Liebert DataMate (1-3 Ton) Warranty Inspection Check Sheet

Similar documents
Liebert InteleCool Warranty Inspection Check Sheet

Liebert CRV Warranty Inspection Check Sheet

Liebert Small System MCD and PFH Condensers (1-5 Ton) Warranty Inspection Check Sheet

Liebert Xtreme Density Chiller (XDC) Unit Warranty Inspection Check Sheet

Liebert Fin/Tube Condenser Warranty Inspection Check Sheet

Service Step by Step Trouble-Shooting Check-List

Liebert Challenger 3000/Liebert Challenger ITR with Liebert icom Control. Operation & Maintenance Manual - 50 & 60Hz

Installation, Operating & Maintenance Instructions. Air Handler Models: AH & AV

/ No. (\01. la-ejl~ Withthe MainDisconnectOFFcheckthe following: Owner Address I~O ~.Cc:t\". ~\\A. Contact Name, Contact Telephone # Installation Date

Series 9. Commissioning Checklist. MISSION CRITICAL Air Conditioning Systems. ClimateWorx International Inc.

BasicTroubleshooting Information and Guidelines

Installation, Operating & Maintenance Instructions. Horizontal Models: LH & HL

SECTION COMPUTER ROOM AIR CONDITIONING SYSTEMS

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

Preventative Maintenance Tables

CROWN. Boiler Co. Santa-Fe Series. Hydronic Air Handlers INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

INSTALLATION AND OPERATIONAL MAINTENANCE MANUAL

2 THERMOSTAT DETAILS 3 REMOVING OLD THERMOSTAT

Installation, Operation, and Maintenance Manual

MASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

Liebert Datamate: R-407C Parts Manual

IF79 CAUTION CONTENTS YOUR THERMOSTAT REPLACES 1 PREPARATIONS. Installation Instructions for. Heating & Air Conditioning

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

SA Series Start up Report

Panel Fan Series Operators Manual (Galvanized and Polymer)

RHGN-H: COMMERCIAL AIR HANDLER WITH VARIABLE FREQUENCY DRIVE (VFD) NOMINAL 10 TONS R-410A REFRIGERANT 2-STAGE AIR-FLOW

F1 Series. Installation, Operation & Maintenance. Indoor Air Handing Units WARNING WARNING WARNING NOTICE QUALIFIED INSTALLER

SA Series Startup Form

BESF Box Ventilator USA CAN. Product Information. Mechanical Installation. ... Chapter 3. Electrical Installation. ... Chapter 4

Verde GSE PCA Bridge and Ground Mount Units 30/45/60/90/120 Tons. Installation and Maintenance Manual

Emerson Blue Easy Set 1H/1C

1F Non-programmable Electronic Digital Heat Pump Thermostat INSTALLATION AND OPERATION INSTRUCTIONS

MANUAL INSTALLATION. Fan Column. v200 Issue Date: 01/18/ Price Industries Limited. All rights reserved.

Safety & Installation Instructions

INSTALLATION AND OPERATIONAL MAINTENANCE MANUAL

Construction Standards Page

A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems.

PRO Installation. Touch Wi-Fi Thermostat

Liebert CW Thermal Management System

DISPOSER CONTROL CENTER

CHILLER. Model CH3000. Operator s & Installation Manual

RSIF power venter USA CAN READ AND SAVE THESE INSTRUCTIONS! Installation and operation manual. Product information Chapters 1 + 2

RSIF Power Venter USA CAN. Product Information. ... Chapters Mechanical Installation. ... Chapter 3. Electrical Installation. ...

2 THERMOSTAT DETAILS 3 REMOVING OLD THERMOSTAT

SYSTEM 2000 CHILLED WATER (CAC) EC SERIES -INSTALLATION OPERATIONS AND MAINTENANCE MANUAL-

Cased Aluminum Coils "Dedicated Upflow / Downflow" Convertible to horizontal with separately purchased kit

Chromalox. Installation, Operation. Portable Industrial Unit Blower Air Heater Types SDRA and SDRA-RG RENEWAL PARTS IDENTIFICATION

L A signature series TA T N E RE O, A L L A T S IN

PRO Installation. Thermostat Wi-Fi

Installation, Operation & Service Manual

Liebert DSE Thermal Management System

Trouble Shooting Guide FAA, 3-phase (D3631)

Surna 25-Ton Chiller Operating & Maintenance Manual

Direct Fired Heater Model AD Specification

Emerson Inspire 1HDEZ Installation Instructions. Thermostat/Interface Equipment Control TROUBLESHOOTING

1F98EZ-1421, Easy Install

Installation, Operating & Maintenance Instructions. High Performance Horizontal Models: HH & CH

Bug Killers. Read all instructions before using the bug killer. Contents

USER'S MANUAL PGE Single Package Rooftop

Internal ridged board 1" x 1.5 foil face installation shall be installed on roof, walls and base of casing.

PRO Installation. Touch Wi-Fi Thermostat

BK17 Heater. Read all instructions before using the heater. Contents

40 RM/RMS Packaged Air-Handling Units

User s Information Manual

INSTALLATION AND SERVICE MANUAL FOR THE SERIES 1000-P FAN SERIES (PNEUMATIC CONTROL) SERIES 1000-H FAN SERIES (HYDRAULIC CONTROL) GEN 2

S150 S300 CONSTRUCTION HEATERS. Rev: August 15, 2008 SERVICE AND MAINTENANCE MANUAL No PLEASE RETAIN FOR FUTURE REFERENCE PRODUCTS

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

For an administrative fee of $9.97, you can get an un-locked, printable version of this book.

INSTALLATION AND SERVICE MANUAL FOR THE SERIES 2000 & SERIES 3000 FAN SERIES GEN 2

URS-1 SERVICE AND PARTS MANUAL SERIAL NUMBERS: UP TO

RSV Chimney Fan USA CAN. Start Up and Configuration. ... Chapter 5. Maintenance and Troubleshooting... Chapter 6. Job Name: Installer:

1F Non-Programmable Electronic Digital Multi-Stage Thermostat INSTALLATION AND OPERATION INSTRUCTIONS

Standard and CELDEK Evaporative Cooler Modules Installation, Operation, and Maintenance Manual

M2 Series Startup Form

T8600D Chronotherm IV Deluxe Programmable Thermostats

BK5 Bug Killer. Read all instructions before using the bug killer. Contents

INSTALLATION AND SERVICE MANUAL FOR THE SERIES 2000 & SERIES 3000 FAN SERIES GEN 1

Liebert PDX and PCW Thermal Management Systems

Installation Instruction

Instruction Manual. Bottle Cooler. Models HBC-50 (-S) HBC-65 (-S) HBC-80 (-S) HBC-95 (-S) hoshizakiamerica.com. Issued: Revised:

AquaSaver DISPOSER CONTROL CENTER Installation Manual. Model AS-101K

KITS COMMON TO HEATING AND COOLING EQUIPMENT 504,652M 03/04. Supersedes 503,249M

MFD Mechanical Fireplace Damper

Locally Controlled Bug Killers. Read all instructions before using the bug killer. Contents

Deluxe Programmable Thermostats

Packaged Air Conditioning Units. Owner s Guide to Operating and Maintaining Your Air Conditioner. This manual should be left with the owner.

INSTALLATION INSTRUCTIONS

Model No. Serial No. Original Purchaser. Address. City and State Zip. Dealer. Address. City and State Zip. Installation Date Name Signature

Installation Instructions

AFI2538AE* AFI 2538AE*0, MFI2568AE* MFI2568AE*0 CAUTION

Three Phase Simplex. Installation (937) Installation Instructions and Operation/Troubleshooting Manual. Installation of Floats.

CAUTION. No-Load Performance, Controls in Normal Position

AXPR Wall Mounted Axial Panel Fans

BESF Box Ventilator. Installation & Operating Manual USA CAN READ AND SAVE THESE INSTRUCTIONS

Bottom Mount Refrigerator---Technical Information

Intelligent Electronic Enclosure Thermal Management Systems

MARVAIR SCHOLAR III HEAT PUMPS & AIR CONDITIONERS MODELS VAIA & VAISA EXPLODED VIEW PARTS ID

Mortex INSTALLATION INSTRUCTIONS AIR CONDITIONING & HEAT PUMP INDOOR COILS

Operation Manual. AvantAC Classic Bus Air Conditioning Units. Carrier Transicold China

AllStyle Coil Company, LP 7037 Brittmore Houston, TX Phone Fax

Transcription:

The following information must be fully completed and forwarded to your local Liebert sales office to establish your equipment warranty. Installer Address Owner Address Owner e-mail address Installation Date Was the unit received in good condition? Yes No If no, has the carrier been notified? Yes No Have the manuals been kept with unit? Yes No PRE-START-UP DataMate Serial Number DataMate Model Number Condenser / Drycooler Serial Number Condenser / Drycooler Model Number Compressor Serial Number Compressor Model Number Arc flash and electric shock hazard. Open all local and remote electric power disconnect switches, verify with a voltmeter that power is off and wear personal protective equipment per NFPA 70E before working within the electric control enclosure or any hazardous voltage electric connection enclosure. Failure to comply can cause serious injury or death. Page 1 of 5 2014 Emerson Electric Co. All rights reserved. PSWI-8542-403-RE Rev.3 10/2015

With the electric power to the unit OFF check the following items as noted: Internal piping clamps tight and secure on Evaporator and Condenser. Field piping properly supported and secure. Hot Gas line pitched according to User Manual. Field piping trapped according to User Manual. Field piping properly sized according to the User Manual. ALL electrical connections are tight and properly terminated on Evaporator and Condenser. Heat Rejection Interlock wiring has been correctly installed between Evaporator and Condenser. Equipment is installed level. Remove all debris from unit area. Water supply line(s), condensate pump, or gravity drain connections are tight and do not leak. Drain lines are open and clear of dirt and debris. Verify Proper Water/Glycol Maintenance/Treatment has been performed. Strainers Yes No (if no, conformation available please inform end user) Shut off valves Filters are installed in the unit? Filter Size Quantity Blower drive system rotates freely. Main fan HP Voltage Page 2 of 5 2014 Emerson Electric Co. All rights reserved. PSWI-8542-403-RE

Evaporator Inspection Liebert DataMate (1-3 Ton) Risk of electric shock, contact with high speed moving parts and hot surfaces, Can cause serious injury or death. Use extreme caution when working inside the unit cabinet of an energized unit near bare live hazardous voltage terminals, high speed moving parts such as blower wheels and shafts, pulleys, belts, EC fan blades and hot surfaces such as motors, heater elements, hot gas lines, and humidifier bottle 1. Check voltage at disconnect and record. L1- L2-L3 L1-L3 2. Close all local and remote electric power disconnect switches. Verify with a voltmeter that power is on and the supply voltage matches the marked unit voltage rating. Arc flash and electric shock hazard. Wear personal protective equipment per NFPA 70E before working within the electric control enclosure or any hazardous voltage electric connection enclosure. Use extreme caution when checking the status of live hazardous voltage circuits. Failure to comply can cause serious injury or death. Check unit electrical phasing with a phase meter. If phasing is incorrect, change wiring at input source to unit. Do not change any unit or component phasing. Check the compressors for proper rotation by bumping the contactors and watching the gauge pressures. If the pressures are equalized and the compressor sounds noisy, then compressor is running backwards. 3. Check and record control voltage transformers for proper output. (Secondary voltage should not be under 23 VAC or exceed 27 VAC under load, change tap if necessary). T1 Volt 5. Enable Fans and record Main Fan amperage. 6. Enable reheats by increasing the temperature set-point. Record amperage. Disable Reheats after test. Page 3 of 5 2014 Emerson Electric Co. All rights reserved. PSWI-8542-403-RE

7. Enable Humidifier and record amperage. Check for leaks at all piping connections. Disable Humidifier after test. Risk of electric shock and contact with extremely hot parts, can cause serious injury or death. Use extreme caution when working near bare live hazardous voltage terminals or energized humidifier bottle. 10. Check condensate pump for proper operation by filling pump with water. Check for leaks at all piping connections. Record pump amperage. (If Applicable) Risk of electric shock and contact with hot motor surfaces, Can cause serious injury or death. Use extreme caution when working near bare live hazardous voltage terminals or the energized condensate pump motor. Do not remove the condensate pump electric connection terminal cover. Use extreme caution and do not spill water on the motor or the electric connection cover. Chilled Water Units Decrease temperature setpoint to energize valve motor. Check for full valve travel. Adjust controls out of cooling mode. Check for complete valve closure. Check for leaks at all piping connections. Compressorized Units Continue Start-up utilizing the Liebert Small System Condensers (1-5 Ton) Warranty Inspection Check Sheet NOTE: Adjust all set-points for proper operation after testing. Adjust hot gas bypass to customers load. Page 4 of 5 2014 Emerson Electric Co. All rights reserved. PSWI-8542-403-RE

Your Start-up is now complete. Liebert DataMate (1-3 Ton) Your input is important to us. Was start up successful (no factory issues)? If yes, please check the yes box. If the start up was not successful (factory issues) please check the no box and supply detailed information below. You may also provide comments below even if you had a successful start-up. Yes No Comments: START-UP PERFORMED BY START-UP DATE (Please print name) COMPANY PHONE # IMPORTANT: This form must be properly completed and returned to your local Liebert Sales office. If you do not know who your local Liebert sales office is, call 1-800-Liebert or check our website at: http://www.emersonnetworkpower.com/en-us/brands/liebert/pages/default.aspx Page 5 of 5 2014 Emerson Electric Co. All rights reserved. PSWI-8542-403-RE