Installation Smoke Detector ELQZ , GOLD

Similar documents
Installation instructions for the optical detector with built-in control unit, TBLZ-1-72-a GOLD/COMPACT

Instructions for the BASIC BCRW Fan, Sizes General

Installation Instruction Venturi-Air Duct Kit. (Part No. S )

Instructions. Duct Mount Accessory Q Rev: 11/

Ionisation single-tube smoke detector for duct mounting

E-PDD Duct Smoke Detector Installation Sheet

FX-PDD Duct Smoke Detector Installation Sheet

Snifter ATEX22 VERSION. User Manual. Distributor

INSTRUCTIONS. Duct Mount Kit Q900. Description. Operation

TrueAlarm Analog Sensing

D2E Duct Smoke Detector

Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608)

Installation Manual: PAD100-DUCTR Analog Addressable Duct Detector

Air Specialties Express, 448 S. Main St., P. O. Box , Verona, WI Phone: (877) Fax: (608)

DH500ACDC Intelligent Air Duct Smoke Detector Housing

DETECTOR TEST LOG. Detector Identification Information DHX-501 INTELLIGENT AIR DUCT SMOKE DETECTOR HOUSING INSTALLATION AND MAINTENANCE INSTRUCTIONS

PRODUCT OVERVIEW SM-501 AT-A-GLANCE

Sintrol Snifter A1+ Manual. Version 1.2.2

TYPE C: RETURN AIR UNDER POSITIVE PRESSURE FROM SEPARATE BLOWER

You in Control PRODUCT OVERVIEW

Hodge Clemco Ltd. MJC Mini Cartridge Filters Owners Manual. TSOM 556 Date of issue 13/07/04. Hodge Clemco Ltd

Electro Controls. Flow WattsIndustries.co.uk

DMFPM-2R MULTIFUNCTIONAL

SK-Duct Air Duct Smoke Detector

Installation Instructions for Duct Accessories GOLD/SILVER C/COMPACT

Snifter. User Manual. Distributor

USER INSTRUCTIONS FOR 0.25 LITRE MINI DEHUMIDIFIER - MODEL NO. DHMD025

QAF63.2-J QAF63.6-J. Frost detectors. for use on the air side

Analog Room Pressure Monitor RPC Series

Silencer Preheater unit Electric post-heating unit Water circulated post-heating unit CO 2 sensor %RH sensor Pressure difference switch LON converter

ZIOU/230 - MAINS IO INSTRUCTION MANUAL

D350PL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS

SERVICE INSTRUCTIONS FOR. Fire Alarm System MINI-2000

LZP-2 ZONE CONTROL PANEL

VFL, VFLPG, VTL and VRA Rectangular electric duct heaters

Contents. Technical Description of the Air Handling Unit General, Specification Function, Functional Sections

DH100ACDCI Ionization Air Duct Smoke Detector

D350RPL INTELLIGENT PHOTOELECTRONIC DUCT SMOKE DETECTOR WITH EXTENDED AIR SPEED RANGE INSTALLATION AND MAINTENANCE INSTRUCTIONS

TRN100BPT, TRN100BP, and TRN100BPC Air Duct Smoke Detector with Extended Air Speed Range

DH100ACDCLP Air Duct Smoke Detector with Extended Air Speed Range

l High precision, computer-designed parabolic optical system,. Dual element pyro-electric sensor.

Xenex Conventional Fire Detection & Alarm System

MODELS N150/300/675/900/1500/2500/2600 INSTALLATION, SERVICING AND MAINTENANCE INSTRUCTIONS

PRODUCT OVERVIEW. SL-2000 AT-A-GLANCE MODEL NUMBER: SL-2000-N 4-Wire Ionization Duct Smoke Detector SL-2000-P 4-Wire Photoelectric Duct Smoke Detector

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side

QFM41.. Duct sensors QFM41.. AQF4150 AQF3153. Symaro. for relative humidity and temperature with calibration certificates

Instructions for the fan motor control system, SILVER C

Self-regulating vacuum pumps. Characteristics. Ø max. vacuum air drawn in L2 model nozzle (%) Specifications. Curves: see page 9/27.

QAF63.2 QAF63.6. Frost sensors for use on the air side. Building Technologies HVAC Products

DH400 Air Duct Smoke Detector

Air heater/cooler in combination with ground source heat pump

INSTALLATION, BALANCING & MAINTENANCE

INSTALLATION AND MAINTENANCE

S304 and S305 Dust Emission Monitors. User Manual. Distributor

DH100ACDCI Ionization Air Duct Smoke Detector

You in Control PRODUCT OVERVIEW SM-501 AT-A-GLANCE

Accuracy by Design Products for the HVAC Professional

CV Circular electric duct heaters

Model 1750A/ 1770A Dehumidifier Installation Instructions

Duct Temperature Sensors

GLEB Kitchen exhaust fan

Duct smoke housings, 4-wire D341/D341P and D342/D342P

The Silent Range Pure Elegance & Tranquillity. The widest range of ultra quiet silent fans

DB110xA, DB1131A, SO620A, DB1151A Detector bases and accessories

APPLICATION BULLETIN COMBUSTION TURBINE FACILITIES. Overview

Duct and Rough Service Carbon Monoxide Sensor

GOLD RX, GOLD RX 12 GOLD RX,

DICTATOR Hold-Open Systems for Hazardous Areas

QFM21... Siemens Building Technologies HVAC Products. Symaro Duct Sensors. for relative humidity and temperature

Conventional Fire Alarm System 2014 V1.2

KITCHEN EXHAUST FAN GLEC-6 INSTALLATION AND MAINTENANCE

Installation and Maintenance

WATLOW IND. WATROD Modular Duct Heater Installation & Maintenance Manual I&M NUMBER: Page: 1 Date:6/11/2008 Rev: 2

Hygro and Hygrothermal Transducers (Capacitive) for Air Conditioning Applications

DH100LP Air Duct Smoke Detector with Extended Air Speed Range

DUCT SMOKE DETECTORS IQ8

READ AND SAVE THESE INSTALLATION INSTRUCTIONS

WHHR Midi & Midi Lite

Self-regulating vacuum pumps. Characteristics. Ø max. vacuum air drawn in L2 model nozzle (%) Specifications. Curves: see page 9/27.

Steam Injection Humidifiers for use with steam boilers PRODUCT CATALOG

eco PREMIUM ENERGY RECOVERY UNIT» Technical instruction

Duct smoke housing, 2-wire D340/D340P

System 800 Addressable Fire Detection & Alarm System

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

INSTALLATION DO S AND DON TS

Installation Instructions

DNR-AUS Duct Smoke Detector

EUKC Cooling Unit. Compulsory declaration and recurring. The unit must NOT be used in any other way than as a cooling unit!

CV Circular electric duct heaters

Primo Hotel. General. Indoor climate units for hotel rooms

FireNET Vapor VPR-SD2

Type FK-EU FOR DIVERSE APPLICATIONS. Homepage > Products > Fire and Smoke Protection > Fire dampers > Type FK-EU

USER'S MANUAL PU SENS 01 (A11) PU SENS 01 (A19) Sensor Control Panel

FDBZ290 Air sampling smoke detection kit

F17W44_MFB_F_EN INSTALLATION INSTRUCTIONS

DH500 Intelligent Air Duct Smoke Detector Housing

DNR Duct Smoke Detector

LASER ASPIRATED SMOKE DETECTOR

Transcription:

Installation Smoke Detector ELQZ-2-428-2, GOLD General The ELQZ-2-428-2 smoke detector is used for measuring any smoke present in ventilation ducts. It consists of an ionising detector mounted in an adaptor system where both the tube and enclosure are designed for optimum airflow through the detector. The system meets all the fire safety requirements for air velocities between 0.2 m/s and 20 m/s. The smoke detector is used together with a control unit (fitted inside an ELQA equipment cubicle or a separate equipment cubicle for the smoke detection and warning function) for controlling fans, fire and smoke dampers. Operation If any smoke is detected, a red LED on the detector lights up and the detector transmits an alarm signal to the control unit. Any accumulation of impurities in the smoke detector will make it more sensitive and gradually approach its alarm condition. To avoid unnecessary alarms caused by fouling, the detector is equipped with a service alarm (green LED). When lit, this LED indicates that the detector ought to be cleaned. Tecnical details Type of detector Ionising Power supply Power consumption: In-operation Service alarm Smoke alarm Permissible ambient temperature Permissible humidity Inclosure Class Weight 24VDC (from control unit) Max 0,04mA ~ 13mA ~ 48mA -20 C to +50 C Max 99% rh IP54 800g Accessories The ELQZ-1-428-2-1 Mounting bracket should be used for mounting the detector on a circular or insulated duct. Maintenance Whenever the smoke detector becomes fouled, it will be more sensitive and may trip the service alarm. This situation can easily be delayed by vacuum cleaning the detector once a year. Dimensions Venturi tube length 600 mm. (All dimensions in mm) Specifications are subject to alteration without notice. www.swegon.se 1

GB.ELQZ428.050101 Installation and Location Install the smoke detector with the airflow direction arrow on its cover pointing in the direction of airflow through the ducting. The detector can be mounted on the side or top of the duct for vertical or horizontal air flow. If the ambient temperature varies radically, for example outdoors or in cold attics, insulate the detector to protect it from the ambient air and prevent the formation of condensation inside the detector housing. To ensure satisfactory smoke detection, the smoke detector should be located at a distance, in the direction of airflow, that is equivalent to at least 3 x the hydraulic diameter of the duct upstream of the nearest source of disturbance in the ducting (see the examples of sources of disturbance below). If it is located downstream of the nearest source of disturbance, its distance from this source should be equivalent to at least 5 x the hydraulic diameter of the ducting. Examples of sources of disturbance FAN SILENCER DAMPER COIL Hydraulic diameter CIRCULAR DUCT BEND MIN 3xdh BRANCH d = D h Ø D RECTANGULAR DUCT d = h 2xHxB H+B H ADAPTER EXTRACT AIR SUPPLY AIR B AIR HANDLING UNIT 2 www.swegon.se AIR HANDLING UNIT Specifications are subject to alteration without notice.

1 Drill an opening in the duct. 35 mm dia. opening for smoke detector without mounting bracket. 50 mm dia. opening for smoke detector with mounting bracket (see item 10). 2 Do not cut this end! End plug. Measure the ventilation duct. Cut the tube to an appropriate length, if needed. The tube should penetrate 90% of the duct diameter into the duct. Insert the end plug. 3 Lock the tube in position by means of the stop screw. Slip the seal onto the tube. Insert the tube in the bottom of the detector housing. IMPORTANT! The arrow on the plastic cover must point in the same direction as that of the air flowing through the duct. 4 Mount the tube and the detector on the duct. Secure the detector housing at the 3 points indicated by the arrows. Specifications are subject to alteration without notice. www.swegon.se 3

5 Flow indicator. CAUTION! The indicator doesn't rotate; it rocks. If the indicator doesn't move at all, it is advisable to consider relocating the detector. 6 Insert the block. 7 Electric wiring. If only one smoke detector is connected to the system, install the final resistor (2,2kΩ) in this detector. If several smoke detectors are to be connected to one control unit, wire the final resistor (2,2kΩ) in the last detector in the loop. Fit only one resistor per loop! Connect the electric wiring as shown in the wiring diagram. 4 www.swegon.se Specifications are subject to alteration without notice.

8 Performance checks. Check that the detector operates correctly. Expose the detector to smoke from a match or a suitable spray for testing smoke detectors. 9 Secure the cover by means of screws. Fit the cover on the detector. Do not drill any holes in the plastic cover for fitting identification plates or the like. Doing so will cause leakage, which will seriously impair detector performance. Specifications are subject to alteration without notice. www.swegon.se 5

10 ELQZ-1-428-2-1 Mounting bracket for a circular duct or an insulated rectangular duct. The mounting bracket enables the detector to be installed on a duct having a diameter as small as 100 mm. Secure the legs of the Fäst bracket beslagets to the duct. ben på kanalen. Håltagning Opening: Ø 50 mm Ø 50 mm. Beslaget The bracket är lätt att is easy böja/forma to bend/form så att det to passar fit on runda circular eller or plana flat kanaler. duct surfaces. Beslaget The bracket levereras is plant. supplied completely flat. Circular Rund kanal. duct Rubber Gummitätning. seal Rubber Gummitätning. seal Insulated Isolerad plan kanal. rectangular duct FINAL INSPECTION Make sure thatthe arrow on the detector cover points in the direction of airflow. Check that the cover and its gasket seals properly against the base and that nothing is lodged in between them, such as insulation. Check that the plug is properly seated in the test hole. Check that the flow indicator indicates airflow (is rocking). It is advisable to test the performance of the detector in full scale. Fault tracing. The smoke detector indicates a service alarm. The detector has become fouled and needs to be cleaned. This can appropriately be done by vacuum cleaning or by carefully blowing surfaces clean with compressed air. The service alarm may trip sooner than expected if the newly installed ducting hasn t been properly cleaned before the system is commissioned. The smoke detector initiates an alarm when no smoke is present. The smoke detector has been located where condensation can form inside it, such as outdoors, in a cold attic, a kitchen or the like. An alarm is indicated by the control unit only. Measure the resistance of the loop (2,2kΩ) from the control unit. Check that the control unit is OK by wiring the final resistor to the smoke detector output on the control unit. Use a voltmeter to check that 24 V DC with the correct polarity is present in the socket below the detector. 6 www.swegon.se Specifications are subject to alteration without notice.