufactured Home August 2010

Subcontract Agreement No.

Element Z General Design Requirements Existing Facilities Information

Exhibit J. Subcontract Agreement No.

SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW)

SECTION C. Section Cable Trays for Electrical Systems: Additional identification requirements for cable tray systems.

SECTION PANELBOARDS Painting Wire and Cable Overcurrent Protective Devices.

Element Z General Design Requirements Existing Facilities Information

CxA to Answer this Section

OPERATING AND MAINTENANCE MANUAL FOR PLATE HEAT EXCHANGER INDIRECT FIRED WATER HEATER. Electric Heater Company Base Model "BWXP"

DIVISION 15 MECHANICAL

FHCRC/SCCA Facility Design Manual

SECTION IDENTIFICATION FOR ELECTRICAL SYSTEMS

FACILITY STANDARDS (FS) 2 TABLE OF CONTENTS

FIRE ALARM: BY OTHERS, IF REQUIRED.

FIRE ALARM: BY OTHERS, IF REQUIRED.

Appendix B. Facilities Assessment Report

A. This Section includes the following domestic water piping specialties:

Integrated Automation

CADDY CORPORATION. Utility Distribution Systems

ELECTRICAL Seminar. B A L A Consulting Engineers, Inc. Edward J. Lynch, PE Vice President, Electrical Department Manager.

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

COMMON WORK RESULTS FOR ELECTRICAL: Basic Electrical Materials Methods

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

COMcheck Software Version Mechanical Compliance Certificate

.4 Do complete installation in accordance with latest Electrical Bulletins of the local inspection authority.

SECTION : FIRE ALARM & DETECTION SYSTEMS

Oberon s National Electric Code (NEC)Compliance Statement and Underwriters Laboratories (UL ) Considerations for Oberon Products

Union County Vocational - Technical Schools Scotch Plains, New Jersey

OKLAHOMA STATE UNIVERSITY - BUILDING DESIGN STANDARDS

DOCUMENT TABLE OF CONTENTS

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

State College Area School District High School South Building EXISTING CONDITIONS ASSESSMENT

Design and Construction Standards SECTION PLUMBING EQUIPMENT

1.1 This section applies to air handling units for HVAC Systems.

State College Area School District High School North Building EXISTING CONDITIONS ASSESSMENT

SECTION PLUMBING EQUIPMENT

National Electrical Code

Demonstration and Training of MEP Systems Page 1 of 15

SECTION P01 LIGHTING AND APPLIANCE PANELBOARDS - A-SERIES

C. Shop Drawings: For boilers, boiler trim, and accessories. Include plans, elevations, sections, details, and attachments to other work.

Partner. Peerless. Indirect-Fired. Water Heater. Installation, Operation & Maintenance Manual

APPENDIX L ALTERNATE PLUMBING SYSTEMS

SECTION : CAMPUS CENTRAL METERING SYSTEM DESIGN

ENGINE GENERATORS AND ACCESSORIES

Electrical Design Guidelines Table of Contents

Electrical Inspection Service & Distribution

Division 26 ELECTRICAL TABLE OF CONTENTS

AFUE 95% Heating Input 50,000 to 200,000 Btuh

TESTING, ADJUSTING AND BALANCING

COMcheck Software Version Review Mechanical Compliance Certificate

MUKWONAGO AREA SCHOOL DISTRICT CAPITAL IMPROVEMENT / MAINTENANCE STUDY

PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:

DOMESTIC WATER PACKAGED BOOSTER PUMPS

Building Department Informational Handout

Hubbell NX500 High Efficiency Gas Condensing Water Heater

A. This Section includes the following emergency plumbing fixtures:

S AGE E NGINEERING A SSOCIATES, LLP

NPE-A and NPE-S Condensing Tankless Water Heaters

SUMMARY 1234 Main St.Severn Buyer Name 07/18/2018 9:00AM

Dear Concessionaire,

DESIGN AND CONSTRUCTION STANDARDS GENERAL DESIGN GUIDELINES

NPE-A and NPE-S Condensing Tankless Water Heaters

SCO # 1 & 2 PUNCLH LIST Project Name: VANCLEAVE UPPER ELEMENTARY CLA#: 13003

Assembly Code Identity Data System. Omniclass Number and Title

Weil-McLain part numbers are found in Weil-McLain Boilers and Controls Repair Parts Lists.

SECTION ELECTRIC-DRIVEN, FIRE PUMPS

SYSTEM DESIGN REQUIREMENTS

DIVISION 23 HVAC Hydronic Piping Systems

Trinity Lx400 High Efficiency Gas Condensing Boiler & Water Heater

TABLE OF CONTENTS CHAPTER 1 GENERAL RULES CHAPTER 2 WIRING AND PROTECTION... 51

Trinity Lx200 High Efficiency Gas Condensing Boiler & Water Heater

A. Furnish and install wiring devices and plates as specified herein and as shown on the Drawings.

21. Plumbing fixture mixing valves, PRV, electronic faucets and flush valve(excluding batteries)optional Cost proposal to include these device

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

TABLE OF CONTENTS. Part I Administrative... 1

TABLE OF CONTENTS GENERAL... 2 A. DEFINITIONS DIGITAL, ADDRESSABLE FIRE ALARM SYSTEM... 2

A. Product Data: Include rated capacities, furnished specialties and accessories.

NPE-A and NPE-S Condensing Tankless Water Heaters

GARCIA GALUSKA DESOUSA Consulting Engineers

CONTENTS AUTOMATIC TRANSFER SWITCHES

iq251, Gen II Submittal Data

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #

Cook - Wissahickon Elementary School

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM

Mechanical Compliance Certificate

HYDRONIC SPECIALTIES TACO AC(F)-CA 05/08/2008

NPE-A and NPE-S Condensing Tankless Water Heaters

16.34 Multiplex Fire Alarm System Construction Standards Page 1 of 5

i200, Gen II i250, Gen II Submittal Data

ACBH/ACBV ACTIVE CHILLED BEAM INSTALLATION MANUAL. Date: 05/12 Reference # : L-50.

CARBON DIOXIDE SYSTEMS FOR BEVERAGE DISPENSING PERMIT REQUIREMENTS

007100S01 - PROGRAM DESIGN CRITERIA

M001. Revenue Services ISSUED FOR CONSTRUCTION SEPTEMBER. 2, East State Parkway Schaumburg, Illinois Do Not Scale Drawings

Transcription:

SECTION 01 70 10: MEPS IDENTIFICATION & LABELING 1. GENERAL A. The intent of this section is to define the labeling and identification requirements for building mechanical, electrical, plumbing, and specialty systems (MEPS) installed within buildings. 2. ACCESSIBLE CEILINGS & ACCESS HATCHES A. MEPS equipment located above accessible or hung ceilings: provide labels on the ceiling T- bars to indicate the device location above the ceiling. B. MEPS equipment located behind wall or hard ceiling hatches: provide label on hatch to indicate the device behind. For finished areas where labeling is objectionable, install labels on the latch side or back of the access door. C. Labels to be machine-printed, adhesive label, minimum ¼ high letters, black text on white background. 3. EQUIPMENT INVENTORY A. In addition to the MEPS equipment labeling described herein, Brown also identifies each piece of equipment with an equipment inventory identification tag or barcode. The equipment inventory is created through submittal of the equipment information from the project to the FM Preventive Maintenance team or the selected inventory service provider during each project. B. For small projects and equipment replacements, the inventory information and barcode tags are normally created and affixed by the FM Preventive Maintenance team. C. For large projects, new buildings, complete gut and remodel of an existing building, the project construction contractor to work with the Brown inventory service provider to create the required equipment inventory information and barcoding, which will then be provided to the preventive maintenance team for loading into the Facilities Management maintenance management system D. The inventory service provider is: Building Maintenance Optimization Consultants (BMOC) 2321 4 th St., Suite 203 Tucker, GA 30084 Contact: Jonathan C. Thomas, PE, CEM, LEED AP O+M President Phone: (770) 313.1858 Email: info@buildingmoc.com E. Label and tag all MEPS equipment, controllers, control cabinets, and BAS cabinets by the name and designation shown on the project schedules or record drawings. F. Labels must be: Machine labeled or engraved nameplates, with permanent contact adhesive Black text on white background February 16, 2017 Page 1 of 6

Label size as required, no smaller than 1 x 3 inches, minimum letter size of ½ G. For equipment controllers and control cabinets, such as motor starters, VFDs, lighting contactors, heat trace control cabinets, etc. label front of cabinet to denote the load controlled. 4. ELECTRICAL CIRCUITS IDENTIFICATION A. Label all electrical and electrically-powered equipment, such as motor starters, VFDs, control cabinets, air handlers, pumps, chillers, BAS cabinets, transformers, disconnect switches, panelboards, etc. with an engraved nameplate denoting: Equipment Designation, Operating voltage, phase Source panelboard or switchboard The specific circuit number (for disconnection and isolation) B. For equipment connected to normal power supply, labels to be white background with black lettering. C. For equipment connected to Emergency, Standby or Legally-required power supplies, nameplates to be orange background with black lettering D. Minimum text size: ¼ Example Standby Power Tag 5. ELECTRICAL JUNCTIONS, PULL BOXES & CONDUITS A. Label lighting fixture outlet boxes with their panelboard and circuit number. B. Label the covers of electrical junction boxes, pull boxes, terminal cabinets and wireways with the circuit types contained within (e.g. lighting, receptacles, telecommunications). C. Junction boxes and outlet boxes for fire alarm use to be painted red. D. Junction boxes for BAS to be painted yellow. E. Conduits (2 and larger) and wireways containing electrical circuits over 600 volts, where run within buildings and accessible spaces, to be painted orange. 6. RECEPTACLES, SWITCHES & WIRING DEVICES A. Label each wiring device faceplate with the source panelboard and circuit number. B. Labels to be machine-printed, non-smudge type, adhesive label, black text on white or clear background. 7. PANELBOARD, SWITCHBOARD, CIRCUIT BREAKERS, & DISCONNECT SWITCH CIRCUITS February 16, 2017 Page 2 of 6

A. Panel and switchboard circuit directories to be type-written. Provide new directories when changes are made to add or remove circuits. B. Circuit directories to be specific for the load served and include the equipment tag (e.g. HTHW pump P-3). C. Branch circuit directories and labels to be specific to the type of load and the room or area served (e.g. receptacles - room 405). D. Provide labels on each adjustable-trip circuit breaker and fused disconnect noting the device s design setting for overcurrent protection (e.g.: a 400-amp frame circuit breaker calibrated for 250 amps to be labeled 250-amp trip ). 8. PIPING A. Piping label color coding and size per ANSI /ASME A13.1 and as follows: 1. Potable Water Green with white letters/numbers 2. Unsafe (Non-Potable) Water Gray with white letters 3. Storm, Sanitary and Lab Waste Water - Gray with white letters 4. Chilled Water Green with white letters 5. Condenser Water Green with white letters 6. Steam Yellow with black letters 7. Steam Condensate - Yellow with black letters 8. High Temperature Hot Water (HTHW) dual-label: Yellow with black letters, and Danger - red with white letters 9. Medium Temperature Hot Water (MTHW) Yellow with black letters 10. Dual-Temperature systems (MTHW/Chilled Water) - Yellow with black letters 11. Fire Suppression Water Red with white letters 12. Fire Suppression Chemical and Gases - Red with white letters 13. Toxic and Corrosive liquids Orange with black letters 14. Flammable fluids (e.g. diesel fuel) Yellow with black letters 15. Compressed Air / Oxygen Blue with white letters 16. Natural Gas / Combustible Gases Yellow with black letters 17. Compressed Air Blue with white letters B. Place labels over installed insulation on the pipe. Painted or stenciled labels on insulation jacket are not permitted. C. Install pipe markers as follows: 1. Each side of every valve 2. Each tee or wye 3. Each point of exit an entry where piping passes through walls, floors, partitions, or ceilings 4. At each piping change of direction 5. Every 25 ft. on straight runs of pipe D. Provide arrow markers adjacent to each pipe label with the arrow showing direction of flow; use double-headed arrows or an arrow on either side of pipe label if flow can be in both directions. E. Building Exterior Walls & Foundations: February 16, 2017 Page 3 of 6

1. Identify each piping penetration entering/leaving the building with a wall mounted identification sign. 2. Identification sign language to include: Piping system The destination of the other building or utility service that piping is connecting to: 9. VALVES A. Tag valves in each piping system with a brass or aluminum tag, attached to the valve with brass or aluminum chain B. Label and tag by the name and designation shown on the record drawings; minimum 3/8 high black letters; Utilize a 2-line tag nomenclature per below: 1. Line 1 - System Type: Common system type abbreviations include, but are not limited to: LPS - Low Pressure steam HPS - High Pressure steam MTHW - Medium Temperature Hot Water HTHW - High Temperature Hot Water DT - Dual Temperature (Heating & Cooling) DW - Domestic Water DHW - Domestic Hot Water NPW - Non-Potable Water NPHW - Non-Potable Hot Water CHW - Chilled Water CW - Condenser Water HR - Heat Recovery PCW - Process Cooling Water 2. Line 2 Valve Type & Number: Per the following, with X being a unique number and/or letter designation: February 16, 2017 Page 4 of 6

CV - X: Control Valve BPV - X: Bypass valve, to bypass control valves and for allowing flow from the supply to the return side of a heating or cooling system WV - X: Heating System Warm-up valve, to bypass a control valve of a heating system VV-X: System vent valve DV- X: System drain valve ZV- X: Zone isolation valve, for system branch isolation IV - X: Isolation valve for building services, equipment such as heat exchangers, or control valves C. Individual isolation valves to isolate equipment do not require identification where they are located immediately adjacent to the equipment: D. Subsequent projects including additional valves to be added to the existing record drawings. 10. STEAM TRAPS A. Provide list of each trap location and trap type to FM-Operations: this information will be used by Brown s Service Provider to provide and install tags at each steam trap location, and to update the existing steam trap master database. 11. DUCTWORK A. Label ductwork with color-coded, preprinted labels to identify service and direction of flow. Label to include system designation and air type (e.g. AHU-1 Supply Air). B. Label size: 2-1/2 minimum height x length as required, with minimum 1-1/2 high lettering. C. Duct Label Color-Coding: Supply Air Green with white letters/numbers Exhaust Air Yellow with black letters Return Air, Supply Air or Relief Air - Blue with white letters E. Duct Label Application: Within each room or space On each side of walls, floors, ceilings and other duct penetrations Near major equipment and points of origin or termination February 16, 2017 Page 5 of 6

Every 50 ft. on straight runs of duct Label branches from main supply and exhaust ducts to identify rooms and areas served February 16, 2017 Page 6 of 6