FCR 05, FCR 07. Power factor correction controller. User and service manual

Similar documents
FCR05, FCR07. Power factor correction controller. User and service manual. version 3.4 (FW version 8.91 and newer)

FCR06, FCR12. Power factor correction controller. User and service manual. version 3.1

DKG-108 POWER FACTOR CONTROLLER

03.03.mmm REV.2 09/01

RKR-1T12C Hi-Tech REACTIVE POWER CONTROLLER USER GUIDE

Varlogic NRC12. Power factor controller. User manual

User Manual. Dryer Controller M720

Small in size, with grand features USER GUIDE Elle-même petite, mais avec caractéristique grand

Dryer Controller M720

BS-316. Gas detection control panel up to 16 inputs. Installation operation manual

ALPTEC Power factor controller

User manual CLIMATIC 200/400 - Controller. Providing indoor climate comfort

SUPERINTEND VRE-08/16/32/64

DIGITAL ALARM UNIT Model ALU-AP

AGC 200 Advanced Gen-set Controller OPERATOR S MANUAL

Lubrication cycle IP Enclosure Rating. 110 VAC, 220/230 VAC (50/60 Hz) Alarm Fault Relay Contacts. IP-55 (Liquid tight connector)

DC VOLTMETER DCV-10 / 10A / 10C / 10S / 10CS / 11 / 11A / 11C / 11S / 11CS. A4741 / Rev.1

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

POWER FACTOR CORRECTION SYSTEMS USER MANUAL

User Manual 120/240/300 Outdoor Motion Detector

ENERGY LIGHT USER S GUIDE ENERGY LIGHT USER S GUIDE

Installation and Operating Manual

ECL Comfort 110, application 116

1. Instruction. 1.5 Warranty Comar Condensatori S.p.A. guarantees its own products for twelve months from purchase

COMPUTER plus T8/14 INSTRUCTION MANUAL

Thermal protection device for electric units

VERTEX VT10 SERIES PID OPERATION MANUAL MICROPROCESSOR BASED PID CONTROLLER

Module Features are-configurable, no module jumpers to set

MO n : 12JMC rév A

IP65 High Bay Dual Sense Sensor

Operating Manual RCM420

OPERATION MANUAL. Daikin Altherma indoor unit EKHVMRD50ABV1 EKHVMRD80ABV1 EKHVMYD50ABV1 EKHVMYD80ABV1

DX2002 OPERATING AND PROGRAMMING INSTRUCTIONS

Instruction Manual PCS-400-XY. Pump Controller. Y=2: 4-20 ma Y=6: 0-10 VDC X=5: 1-5 VDC. 4 Pump Control Relays 1 Alarm Relay 1 Signal Fail

Element. Controller. Manual for use and maintenance. Element. Climate Controller. Ag/MIS/UMGB /17 Rev 1.0 P/N:

Dixell Installing and Operating Instructions release 7.0

I/A Series 716C 1/16 DIN Temperature Controller

Dual Technology Wall Switch Occupancy Sensor. Manual & Specification

CTT8 TEMPERATURE MONITOR DEVICE

DIGITAL TEMPERATURE RELAY TR-100

64.7 Ø85. (1) Sensor inset (2) Lens pluggable. (3) Protection cover (covers the high-voltage terminals). (4) Ceiling (drill hole Ø70mm).

Table of Contents 1. OVERVIEW SYSTEM LAYOUT SPECIFICATIONS FUNCTION... 11

M15051) INSTRUCTION MANUAL

ASSEMBLY AND USE INSTRUCTIONS R8 POWER FACTOR CONTROLLERS

Carbon Monoxide Transmitter

Installer Manual KNX Touchscreen Thermostat

Mark 25 Ultrapure Water Conductivity Analyzer

Halton SAFE / 7.14 user guide and installation instructions

Smart Temp. Model

OVEN INDUSTRIES, INC.

Interactive Fire Control Panel IFS7002 one signal loop Instruction Manual

BSR Addressable Fire Detection control panel. Installation operation manual

PIR/INT & PIR/INT-D. Batten mount PIR detectors. Product Guide. Overview. Features

Safety Temperature Limiter STL 50 Certified to DIN EN (replaces DIN 3440)

Process & TeMPerATUre UniversAl input DigiTAl MeTers

DOCUMENTATION IPS640

DOCUMENTATION IPS640

INDEX 1- Introduction The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops The Control Panel 4 and 8 Loops...

EXPERT TRI-STAR. Temperature controller. User s Manual

TERMO-Blok TERMO-Extra TERMO-Blok PTV

Phone-A-Stat. MODEL Command Center With Thermostat Operation, Maintenance & Installation Manual. Introduction.

JDDT1 - Single Stage Digital Thermostat

Eswa DC-1. Thermostat for Floor Heating

Before using your air conditioner, please read this manual carefully and keep it for future reference. ACDC12B

VERSO-P, VERSO-R Series Air Handling Units with C3 Control System Electrical Installation and Operation Manual

LCF Touch Modbus Datasheet Application Security Advice Caution

PACSystems* RX3i. Thermocouple Input Module, 12 Channels, IC695ALG412. GFK-2578B October 2011

OPERATING INSTRUCTIONS

D-TECT 2 IP. GJD230 IP Motion Detector

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63

Menu Structure Power Factor Controller CR4.0

Integrated PIR detectors

Electronic Temperature Controller 70304,

DS 96/48 P. Digital indicator. Short manual 41/33-89 EN Rev. 00 DIM

EBMPIR-MB. Batten mount PIR detectors. Product Guide. Overview. Features

SAS6000UTK-7 UNIVERSAL THERMOSTAT

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS

ION7300 Series Revenue Meter

CONTROLS INSTRUCTIONS MANUAL ENGLISH

Power Management Module-c (PMM-c)

F4 Process Controller Installation and Operation Guide

DIESEL ENGINE CONTROL UNIT DCU USER S MANUAL - N-2000 Lillestrøm, Norway Tel: (+47) Fax: (+47)

OPERATION MANUAL. Indoor unit for hot water heat pump system and options EKHBH016AB EKHBX016AB

Process Alarm Module RTA 421

MTDPC. (also known as MTPC) INSTALLATION AND OPERATION MANUAL MultiTrode Pump Controller

SCHMIDT LED Measured Value Display MD Instructions for Use

R1000 / R1040 / R1080

ND4000 Manual Marine Hydraulics

ORP (mv) Controller Model: ORP-XP2. UP DOWN ENTER Time & Date Main Menu Alarm Reset

, ,

DPC-1 Programmable digital thermostat with communication Versión 2.0. Technical Information. Ref: N

IP65 High Bay Dual Sense Sensor

DIGITAL LIGHT CONTROLLER

FIL-SPL Flow-through heater for central heating USER MANUAL

Sierra Model 951 Digital Flo-Box. Instruction Manual Part Number IM-951 Revision A 09-05

TE809-Ats Instructions Manual

Insulation fault evaluator EDS460-DG

Software Version 2.01 LEVEL MONITOR MODEL 220

APC BC300 Series 40kW 208/450/480V User Guide

Operating Manual VMD420

Transcription:

FCR 05, FCR 07 Power factor correction controller User and service manual version 2.3 Czech Republic Czech Republic 1

Content 1. Control and signal elements... 3 2. Device description... 4 3. Instruction manual for connection and operation...4 4. Description of the function... 5 5. Installation of the device... 5 6. Controller parameter setting... 6 6.1. Target cosφ setting (CoS)... 7 6.2. Current transformer ratio setting (Itr)... 7 6.3. Automatic detection of compensation stages (Aut)...8 6.4. Deceleration of regulation at over compensation (Sht)...8 6.5. Manual setting of compensation stages (StP)...8 6.6. Discharging time (dit)... 8 6.7. Delay for disconnection (dip)... 8 6.8. Fixed capacitor stages (FSt)... 8 6.9. Connection configuration (Con)... 9 6.10. Alarms... 9 6.11. Regulation to average or instantaneous power factor (_CS)...9 6.12. System frequency (Fr)... 10 6.13. Password for entering setup mode (Cod)...10 6.14. Restart (res)... 10 7. Displayed values... 10 7.1. Cosφ... 11 7.2. Apparent current... 11 7.3. Voltage... 11 7.4. Powers... 11 7.5. De-compensation delay... 11 7.6. Number of stage circuit closings...11 8. Manual operation... 11 9. Alarm notification... 11 10. Technical features... 12 Czech Republic Czech Republic 2

1. Control and signal elements Picture 1. Description of front control panel 1. LED ind it is ON in the case of inductive cosφ 2. LED cap it is ON in the case of capacitive cosφ 3. LED cosf it is ON when instantaneous or average value of cosφ is shown on the display 4. LED amp/volt it is ON when value of measured current/voltage is shown on the display 5. LED alarm it is ON when alarm is present 6. LED STAGES LEDs indicate status of each stage individually 7. Buttons for regulator control Picture 2. Device terminal connection Czech Republic Czech Republic 3

2. Device description Power factor correction regulator FCR05 / FCR07 is designed for power factor control in low voltage system networks 50/60 Hz. FCR05 / FCR07 is small but powerful regulator, which allows to control compensation cabinets with 5 respective 6 contactor stages. Functions and design of regulators FCR05 and FCR07 are the same. FCR07 regulator is just equipped by more controlled outputs (6 7 / alarm). FCR05 and FCR07 controller measures also following parameters: Power factor, power factor inductive at consumption, power factor capacitive at consumption Phase voltage of measured phase, THDU and odd harmonics up to 19 th Current in the measured phase, THDI and odd harmonics up to 19 th Apparent power, active power, reactive power and allowed reactive power Number of connections of each stage 3. Instruction manual for connection and operation Default parameters are set to the device in production, according to the table 1. Supply voltage has to be taken from regulated network, because it is used also for voltage measuring circuit. Value of this supply voltage is on the product label. Current for current measuring circuit can be take from any phase. By default the connection of the regulator is that voltage is connected between phase L1 N and current transformer to the phase L1. The connection of device is shown at picture 3. Commissioning procedure: 1. Make connection according to connection diagram at picture 3. 2. Connect supply voltage. In the case that the value of current is lower than 10 ma, the display will show ---. If not, the display will show instantaneous value of power factor. 3. Press button SET for the time longer than 5 seconds. After that device will switch to the setup menu and on the display will appear parameter CoS. 4. By pressing the button SET once again display will show target cosφ. Setting the targeting values of cosφ is done via buttons (+) and (-). 5. Confirmation of the set value CoS is done by pressing the button SET. 6. Press the button until the parameter Itr will appear on the display. This parameter means transformer ratio of current transformer. 7. Press the button SET and on the display will appear set value of transformer ratio (default value is 1). 8. Using the buttons, set known value of transformer ratio. 9. By pressing button SET confirm set value. On the display will appear again the parameter Itr. 10. Now again, by using the buttons, move to the parameter Aut and by pressing button SET confirm it. Via button switch to the value on and via button SET confirm set value. Device automatically perform phasing of measured voltage, current and detection of connected compensation stages. All parameters will be saved to the internal memory. When the detection is finished, parameter Aut will be automatically changed to the value off. 11. Verify if detection of power of all stages was done correctly. Press button SET for time of 5 seconds to enter setup mode. By pressing button move to the parameter StP. Press again button SET and LED 1 of first stage will turn On. Another pressing the button SET will make the value of the power of the first stage be shown on the display. If the value is not correct, it should be changed by pressing buttons, until the correct value. In the case of capacitor stage, LED cap, placed at the left side of display, has to light. If the power is correct press again button SET and on the display will appear again parameter StP. Via button move to another stage and LED 2 will turn On. Repeat the same procedure the same way like for the first stage. Following the same control or setting of all stages should be done. At the end press button SET until value of power factor will appear on the display. 12. If everything is set correctly, on the display is shown real instantaneous value of power factor. Regulator FCR05 or FCR07 is ready for operation. Other parameters may remain on having the default values, that were made by the manufacturer. In the case that Czech Republic Czech Republic 4

further changes are necessary, the user should follow detailed manual given in chapter 6. 4. Description of the function Device digitizes measured phase voltage and current in one phase. Then, from those values, parameters like: power factor, effective values of voltage and current, apparent power and reactive power, are being counted. Calculation of the compensation power that is needed is done by using the value of allowed reactive power, which is set in the device in the form of requested power factor. According to its size, regulator will switch on or switch off appropriate capacitor stages. Within the scope of each power level, regulator uses method of circle switching. All the time connects this stage at appropriate power level which was switched off for longest time. Everything is made so that regulator will reach optimal compensation in one regulation cycle with minimum number of switched stages. 5. Installation of the device Controllers FCR05 and FCR07 are designed in metal box, which provides perfect EMC shielding. Controller's design also provides panel mounting, into the hole 91 x 91 mm. The connection of the wires is from the back side of regulator, to the terminal box. Measuring and auxiliary voltages are being taken from supply voltage, which must be protected by fuse 6 A. Picture 3: Connection of measuring circuits Picture 4: Position of controller in the compensation system Location of the current transformer has to allow both current of the load and the current of the capacitor to be measured together. The complete connection is shown at the picture. There is only one rule that should be considered. Stages with the same power have to be connected side by side. For example: Stage No. 1 Stage No. 2 Stage No. 3 Stage No. 4 Stage No. 5 Stage No. 6 6,25 kvar 6,25 kvar 25 kvar - 12,5 kvar 12,5 kvar However, ranging the powers in accordance is not necessary. There could be even gaps between particular power levels. For example, stages 1 and 2 could be connected, then stage 3 disconnected, stages 4 and 5 connected and so on. Czech Republic Czech Republic 5

6. Controller parameter setting Picture 3. Connection of FCR05 / FCR07 controller Considering various usage of controllers FCR05 and FCR07, there is a number of programmable parameters. For easy start, regulator is set to default parameters, made by manufacturer. Set parameters are stated in the following table. For fast start, the parameters that should necessary be set are cosφ and transformer ratio of current transformer. Eventually, transformer ratio of voltage transformer could also be set. Further more, there are also other parameters that could be set, in accordance to the customer request. In order to avoid any unwanted reprogramming of the device, it is possible to protect access to setup mode by setting the three digits password. By default, new controller does not have any password protection activated. It is recommended to activate password protection after setting all parameters. After the protection has been activated, it is possible to see all set parameters, but not to change any of them. For checking respective setting set parameters follow those instructions: 1. Press the button SET for 5 seconds. Device switches to the setup mode and parameter CoS will appear on the display. This is a symbol of parameter whose currently set value will appear after another pressing of button SET. 2. Via buttons, is possible to set the requested value of specified parameter. 3. By pressing the button SET again, regulator will save changed value to the internal memory and on display symbol of the set parameter will appear again. Via buttons, it is possible to move to another parameter (see the table below). 4. If the offered parameter is not the one, which is requested to be modified, follow via buttons, to the requested parameter. 5. Regulator turns back automatically from setup mode after 1 minute without any keyboard action, or by repeated pressing of button SET during returning from parameter value setting. Important While setup mode is activated, device is not regulating. Controller will not react to the power factor changes, neither to the changes of other monitored variables. Alarm output will not operate as well. Czech Republic Czech Republic 6

Parameter Description Factory setting Setting range CoS target cosφ ind 0,98 0,80 cap.... 0,80 ind. in steps of 0,01 Itr current transformer ratio 1 1... 600 in steps of 1 Aut automatic detection of compensation stages off on / off Sht deceleration of regulation in the case of over-compensation 60 0... 999 s in steps of 1 s StP manual setting of compensation stages 0 0... 99,9 kvar cap. in steps of 0,1 or overdrive of 1 dit discharging time for contactor stage 30 5... 900 s in steps of 5 s or overdrive of 50 s dip delay for disconnection of contactor stage 15 5... 900 s in steps of 5 s or overdrive of 50 s FSt fixed capacitor stages Aut Aut / off / on Con connection configuration 0 0... 300 in steps of 60 ULA under-voltage alarm off on / off at off alarm does not operate UHA over-voltage alarm off on / off at off alarm does not operate IHA over-current alarm off on / off at off alarm does not operate COA alarm for cosφ, that is permanently over set limits off on / off at off alarm does not operate rsa alarm for exceeding of maximum number of stage circuit closing _CS regulation to the average power factor on off on / off at off alarm does not operate on / off at off device regulates to instantaneous cosφ Fr system frequency 50 50Hz / 60Hz Cod password for access to setup mode 000 any three digits number 001... 999 RES reset to the factory setting - - Table 1. Setup menu parameters Note Overdrive is activated by permanent pressing of button or. 6.1. Target cosφ setting (CoS) Press the button SET at least for 5 second for entering setup mode. On the display will appear parameter symbol CoS. After another pressing of button SET display will show set value. Via buttons, set new requested value in the limits from 0,8 inductive to 0,8 capacitive. Another pressing of button SET saves new value to the memory and on display it will appear again symbol CoS. 6.2. Current transformer ratio setting (Itr) If setup mode is activated, move by buttons, to the parameter Itr. After pressing button SET, the set value will appear on the display. Via buttons, is possible to change value of transformer ratio. Another press of button SET saves new value to the memory and on display, symbol Itr will appear again. It is important to have in mind that the value which is set, is ratio itself. It means that, for example, if primary nominal current of transformer is 50 A and secondary is 5 A then set parameter value is Itr = 10. Caution Measurement range of the current inputs is from 10 ma to 6 A. Maximum of the current transformer ratio is 3000 / 5 A. If the current value is over 5,3 A, alarm will be started, in the case it is enabled. Czech Republic Czech Republic 7

6.3. Automatic detection of compensation stages (Aut) Another parameter in the menu is function Aut. After pressing of button SET, the display will show off. Via buttons, change to the value on. After the pressing of button SET automatic detection will start to detect connected stages. The symbol Con will appear on the display, and first capacitor stage will be switched on and off 6 times in the cycle of 20 seconds. Detection of controller connection to the system is followed by detection of power of connected capacitor stages. During detection, the measured values of each stage are shown on the display. Measured values are being rounded on 0,5 kvar. After the detection is finished, the regulator will switch parameter Aut back to off. Important In some cases controller is not able to make automatic detection and in place of measured power shows zeros. It can happen in places with very fast changes of network parameters, where measured values will not be correct. In this case regulator shows Er1 and it is necessary to set parameters manually, after detailed network measurements. 6.4. Deceleration of regulation at over compensation (Sht) This parameter is represented by symbol Sht. This function is used for slowing down the regulation during overcompensation. At under-compensation regulation is slowed down according to average power factor. This function assures reduction of switch on/off operation of contactor stages. After pressing the button SET, display will show set value of deceleration. By buttons, it is possible to change value and button SET saves this into the memory. Current situation of regulation deceleration during over-compensation is shown under parameter Sht, in the menu of measured values. 6.5. Manual setting of compensation stages (StP) After parameter Sht the parameter that follows in the menu is StP. Pressing the button SET will enter the sub menu, where it is necessary to select the stage, which has to be set, via buttons,. Selected stage will be signalized by green LED. By pressing button SET on display will appear set value of stage that is signalized by relevant green LED. Via buttons, it is possible to change the value and by pressing button SET to save this into memory. Via buttons, select another stage, which must be set and follow the same procedure as before. After setting of all stages, keep pressing button SET until display will show StP and all LED's will be off. 6.6. Discharging time (dit) For setting the absorption of stages, parameter dit is available in the menu. By this parameter, it is possible to set, for each stage separately, suitable time for capacitor discharge. This time can be set from 5 to 900 seconds. Default factory setting value is 30 seconds. Setting procedure is according to the same rules as another parameters explained before. 6.7. Delay for disconnection (dip) This parameter is represented on the display by symbol dip. It is the minimum time for contactor stage circuit closing. It is possible to be set from 5 to 900 seconds. Setting procedure is according to the same rules as another parameters explained before. 6.8. Fixed capacitor stages (FSt) On the display it is represented by symbol FSt. This parameter allows to set stages as a fixed ones. The regulator is not counting those stages for regulation cycle. Each stage can stay in three working regimes. Aut stage is normally regulated by controller off always off (status indication LED blinks red) on always on (status indication LED blinks green) Setting procedure is according the same rules as another parameters explained before. Czech Republic Czech Republic 8

6.9. Connection configuration (Con) If the controller is connected according the connection diagram on the picture 3 correction angle is 0 which is default factory configuration. If the regulator is not connected according to this connection diagram, then it is necessary to make angle correction by displacement of measuring current and voltage. This parameter allows to set angle movement from 0 to 300 in steps of 60. On the display symbol Con will be shown. After pressing the button SET, the display will show set value. Via buttons, it is possible to change the value. Another press of button SET will save new value into the memory. 6.10. Alarms Table 2. Phase shift setting for supply and measuring voltage 230 V AC Controller is able provide with five different alarms. For the alarm remote signalization, the output relay 6 (7) is performed. When there is any alarm parameter enabled in the setup, then output 6 (7) is automatically used for remote alarm signalization but only in case that power of last is 0! Otherwise the alarm will not affect last output and will be signalized on display only. Individual events, which activate alarms are possible to be defined by following procedure. In setup mode move to the first item of alarm event, which is alarm at under-voltage. On the display symbol ULA will appear. After pressing the button SET, display will show if alarm is enabled or disabled. Value off means that alarm is disabled. Value on means that alarm is enabled. Via buttons, it is possible to change on / off. By pressing button SET new value is saved into the regulator memory. Following the same procedure sets other alarm events. Alarm Condition of activation ULA measuring voltage < Unominal - 20% UHA measuring voltage > Unominal + 14% IHA COA measuring current on regulator terminals > 5,3 A it is permanently not possible to reach set power factor for 15 minutes rsa if any of contactor stage overpasses maximum allowed circuit closing = 99.999 6.11. Regulation to average or instantaneous power factor (_CS) This setting defines if regulator will regulate slow stages to average or instantaneous power factor. If the set value is on then usage of contactor stages is affected by average power factor. If the set value is off then regulation is performed only according to instantaneous power factor. In setup mode move via button, to the item _CS. After pressing of button SET display will show set value on / off. Via buttons, it is possible to change this value. Another pressing of button SET saves new value into the regulator memory. Czech Republic Czech Republic 9

6.12. System frequency (Fr) Parameter Fr defines the system frequency of network which is important for correct calculation of fundamental signal. Factory preset value 50Hz is common for most of the countries. 6.13. Password for entering setup mode (Cod) Thanks to password is possible to protect regulator against unauthorized configuration. Without proper password knowledge it is possible only see set parameters but not to change them. Password is set as three digit number. In setup mode move via buttons, to the parameter Cod. After pressing of button SET display will show - - -. First dash from left side is blinking. Via button set number from 0 9 and confirm by button. Now second dash is blinking and first set number lights on the display. Keep the same procedure until last number is set. By pressing of button SET, password for entering setup mode is saved into the memory. From this moment it is necessary, for each change, type password in order to enter setup mode. Otherwise any change will not be accepted. 6.14. Restart (res) This function restores default configuration. It is last item in the menu and it is represented on the display by symbol res. Press the button SET and keep it. At the same time press the button. LED of capacitor stages will turn on and then slowly will start to go down. This cycle will repeat two times. After that, the display will show instantaneous value of power factor. Factory setting will be restored. Important After restart, it is necessary to set device again as well as make auto detection. 7. Displayed values Value choice, which will be shown on the display is independent on the operation of the regulator itself. It is possible to change it at any time. LED on the right side of display identifies sort of shown value. Shown values are divided to levels so that values in one level are closely related. For switching between particular levels use button and for changing screens within one level use button. Splitting of shown values to the levels is clear from following list. For returning to the instantaneous cosφ represented by symbol CoS press button SET. CoS instantaneous cosφ ics inductive average cosφ at consumption ċcs capacitive average cosφ at consumption IAP apparent current [A] thd THDI of current [%] H03 3 rd harmonic of current [%] UEF phase voltage effective value [V] thd THDU of voltage [%] H03 3 rd harmonic of voltage [%] ics inductive average cosφ at distribution H05 H05 5 th harmonic of current [%] 5 th harmonic of voltage [%] ċcs capacitive average cosφ at distribution.... H19 19 th harmonic of current [%].... H19 19 th harmonic of voltage [%] PAP apparent power [kva] PrL active power [kw] PLC reactive power [kvar] rcp allowed reactive power [kvar] Sht deceleration time [s] r_1 number of operation of 1 st stage r_2 number of operation of 2 nd.... stage r_7 number of operation of 7 th stage Table 3. Map of monitoring screens Czech Republic Czech Republic 10

7.1. Cosφ Displaying the cosφ is default indication. This value will appear on display after supply voltage connection and if in current input the current flow is 10 ma. Red LED on the left side of display marked as ind and cap indicates if measured power factor is in inductive or capacitive area. If measuring current drops below 10 ma, then regulator disconnects all stages and on the display will appear "- - -". By button it is possible move to average inductive power factor indication. At first, the display will show symbol ics and then after 1 second numeric value will be shown. Following the same procedure it is possible to move to average capacitive power factor represented by symbol ċcs. 7.2. Apparent current Pressing of button will move to another level - apparent current. Symbol IAP will appear on the display for 1 second. After that, the display will show effective value of apparent current on primary side of current transformer, assuming that correct transformer ratio is set in SET mode, under the parameter Itr. 7.3. Voltage This level is exactly the same as previous level, but for network voltage. 7.4. Powers Another level offers values of four powers. At the first position there is apparent power PAP, following by active power PrL and reactive power PLC. The shown value is allowed reactive power rcp which means the reactive power that can be present while the targeted cosφ is reached. 7.5. De-compensation delay This parameter Sht shows actual remaining time (seconds) to regulation action at over-compensation. Displayed value is decreased each second by square of difference between true control deviation and requested power factor value. 7.6. Number of stage circuit closings Number of stage circuit closings is divided to the six independent levels. For the first stage, the display will show symbol r_1 and after it disappears the number of first stage circuit closings will be displayed. By simultaneous pressing of buttons and SET this information can be erased. To another level, where information about second stage is, move by pressing the button. The rest of procedure is the same as for the first stage. 8. Manual operation Switching the regulator to the setup mode and by subsequent press of button and then SET, manual operation of compensation stages will be activated. On the display, symbol St1 will be shown for 1 second. After that, it will be replaced by actual value of cosφ, which is blinking (manual mode indication). Button allows to change stage status with respecting the set discharging time and delay for stage disconnection. It means that if the stage was disconnected, pressing the button will switch the stage on. If the stage was connected, the same button will switch the stage off. For another stage selection press button. After pressing this button, the display will show for 1 second symbol St2, representing another stage. The whole procedure is the same like for the previous stage. By pressing the button SET, manual mode can be deactivated. 9. Alarm notification If at least one of enabled alarm events appears, the alarm output relay No. 6 for FCR05 (No. 7 for FCR07) will switch on for 1 min and LED labelled alarm will blink. This LED will also blink after the alarm event disappears, until it gets cancelled by button SET. Alarm notification does not have any influence to regulator behaviour. The symbol of alarm sort is shown on the display after pressing of button SET. Another pressing the button SET will cancel shown alarm. If more alarm events happened, another event symbol will appear on the display. Keeping the same procedure, it is possible to follow till last alarm event is not canceled. In the displayed values mode it is possible to find out which values of alarm events activated alarm (chapter 7). Alarm event symbols are the same as symbols used during alarm setting in setup mode. Czech Republic Czech Republic 11

10. Technical features Parameter Value Supply voltage = measuring voltage 230 V AC 50 Hz (+10%,-15%) Frequency 50/60 Hz Current range 0,01... 5,3 A Current measurement accuracy (I > 200 ma) ±10 ma (class 5) Power consumption 3,2 VA Output channels number FCR 05 (FCR 07) 5 or 6 (6 or 7) Alarm output 250 VAC / 5A Switching power of relay contacts 250 VAC / 5A Range of requested power factor 0,8 ind.... 0,8 cap. Reconnection delay 5... 900 s Switching off delay 5... 900 s Compensation stages value setting manually / automatically Temperature limit -25 C... +70 C Front panel 97 mm x 97 mm Panel cutout 91 mm x 91 mm Site depth 55 mm Weight 0,65 kg Protection degree IP20 rear cover/ IP54 front panel Standards EN 61010-1, EN50081-1, EN50082-1 Czech Republic Czech Republic 12