Similar documents
1

H4T R410A. refrigerant

ARS. 1

ARV.

RAH Ka AIR COOLED WATER CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS. COOLING CAPACITY FROM 387 TO 1207 kw 1 AND 2 COOLING CIRCUITS

BRAN Residential chillers and heat pumps. Reversible unit, air source for outdoor installation 4,81-27,2 kw <<< BACK INDEX.

AIR-COOLED LIQUID CHILLER FOR OUTSIDE INSTALLATION FROM 4,3 TO 35,1 kw

CMA TECHNICAL MANUAL CONDENSING UNITS FOR OUTDOOR INSTALLATION O L S A F RA N

AIR COOLED HEAT PUMP FOR OUTDOOR INSTALLATION FROM 4,2 TO 35,1 kw

AIR COOLED CHILLERS FOR OUTDOOR INSTALLATION WITH INTEGRATED FREE COOLING MULTISCROLL SERIES

Epsilon Echos kw. General information Air-Water unit with scroll compressors driven by DC inverter. Unique selling points

GPE Kc UNITS FOR 4-PIPE SYSTEMS WITH SCROLL COMPRESSORS. COOLING CAPACITY FROM 77 TO 426 kw - 2 COOLING CIRCUITS. GPE 802 Kc + CF + GP + MV + P1

TOTAL HEAT RECOVERY MULTI-PURPOSE HEAT PUMPS

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

EASY_R R407C. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans. 5,2 41,5 kw T_ESY_R_0508_GB

AIR COOLED FREE-COOLING CHILLERS WITH SCROLL COMPRESSORS AND AXIAL FANS

AIR COOLED CHILLER FOR OUTDOOR INSTALLATION FROM 4,3 TO 35,1 kw

MULTIPLO PF Multifunction chillers for indoor installation. Cooling Capacity: kw Heating Capacity: kw

> HGA AIR - WATER HEAT PUMPS FOR OUTDOOR INSTALLATION. Available range. Unit description. Options. Accessories

HYDRONIC RESIDENTIAL

PRODUCT GUIDE

Aquaflair TRAC-TRAF-TRAH

AIR COOLED CHILLERS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS

Modular Air-cooled Chillers

SMART. 4,9 49,5 kw. Air cooled liquid chillers and heat pumps equipped with scroll compressor and axial fans T_SMT_0609_GB

LCP kw. Outdoor monobloc air-water unit. Total heat recovery multi-purpose units LCP PLUS

Air cooled industrial chillers

Blue Box Epsilon Echos +

RAS Kp AIR COOLED CHILLERS WITH RECIPROCATING COMPRESSORS AND AXIAL FANS REFRIGERANT R290 LIQUID CHILLERS - AIR COOLED AIR

Kälte Klima. Air cooled water chillers air cooled reversible heat pumps from 45 kw to 320 KW. Compressors Scroll SCAEY DE 88 04/11 12/10

New CGAF Air Cooled Scroll Chiller. New Air-Cooled Scroll Chiller CGAF

Multi-pipe Units with Scroll Compressors. Model CMAA Cooling capacity kw Heating capacity kw

pyxis hp "u" pyxis hp "u" IDEA NEW rcgroupairconditioning

Kälte Klima. Air cooled liquid chiller Free-Cooling from 45 kw to 385 kw. Scroll Compressors SCAEY-FC DE 98

Zeta Rev LN HP Prochill Bluebox Print Date: 07/17/2017

INVERTER SCROLL. LG Electronics Distributed by. Copyright 2017 LG Electronics. All rights reserved.

CMA CONDENSING UNITS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL

Packaged air cooled liquid chillers for outdoor installation kw. technicalcatalogue T_EGL_1012_GB

Technical Catalogue. Air-Cooled Liquid Chillers with screw compressors Nominal cooling capacity: kw 50 Hz

Dunham Bush Air Cooled Screw Chiller AFVX B 6SR Series

Advance Split

ERAH MC Ka. Range kw. AIR COOLED CHILLERS WITH SCREW COMPRESSORS AND AXIAL FANS FOR OUTDOOR INSTALLATION (Standard line)

Air Cooled Chillers & Heat Pumps WinPACK HE-A

INVERTER SCROLL INVERTER SCROLL INVERTER SCROLL. LG Electronics Distributed by

NRP MULTIPURPOSE HEAT PUMPS 2 AND 4-PIPE SYSTEMS PLUS PRODUCTION OF DOMESTIC HOT WATER

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw

EKS/HE. MultiScroll Air-cooled liquid chillers High efficiency. Solution B - Base I - Integrata

30RB/RQ 039S-160S Refrigerant HFC-410A Nominal cooling capacity kw Nominal heating capacity kw

Kälte Klima. Air cooled liquid chiller Free-Cooling from 45 kw to 365 kw. Scroll Compressors SCAEY-FC DE 98

Galletti Water chillers and heat pumps catalogue

MPI DC 8-29 kw. Outdoor monobloc unit with BLDC compressor. Air chillers and heat pumps MPI DC PLUS

RTA TECHNICAL MANUAL AIR-WATER CHILLERS AND HEAT PUMPS FOR OUTDOOR INSTALLATION O L S E A F RA N

Construction details: Structure and base in hot dip galvanised sheet steel with epoxy pain finish (RAL 9002)

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

Modular Air Cooled Scroll Chillers

Flex Series Heat Pumps

Conditioning your ambient, maximising your comfort.

HIWARM COMPACT kw

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

O L R E RGA ST RA N AIR-WATER CHILLERS AND HEAT PUMPS FOR OUTDOOR INSTALLATION TECHNICAL MANUAL

GHE GHE. Dehumidifiers for radiant cooling systems with heat recovery VERSIONS ACCESSORIES

50A KP 70A KP 90A KP 120A KP 150A KP 210A

30RB Air-Cooled Liquid Chillers. Nominal cooling capacity 8-14 kw. Features. Quiet operation

EQSL TECHNICAL CATALOGUE AIR COOLED WATER CHILLER UNITS AXIAL FANS. Models: 300 V2 F V2 F16. Cooling capacity: 299 to 1310 KW

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

MPE 4-76 kw. Outdoor monobloc unit. Air chillers and heat pumps MPE PLUS. Efficiency under all operating conditions. 152 galletti.

SyScroll 40 to 75 Air NEW

FHE FHE. Dehumidifiers for radiant cooling systems with heat recovery. Versions

LSA LSA A + Air cooled water chillers with axial fans VERSIONS ACCESSORIES

HIWARM kw. Air-water system with external and internal BLDC unit. Total heat recovery multi-purpose units HIWARM PLUS

AIR TO WATER UNITS WITH SCROLL COMPRESSORS AND CENTRIFUGAL FANS (PLUG FAN), FOR INDOOR INSTALLATION kw

Be sustainable while protecting your business

GLIDER EVO FREE GLIDER EVO FREE GLYCOL FREECOOLING. rcgroupairconditioning

CRIMSON & CRIMSON MAX

30RB Air-Cooled Liquid Chillers PRODUCT SELECTION DATA. Easy and fast installation. Compact, reliable and efficient

NEOSYS. AIR TO WATER LIQUID CHILLER kw. AIR TO WATER HEAT PUMP kw. lennoxemea.com

BRH. Climaveneta Technical Bulletin. Water-cooled liquid chillers ,5-35,1 kw. Versatile High efficiency Maximum silent-running

AQH 40 to 130. u Air-to-Water Reverse Cycle Heat Pumps. 40 to 131 kw. 45 to 141 kw. Engineering Data Manual

Conditioning your ambient, maximising your comfort.

pyxis u pyxis ua NEW rcgroupairconditioning

Chillers, air and water cooled, featuring centrifugal compressors with magnetic levitation, from 200 to kw

Air cooled chillers. Air cooled chillers with brushless oil-free compressors. RAC. Ka Series - 1 or 2 cooling circuits capacity from 300 to 1400 kw

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

LER kw. Indoor motor-driven evaporating units. Motor-driven evaporating units LER PLUS

44,9 202,0 kw. technicalcatalogue

Neosys Product catalogue

BETA ECHOS. Air/water cooled chillers and heat pumps kw. General BETA ECHOS is a range of chillers and ductable air-water heat pumps.

GHE Dehumidifiers for radiant cooling systems with heat recovery

Air-to-water scroll chillers

RMA AIR-WATER CHILLERS AND HEAT PUMPS FOR OUTDOOR INSTALLATION INSTALLATION AND OPERATION MANUAL

WATER COOLED HEAT PUMP VERTICAL UNIT CONSOLE TYPE OR RECESSED

30RB/RQ 039S-160S. Air-Cooled Liquid Chiller Reversible Air-To-Water Heat Pump Nominal cooling capacity: kw Nominal heating capacity: kw

Next P kw COOLING 5 93 kw HEATING. technicalcatalogue. Heat pump air conditioners with upflow air delivery T_NXTP_0411_GB

DOMINO. Line Heavy Commercial & Industrial. Air/water chillers with axial or centrifugal fans; plate or shell and tube exchangers.

Большая библиотека технической документации каталоги, инструкции, сервисные мануалы, схемы.

30RQV NEW. Nominal cooling capacity kw Nominal heating capacity kw AIR-TO-WATER HEAT PUMPS HEATING. Easy and fast installation

kw. technicalcatalogue

TCHVZ TCEVZ

2017 HYDRONIC SYSTEMS MINI CHILLER FULL DC INVERTER. AIR-TO-WATER HEAT PUMP cooling - heating

Transcription:

SA 1

INDEX Available versions...pag. 4 Structure of electro-galvanized and painted steel sheet...pag. 5 Ecological refrigerant R410A...pag. 5 Scroll compressors...pag. 6 Condenser coils...pag. 6 Brazed plates evaporators...pag. 7 Axial fans...pag. 7 Thermostatic expansion valves...pag. 8 Electronic expansion valves...pag. 8 4-way reversing valve...pag. 9 Electronic regulation...pag. 9 Hydronic circuit... pag. 10 Operating range... pag. 11 Versions and accessories... pag. 11 Technical sheets... pag. 12 Performances...pag. 36 Dimensional drawings...pag. 49 Space for unit installation...pag. 57

SA Air cooled water chillers and heat pumps, axial fans, hermetic scroll compressors, brazed plate evaporators, refrigerant gas R410A, condensing unit. Minimum 2 compressors for each circuit. Units designed for commercial or industrial applications. Only for outdoor installation. Cooling capacity from 50 up to 752 kw Heating capacity from 55 up to 636 kw R410A refrigerant 3

Available versions CHILLER: basic version with large operative range of outdoor air temperature (-15 C up to 43 C). HEAT PUMP: with large operative range of outdoor air temperature (-10 C up to 40 C in heating mode); used for hydronic circuits with 2 tubes, during winter produces hot water up to 50 C, and during summer produces cold water. ENERGY: chiller and heat pump with oversized evaporator and condenser, for maximum energy saving; very large operative range of outdoor air temperature from -15 C up to 46 C. TOP: unit with largest evaporator and condenser surfaces, for energy performances at top of the market with EER>3,1 W/W for all sizes. Large operative range of outdoor air temperature (-15 C up to 43 C). SILENT: unit equipped with soundproof compressors and fan speed decreased for limited noise levels. The unit can work during the night with reduced fan speed. CONDENSING UNITS: this units are supplied without evaporator, expansion valve and hydronic components; they are able to be connected with a remote direct expansion heat exchanger (example a cooling coil inside an air handling unit (AHU)). PARTIAL HEAT RECOVERY (desuperheater): an heat exchanger is inserted along the compressors discharge line before the condenser, it s able to desuperheat the hot gas and produces hot water up to 55 C. The amount of recovered energy is around the 30% of the cooling energy production. TOTAL HEAT RECOVERY: a water condenser is inserted on the discharge line of the compressors in parallel with the air condenser, when the recovery circuit is not satisfied, a changeover valve diverts the refrigerant hot gas in the water condenser, to transfer the total condensing energy on the hot water circuit. The amount of recovered energy is around the 135% of the cooling energy production. TWO FREECOOLING VERSIONS: STANDARD FREECOOLING: near the finned condenser there is a second finned heat exchanger with water inside (freecooling exchanger); if the external air temperature falls below than a conveniently limit, a switch valve diverts the water flow through the freecooling exchanger (freecooling and compressors work together); when outdoor air temperature falls under a second project limit, all compressors are completely stopped: - The air flow by fans cools directly the water inside the freecooling exchanger and the EER of the unit increase up to 20-22 W/W. - This solution needs to use water with antifreeze for the winter period for antifreeze protection. FREECOOLING WITH SEPARATED CIRCUIT: the freecooling circuit is separate from user circuit, so the antifreeze mixture charge can be limit to it; the chiller mode has more efficiency and the user plant is in global less expensive. CLIENT: units with special equipment or devices. 4

Features Structure of electro-galvanized and painted steel sheet Air condensed water chiller with scroll compressors. Ecological refrigerant R410A This refrigerant R410A with zero ozone depletion potential (ODP=0) together with a very low value for the global warming effective potential, is the best choice for circuits with scroll compressors. Thanks to its characteristics of heat transfer and its heat capacity in the gas phase, allows high yields of condensers having small diameter tube, and can reduce the airflow needed for condensation. R410A 5

Scroll compressors two or three high-efficiency scroll compressors, on each circuit refrigerator for maximum energy efficiency at partial loads. The choice of scroll compressor allows you to have low vibration and noise emissions. Reliability is high thanks to the reduced number of moving parts and to the high capacity of the compressor to adapt to many different conditions. Scroll Compressor section Due to its construction, hermetic scroll compressors withstand at flooded start much better than the piston or screw compressors (in faulty conditions). In addition thanks to have multiple compressors on the same circuit, when only one of them is started (this happen during many hours in a year) it can work with oversized of the heat exchangers and this produce a bigger efficiency during working conditions partialized. The example is as follows: If a circuit with two compressors has a value of EER= 2.70 W/W, when on the same circuit only one compressor operates the EER value climbs to 3.74 W/W; the result of this technology is that the value of ESEER (seasonal average efficiency) increases much more than in chillers with only one compressor per circuit. Condenser coils with high-efficiency design, equipped by internally grooved copper tubes for maximize the heat exchange, with small diameter to minimize the refrigerant charge. Finned condenser The special profile of the fins allows to obtain excellent performance of heat exchange with the air, together with the use of internally grooved tubes we have low values of the condensing temperature and consequently high compressors performances. In the case of heat pumps, the fins have hydrophilic surface treatment in order to obtain high performance of water drain during defrosting of the battery. 6

Brazed plates evaporators specifically designed for R410A, made in stainless steel. In addition to a very high mechanical resistance, due to the use of stainless steel, they have high corrosion resistance. These evaporators work in perfect countercurrent, and allow to have very high evaporation temperature compared other kind of evaporator, for maximize EER performance. An integrated distributor guarantees a perfect equalization of the refrigerant gas flow inside each plate heat exchanger, for maximum performances. On heat pumps the evaporator commutates to condenser mode and produces hot water. Brazed plate evaporator Axial fans The chillers are normally supplied with fans equipped with AC motor, controlled by a fan speed controller (cut phase regulator) that allows the modulation of speed so as to manage the condensing pressure with the change of cooling load and outdoor air temperature. Fans are available on request with a EC motor (Electronically Commutated Motor) that enable high performance. At full load, an EC motor saves 20% energy compared to a conventional AC motor, and the difference increases up to 57% when the comparison is made at partialized conditions, with the air flow capacity equal to half of the maximum flow. The higher cost of the fans with EC motor is repaid by the energy saving after about 2 years of unit work. In addition to energy saving the low axial fans speed,facilitate limited noise levels when the unit works during the night. Fan with AC motor Fan with EC motor 7

Thermostatic expansion valves Standard production is equipped by thermostatic expansion valves to ensure a return of dry gas to the compressor. Electronic expansion valves on request by request the unit can be equipped with electronic expansion valves. These valves, via an electronic driver, a temperature sensor and a pressure transmitter, are able to provide a more precise value of superheating. The graph below shows the effect of switching between the operation of a chiller with a TEV (thermostatic expansion valve) to an EEV (electronic expansion valve). The lowering of the average superheat value, the stability of the value itself and the operating pressure are clearly evident. Its use is highly recommended in the case of heat pumps, where in winter operation, it allows to have a very low superheating (this allow COP increasing) and the correct function of unit also with much lower outdoor air temperatures, up to 3 C less compared to use of thermostatic valves. Carel controllers and Electronic Expansion Valve 8

4-way reversing valve Used for heat pump version converts the refrigerant circuit configuration from chiller to heat pump. When switched on, the unit is converted to heat pump (the chiller evaporator works at condenser mode and produces hot water - winter). When switched off the refrigerant circuit is converted to chiller mode (summer) or defrosting (winter). 4 ways reversing valve Electronic regulation by a microprocessor card for the management and control of all functional parameters The controls normally used are parametric products of Carel. For chillers up to 4 compressors the used control is μc2-se. For the other units is used μc3 with a semigraphic terminal, where available languages are English, Italian and Spanish. On request or for special units, it is possible use controllers belonging to family Carel pco or from other manufacturers. In any case, the functions controlled are: a. regulation on inlet water temperature, with the alternative possibility of adjusting the output water temperature; b. management of cooling capacity (or heating) with turning ON or OFF the compressors, depending on the request of the hydronic circuit; the control is such that the number of operating hours per year of each compressor, is the same for everyone; c. prevent high pressure - this function allows you to turn off one of the compressors on the same circuit when the condensing pressure rises too much; d. reverse cycle for hot gas defrost; e. fan speed regulation (to handle the condensing pressure as a function of load and air ambient temperature) allows to use the chiller also in very low ambient temperatures; f. management of evaporating pressure in heat pump mode - this feature allows the modulation of the fans when the outdoor air temperature is above 5-6 C to reduce noise emissions to a minimum level; g. antifreeze heaters - a set of heaters protect the parts of circuits containing water when their temperature ( caused from low outdoor air temperature) drops below the safety threshold; h. low noise mode this feature as standard on SILENT version, allows you to change the fan speed adjustment in the night hours, with limited noise emission; i. evaporator pump control; backup evaporator pump; rotation pumps (active only in the presence of double pump); μc2se μc3 semigraphic terminal 9

energy save mode (pump switched on only when needed) - this feature allows a considerable energy saving, trough turning ON the pump for only as long it is necessary - this function is useful when you have constant water flow on chiller side and variable water flow on the system side, by inserting a manifold by-pass between them: the maximum benefit is obtained when a buffer tank is installed; j. water flow switch; k. variable set point of water temperature depending on outdoor air temperature (sliding set temperature) or by external contact; l. start compressors by external contacts (only condensing units); m. communication with supervisory systems; n. anti freeze alarm; o. high low pressure alarms p. compressors alarm q. water flow alarm r. pump alarm Hydronic circuit The unit is normally equipped with Victaulic flexible couplings complete with clamps and solder terminals. On request the unit can be completed with the provision of pump, safety valve, water filter, buffer tank and backup pump. It is possible to choose between low pressure pump, and high pressure pump with standard performance. For special requirements is possible to install special pumps, but in this case the buffer tank is not available. The circuits are protected against freezing by heaters, down to outdoor air temperature of -15 C. On heat pumps the expansion vessel is not supplied. On freecooling version buffer tank is not available. 10

Operating range thank to the use of fan speed controller the operating range is very wide. operating ranges for cooling and heating modes Versions and accessories on demand N...Basic E...High Energy efficiency H...Heat pump C...Condensing unit R...Partial recovery (desuperheater) (1) R1...Total recovery (1) F...Freecooling S...Silent CLIENT Special features on specific customer needs EEV... Electronic expansion valve/s P1...Hydronic Kit with pump, safety valve, water filter P2...Hydronic Kit with double pump, safety valve, water filter P3...Hydronic Kit with high pressure pump, safety valve, water filter P4...Hydronic Kit with double high pressure pump, safety valve, water filter P1S...P1 + Buffer tank, electric heater and expansion vessel (2) P2S...P2 + Buffer tank, electric heater and expansion vessel (2) P3S...P3 + Buffer tank, electric heater and expansion vessel (2) P4S...P4 + Buffer tank, electric heater and expansion vessel (2) RIC...configuration with bypass of primary circuit integrated on unit RS485..RS 485 serial interface (MODBUS protocol) RS232..RS 232 serial interface LON...LonWorks interface KON...Konnex interface BAC1...Bacnet MS/TP interface BAC2...Bacnet Ethernet/IP interface WEB...WEB server for remote control CK...Clock board RIF...Power factor corrector ST...Low starting current device AV...Anti-vibration mountings PR...Remote control panel TP...Tropical adaptation (3) EF...Fan with EC motor SOV...2 way shut-off valve for safety valves KK...Low outdoor air temperature start device (1) SA-52, 52E, 60 only if not present buffer tank (2) For SA-..-H (heat pumps) the expansion vessel is not supplied (3) Only E version 11

Technical Sheets SA-N Size 5 6 7 8 10 11 12 13 15 Cooling capacity 50,1 55,7 64,9 71,1 86,9 101,5 114,6 128,0 146,0 Power input 20,1 23,4 25,5 29,3 35,0 40,1 45,4 50,9 57,4 Maximum power input at limit conditions 25,9 29,5 33,1 38,2 46,2 52,8 59,3 66,0 76,2 Maximum outdoor air temperature ( C) 42,0 41,0 42,0 41,0 42,5 42,5 42,3 42,0 42,0 Water flow (m3/h) 8,6 9,6 11,2 12,2 14,9 17,5 19,7 22,0 25,1 Pressure loss of hydronic circuit (kpa) 38 47 50 61 72 62 42 52 55 EER (kw/kw) 2,49 2,38 2,54 2,42 2,48 2,53 2,52 2,51 2,54 ESEER (kw/kw) 3,82 3,72 3,86 3,76 3,81 3,85 3,85 3,84 3,86 Sound pressure at 10m (db(a)) 47,4 47,4 47,3 49,1 51,6 52,0 51,2 51,1 52,1 Total air flow (m3/h) 18000 18000 20800 20800 38000 38000 38000 38000 38000 Number of compressors (n.) 2 2 2 2 2 2 3 3 4 Number of circuits (n.) 1 1 1 1 1 1 2 2 2 Rated current at nominal conditions (A) 39 46 50 57 68 78 89 99 112 Maximum current at full load (A) 52 59 66 75 91 103 116 128 147 Maximum starting current (A) 170 186 193 220 258 271 284 329 295 Buffer tank capacity (lt) 180 180 180 180 330 330 330 330 330 Maximum operating pressure PS (bar) 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 Power input of low pressure pump 0,78 0,85 1,00 1,08 1,26 1,39 1,48 2,04 2,18 Amperage of low pressure pump (A) 1,6 1,7 2,1 2,2 2,6 2,9 3,1 4,2 4,5 Available pressure with low prevalence hydronic kit (kpa) 96 79 100 86 65 67 77 105 86 Power input of high pressure pump (A) 1,0 1,1 1,2 1,3 1,6 1,8 1,9 2,3 2,5 Amperage of high pressure pump (A) 2,0 2,2 2,5 2,7 3,2 3,6 3,9 4,7 5,1 Available pressure with high prevalence hydronic kit (kpa) FREE COOLING 176 167 162 149 134 126 138 174 161 Cooling capacity 46,1 51,2 59,7 65,4 80,0 93,3 105,5 117,7 134,3 Pressure loss of hydronic circuit at chiller mode (kpa) Pressure loss of hydronic circuit at freecooling mode (kpa) Power input 1,6 1,6 1,8 1,8 3,4 3,4 3,4 3,4 3,4 Water flow (m3/h) 8,6 9,6 11,2 12,2 14,9 17,5 19,7 22,0 25,1 52 63 67 82 98 83 57 70 74 83 101 108 132 156 133 91 113 118 Number of antivibrating supports 4 4 4 6 6 6 6 6 6 Load capacity required to single antivibrating support (dan) Total weight with no water and excluded any hydronic kit and buffer tank (kg) 282 311 359 260 313 359 399 439 490 627 691 798 868 1042 1196 1331 1463 1632 12

Basic version 18 20 23 27 30 36 41 46 52 60 67 75 162,0 186,9 225,4 259,9 290,2 328,2 380,4 440,7 501,0 569,2 671,9 752,3 63,0 75,0 91,2 98,3 121,8 125,6 151,4 181,4 204,7 227,2 272,1 309,2 83,9 97,5 117,6 131,2 153,0 164,4 190,5 231,6 248,7 283,6 343,8 378,4 42,8 41,5 41,5 43,5 40,3 43,1 42,0 41,3 41,2 41,5 41,5 40,5 27,9 32,1 38,8 44,7 49,9 56,5 65,4 75,8 86,2 97,9 115,6 129,4 53 61 70 67 91 66 71 69 47 56 79 79 2,57 2,49 2,47 2,64 2,38 2,61 2,51 2,43 2,45 2,51 2,47 2,43 3,88 3,82 3,80 3,94 3,72 3,92 3,83 3,76 3,78 3,83 3,80 3,77 53,6 54,0 54,1 54,8 55,6 56,6 57,9 58,1 58,2 59,4 60,7 61,8 54000 55500 62550 83000 78000 110400 110400 154000 147200 147200 186000 184000 4 4 4 4 4 4 4 6 6 6 8 8 2 2 2 2 2 2 2 2 2 2 4 4 123 147 178 192 238 245 296 354 400 444 531 604 163 188 225 253 291 314 363 442 475 539 651 715 334 360 431 460 550 651 702 709 819 887 1004 1072 330 330 330 330 330 660 660 660 660 660 660 660 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 2,26 2,31 2,73 3,31 3,70 4,70 5,45 6,32 7,18 8,16 9,10 10,78 4,7 4,8 5,6 6,8 7,6 9,7 11,3 13,0 14,8 16,8 18,8 22,3 79 46 63 89 65 112 105 107 127 117 86 95 2,6 2,7 4,2 4,6 5,3 6,5 7,6 8,8 10,0 11,3 12,8 15,0 5,4 5,6 8,6 9,4 11,0 13,5 15,6 18,1 20,6 23,4 26,5 30,9 151 126 143 149 135 182 175 177 197 187 156 165 149,0 172,0 207,4 239,1 266,9 302,0 350,0 405,5 460,9 523,7 531,9 526,6 4,8 4,9 5,6 7,4 6,9 9,8 9,8 13,7 13,1 13,1 16,5 16,4 27,9 32,1 38,8 44,7 49,9 56,5 65,4 75,8 86,2 97,9 115,6 129,4 72 82 94 91 123 89 96 93 64 76 107 107 116 131 150 145 196 142 154 149 103 121 171 172 6 6 6 8 8 8 8 8 8 8 10 10 533 595 682 562 600 665 770 893 1015 1153 1089 1219 1775 1984 2274 2499 2669 2954 3424 3967 4509 5123 6047 6771 Technical specifications at following conditions Cooling: water (in/out) 12/7 C; outdoor air 35 C; (Evaporating 4,5 C for condensing unit) Heating: water (in/out) 40/45 C; outdoor air 7 C d.b./87% RH Free cooling: water (in/out) 15/10 C, outdoor air 2 C Power supply: 400V - 3-50Hz Sound pressure on free field reflecting surface (directivity fact. 2) according to ISO 3744 13

Technical Sheets SA-E Size 5 6 7 8 10 11 12 13 15 Cooling capacity 48,7 55,5 62,7 70,9 82,0 95,5 112,0 124,8 144,0 Power input 16,2 18,5 21,1 24,3 27,1 32,2 36,2 42,4 47,4 Maximum power input at limit conditions 21,4 24,6 28,0 31,9 35,7 42,6 48,2 56,4 62,8 Maximum outdoor air temperature ( C) 46,5 46,5 45,8 46,5 46,5 46,4 46,5 45,5 46,5 Water flow (m3/h) 8,4 9,5 10,8 12,2 14,1 16,4 19,3 21,5 24,8 Pressure loss of hydronic circuit (kpa) 32 40 42 53 51 42 36 45 41 EER (kw/kw) 3,01 3,00 2,98 2,92 3,02 2,97 3,09 2,95 3,04 ESEER (kw/kw) 4,18 4,18 4,17 4,13 4,19 4,16 4,23 4,15 4,20 Sound pressure at 10m (db(a)) 47,3 47,4 47,4 47,3 51,2 50,8 51,2 50,4 52,0 Total air flow (m3/h) 18000 19100 19350 27040 33200 36000 38400 38400 55500 Number of compressors (n.) 2 2 2 2 2 3 3 4 4 Number of circuits (n.) 1 1 1 1 1 2 2 2 2 Rated current at nominal conditions (A) 32 36 41 47 53 63 71 83 93 Maximum current at full load (A) 47 52 59 69 79 90 102 115 132 Maximum starting current (A) 165 170 186 196 223 235 270 244 262 Buffer tank capacity (lt) 180 180 180 330 330 330 330 330 330 Maximum operating pressure PS (bar) 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 Power input of low pressure pump 0,70 0,78 0,86 0,94 1,30 1,44 1,56 1,61 2,40 Amperage of low pressure pump (A) 1,5 1,6 1,8 1,9 2,7 3,0 3,2 3,3 5,0 Available pressure with low prevalence hydronic kit (kpa) 97 86 80 65 90 90 84 66 101 Power input of high pressure pump (A) 0,9 1,1 1,2 1,3 1,5 1,8 2,1 2,3 2,5 Amperage of high pressure pump (A) 1,9 2,2 2,4 2,7 3,1 3,8 4,3 4,6 5,1 Available pressure with high prevalence hydronic kit (kpa) FREE COOLING 182 174 170 158 147 201 199 183 168 Cooling capacity 40,3 45,9 51,9 58,7 67,9 79,1 92,7 103,4 119,3 Pressure loss of hydronic circuit at chiller mode (kpa) Pressure loss of hydronic circuit at freecooling mode (kpa) Power input 1,6 1,7 1,7 2,4 3,0 3,2 3,4 3,4 4,9 Water flow (m3/h) 8,4 9,5 10,8 12,2 14,1 16,4 19,3 21,5 24,8 43 53 57 71 68 57 49 61 55 69 86 91 113 109 91 78 97 88 Number of antivibrating supports 4 4 6 6 6 6 6 6 6 Load capacity required to single antivibrating support (dan) Total weight with no water and excluded any hydronic kit and buffer tank (kg) 296 327 251 273 328 377 419 461 514 658 726 838 911 1094 1256 1398 1536 1714 14

High Energy Efficiency version 18 20 23 27 30 36 41 46 52 60 67 160,8 181,0 211,1 248,4 285,0 317,9 374,0 414,6 480,6 573,0 613,5 53,8 60,6 66,2 84,6 94,8 113,4 127,3 142,7 168,5 198,8 214,8 71,4 80,7 87,7 112,7 125,4 150,7 168,6 189,6 224,5 264,4 286,0 46,5 46,2 46,5 45,5 46,5 45,0 46,5 45,8 45,0 45,5 45,0 27,6 31,1 36,3 42,7 49,0 54,7 64,3 71,3 82,7 98,6 105,5 42 47 46 57 79 55 60 46 49 61 56 2,99 2,98 3,19 2,93 3,00 2,80 2,94 2,91 2,85 2,88 2,86 4,17 4,17 4,28 4,14 4,18 4,06 4,14 4,12 4,09 4,11 4,09 53,3 53,2 54,8 54,9 56,0 56,6 57,9 58,6 58,1 59,4 61,0 57000 63000 85000 80000 110000 108000 146000 146000 147200 186000 184000 4 4 4 4 4 4 4 4 6 6 6 2 2 2 2 2 2 2 2 2 2 2 105 118 129 165 185 221 249 279 329 388 419 151 166 191 228 260 298 338 370 442 514 546 299 337 363 434 468 558 675 709 709 860 894 330 330 330 330 660 660 660 660 660 660 0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 2,40 2,30 3,27 3,36 3,63 3,80 5,06 5,61 6,51 7,76 8,30 5,0 4,7 6,8 6,9 7,5 7,8 10,5 11,6 13,4 16,0 17,1 91 66 91 110 77 93 107 120 115 101 110 2,6 2,7 4,5 4,7 5,2 5,6 7,1 7,9 9,2 11,0 11,7 5,4 5,6 9,2 9,8 10,8 11,5 14,8 16,4 19,0 22,6 24,2 158 138 161 180 147 163 177 190 185 171 180 133,1 149,9 174,8 205,7 236,0 263,2 309,7 343,3 398,0 474,5 507,9 5,1 5,6 7,6 7,1 9,8 9,6 13,0 13,0 13,1 16,5 16,4 27,6 31,1 36,3 42,7 49,0 54,7 64,3 71,3 82,7 98,6 105,5 57 63 62 77 107 74 81 62 66 83 76 91 101 100 124 171 119 130 99 106 132 121 6 6 8 8 8 8 8 8 8 10 10 559 625 537 590 631 702 806 912 1058 968 1280 1864 2084 2387 2623 2802 3121 3582 4053 4703 5379 7110 Technical specifications at following conditions Cooling: water (in/out) 12/7 C; outdoor air 35 C; (Evaporating 4,5 C for condensing unit) Heating: water (in/out) 40/45 C; outdoor air 7 C d.b./87% RH Free cooling: water (in/out) 15/10 C, outdoor air 2 C Power supply: 400V - 3-50Hz Sound pressure on free field reflecting surface (directivity fact. 2) according to ISO 3744 15

Technical Sheets SA-TOP Size 5 6 7 8 10 11 12 13 Cooling capacity 50,1 60,6 68,3 78,5 88,2 103,9 117,5 135,7 Power input 16,0 19,2 21,7 24,3 27,4 31,7 37,6 43,5 Maximum power input at limit conditions 20,4 24,3 27,7 30,8 34,8 40,4 48,1 55,2 Maximum outdoor air temperature ( C) 43,9 44,9 43,5 46,8 45,7 44,5 42,9 45,5 Water flow (m3/h) 8,6 10,4 11,7 13,5 15,2 17,9 20,2 23,3 Pressure loss of hydronic circuit (kpa) 24 31 38 37 41 26 29 35 EER (kw/kw) 3,13 3,16 3,14 3,22 3,22 3,28 3,12 3,12 ESEER (kw/kw) 4,25 4,26 4,25 4,29 4,29 4,32 4,25 4,24 Sound pressure at 10m (db(a)) 47 47 47 50 51 51 51 52 Total air flow (m3/h) 18750 24600 24500 39000 39000 40500 40500 59000 Number of compressors (n.) 2 2 2 2 2 3 3 4 Number of circuits (n.) 1 1 1 1 1 2 2 2 Rated current at nominal conditions (A) 31 37 42 48 54 62 73 85 Maximum current at full load (A) 50 58 65 72 82 94 107 124 Maximum starting current (A) 165 173 189 196 223 235 270 248 Buffer tank capacity (lt) 180 330 330 330 330 330 330 330 Maximum operating pressure PS (bar) 6 6 6 6 6 6 6 6 Power input of low pressure pump 0,7 0,8 0,9 1,0 1,1 1,5 1,6 1,6 Amperage of low pressure pump (A) 1,5 1,7 1,9 2,1 2,2 3,1 3,3 3,4 Available pressure with low prevalence hydronic kit (kpa) 110 100 91 83 73 112 102 87 Power input of high pressure pump (A) 1,0 1,1 1,3 1,4 1,6 2,0 2,2 2,4 Amperage of high pressure pump (A) 2,0 2,4 2,6 3,0 3,2 4,1 4,5 4,9 Available pressure with high prevalence hydronic kit (kpa) FREE COOLING 190 181 172 164 155 216 206 191 Cooling capacity 46,1 55,7 62,8 72,2 81,1 95,6 108,1 124,9 Pressure loss of hydronic circuit at chiller mode (kpa) Pressure loss of hydronic circuit at freecooling mode (kpa) Power input 1,8 2,5 2,6 3,6 3,7 3,6 3,7 5,5 Water flow (m3/h) 8,6 10,4 11,8 13,5 15,2 17,9 20,2 23,4 24 31 38 37 41 26 30 35 43 55 68 66 74 47 53 63 Number of antivibrating supports 4 4 6 6 6 6 6 6 Load capacity required to single antivibrating support (dan) Total weight with no water and excluded any hydronic kit and buffer tank (kg) 327 366 273 304 365 419 466 512 653 758 820 911 1094 1256 1398 1536 16

Top Energy Efficiency version 15 18 20 23 27 30 36 41 46 52 153,3 170,9 198,9 235,5 275,1 303,5 357,9 406,7 455,9 526,0 48,4 55,0 61,3 74,2 85,4 97,1 112,2 128,7 144,8 169,4 61,6 70,3 77,9 94,8 108,4 123,7 142,4 164,0 185,1 216,1 44,3 43,0 45,1 43,0 45,1 43,8 45,4 44,0 42,5 43,5 26,4 29,4 34,2 40,5 47,3 52,2 61,6 69,9 78,4 90,5 30 36 46 45 48 45 36 38 30 40 3,17 3,11 3,25 3,17 3,22 3,12 3,19 3,16 3,15 3,11 4,27 4,24 4,30 4,27 4,29 4,25 4,28 4,26 4,26 4,24 52 53 54 55 56 56 57 57 56 59 59000 59000 82000 81500 114000 112000 153400 152600 152000 190000 4 4 4 4 4 4 4 4 4 6 2 2 2 2 2 2 2 2 2 2 94 107 120 145 167 190 219 251 283 331 138 158 177 213 247 273 320 354 388 471 262 299 340 376 442 468 565 664 698 716 330 330 330 330 330 660 660 660 660 660 6 6 6 6 6 6 6 6 6 6 2,4 2,4 2,1 3,0 3,7 3,9 4,3 5,5 6,2 7,1 5,0 4,9 4,3 6,2 7,7 8,0 8,8 11,4 12,7 14,7 115 93 54 77 122 115 114 132 140 130 2,5 2,7 2,8 4,3 5,3 5,6 6,3 7,8 8,7 10,1 5,2 5,5 5,7 8,9 10,9 11,5 12,9 16,0 18,0 20,8 173 154 121 147 192 185 184 202 210 200 141,0 157,2 183,0 216,7 253,1 279,2 329,2 374,1 419,4 483,9 5,5 5,7 7,7 7,9 11,5 11,5 14,7 15,0 14,8 19,0 26,4 29,4 34,2 40,5 47,4 52,2 61,6 70,0 78,5 90,6 30 36 46 45 48 45 36 38 30 40 55 64 83 81 87 81 66 68 53 72 6 6 8 8 8 8 8 8 8 8 571 621 514 597 656 704 780 896 1013 1176 1719 1897 2069 2387 2623 2817 3158 3548 4053 4703 Technical specifications at following conditions Cooling: water (in/out) 12/7 C; outdoor air 35 C; (Evaporating 4,5 C for condensing unit) Heating: water (in/out) 40/45 C; outdoor air 7 C d.b./87% RH Free cooling: water (in/out) 15/10 C, outdoor air 2 C Power supply: 400V - 3-50Hz Sound pressure on free field reflecting surface (directivity fact. 2) according to ISO 3744 17

Technical Sheets SA-S Size 5 6 7 8 10 11 12 13 15 Cooling capacity 47,6 52,9 61,7 67,5 82,6 96,4 108,9 121,6 138,7 Power input 21,4 24,9 27,2 31,3 37,2 42,6 48,3 54,2 61,2 Maximum power input at limit conditions 25,9 29,5 33,1 38,2 46,2 52,8 59,3 66,0 76,2 Maximum outdoor air temperature ( C) 42,0 41,0 42,0 41,0 42,5 42,5 42,3 42,0 42,0 Water flow (m3/h) 8,2 9,1 10,6 11,6 14,2 16,6 18,7 20,9 23,9 Pressure loss of hydronic circuit (kpa) 38 46 48 59 70 59 40 50 52 EER (kw/kw) 2,22 2,13 2,27 2,16 2,22 2,26 2,25 2,24 2,27 ESEER (kw/kw) 3,57 3,47 3,61 3,51 3,57 3,61 3,60 3,59 3,61 Sound pressure at 10m (db(a)) 42,3 42,3 42,3 43,8 44,3 46,6 46,0 45,9 46,8 Total air flow (m3/h) 16200 16200 18720 18720 34200 34200 34200 34200 34200 Number of compressors (n.) 2 2 2 2 2 2 3 3 4 Number of circuits (n.) 1 1 1 1 1 1 2 2 2 Rated current at nominal conditions (A) 42 49 53 61 73 83 94 106 119 Maximum current at full load (A) 52 59 66 75 91 103 116 128 147 Maximum starting current (A) 170 186 193 220 258 271 284 329 295 Buffer tank capacity (lt) 180 180 180 180 330 330 330 330 330 Maximum operating pressure PS (bar) 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 Power input of low pressure pump 0,74 0,81 0,96 1,04 1,21 1,35 1,44 1,98 2,13 Amperage of low pressure pump (A) 1,5 1,7 2,0 2,1 2,5 2,8 3,0 4,1 4,4 Available pressure with low prevalence hydronic kit (kpa) 97 88 111 99 85 78 90 123 108 Power input of high pressure pump (A) 0,9 1,0 1,2 1,3 1,5 1,7 1,8 2,2 2,4 Amperage of high pressure pump (A) 1,9 2,1 2,4 2,6 3,1 3,5 3,8 4,6 5,0 Available pressure with high prevalence hydronic kit (kpa) FREE COOLING 177 168 163 151 137 129 141 177 165 Cooling capacity 43,8 48,7 56,7 62,1 76,0 88,7 100,2 111,9 127,6 Pressure loss of hydronic circuit at chiller mode (kpa) Pressure loss of hydronic circuit at freecooling mode (kpa) Power input 1,4 1,4 1,7 1,7 3,0 3,0 3,0 3,0 3,0 Water flow (m3/h) 8,2 9,1 10,6 11,6 14,2 16,6 18,7 20,9 23,9 51 61 65 80 94 80 54 68 70 81 98 104 128 150 128 87 108 112 Number of antivibrating supports 4 4 4 6 6 6 6 6 6 Load capacity required to single antivibrating support (dan) Total weight with no water and excluded any hydronic kit and buffer tank (kg) 288 317 366 266 319 366 407 448 499 639 705 814 885 1063 1220 1358 1492 1665 18

Silent version 18 20 23 27 30 36 41 46 52 60 67 75 153,9 177,6 214,1 246,9 275,6 311,8 361,4 418,7 476,0 540,8 638,3 714,7 67,0 79,9 97,1 104,6 129,7 133,3 160,9 193,3 217,6 241,6 289,1 328,8 83,9 97,5 117,6 131,2 153,0 164,4 190,5 231,6 248,7 283,6 343,8 378,4 42,8 41,5 41,5 43,5 40,3 43,1 42,0 41,3 41,2 41,5 41,5 40,5 26,5 30,5 36,8 42,5 47,4 53,6 62,2 72,0 81,9 93,0 109,8 122,9 51 57 66 64 87 64 69 76 46 54 76 76 2,30 2,22 2,21 2,36 2,13 2,34 2,25 2,17 2,19 2,24 2,21 2,17 3,64 3,57 3,55 3,70 3,47 3,68 3,59 3,51 3,53 3,58 3,56 3,52 48,2 48,6 48,7 49,5 50,2 52,0 53,5 52,7 53,6 55,0 55,1 56,2 48600 49950 56295 74700 70200 99360 99360 138600 132480 132480 167400 165600 4 4 4 4 4 4 4 6 6 6 8 8 2 2 2 2 2 2 2 2 2 2 4 4 131 156 190 204 253 260 314 378 425 472 565 642 163 188 225 253 291 314 363 442 475 539 651 715 334 360 431 460 550 651 702 709 819 887 1004 1072 330 330 330 330 330 660 660 660 660 660 660 660 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 2,22 2,30 2,76 3,34 3,51 3,72 4,89 5,67 6,44 7,32 8,64 9,68 4,6 4,8 5,7 6,9 7,3 7,7 10,1 11,7 13,3 15,1 17,8 20,0 95 68 82 92 55 71 81 68 90 72 73 68 2,5 2,7 2,8 4,7 5,0 5,5 6,9 8,0 9,1 10,3 12,2 13,7 5,3 5,6 5,7 9,7 10,4 11,3 14,3 16,5 18,8 21,3 25,2 28,2 154 130 152 162 125 141 151 138 160 142 143 138 141,6 163,4 197,0 227,1 253,6 286,9 332,5 385,2 437,9 497,5 587,3 657,5 4,3 4,4 5,0 6,6 6,2 8,8 8,8 12,3 11,8 11,8 14,9 14,7 26,5 30,5 36,8 42,5 47,4 53,6 62,2 72,0 81,9 93,0 109,8 122,9 69 78 89 86 117 87 94 103 62 73 103 103 110 124 142 138 188 139 150 164 99 117 165 164 6 6 6 8 8 8 8 8 8 8 10 10 543 607 696 573 612 678 786 910 1035 1176 1110 1243 1811 2024 2319 2549 2722 3013 3492 4046 4599 5226 6168 6906 Technical specifications at following conditions Cooling: water (in/out) 12/7 C; outdoor air 35 C; (Evaporating 4,5 C for condensing unit) Heating: water (in/out) 40/45 C; outdoor air 7 C d.b./87% RH Free cooling: water (in/out) 15/10 C, outdoor air 2 C Power supply: 400V - 3-50Hz Sound pressure on free field reflecting surface (directivity fact. 2) according to ISO 3744 19

Technical Sheets SA-E-S Size 5 6 7 8 10 11 12 13 15 Cooling capacity 46,3 52,7 59,6 67,3 77,9 90,8 106,4 118,6 136,8 Power input 17,2 19,7 22,4 25,7 28,8 34,2 38,5 45,1 50,4 Maximum power input at limit conditions 21,4 24,6 28,0 31,9 35,7 42,6 48,2 56,4 62,8 Maximum outdoor air temperature ( C) 46,5 46,5 45,8 46,5 46,5 46,4 46,5 45,5 46,5 Water flow (m3/h) 8,0 9,1 10,3 11,6 13,4 15,6 18,3 20,4 23,5 Pressure loss of hydronic circuit (kpa) 31 38 41 51 49 41 35 43 39 EER (kw/kw) 2,69 2,68 2,66 2,62 2,71 2,66 2,76 2,63 2,72 ESEER (kw/kw) 3,98 3,97 3,95 3,92 3,99 3,95 4,03 3,93 3,99 Sound pressure at 10m (db(a)) 42,2 42,2 42,2 45,1 43,2 45,4 45,7 45,2 46,9 Total air flow (m3/h) 16200 17190 17415 24336 29880 32400 34560 34560 49950 Number of compressors (n.) 2 2 2 2 2 3 3 4 4 Number of circuits (n.) 1 1 1 1 1 2 2 2 2 Rated current at nominal conditions (A) 34 38 44 50 56 67 75 88 98 Maximum current at full load (A) 47 52 59 69 79 90 102 115 132 Maximum starting current (A) 165 170 186 196 223 235 270 244 262 Buffer tank capacity (lt) 180 180 180 330 330 330 330 330 330 Maximum operating pressure PS (bar) 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 Power input of low pressure pump 0,72 0,81 0,93 1,03 1,16 1,29 1,43 1,95 2,11 Amperage of low pressure pump (A) 1,5 1,7 1,9 2,1 2,4 2,7 2,9 4,0 4,4 Available pressure with low prevalence hydronic kit (kpa) 104 95 119 108 98 100 98 132 116 Power input of high pressure pump (A) 0,9 1,0 1,1 1,3 1,4 1,6 1,8 2,2 2,4 Amperage of high pressure pump (A) 1,9 2,1 2,3 2,6 2,9 3,3 3,7 4,5 4,9 Available pressure with high prevalence hydronic kit (kpa) FREE COOLING 183 175 171 159 149 151 148 186 172 Cooling capacity 38,3 43,6 49,3 55,7 64,5 75,1 88,1 98,2 113,3 Pressure loss of hydronic circuit at chiller mode (kpa) Pressure loss of hydronic circuit at freecooling mode (kpa) Power input 1,4 1,5 1,5 2,2 2,7 2,9 3,1 3,1 4,4 Water flow (m3/h) 8,0 9,1 10,3 11,6 13,4 15,6 18,3 20,4 23,5 42 52 55 68 66 55 47 58 53 68 83 88 109 106 89 75 93 84 Number of antivibrating supports 4 4 6 6 6 6 6 6 6 Load capacity required to single antivibrating support (dan) Total weight with no water and excluded any hydronic kit and buffer tank (kg) 302 333 256 279 335 384 428 470 524 671 741 855 929 1116 1281 1426 1566 1748 20

High Energy Efficiency - Silent version 18 20 23 27 30 36 41 46 52 60 67 152,7 171,9 200,5 236,0 270,7 302,0 355,3 393,8 456,6 544,4 582,8 57,1 64,5 70,3 90,0 100,7 120,6 135,1 151,7 179,3 211,4 228,5 71,4 80,7 87,7 112,7 125,4 150,7 168,6 189,6 224,5 264,4 286,0 46,5 46,2 46,5 45,5 46,5 45,0 46,5 45,8 45,0 45,5 45,0 26,3 29,6 34,5 40,6 46,6 51,9 61,1 67,7 78,5 93,6 100,2 40 44 44 54 75 54 54 45 48 59 54 2,67 2,67 2,85 2,62 2,69 2,50 2,63 2,60 2,55 2,58 2,55 3,96 3,96 4,09 3,92 3,97 3,83 3,93 3,90 3,86 3,89 3,87 47,6 47,6 49,0 49,1 50,5 50,8 52,5 53,2 52,2 54,0 54,5 51300 56700 76500 72000 99000 97200 131400 131400 132480 167400 165600 4 4 4 4 4 4 4 4 6 6 6 2 2 2 2 2 2 2 2 2 2 2 112 126 137 176 197 235 264 296 350 413 446 151 166 191 228 260 298 338 370 442 514 546 299 337 363 434 468 558 675 709 709 860 894 330 330 330 330 660 660 660 660 660 660 0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 2,22 2,29 2,76 3,19 3,66 4,09 4,81 5,33 6,18 7,37 7,89 4,6 4,7 5,7 6,6 7,6 8,4 9,9 11,0 12,8 15,2 16,3 102 80 117 102 77 103 98 102 91 67 99 2,5 2,7 3,9 4,5 5,2 5,8 6,8 7,5 8,7 10,4 11,1 5,2 5,5 8,0 9,3 10,7 11,9 14,0 15,5 18,0 21,5 23,0 161 142 187 172 147 173 168 172 161 137 169 126,5 142,4 166,0 195,4 224,2 250,1 294,2 326,1 378,1 450,8 482,5 4,6 5,0 6,8 6,4 8,8 8,6 11,7 11,7 11,8 14,9 14,7 26,3 29,6 34,5 40,6 46,6 51,9 61,1 67,7 78,5 93,6 100,2 55 60 60 74 102 72 72 60 65 80 73 87 96 95 118 163 116 116 96 103 128 117 6 6 8 8 8 8 8 8 8 10 10 570 638 548 602 643 716 822 930 1079 988 122 1901 2125 2435 2676 2858 3183 3654 4134 4797 5487 7252 Technical specifications at following conditions Cooling: water (in/out) 12/7 C; outdoor air 35 C; (Evaporating 4,5 C for condensing unit) Heating: water (in/out) 40/45 C; outdoor air 7 C d.b./87% RH Free cooling: water (in/out) 15/10 C, outdoor air 2 C Power supply: 400V - 3-50Hz Sound pressure on free field reflecting surface (directivity fact. 2) according to ISO 3744 21

Technical Sheets SA-TOP-S Size 5 6 7 8 10 11 12 13 Cooling capacity 47,6 57,5 64,9 74,6 83,8 98,7 111,6 128,9 Power input 17,0 20,3 23,1 25,8 29,1 33,7 40,0 46,1 Maximum power input at limit conditions 20,4 24,3 27,7 30,8 34,8 40,4 48,1 55,2 Maximum outdoor air temperature ( C) 43,9 44,9 43,5 46,8 45,7 44,5 42,9 45,5 Water flow (m3/h) 8,2 9,9 11,2 12,8 14,4 17,0 19,2 22,2 Pressure loss of hydronic circuit (kpa) 23 29 36 35 39 25 28 33 EER (kw/kw) 2,80 2,83 2,81 2,89 2,88 2,93 2,79 2,80 ESEER (kw/kw) 4,06 4,08 4,06 4,11 4,11 4,14 4,05 4,05 Sound pressure at 10m (db(a)) 42 45 45 45 43 45 46 47 Total air flow (m3/h) 16875 22140 22050 35100 35100 36450 36450 53100 Number of compressors (n.) 2 2 2 2 2 3 3 4 Number of circuits (n.) 1 1 1 1 1 2 2 2 Rated current at nominal conditions (A) 33 40 45 50 57 66 78 90 Maximum current at full load (A) 50 58 65 72 82 94 107 124 Maximum starting current (A) 165 173 189 196 223 235 270 248 Buffer tank capacity (lt) 180 330 330 330 330 330 330 330 Maximum operating pressure PS (bar) 6 6 6 6 6 6 6 6 Power input of low pressure pump 0,7 0,9 1,0 1,1 1,2 1,4 1,5 2,0 Amperage of low pressure pump (A) 1,5 1,8 2,1 2,3 2,5 2,8 3,0 4,2 Available pressure with low prevalence hydronic kit (kpa) 111 102 122 116 108 116 107 142 Power input of high pressure pump (A) 0,9 1,1 1,2 1,4 1,5 1,7 1,9 2,3 Amperage of high pressure pump (A) 1,9 2,3 2,5 2,8 3,1 3,5 3,9 4,7 Available pressure with high prevalence hydronic kit (kpa) FREE COOLING 191 183 174 167 159 167 157 197 Cooling capacity 43,8 52,9 59,7 68,6 77,1 90,8 102,7 118,6 Pressure loss of hydronic circuit at chiller mode (kpa) Pressure loss of hydronic circuit at freecooling mode (kpa) Power input 1,8 2,5 2,6 3,6 3,7 3,6 3,7 5,4 Water flow (m3/h) 8,2 9,9 11,2 12,8 14,4 17,0 19,2 22,2 23 30 36 35 40 25 28 33 42 53 65 64 71 44 50 59 Number of antivibrating supports 74 74 74 74 74 74 74 74 Load capacity required to single antivibrating support (dan) Total weight with no water and excluded any hydronic kit and buffer tank (kg) 300 336 251 279 335 384 428 470 666 746 836 929 1116 1281 1426 1566 22

Top Energy Efficiency - Silent version 15 18 20 23 27 30 36 41 46 52 145,6 162,3 189,0 223,7 261,4 288,3 340,0 386,3 433,1 499,7 51,3 58,4 65,0 78,8 90,5 103,0 118,9 136,6 153,6 179,8 61,6 70,3 77,9 94,8 108,4 123,7 142,4 164,0 185,1 216,1 44,3 43,0 45,1 43,0 45,1 43,8 45,4 44,0 42,5 43,5 25,0 27,9 32,5 38,5 45,0 49,6 58,5 66,4 74,5 85,9 29 34 44 43 46 43 35 36 29 39 2,84 2,78 2,91 2,84 2,89 2,80 2,86 2,83 2,82 2,78 4,08 4,04 4,12 4,08 4,11 4,05 4,09 4,07 4,07 4,04 47 48 45 46 47 47 49 48 47 50 53100 53100 73800 73350 102600 100800 138060 137340 136800 171000 4 4 4 4 4 4 4 4 4 6 2 2 2 2 2 2 2 2 2 2 100 114 127 154 177 201 232 267 300 351 138 158 177 213 247 273 320 176 32 471 262 299 340 376 442 468 565 421 29 716 330 330 330 330 330 660 660 660 660 660 6 6 6 6 6 6 6 6 6 6 2,2 2,3 2,3 2,7 3,5 3,9 4,6 5,2 5,9 6,8 4,5 4,7 4,8 5,6 7,3 8,1 9,5 10,8 12,1 14,0 123 103 67 100 124 127 135 134 141 131 2,5 2,6 2,7 4,0 5,0 5,5 6,5 7,4 8,3 9,5 5,1 5,4 5,7 8,2 10,3 11,4 13,4 15,2 17,1 19,7 180 163 131 170 194 197 205 204 211 201 134,0 149,3 173,8 205,8 240,5 265,2 312,8 355,4 398,5 459,7 5,4 5,6 7,6 7,7 11,3 11,3 14,6 14,8 14,6 18,8 25,1 27,9 32,5 38,5 45,0 49,6 58,5 66,5 74,6 86,0 29 34 44 43 46 43 35 36 29 39 52 61 79 78 83 77 63 66 52 70 74 74 74 74 74 74 74 74 74 74 524 570 629 548 602 646 716 822 930 1079 1748 1901 2096 2435 2676 2873 3183 3654 4134 4797 Technical specifications at following conditions Cooling: water (in/out) 12/7 C; outdoor air 35 C; (Evaporating 4,5 C for condensing unit) Heating: water (in/out) 40/45 C; outdoor air 7 C d.b./87% RH Free cooling: water (in/out) 15/10 C, outdoor air 2 C Power supply: 400V - 3-50Hz Sound pressure on free field reflecting surface (directivity fact. 2) according to ISO 3744 23

Technical Sheets SA-H-N Size 5 6 7 8 10 11 12 13 Cooling capacity 49,3 54,8 63,9 69,9 85,5 99,8 112,8 125,9 Power input 20,1 23,4 25,5 29,3 35,0 40,1 45,4 50,9 Maximum power input at limit conditions 25,9 29,5 33,1 38,2 46,2 52,8 59,3 66,0 Maximum outdoor air temperature ( C) 42,0 41,0 42,0 41,0 42,5 42,5 42,3 42,0 Water flow (m3/h) 8,5 9,4 11,0 12,0 14,7 17,2 19,4 21,7 Pressure loss of hydronic circuit (kpa) 38 46 49 60 72 61 41 52 EER (kw/kw) 2,45 2,34 2,50 2,38 2,44 2,49 2,48 2,47 ESEER (kw/kw) 3,78 3,69 3,83 3,72 3,78 3,82 3,81 3,80 Heat capacity 55,7 61,9 72,2 79,0 96,6 112,8 127,5 142,3 Power input (heating mode) 19,3 22,4 24,5 28,2 33,6 38,5 43,6 48,9 Water flow (heating mode) (m3/h) 9,6 10,6 12,4 13,6 16,6 19,4 21,9 24,5 Pressure loss of hydronic circuit (kpa) 49 59 63 77 91 78 53 66 Minimum operating outdoor air temperature in heating mode ( C) -10,1-9,5-9,5-8,9-11,0-10,4-9,7-9,1 COP (kw/kw) 2,88 2,76 2,94 2,80 2,88 2,93 2,92 2,91 Sound pressure at 10m (db(a)) 47,4 47,4 47,3 49,1 51,6 52,0 51,2 51,1 Total air flow (m3/h) 18000 18000 20800 20800 38000 38000 38000 38000 Number of compressors (n.) 2 2 2 2 2 2 3 3 Number of circuits (n.) 1 1 1 1 1 1 2 2 Rated current at nominal conditions (A) 39 46 50 57 68 78 89 99 Maximum current at full load (A) 52 59 66 75 91 103 116 128 Maximum starting current (A) 170 186 193 220 258 271 284 329 Buffer tank capacity (lt) 180 180 180 180 330 330 330 330 Maximum operating pressure PS (bar) 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 Power input of low pressure pump 0,78 0,85 1,00 1,08 1,26 1,39 1,48 2,04 Amperage of low pressure pump (A) 1,6 1,7 2,1 2,2 2,6 2,9 3,1 4,2 Available pressure with low prevalence hydronic kit (kpa) 96 79 100 86 65 67 77 105 Power input of high pressure pump (A) 1,0 1,1 1,2 1,3 1,6 1,8 1,9 2,3 Amperage of high pressure pump (A) 2,0 2,2 2,5 2,7 3,2 3,6 3,9 4,7 Available pressure with high prevalence hydronic kit (kpa) 176 167 162 149 134 126 138 174 Number of antivibrating supports 4 4 4 6 6 6 6 6 Load capacity required to single antivibrating support (dan) Total weight with no water and excluded any hydronic kit and buffer tank (kg) 305 336 388 281 338 388 431 474 677 747 862 937 1126 1292 1438 1580 24

Heat Pump - Basic version 15 18 20 23 27 30 36 41 46 52 60 143,6 159,4 183,9 221,8 255,7 285,5 323,0 374,3 433,7 489,7 562,7 57,4 63,0 75,0 91,2 98,3 121,8 125,6 151,4 181,4 206,3 243,2 76,2 83,9 97,5 117,6 131,2 153,0 164,4 190,5 231,6 265,0 305,4 42,0 42,8 41,5 41,5 43,5 40,3 43,1 42,0 41,3 41,2 40,3 24,7 27,4 31,6 38,1 44,0 49,1 55,6 64,4 74,6 84,2 96,8 54 53 60 68 66 90 65 71 78 65 60 2,50 2,53 2,45 2,43 2,60 2,34 2,57 2,47 2,39 2,37 2,31 3,83 3,85 3,78 3,77 3,91 3,69 3,88 3,80 3,73 3,71 3,66 162,3 180,1 207,8 250,6 289,0 322,6 365,0 423,0 490,1 553,3 635,9 55,1 60,5 72,0 87,5 94,3 116,9 120,5 145,4 174,1 198,1 233,5 27,9 31,0 35,7 43,1 49,7 55,5 62,8 72,8 84,3 95,2 109,4 69 67 76 87 84 114 84 90 99 83 76-8,3-9,8-9,1-8,6-9,6-8,4-9,9-9,0-9,9-9,1-8,0 2,94 2,98 2,88 2,86 3,06 2,76 3,03 2,91 2,81 2,79 2,72 52,1 53,6 54,0 54,1 54,8 55,6 56,6 57,9 58,1 57,8 58,6 38000 54000 55500 62550 83000 78000 110400 110400 154000 150000 147200 4 4 4 4 4 4 4 4 6 8 8 2 2 2 2 2 2 2 2 2 4 4 112 123 147 178 192 238 245 296 354 403 475 147 163 188 225 253 291 314 363 442 503 579 295 334 360 431 460 550 651 702 709 723 853 330 330 330 330 330 330 660 660 660 660 660 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 2,18 2,26 2,31 2,73 3,46 3,86 4,37 5,07 5,87 6,63 7,62 4,5 4,7 4,8 5,6 7,1 8,0 9,0 10,5 12,1 13,7 15,7 86 79 46 63 88 61 89 78 64 70 63 2,5 2,6 2,7 1,4 5,1 5,7 6,4 7,5 8,6 9,7 11,2 5,1 5,4 5,6 2,9 10,5 11,7 13,3 15,4 17,8 20,1 23,1 161 151 126 143 168 141 169 158 144 150 143 6 6 6 6 8 8 8 8 8 8 8 529 575 643 737 607 649 718 832 964 1088 1251 1763 1917 2143 2456 2698 2882 3190 3697 4284 4837 5559 Technical specifications at following conditions Cooling: water (in/out) 12/7 C; outdoor air 35 C; (Evaporating 4,5 C for condensing unit) Heating: water (in/out) 40/45 C; outdoor air 7 C d.b./87% RH Free cooling: water (in/out) 15/10 C, outdoor air 2 C Power supply: 400V - 3-50Hz Sound pressure on free field reflecting surface (directivity fact. 2) according to ISO 3744 25

Technical Sheets SA-H-E Size 5 6 7 8 10 11 12 13 Cooling capacity 47,9 54,6 61,7 69,7 80,6 94,0 110,2 122,8 Power input 16,2 18,5 21,1 24,3 27,1 32,2 36,2 42,4 Maximum power input at limit conditions 21,4 24,6 28,0 31,9 35,7 42,6 48,2 56,4 Maximum outdoor air temperature ( C) 47,0 46,0 45,8 47,3 47,5 46,4 47,1 45,5 Water flow (m3/h) 8,4 9,5 10,8 12,2 14,1 16,4 19,3 21,5 Pressure loss of hydronic circuit (kpa) 32 40 42 53 51 42 36 45 EER (kw/kw) 2,96 2,95 2,93 2,87 2,98 2,92 3,04 2,90 ESEER (kw/kw) 4,16 4,15 4,14 4,10 4,16 4,13 4,20 4,12 Heat capacity 54,2 61,7 69,8 78,8 91,1 106,2 124,5 138,8 Power input (heating mode) 15,7 18,0 20,4 23,5 26,3 31,2 35,2 41,1 Water flow (heating mode) (m3/h) 9,3 10,6 12,0 13,6 15,7 18,3 21,4 23,9 Pressure loss of hydronic circuit (kpa) 40 49 52 65 63 52 45 56 Minimum operating outdoor air temperature in heating mode ( C) -10,5-10,2-9,6-10,7-10,9-10,6-10,2-9,5 COP (kw/kw) 3,45 3,44 3,41 3,35 3,47 3,40 3,54 3,38 Sound pressure at 10m (db(a)) 47,3 47,4 47,4 47,3 51,2 50,8 51,2 50,4 Total air flow (m3/h) 18000 19250 19350 27040 33200 36000 38400 38400 Number of compressors (n.) 2 2 2 2 2 3 3 4 Number of circuits (n.) 1 1 1 1 1 2 2 2 Rated current at nominal conditions (A) 32 36 41 47 53 63 71 83 Maximum current at full load (A) 47 52 59 69 79 90 102 115 Maximum starting current (A) 165 170 186 196 223 235 270 244 Buffer tank capacity (lt) 180 180 180 330 330 330 330 330 Maximum operating pressure PS (bar) 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 Power input of low pressure pump 0,70 0,78 0,86 0,94 1,30 1,44 1,56 1,61 Amperage of low pressure pump (A) 1,5 1,6 1,8 1,9 2,7 3,0 3,2 3,3 Available pressure with low prevalence hydronic kit (kpa) 97 86 80 65 90 90 84 66 Power input of high pressure pump (A) 0,9 1,1 1,2 1,3 1,5 1,8 2,1 2,3 Amperage of high pressure pump (A) 1,9 2,2 2,4 2,7 3,1 3,8 4,3 4,6 Available pressure with high prevalence hydronic kit (kpa) 182 174 170 158 147 201 199 183 Number of antivibrating supports 4 4 6 6 6 6 6 6 Load capacity required to single antivibrating support (dan) Total weight with no water and excluded any hydronic kit and buffer tank (kg) 320 353 272 295 355 407 453 498 711 784 905 984 1182 1357 1509 1659 26

Heat Pump - High Energy Efficiency version 15 18 20 23 27 30 36 41 46 52 141,7 158,2 178,1 207,7 244,4 280,4 312,8 368,0 407,9 473,0 47,4 53,8 60,6 66,2 84,6 94,8 113,4 127,3 142,7 168,5 62,8 71,4 80,7 87,7 112,7 125,4 150,7 168,6 189,6 224,5 47,5 46,5 46,2 48,0 45,5 47,0 45,0 46,5 45,8 45,0 24,8 27,6 31,1 36,3 42,7 49,0 54,7 64,3 71,3 82,7 41 42 47 46 57 79 55 60 46 49 2,99 2,94 2,94 3,14 2,89 2,96 2,76 2,89 2,86 2,81 4,17 4,15 4,14 4,25 4,11 4,15 4,02 4,11 4,09 4,06 160,2 178,7 201,2 234,7 276,2 316,9 353,5 415,9 461,0 534,4 46,0 52,1 58,8 64,2 82,1 92,0 110,0 123,5 138,4 163,5 27,5 30,7 34,6 40,4 47,5 54,5 60,8 71,5 79,3 91,9 51 52 58 57 71 98 68 74 56 61-10,7-10,3-10,2-10,9-9,8-10,7-10,0-10,7-10,2-9,5 3,48 3,43 3,42 3,66 3,36 3,44 3,21 3,37 3,33 3,27 52,0 53,3 53,2 54,8 54,9 56,0 56,6 57,9 58,6 58,1 55500 57000 63000 85000 80000 110000 108000 146000 146000 147200 4 4 4 4 4 4 4 4 4 6 2 2 2 2 2 2 2 2 2 2 93 105 118 129 165 185 221 249 279 329 132 151 166 191 228 260 298 338 370 442 262 299 337 363 434 468 558 675 709 709 330 330 330 330 330 660 660 660 660 660 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 2,40 2,40 2,30 3,27 3,36 3,86 4,30 5,06 5,61 6,51 5,0 5,0 4,7 6,8 6,9 8,0 8,9 10,5 11,6 13,4 101 91 66 103 110 87 113 107 120 115 2,5 2,6 2,7 4,6 4,7 5,4 6,1 7,1 7,9 9,2 5,1 5,4 5,6 9,5 9,8 11,2 12,5 14,8 16,4 19,0 168 158 138 183 180 157 183 177 190 185 6 6 6 8 8 8 8 8 8 8 555 604 675 580 638 681 758 870 985 1143 1851 2013 2250 2578 2833 3026 3370 3869 4377 5079 Technical specifications at following conditions Cooling: water (in/out) 12/7 C; outdoor air 35 C; (Evaporating 4,5 C for condensing unit) Heating: water (in/out) 40/45 C; outdoor air 7 C d.b./87% RH Free cooling: water (in/out) 15/10 C, outdoor air 2 C Power supply: 400V - 3-50Hz Sound pressure on free field reflecting surface (directivity fact. 2) according to ISO 3744 27

Technical Sheets SA-H-S Size 5 6 7 8 10 11 12 13 Cooling capacity 46,9 52,0 60,7 66,4 81,2 94,8 107,2 119,6 Power input 21,5 25,0 27,3 31,4 37,3 42,8 48,5 54,4 Maximum power input at limit conditions 25,9 29,5 33,1 38,2 46,2 52,8 59,3 66,0 Maximum outdoor air temperature ( C) 42,0 41,0 42,0 41,0 42,5 42,5 42,3 42,0 Water flow (m3/h) 8,1 9,0 10,4 11,4 14,0 16,3 18,4 20,6 Pressure loss of hydronic circuit (kpa) 37 45 48 59 69 59 40 50 EER (kw/kw) 2,18 2,08 2,22 2,12 2,18 2,22 2,21 2,20 ESEER (kw/kw) 3,53 3,43 3,57 3,46 3,52 3,57 3,56 3,55 Heat capacity 53,0 58,8 68,6 75,1 91,8 107,2 121,1 135,2 Power input (heating mode) 19,3 22,4 24,5 28,2 33,6 38,5 43,6 48,9 Water flow (heating mode) (m3/h) 9,1 10,1 11,8 12,9 15,8 18,4 20,8 23,3 Pressure loss of hydronic circuit (kpa) 48 58 61 75 88 75 51 63 Minimum operating outdoor air temperature in heating mode ( C) -10,1-9,5-9,5-8,9-11,0-10,4-9,7-9,1 COP (kw/kw) 2,74 2,62 2,80 2,66 2,73 2,79 2,78 2,77 Sound pressure at 10m (db(a)) 42,2 42,2 42,2 43,2 45,9 46,1 45,7 45,6 Total air flow (m3/h) 16200 16200 18720 18720 34200 34200 34200 34200 Number of compressors (n.) 2 2 2 2 2 2 3 3 Number of circuits (n.) 1 1 1 1 1 1 2 2 Rated current at nominal conditions (A) 42 49 53 61 73 83 95 106 Maximum current at full load (A) 52 59 66 75 91 103 116 128 Maximum starting current (A) 170 186 193 220 258 271 284 329 Buffer tank capacity (lt) 180 180 180 180 330 330 330 330 Maximum operating pressure PS (bar) 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 Power input of low pressure pump 0,68 0,74 1,03 1,11 1,30 1,43 1,53 2,26 Amperage of low pressure pump (A) 1,4 1,5 2,1 2,3 2,7 3,0 3,2 4,7 Available pressure with low prevalence hydronic kit (kpa) 97 88 112 100 86 80 92 125 Power input of high pressure pump (A) 1,1 1,2 1,4 1,5 1,8 2,0 2,1 2,8 Amperage of high pressure pump (A) 2,3 2,5 2,9 3,1 3,6 4,1 4,4 5,9 Available pressure with high prevalence hydronic kit (kpa) 177 168 164 152 138 131 142 169 Number of antivibrating supports 4 4 4 6 6 6 6 6 Load capacity required to single antivibrating support (dan) Total weight with no water and excluded any hydronic kit and buffer tank (kg) 311 343 396 287 344 395 440 483 690 762 879 956 1148 1318 1466 1611 28

Heat Pump - Silent version 15 18 20 23 27 30 36 41 46 52 60 136,5 151,4 174,7 210,7 242,9 271,2 306,8 355,6 412,0 465,2 534,6 61,4 67,3 80,2 97,4 105,0 130,1 133,7 161,5 194,0 219,9 259,5 76,2 83,9 97,5 117,6 131,2 153,0 164,4 190,5 231,6 265,0 305,4 42,0 42,8 41,5 41,5 43,5 40,3 43,1 42,0 41,3 41,2 40,3 23,5 26,0 30,1 36,2 41,8 46,7 52,8 61,2 70,9 80,0 92,0 51 50 56 65 63 86 64 69 75 63 58 2,22 2,25 2,18 2,16 2,31 2,08 2,29 2,20 2,12 2,12 2,06 3,57 3,60 3,53 3,51 3,66 3,43 3,64 3,55 3,47 3,46 3,40 154,2 171,1 197,4 238,1 274,5 306,5 346,7 401,8 465,6 525,7 604,1 55,1 60,5 72,0 87,5 94,3 116,9 120,5 145,4 174,1 198,1 233,5 26,5 29,4 34,0 41,0 47,2 52,7 59,6 69,1 80,1 90,4 103,9 65 64 72 83 81 110 82 88 96 81 74-8,3-9,8-9,1-8,6-9,6-8,4-9,9-9,0-9,9-9,1-8,0 2,80 2,83 2,74 2,72 2,91 2,62 2,88 2,76 2,67 2,65 2,59 46,2 47,8 48,0 48,1 49,0 49,5 51,3 52,4 52,2 52,0 52,5 34200 48600 49950 56295 74700 70200 99360 99360 138600 135000 132480 4 4 4 4 4 4 4 4 6 8 8 2 2 2 2 2 2 2 2 2 4 4 120 131 157 190 205 254 261 315 379 429 507 147 163 188 225 253 291 314 363 442 503 579 295 334 360 431 460 550 651 702 709 723 853 330 330 330 330 330 330 660 660 660 660 660 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 2,37 2,41 2,35 3,28 3,29 3,67 4,15 4,81 5,58 6,30 7,24 4,9 5,0 4,8 6,8 6,8 7,6 8,6 9,9 11,5 13,0 14,9 111 98 71 77 93 67 92 82 70 74 70 3,1 3,2 3,4 1,2 4,6 5,2 5,9 6,8 7,9 8,9 10,2 6,3 6,7 6,9 2,4 9,6 10,7 12,1 14,0 16,3 18,4 21,1 157 146 123 147 163 137 162 152 140 144 140 6 6 6 6 8 8 8 8 8 8 8 539 587 656 751 619 661 732 849 983 1110 1276 1798 1956 2186 2505 2752 2940 3254 3771 4370 4934 5670 Technical specifications at following conditions Cooling: water (in/out) 12/7 C; outdoor air 35 C; (Evaporating 4,5 C for condensing unit) Heating: water (in/out) 40/45 C; outdoor air 7 C d.b./87% RH Free cooling: water (in/out) 15/10 C, outdoor air 2 C Power supply: 400V - 3-50Hz Sound pressure on free field reflecting surface (directivity fact. 2) according to ISO 3744 29

Technical Sheets SA-H-E-S Size 5 6 7 8 10 11 12 13 Cooling capacity 45,5 51,9 58,6 66,2 76,6 89,3 104,7 116,7 Power input 17,3 19,8 22,5 25,8 28,8 34,3 38,7 45,2 Maximum power input at limit conditions 21,4 24,6 28,0 31,9 35,7 42,6 48,2 56,4 Maximum outdoor air temperature ( C) 47,0 46,0 45,8 47,3 47,5 46,4 47,1 45,5 Water flow (m3/h) 7,8 8,9 10,1 11,4 13,2 15,4 18,0 20,1 Pressure loss of hydronic circuit (kpa) 31 38 40 50 49 41 34 42 EER (kw/kw) 2,64 2,63 2,61 2,56 2,66 2,60 2,71 2,58 ESEER (kw/kw) 3,94 3,93 3,91 3,88 3,95 3,91 3,99 3,89 Heat capacity 51,4 58,6 66,3 74,8 86,6 100,9 118,3 131,9 Power input (heating mode) 15,7 18,0 20,4 23,5 26,3 31,2 35,2 41,1 Water flow (heating mode) (m3/h) 8,8 10,1 11,4 12,9 14,9 17,4 20,3 22,7 Pressure loss of hydronic circuit (kpa) 40 49 51 64 62 52 44 54 Minimum operating outdoor air temperature in heating mode ( C) -10,5-10,2-9,6-10,7-10,9-10,6-10,2-9,5 COP (kw/kw) 3,28 3,26 3,24 3,18 3,29 3,23 3,36 3,21 Sound pressure at 10m (db(a)) 42,2 42,2 42,2 45,1 45,7 45,4 45,7 45,2 Total air flow (m3/h) 16200 17325 17415 24336 29880 32400 34560 34560 Number of compressors (n.) 2 2 2 2 2 3 3 4 Number of circuits (n.) 1 1 1 1 1 2 2 2 Rated current at nominal conditions (A) 34 39 44 50 56 67 76 88 Maximum current at full load (A) 47 52 59 69 79 90 102 115 Maximum starting current (A) 165 170 186 196 223 235 270 244 Buffer tank capacity (lt) 180 180 180 330 330 330 330 330 Maximum operating pressure PS (bar) 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 Power input of low pressure pump 0,66 0,74 0,82 0,90 1,24 1,38 1,51 1,58 Amperage of low pressure pump (A) 1,4 1,5 1,7 1,9 2,6 2,9 3,1 3,3 Available pressure with low prevalence hydronic kit (kpa) 104 95 92 79 99 101 99 84 Power input of high pressure pump (A) 1,1 1,2 1,3 1,5 1,7 1,9 2,1 2,2 Amperage of high pressure pump (A) 2,2 2,5 2,8 3,1 3,5 3,9 4,3 4,6 Available pressure with high prevalence hydronic kit (kpa) 184 175 172 160 151 152 150 134 Number of antivibrating supports 4 4 6 6 6 6 6 6 Load capacity required to single antivibrating support (dan) Total weight with no water and excluded any hydronic kit and buffer tank (kg) 326 360 277 301 362 415 462 508 725 800 923 1004 1206 1384 1540 1692 30

Heat Pump - High Energy Efficiency - Silent version 15 18 20 23 27 30 36 41 46 52 134,7 150,3 169,2 197,3 232,2 266,4 297,2 349,6 387,5 449,3 50,6 57,3 64,7 70,5 90,3 101,0 121,0 135,5 152,2 179,9 62,8 71,4 80,7 87,7 112,7 125,4 150,7 168,6 189,6 224,5 47,5 46,5 46,2 48,0 45,5 47,0 45,0 46,5 45,8 45,0 23,2 25,8 29,1 33,9 39,9 45,8 51,1 60,1 66,7 77,3 39 40 44 44 54 74 53 53 44 47 2,66 2,62 2,61 2,80 2,57 2,64 2,46 2,58 2,55 2,50 3,96 3,92 3,92 4,05 3,88 3,94 3,79 3,89 3,86 3,82 152,2 169,8 191,2 223,0 262,4 301,0 335,8 395,1 437,9 507,7 46,0 52,1 58,8 64,2 82,1 92,0 110,0 123,5 138,4 163,5 26,2 29,2 32,9 38,4 45,1 51,8 57,8 68,0 75,3 87,3 49 51 56 56 68 95 68 68 57 61-10,7-10,3-10,2-10,9-9,8-10,7-10,0-10,7-10,2-9,5 3,31 3,26 3,25 3,47 3,20 3,27 3,05 3,20 3,16 3,11 46,9 47,6 47,6 49,0 49,1 50,5 50,8 52,5 53,2 52,2 49950 51300 56700 76500 72000 99000 97200 131400 131400 132480 4 4 4 4 4 4 4 4 4 6 2 2 2 2 2 2 2 2 2 2 99 112 126 138 176 197 236 265 297 351 132 151 166 191 228 260 298 338 370 442 262 299 337 363 434 468 558 675 709 709 330 330 330 330 330 660 660 660 660 660 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 6,0 1,63 2,41 2,38 2,12 3,14 3,61 4,02 4,73 5,25 6,08 3,4 5,0 4,9 4,4 6,5 7,4 8,3 9,8 10,8 12,6 69 105 84 54 104 79 104 99 103 93 2,4 3,2 3,3 3,2 4,4 5,1 5,7 6,7 7,4 8,6 4,9 6,6 6,9 6,6 9,2 10,5 11,7 13,8 15,3 17,7 118 153 135 124 174 149 174 169 173 163 6 6 6 8 8 8 8 8 8 8 566 616 689 592 650 695 773 888 1005 1166 1888 2053 2295 2630 2890 3087 3438 3946 4465 5181 Technical specifications at following conditions Cooling: water (in/out) 12/7 C; outdoor air 35 C; (Evaporating 4,5 C for condensing unit) Heating: water (in/out) 40/45 C; outdoor air 7 C d.b./87% RH Free cooling: water (in/out) 15/10 C, outdoor air 2 C Power supply: 400V - 3-50Hz Sound pressure on free field reflecting surface (directivity fact. 2) according to ISO 3744 31

Technical Sheets SA-C-N Condensing Unit - Basic version Size 5 6 7 8 10 11 12 13 15 18 20 23 27 30 Cooling capacity 51,1 57,3 66,3 73,2 89,5 104,0 118,1 131,8 149,6 166,0 190,6 232,1 269,6 298,1 Power input 20,1 23,4 25,5 29,3 35,0 40,1 45,4 50,9 57,4 63,0 75,0 91,2 98,3 121,8 Maximum power input at limit conditions 25,9 29,5 33,1 38,2 46,2 52,8 59,3 66,0 76,2 83,9 97,5 117,6 131,2 153,0 Maximum outdoor air temperature ( C) 41,2 39,8 41,2 39,8 41,3 41,5 41,1 40,8 41,0 41,8 40,7 40,3 42,0 39,2 EER (kw/kw) 2,5 2,5 2,6 2,5 2,6 2,6 2,6 2,6 2,6 2,6 2,5 2,5 2,7 2,4 ESEER (kw/kw) 3,86 3,79 3,90 3,82 3,87 3,90 3,91 3,90 3,91 3,93 3,86 3,86 4,01 3,78 Sound pressure at 10m (db(a)) 47,4 47,4 47,3 49,1 51,6 52,0 51,2 51,1 52,1 53,6 54,0 54,1 54,8 55,6 Total air flow (m3/h) 18000 18000 20800 20800 38000 38000 38000 38000 38000 54000 55500 62550 83000 78000 Number of compressors (n.) 2 2 2 2 2 2 2 2 4 4 4 4 4 4 Number of circuits (n.) 1 1 1 1 1 1 1 1 2 2 2 2 2 2 Rated current at nominal conditions (A) 39 46 50 57 68 78 89 99 112 123 147 178 192 238 Maximum current at full load (A) 52 59 66 75 91 103 99 128 147 163 188 225 253 291 Maximum starting current (A) 170 186 193 220 258 271 298 329 295 334 360 431 460 550 Number of antivibrating supports 4 4 4 6 6 6 6 6 6 6 6 6 8 8 Load capacity required to single antivibrating support (dan) Total weight with no water and excluded any hydronic kit and buffer tank (kg) 272 301 348 253 304 350 390 428 479 521 583 668 551 589 605 669 774 842 1014 1166 1298 1428 1595 1737 1943 2228 2449 2617 32

Technical Sheets SA-C-E Condensing Unit - High Energy Efficiency version Size 5 6 7 8 10 11 12 13 15 18 20 23 27 30 Cooling capacity 48,9 55,8 63,2 72,6 82,8 96,3 112,8 125,8 145,8 162,8 183,2 213,7 251,5 289,2 Power input 16,2 18,5 21,1 24,3 27,1 32,2 36,2 42,4 47,4 53,8 60,6 66,2 84,6 94,8 Maximum power input at limit conditions 21,4 24,6 28,0 31,9 35,7 42,6 48,2 56,4 62,8 71,4 80,7 87,7 112,7 125,4 Maximum outdoor air temperature ( C) 46,8 46,4 45,5 46,3 47,1 46,1 46,8 45,2 46,7 46,0 45,7 47,5 45,0 46,4 EER (kw/kw) 3,0 3,0 3,0 3,0 3,1 3,0 3,1 3,0 3,1 3,0 3,0 3,2 3,0 3,1 ESEER (kw/kw) 4,19 4,19 4,18 4,17 4,21 4,17 4,24 4,16 4,22 4,19 4,19 4,30 4,16 4,21 Sound pressure at 10m (db(a)) 47,3 47,4 47,4 47,3 51,2 50,8 51,2 50,4 52,0 53,3 53,2 54,8 54,9 56,0 Total air flow (m3/h) 18000 19100 19350 27040 33200 36000 38400 38400 55500 57000 63000 85000 80000 110000 Number of compressors (n.) 2 2 2 2 2 2 2 4 4 4 4 4 4 4 Number of circuits (n.) 1 1 1 1 1 1 1 2 2 2 2 2 2 2 Rated current at nominal conditions (A) 32 36 41 47 53 63 71 83 93 105 118 129 165 185 Maximum current at full load (A) 47 52 59 69 79 91 103 115 132 151 166 191 228 260 Maximum starting current (A) 165 170 186 196 223 258 271 244 262 299 337 363 434 468 Number of antivibrating supports 4 4 6 6 6 6 6 6 6 6 6 8 8 8 Load capacity required to single antivibrating support (dan) Total weight with no water and excluded any hydronic kit and buffer tank (kg) 286 316 244 265 319 367 409 450 503 547 612 526 579 618 635 702 812 884 1065 1224 1363 1499 1675 1823 2040 2339 2572 2748 Technical specifications at following conditions Cooling: water (in/out) 12/7 C; outdoor air 35 C; (Evaporating 4,5 C for condensing unit) Heating: water (in/out) 40/45 C; outdoor air 7 C d.b./87% RH Free cooling: water (in/out) 15/10 C, outdoor air 2 C Power supply: 400V - 3-50Hz Sound pressure on free field reflecting surface (directivity fact. 2) according to ISO 3744 33

Technical Sheets SA-C-S Condensing Unit - Silent version Size 5 6 7 8 10 11 12 13 15 18 20 23 27 30 Cooling capacity 48,6 54,5 63,0 69,5 85,0 98,8 112,2 125,2 142,1 157,7 181,1 220,5 256,1 283,2 Power input 20,1 23,4 25,5 29,3 35,0 40,1 45,4 50,9 57,4 63,0 75,0 91,2 98,3 121,8 Maximum power input at limit conditions 25,9 29,5 33,1 38,2 46,2 52,8 59,3 66,0 76,2 83,9 97,5 117,6 131,2 153,0 Maximum outdoor air temperature ( C) 41,2 39,8 41,2 39,8 41,3 41,5 41,1 40,8 41,0 41,8 40,7 40,3 42,0 39,2 EER (kw/kw) 2,5 2,5 2,6 2,5 2,6 2,6 2,6 2,6 2,6 2,6 2,5 2,5 2,7 2,4 ESEER (kw/kw) 3,86 3,79 3,90 3,82 3,87 3,90 3,91 3,90 3,91 3,93 3,86 3,86 4,01 3,78 Sound pressure at 10m (db(a)) 42,2 42,2 42,2 45,1 43,2 45,4 45,7 45,2 46,9 47,6 47,6 49,0 49,1 50,5 Total air flow (m3/h) 18000 18000 20800 20800 38000 38000 38000 38000 38000 54000 55500 62550 83000 78000 Number of compressors (n.) 2 2 2 2 2 2 2 2 4 4 4 4 4 4 Number of circuits (n.) 1 1 1 1 1 1 1 1 2 2 2 2 2 2 Rated current at nominal conditions (A) 39 46 50 57 68 78 89 99 112 123 147 178 192 238 Maximum current at full load (A) 52 59 66 75 91 103 99 128 147 163 188 225 253 291 Maximum starting current (A) 170 186 193 220 258 271 298 329 295 334 360 431 460 550 Number of antivibrating supports 4 4 4 6 6 6 6 6 6 6 6 6 8 8 Load capacity required to single antivibrating support (dan) Total weight with no water and excluded any hydronic kit and buffer tank (kg) 278 307 355 258 310 357 397 437 488 531 595 682 562 601 617 682 789 859 1034 1189 1324 1457 1627 1771 1982 2273 2498 2669 34

Technical Sheets SA-C-E-S Condensing Unit - High Energy Efficiency - Silent version Size 5 6 7 8 10 11 12 13 15 18 20 23 27 30 Cooling capacity 46,5 53,0 60,0 69,0 78,6 91,4 107,2 119,5 138,6 154,6 174,1 203,0 238,9 274,8 Power input 16,2 18,5 21,1 24,3 27,1 32,2 36,2 42,4 47,4 53,8 60,6 66,2 84,6 94,8 Maximum power input at limit conditions 21,4 24,6 28,0 31,9 35,7 42,6 48,2 56,4 62,8 71,4 80,7 87,7 112,7 125,4 Maximum outdoor air temperature ( C) 46,8 46,4 45,5 46,3 47,1 46,1 46,8 45,2 46,7 46,0 45,7 47,5 45,0 46,4 EER (kw/kw) 3,0 3,0 3,0 3,0 3,1 3,0 3,1 3,0 3,1 3,0 3,0 3,2 3,0 3,1 ESEER (kw/kw) 4,19 4,19 4,18 4,17 4,21 4,17 4,24 4,16 4,22 4,19 4,19 4,30 4,16 4,21 Sound pressure at 10m (db(a)) 47,4 47,4 47,3 49,1 51,6 52,0 51,2 51,1 52,1 53,6 54,0 54,1 54,8 55,6 Total air flow (m3/h) 18000 19100 19350 27040 33200 36000 38400 38400 55500 57000 63000 85000 80000 110000 Number of compressors (n.) 2 2 2 2 2 2 2 4 4 4 4 4 4 4 Number of circuits (n.) 1 1 1 1 1 1 1 2 2 2 2 2 2 2 Rated current at nominal conditions (A) 32 36 41 47 53 63 71 83 93 105 118 129 165 185 Maximum current at full load (A) 47 52 59 69 79 91 103 115 132 151 166 191 228 260 Maximum starting current (A) 165 170 186 196 223 258 271 244 262 299 337 363 434 468 Number of antivibrating supports 4 4 6 6 6 6 6 6 6 6 6 8 8 8 Load capacity required to single antivibrating support (dan) Total weight with no water and excluded any hydronic kit and buffer tank (kg) 292 322 249 271 326 375 417 459 513 558 624 537 590 631 648 716 829 902 1086 1249 1391 1529 1709 1860 2081 2386 2623 2803 Technical specifications at following conditions Cooling: water (in/out) 12/7 C; outdoor air 35 C; (Evaporating 4,5 C for condensing unit) Heating: water (in/out) 40/45 C; outdoor air 7 C d.b./87% RH Free cooling: water (in/out) 15/10 C, outdoor air 2 C Power supply: 400V - 3-50Hz Sound pressure on free field reflecting surface (directivity fact. 2) according to ISO 3744 35

Performances SA-N Outlet water temperature ( C) 5 6 7 8 10 15 20 5 49,5 19,0 51,1 19,0 52,7 19,1 54,3 19,2 57,4 19,3 65,3 19,7 66,9 19,9 6 55,0 22,0 56,8 22,1 58,5 22,2 60,3 22,2 63,8 22,4 72,5 22,8 74,3 23,0 7 64,1 24,1 66,2 24,1 68,2 24,2 70,3 24,3 74,4 24,5 84,6 24,9 86,7 25,2 8 70,2 27,6 72,5 27,7 74,7 27,8 76,9 27,9 81,4 28,1 92,6 28,6 94,9 28,9 10 85,9 33,0 88,6 33,1 91,3 33,2 94,1 33,3 99,6 33,6 113,3 34,2 116,0 34,5 11 100,2 37,7 103,4 37,9 106,6 38,0 109,8 38,2 116,2 38,4 132,2 39,1 135,4 39,5 32 12 113,3 42,8 116,9 42,9 120,5 43,1 124,1 43,2 131,3 43,6 149,4 44,3 153,0 44,8 13 126,4 47,9 130,5 48,1 134,5 48,3 138,5 48,5 146,6 48,8 166,8 49,7 170,8 50,2 15 144,2 54,1 148,8 54,3 153,4 54,5 158,0 54,7 167,2 55,1 190,2 56,1 194,8 56,7 18 160,0 59,4 165,1 59,6 170,2 59,8 175,3 60,0 185,5 60,4 211,1 61,5 216,2 62,2 20 184,6 70,7 190,5 70,9 196,4 71,2 202,3 71,5 214,1 72,0 243,6 73,3 249,5 74,0 23 222,7 85,9 229,8 86,2 236,9 86,5 244,0 86,8 258,2 87,4 293,7 89,0 300,8 89,9 27 256,8 92,6 264,9 92,9 273,1 93,2 281,3 93,6 297,7 94,2 338,7 95,9 346,9 96,9 30 282,5 114,6 291,5 115,1 300,5 115,5 309,5 115,9 327,6 116,7 372,7 118,8 381,7 120,1 36 324,3 118,3 334,6 118,7 345,0 119,1 355,3 119,6 376,0 120,4 427,8 122,6 438,1 123,9 41 375,8 142,6 387,8 143,2 399,8 143,7 411,8 144,2 435,8 145,2 495,7 147,8 507,7 149,4 46 435,4 170,8 449,3 171,4 463,2 172,1 477,1 172,7 504,9 173,9 574,4 177,0 588,3 178,9 52 495,0 192,8 510,8 193,5 526,6 194,2 542,4 194,9 573,9 196,3 652,9 199,8 668,7 201,9 60 562,4 214,0 580,3 214,8 598,3 215,6 616,2 216,4 652,1 217,9 741,9 221,8 759,8 224,1 67 663,8 256,3 685,0 257,2 706,2 258,2 727,4 259,1 769,8 261,0 875,7 265,6 896,9 268,4 75 743,3 291,3 767,0 292,3 790,7 293,4 814,4 294,5 861,9 296,6 980,5 301,9 1004,2 305,0 5 47,1 20,0 48,6 20,1 50,1 20,1 51,6 20,2 54,7 20,4 62,2 20,7 63,7 20,9 6 52,3 23,2 54,0 23,3 55,7 23,4 57,3 23,4 60,7 23,6 69,0 24,0 70,7 24,3 7 61,0 25,4 63,0 25,4 64,9 25,5 66,9 25,6 70,8 25,8 80,5 26,3 82,5 26,6 8 66,8 29,1 68,9 29,2 71,1 29,3 73,2 29,5 77,5 29,7 88,1 30,2 90,3 30,5 10 81,7 34,7 84,3 34,9 86,9 35,0 89,5 35,1 94,7 35,4 107,8 36,0 110,4 36,4 11 95,4 39,8 98,4 39,9 101,5 40,1 104,5 40,2 110,6 40,5 125,8 41,2 128,8 41,7 35 12 107,8 45,1 111,2 45,3 114,6 45,4 118,1 45,6 125,0 45,9 142,1 46,7 145,6 47,2 13 120,3 50,5 124,1 50,7 128,0 50,9 131,8 51,1 139,5 51,4 158,7 52,4 162,5 52,9 15 137,2 57,0 141,6 57,2 146,0 57,4 150,4 57,7 159,1 58,1 181,0 59,1 185,4 59,7 18 152,2 62,6 157,1 62,8 162,0 63,0 166,8 63,2 176,5 63,7 200,8 64,8 205,7 65,5 20 175,7 74,5 181,3 74,8 186,9 75,0 192,5 75,3 203,7 75,9 231,8 77,2 237,4 78,0 23 211,9 90,5 218,6 90,9 225,4 91,2 232,1 91,5 245,7 92,2 279,5 93,8 286,2 94,8 27 244,3 97,6 252,1 97,9 259,9 98,3 267,7 98,6 283,3 99,3 322,3 101,1 330,1 102,2 30 268,8 120,8 277,4 121,3 285,9 121,7 294,5 122,2 311,7 123,0 354,6 125,2 363,2 126,5 36 308,5 124,7 318,4 125,1 328,2 125,6 338,1 126,0 357,8 126,9 407,0 129,2 416,8 130,5 41 357,6 150,3 369,0 150,9 380,4 151,4 391,8 152,0 414,6 153,1 471,7 155,8 483,1 157,4 46 414,3 180,0 427,5 180,7 440,7 181,4 454,0 182,0 480,4 183,3 546,5 186,6 559,8 188,5 52 470,9 203,2 486,0 204,0 501,0 204,7 516,0 205,5 546,1 206,9 621,2 210,6 636,3 212,8 60 535,1 225,6 552,2 226,4 569,2 227,2 586,3 228,1 620,5 229,7 705,9 233,8 722,9 236,2 67 631,6 270,1 651,8 271,1 671,9 272,1 692,1 273,1 732,4 275,0 833,2 279,9 853,4 282,9 75 707,2 307,0 729,8 308,1 752,3 309,2 774,9 310,4 820,0 312,6 932,9 318,2 955,5 321,5 = Cooling capacity ; = power input; Hc= heating capacity Correction factors for Silent version: Cooling capacity: 0,95; Power input: 1,055 Correction factors for freecooling version: Cooling capacity:0,97 Power input:1,02 Correction factors for ethylen glicol percentage and for difference temperature of water at inlet-outlet, see at end of chapter cooling main value; heating main value 36

SA-N Outlet water temperature ( C) 5 6 7 8 10 15 5 44,7 22,0 46,2 22,2 47,6 22,4 49,0 22,5 51,9 22,9 59,0 23,8 6 49,7 25,5 51,2 25,7 52,8 25,9 54,4 26,1 57,6 26,5 65,5 27,6 7 57,9 27,9 59,8 28,1 61,6 28,4 63,5 28,6 67,2 29,0 76,4 30,1 8 63,4 32,1 65,4 32,3 67,4 32,6 69,5 32,8 73,5 33,3 83,6 34,6 10 77,5 38,3 80,0 38,6 82,5 38,9 85,0 39,2 89,9 39,8 102,3 41,3 11 90,5 43,8 93,4 44,2 96,3 44,5 99,2 44,8 104,9 45,5 119,4 47,3 38 12 102,3 49,7 105,5 50,0 108,8 50,4 112,1 50,8 118,6 51,6 134,9 53,6 13 114,2 55,7 117,8 56,1 121,5 56,5 125,1 57,0 132,4 57,8 150,6 60,0 15 130,2 62,8 134,4 63,3 138,5 63,8 142,7 64,3 151,0 65,3 171,8 67,8 18 144,5 68,9 149,1 69,4 153,7 70,0 158,3 70,5 167,5 71,6 190,6 74,3 20 166,7 82,1 172,0 82,7 177,4 83,3 182,7 84,0 193,3 85,3 219,9 88,5 23 201,1 99,7 207,5 100,5 213,9 101,3 220,3 102,0 233,1 103,6 265,2 107,6 27 231,8 107,5 239,2 108,3 246,6 109,1 254,0 110,0 268,8 111,7 305,8 115,9 30 255,1 133,1 263,2 134,1 271,4 135,2 279,5 136,2 295,8 138,3 336,5 143,6 36 292,8 137,3 302,1 138,4 311,5 139,4 320,8 140,5 339,5 142,7 386,2 148,1 41 339,3 165,6 350,2 166,9 361,0 168,2 371,8 169,5 393,5 172,1 447,6 178,6 46 393,2 198,3 405,7 199,9 418,3 201,4 430,8 202,9 455,9 206,1 518,7 213,9 52 446,9 223,9 461,2 225,6 475,5 227,3 489,7 229,1 518,2 232,6 589,6 241,5 60 507,8 248,5 524,0 250,4 540,2 252,3 556,4 254,3 588,8 258,2 669,9 268,1 67 599,4 297,5 618,5 299,9 637,7 302,2 656,8 304,5 695,1 309,2 790,7 321,0 75 671,1 338,2 692,5 340,8 714,0 343,4 735,4 346,1 778,2 351,4 885,3 364,8 5 43,1 23,5 44,5 23,7 45,9 23,9 47,3 24,1 50,0 24,5 6 47,9 27,3 49,4 27,5 50,9 27,7 52,5 27,9 55,5 28,4 7 55,8 29,8 57,6 30,1 59,4 30,3 61,2 30,5 64,7 31,0 8 61,1 34,3 63,1 34,6 65,0 34,8 67,0 35,1 70,9 35,6 10 74,8 40,9 77,1 41,2 79,5 41,5 81,9 41,8 86,7 42,5 11 87,3 46,8 90,0 47,2 92,8 47,6 95,6 47,9 101,2 48,7 40 12 98,6 53,1 101,7 53,5 104,9 53,9 108,0 54,3 114,3 55,1 13 110,1 59,5 113,6 59,9 117,1 60,4 120,6 60,9 127,6 61,8 15 125,6 67,1 129,6 67,7 133,6 68,2 137,6 68,7 145,6 69,8 18 139,3 73,6 143,8 74,2 148,2 74,8 152,6 75,4 161,5 76,5 20 160,8 87,7 165,9 88,4 171,0 89,1 176,1 89,8 186,4 91,1 23 193,9 106,6 200,0 107,4 206,2 108,2 212,4 109,0 224,8 110,7 27 223,5 114,8 230,7 115,7 237,8 116,6 244,9 117,5 259,2 119,3 30 245,9 142,2 253,8 143,3 261,6 144,5 269,5 145,6 285,2 147,8 36 282,3 146,7 291,3 147,9 300,3 149,0 309,3 150,2 327,4 152,5 41 327,2 177,0 337,6 178,4 348,1 179,7 358,5 181,1 379,4 183,9 46 379,1 211,9 391,2 213,6 403,3 215,2 415,4 216,9 439,6 220,2 52 430,9 239,2 444,7 241,1 458,4 243,0 472,2 244,8 499,7 248,6 60 489,6 265,6 505,2 267,6 520,9 269,7 536,5 271,8 567,7 275,9 67 577,9 318,0 596,4 320,5 614,8 322,9 633,3 325,4 670,2 330,4 75 647,1 361,4 667,7 364,2 688,4 367,0 709,0 369,8 750,3 375,5 = Cooling capacity ; = power input; Hc= heating capacity Correction factors for Silent version: Cooling capacity: 0,95; Power input: 1,055 Correction factors for freecooling version: Cooling capacity:0,97 Power input:1,02 Correction factors for ethylen glicol percentage and for difference temperature of water at inlet-outlet, see at end of chapter cooling main value; heating main value 37

SA-E Outlet water temperature ( C) 5 6 7 8 10 15 20 5 48,1 15,2 49,7 15,3 51,2 15,4 52,7 15,4 55,8 15,5 63,5 15,8 63,1 16,0 6 54,8 17,4 56,6 17,5 58,3 17,6 60,1 17,6 63,6 17,8 72,3 18,1 71,9 18,3 7 62,0 19,8 64,0 19,9 65,9 20,0 67,9 20,1 71,9 20,2 81,8 20,6 81,2 20,8 8 70,0 22,9 72,2 22,9 74,5 23,0 76,7 23,1 81,2 23,3 92,3 23,7 91,8 23,9 10 81,0 25,5 83,6 25,6 86,1 25,7 88,7 25,8 93,9 26,0 106,8 26,5 106,1 26,7 11 94,4 30,3 97,4 30,4 100,4 30,5 103,4 30,6 109,4 30,9 124,5 31,4 123,7 31,7 32 35 12 110,6 34,1 114,2 34,3 117,7 34,4 121,2 34,5 128,3 34,8 146,0 35,4 145,0 35,8 13 123,3 39,9 127,3 40,1 131,2 40,2 135,1 40,3 143,0 40,6 162,7 41,4 161,7 41,8 15 142,3 44,7 146,9 44,8 151,4 45,0 155,9 45,2 165,0 45,5 187,7 46,3 186,5 46,8 18 158,8 50,6 163,9 50,8 169,0 51,0 174,0 51,2 184,2 51,6 209,5 52,5 208,2 53,0 20 178,8 57,1 184,5 57,3 190,2 57,5 195,9 57,8 207,3 58,2 235,9 59,2 234,4 59,8 23 208,5 62,3 215,2 62,5 221,9 62,8 228,5 63,0 241,8 63,4 275,1 64,6 273,4 65,2 27 245,4 79,7 253,2 80,0 261,1 80,3 268,9 80,6 284,6 81,2 323,7 82,6 321,7 83,5 30 281,5 89,3 290,5 89,7 299,5 90,0 308,5 90,3 326,5 91,0 371,4 92,6 369,0 93,5 36 314,1 106,8 324,1 107,2 334,1 107,6 344,1 108,0 364,2 108,8 414,3 110,7 411,7 111,8 41 369,5 119,9 381,3 120,4 393,1 120,8 404,9 121,3 428,5 122,1 487,4 124,3 484,4 125,6 46 409,6 134,4 422,6 134,9 435,7 135,4 448,8 135,9 474,9 136,8 540,3 139,3 536,9 140,7 52 474,9 158,7 490,0 159,3 505,2 159,9 520,3 160,5 550,6 161,6 626,4 164,5 622,5 166,2 60 566,1 187,2 584,2 187,9 602,3 188,6 620,3 189,3 656,5 190,7 746,8 194,0 742,1 196,1 67 606,1 202,3 625,4 203,1 644,7 203,8 664,1 204,5 702,8 206,0 799,5 209,7 794,5 211,9 5 45,8 16,1 47,2 16,1 48,7 16,2 50,2 16,2 53,1 16,4 60,4 16,7 60,0 16,8 6 52,2 18,4 53,8 18,4 55,5 18,5 57,2 18,6 60,5 18,7 68,8 19,0 68,4 19,2 7 59,0 20,9 60,9 21,0 62,7 21,1 64,6 21,1 68,4 21,3 77,8 21,7 77,3 21,9 8 66,6 24,1 68,7 24,2 70,9 24,3 73,0 24,4 77,2 24,5 87,9 25,0 87,3 25,2 10 77,0 26,9 79,5 27,0 82,0 27,1 84,4 27,2 89,3 27,4 101,6 27,9 101,0 28,2 11 89,8 31,9 92,7 32,1 95,5 32,2 98,4 32,3 104,1 32,5 118,5 33,1 117,7 33,4 12 105,3 36,0 108,6 36,1 112,0 36,2 115,4 36,4 122,1 36,6 138,9 37,3 138,0 37,7 13 117,4 42,1 121,1 42,2 124,8 42,4 128,6 42,5 136,1 42,8 154,8 43,6 153,8 44,0 15 135,4 47,1 139,7 47,3 144,0 47,4 148,4 47,6 157,0 47,9 178,6 48,8 177,5 49,3 18 151,1 53,4 155,9 53,6 160,8 53,8 165,6 54,0 175,2 54,3 199,3 55,3 198,1 55,9 20 170,1 60,2 175,6 60,4 181,0 60,6 186,4 60,9 197,3 61,3 224,4 62,4 223,0 63,0 23 198,4 65,7 204,8 65,9 211,1 66,2 217,4 66,4 230,1 66,9 261,8 68,1 260,1 68,8 27 233,5 84,0 241,0 84,3 248,4 84,6 255,9 84,9 270,8 85,6 308,0 87,1 306,1 88,0 30 267,9 94,1 276,4 94,5 285,0 94,8 293,5 95,2 310,6 95,9 353,4 97,6 351,1 98,6 36 298,8 112,6 308,4 113,0 317,9 113,4 327,4 113,8 346,5 114,6 394,2 116,7 391,7 117,9 41 351,6 126,4 362,8 126,9 374,0 127,3 385,2 127,8 407,7 128,7 463,8 131,0 460,8 132,4 46 389,7 141,7 402,1 142,2 414,6 142,7 427,0 143,2 451,9 144,2 514,1 146,8 510,8 148,3 52 451,8 167,3 466,2 167,9 480,6 168,5 495,1 169,1 523,9 170,4 596,0 173,4 592,3 175,2 60 538,7 197,3 555,8 198,1 573,0 198,8 590,2 199,5 624,6 200,9 710,6 204,5 706,1 206,7 67 576,7 213,2 595,1 214,0 613,5 214,8 631,9 215,6 668,7 217,1 760,7 221,0 755,9 223,3 = Cooling capacity ; = power input; Hc= heating capacity Correction factors for Silent version: Cooling capacity: 0,95; Power input: 1,055 Correction factors for freecooling version: Cooling capacity:0,97 Power input:1,02 Correction factors for ethylen glicol percentage and for difference temperature of water at inlet-outlet, see at end of chapter cooling main value; heating main value 38

SA-E Outlet water temperature ( C) 5 6 7 8 10 15 20 5 41,9 18,9 43,2 19,1 44,6 19,2 45,9 19,4 48,6 19,7 55,3 20,4 54,9 20,9 6 47,7 21,6 49,3 21,8 50,8 22,0 52,3 22,1 55,3 22,5 63,0 23,3 62,6 23,9 7 54,0 24,6 55,7 24,8 57,4 25,0 59,1 25,2 62,6 25,6 71,2 26,6 70,7 27,1 8 60,9 28,4 62,9 28,6 64,8 28,8 66,8 29,0 70,7 29,5 80,4 30,6 79,9 31,3 10 70,5 31,7 72,7 31,9 75,0 32,2 77,2 32,4 81,7 32,9 93,0 34,2 92,4 34,9 11 82,2 37,6 84,8 37,9 87,4 38,2 90,0 38,5 95,3 39,1 108,4 40,6 107,7 41,5 40 45 12 96,3 42,4 99,4 42,7 102,5 43,0 105,6 43,4 111,7 44,0 127,1 45,7 126,3 46,7 13 107,4 49,5 110,8 49,9 114,2 50,3 117,7 50,7 124,5 51,5 141,6 53,4 140,8 54,6 15 123,9 55,4 127,8 55,9 131,8 56,3 135,8 56,7 143,7 57,6 163,4 59,8 162,4 61,1 18 138,3 62,8 142,7 63,3 147,1 63,8 151,5 64,3 160,3 65,3 182,4 67,8 181,2 69,3 20 155,7 70,9 160,6 71,4 165,6 72,0 170,6 72,5 180,5 73,6 205,3 76,5 204,1 78,2 23 181,6 77,3 187,4 77,9 193,1 78,5 198,9 79,1 210,5 80,3 239,5 83,4 238,0 85,3 27 213,7 98,9 220,5 99,7 227,3 100,5 234,1 101,2 247,8 102,8 281,8 106,7 280,1 109,1 30 245,1 110,8 252,9 111,7 260,7 112,5 268,6 113,4 284,2 115,2 323,3 119,6 321,3 122,2 36 273,4 132,5 282,1 133,5 290,9 134,6 299,6 135,6 317,0 137,7 360,7 143,0 358,4 146,2 41 321,7 148,8 331,9 150,0 342,2 151,1 352,5 152,3 373,0 154,6 424,3 160,5 421,7 164,1 46 356,6 166,7 367,9 168,0 379,3 169,3 390,7 170,6 413,5 173,3 470,4 179,9 467,4 183,9 52 413,4 196,9 426,6 198,5 439,8 200,0 453,0 201,6 479,4 204,6 545,3 212,5 541,9 217,2 60 492,9 232,3 508,6 234,1 524,3 235,9 540,1 237,7 571,5 241,4 650,2 250,6 646,1 256,2 67 527,6 251,0 544,5 253,0 561,3 254,9 578,2 256,9 611,8 260,8 696,0 270,8 691,7 276,9 5 38,0 22,1 39,2 22,3 40,4 22,4 41,6 22,6 44,1 23,0 6 43,3 25,3 44,7 25,5 46,1 25,7 47,4 25,9 50,2 26,3 7 48,9 28,8 50,5 29,0 52,1 29,2 53,6 29,4 56,8 29,9 8 55,3 33,1 57,0 33,4 58,8 33,7 60,6 33,9 64,1 34,4 10 63,9 37,0 66,0 37,3 68,0 37,6 70,1 37,9 74,1 38,4 11 74,5 43,9 76,9 44,3 79,3 44,6 81,7 45,0 86,4 45,6 12 87,4 49,5 90,2 49,9 93,0 50,3 95,7 50,6 101,3 51,4 13 97,4 57,9 100,5 58,3 103,6 58,8 106,7 59,2 112,9 60,1 15 112,4 64,8 116,0 65,3 119,6 65,8 123,1 66,3 130,3 67,3 18 125,4 73,4 129,4 74,0 133,4 74,5 137,4 75,1 145,4 76,3 20 141,2 82,8 145,7 83,4 150,2 84,1 154,7 84,7 163,7 86,0 23 164,7 90,3 169,9 91,0 175,2 91,7 180,5 92,4 191,0 93,9 27 193,8 115,6 200,0 116,5 206,2 117,4 212,4 118,3 224,7 120,1 30 222,3 129,5 229,4 130,5 236,5 131,5 243,6 132,5 257,8 134,5 36 248,0 154,8 255,9 156,0 263,8 157,2 271,8 158,4 287,6 160,9 41 291,8 173,9 301,1 175,2 310,4 176,6 319,7 177,9 338,4 180,7 46 323,4 194,8 333,8 196,3 344,1 197,8 354,4 199,4 375,1 202,4 52 375,0 230,1 387,0 231,9 398,9 233,7 410,9 235,5 434,8 239,1 60 447,1 271,4 461,4 273,5 475,6 275,6 489,9 277,8 518,4 282,0 67 478,6 293,3 493,9 295,6 509,2 297,8 524,4 300,1 555,0 304,7 = Cooling capacity ; = power input; Hc= heating capacity Correction factors for Silent version: Cooling capacity: 0,95; Power input: 1,055 Correction factors for freecooling version: Cooling capacity:0,97 Power input:1,02 Correction factors for ethylen glicol percentage and for difference temperature of water at inlet-outlet, see at end of chapter cooling main value; heating main value 39

SA-TOP Outlet water temperature ( C) 5 6 7 8 10 15 20 5 49,5 15,1 51,1 14,2 52,7 15,2 54,3 15,2 57,4 15,3 65,3 15,6 66,9 15,8 6 59,8 18,0 61,7 18,1 63,6 18,2 65,5 18,2 69,4 18,4 78,9 18,7 80,8 18,9 7 67,4 20,5 69,6 20,6 71,7 20,6 73,9 20,7 78,2 20,9 89,0 21,2 91,1 21,4 8 77,6 22,9 80,0 23,0 82,5 23,1 85,0 23,2 89,9 23,4 102,3 23,8 104,8 24,0 10 87,1 25,8 89,9 25,9 92,7 26,0 95,5 26,1 101,0 26,3 114,9 26,8 117,7 27,1 32 35 11 102,6 29,9 105,9 30,0 109,2 30,1 112,4 30,2 119,0 30,4 135,4 31,0 138,6 31,3 12 116,2 35,1 119,9 35,2 123,6 35,4 127,3 33,6 134,7 34,1 153,3 35,4 157,0 36,8 13 134,1 40,9 138,4 41,1 142,6 41,2 146,9 39,2 155,5 39,8 176,9 41,3 181,2 42,2 15 151,4 45,6 156,3 45,7 161,1 45,9 165,9 43,6 175,6 44,3 199,8 45,9 204,6 47,0 18 168,8 51,8 174,2 52,0 179,6 52,2 185,0 49,6 195,7 50,3 222,7 52,3 228,1 53,4 20 196,5 57,7 202,8 57,9 209,0 58,1 215,3 55,2 227,9 56,1 259,2 58,2 265,5 59,5 23 232,7 69,9 240,1 70,2 247,5 70,4 254,9 66,9 269,8 67,9 306,9 70,5 314,3 72,1 27 271,8 80,5 280,5 80,8 289,2 81,0 297,8 77,0 315,2 78,2 358,6 81,2 367,2 83,0 30 299,8 91,5 309,4 91,8 319,0 92,2 328,5 87,5 347,7 88,9 395,5 92,3 405,1 94,3 36 353,6 105,7 364,8 106,0 376,1 100,3 387,4 101,1 410,0 102,6 466,4 106,6 477,7 108,9 41 400,1 121,5 412,8 121,9 425,6 115,3 438,4 116,2 463,9 118,0 527,8 122,5 540,5 125,3 46 447,2 137,3 461,5 137,8 475,7 130,3 490,0 131,3 518,6 133,3 589,9 138,4 604,2 141,5 52 519,6 159,5 536,2 160,1 552,8 151,5 569,4 152,6 602,5 155,0 685,5 160,9 702,0 164,5 5 47,1 15,9 48,6 15,9 50,1 16,0 51,6 16,1 54,6 16,2 62,1 16,5 63,6 16,6 6 56,9 19,0 58,7 19,1 60,6 19,2 62,4 19,2 66,0 19,4 75,1 19,7 76,9 19,9 7 64,2 21,6 66,2 21,7 68,3 21,7 70,3 21,8 74,4 22,0 84,6 22,4 86,7 22,6 8 73,8 24,2 76,1 24,3 78,5 24,3 80,9 24,4 85,6 24,6 97,3 25,1 99,7 25,3 10 82,9 27,2 85,6 27,3 88,2 27,4 90,8 27,5 96,1 27,7 109,4 28,2 112,0 28,5 11 97,6 31,5 100,8 31,6 103,9 31,7 107,0 31,8 113,2 32,1 128,8 32,6 131,9 33,0 12 110,6 37,0 114,1 37,1 117,6 37,3 121,1 37,6 128,2 38,1 145,8 39,6 149,4 40,5 13 127,6 43,1 131,7 43,3 135,7 43,5 139,8 43,8 147,9 44,5 168,3 46,2 172,4 47,2 15 144,1 48,0 148,7 48,2 153,3 48,4 157,9 48,7 167,1 49,5 190,1 51,4 194,7 52,5 18 160,6 54,6 165,7 54,8 170,9 55,0 176,0 55,4 186,2 56,3 211,9 58,4 217,0 59,7 20 187,0 60,8 192,9 61,1 198,9 61,3 204,9 61,8 216,8 62,7 246,6 65,1 252,6 66,5 23 221,4 73,7 228,4 73,9 235,5 74,2 242,6 74,8 256,7 75,9 292,0 78,8 299,1 80,6 27 258,6 84,8 266,9 85,1 275,1 85,4 283,4 86,1 299,9 87,4 341,2 90,7 349,4 92,8 30 285,3 96,4 294,4 96,8 303,5 97,1 312,6 97,9 330,8 99,4 376,3 103,2 385,4 105,5 36 336,4 111,4 347,1 111,8 357,9 112,2 368,6 113,0 390,1 114,8 443,8 119,2 454,5 121,8 41 380,7 128,0 392,8 128,5 405,0 129,0 417,1 130,0 441,4 132,0 502,2 137,0 514,3 140,1 46 425,5 144,7 439,1 145,2 452,7 145,7 466,2 146,8 493,4 149,1 561,3 154,8 574,9 158,3 52 494,4 168,1 510,2 168,7 526,0 169,4 541,7 170,7 573,3 173,3 652,2 179,9 668,0 183,9 = Cooling capacity ; = power input; Hc= heating capacity Correction factors for Silent version: Cooling capacity: 0,95; Power input: 1,055 Correction factors for freecooling version: Cooling capacity:0,97 Power input:1,02 Correction factors for ethylen glicol percentage and for difference temperature of water at inlet-outlet, see at end of chapter cooling main value; heating main value 40

SA-TOP Outlet water temperature ( C) 5 6 7 8 10 15 20 5 44,7 17,5 46,1 17,6 47,6 16,8 49,0 16,9 51,8 17,0 59,0 17,3 6 54,0 21,0 55,7 20,1 57,5 20,1 59,2 20,2 62,6 20,3 71,3 20,7 7 60,9 23,8 62,8 22,8 64,8 22,8 66,7 22,9 70,6 23,1 80,3 23,5 8 70,0 26,6 72,3 25,5 74,5 25,6 76,7 25,7 81,2 25,9 92,4 26,3 10 78,7 30,0 81,2 28,7 83,7 28,8 86,2 28,9 91,2 29,1 103,8 29,7 40 45 11 92,7 34,7 95,6 33,2 98,6 33,3 101,5 33,4 107,4 33,7 122,2 34,3 12 104,9 40,8 108,3 39,0 111,6 39,2 115,0 41,7 121,7 42,3 138,4 44,0 13 121,1 47,5 124,9 45,5 128,8 45,7 132,7 48,6 140,4 49,4 159,7 51,3 15 136,7 52,9 141,1 50,6 145,5 50,8 149,8 54,1 158,6 55,0 180,4 57,1 18 152,4 60,2 157,3 57,6 162,1 57,8 167,0 61,6 176,7 62,5 201,1 64,9 20 177,4 67,0 183,1 64,1 188,8 64,4 194,4 68,6 205,7 69,6 234,1 72,3 23 210,1 81,1 216,8 77,7 223,5 78,0 230,2 83,0 243,6 84,3 277,1 87,5 27 245,4 93,4 253,3 89,4 261,1 89,7 268,9 95,6 284,6 97,1 323,8 100,8 30 270,7 106,2 279,4 101,7 288,0 102,0 296,6 108,7 313,9 110,4 357,1 114,6 36 319,3 122,7 329,4 117,4 339,6 124,6 349,8 125,5 370,2 127,5 421,1 132,3 41 361,3 141,0 372,8 135,0 384,3 143,2 395,8 144,3 418,9 146,5 476,5 152,1 46 403,8 159,3 416,7 152,5 429,6 161,8 442,5 163,1 468,2 165,6 532,7 171,9 52 469,2 185,2 484,2 177,3 499,1 188,1 514,1 189,5 544,1 192,4 618,9 199,8 5 43,1 18,7 44,5 18,8 45,9 17,3 47,2 17,4 50,0 17,5 6 52,1 22,4 53,7 20,7 55,4 20,8 57,1 20,8 60,4 21,0 7 58,7 25,4 60,6 23,5 62,5 23,6 64,3 23,7 68,1 23,8 8 67,5 28,5 69,7 26,3 71,8 26,4 74,0 26,5 78,3 26,7 10 75,9 32,1 78,3 29,6 80,7 29,7 83,1 29,8 88,0 30,1 11 89,3 37,1 92,2 34,2 95,0 34,4 97,9 37,9 103,6 34,7 12 101,2 43,6 104,4 40,2 107,6 40,4 110,8 44,6 117,3 45,3 13 116,7 50,8 120,5 46,9 124,2 47,1 127,9 52,0 135,4 52,8 15 131,8 56,5 136,1 52,2 140,3 52,4 144,5 57,8 152,9 58,7 18 147,0 64,3 151,6 59,4 156,3 59,6 161,0 65,8 170,4 66,8 20 171,1 71,6 176,5 66,2 182,0 66,4 187,4 73,3 198,4 74,4 23 202,6 86,7 209,0 80,1 215,5 80,4 222,0 88,8 234,9 90,1 27 236,6 99,8 244,2 92,3 251,7 92,6 259,3 102,2 274,4 103,7 30 261,0 113,5 269,4 104,9 277,7 105,3 286,0 116,2 302,7 118,0 36 307,8 131,1 317,6 121,2 327,5 133,1 337,3 134,2 356,9 136,2 41 348,3 150,7 359,4 139,3 370,5 153,1 381,7 154,3 403,9 156,6 46 389,3 170,3 401,8 157,4 414,2 172,9 426,6 174,3 451,5 177,0 52 452,4 197,9 466,8 182,9 481,3 201,0 495,7 202,5 524,6 205,7 = Cooling capacity ; = power input; Hc= heating capacity Correction factors for Silent version: Cooling capacity: 0,95; Power input: 1,055 Correction factors for freecooling version: Cooling capacity:0,97 Power input:1,02 Correction factors for ethylen glicol percentage and for difference temperature of water at inlet-outlet, see at end of chapter cooling main value; heating main value 41

SA-H-N Outlet water temperature ( C) Outlet water temperature ( C) 5 7 10 40 45 50 Hc Hc Hc 32 35 5 48,7 19,0 51,9 19,1 56,5 19,3 33,2 15,5 6 54,1 22,0 57,6 22,2 62,8 22,4 36,9 18,0 7 63,1 24,1 67,1 24,2 73,2 24,5 43,0 19,7 8 69,1 27,6 73,5 27,8 80,1 28,1 47,1 22,6 10 84,5 33,0 89,9 33,2 98,0 33,6 57,6 27,0 11 98,6 37,7 104,9 38,0 114,4 38,4 67,3 30,9 12 111,4 42,8 118,6 43,1 129,2 43,6 76,0 35,0 13 124,4 47,9 132,4 48,3 144,3 48,8 84,8 39,2 15 141,9 54,1 151,0 54,5 164,6 55,1 96,8 44,3 18 157,5 59,4 167,5 59,8 182,6 60,4-8 107,4 48,6 20 181,7 70,7 193,3 71,2 210,7 72,0 123,9 57,8 23 219,1 85,9 233,1 86,5 254,1 87,4 149,4 70,3 27 252,6 92,6 268,8 93,2 293,0 94,2 172,3 75,7 30 278,0 114,6 295,7 115,5 322,3 116,7 189,6 93,8 36 319,1 118,3 339,4 119,1 370,0 120,4 218,9 99,7 41 369,8 142,6 393,4 143,7 428,8 145,2 251,3 117,3 46 428,5 170,8 455,8 172,1 496,8 173,9 292,2 139,8 52 483,8 192,8 514,7 194,2 561,0 196,3 329,9 159,0 60 556,0 214,0 591,4 215,6 644,7 217,9 379,1 187,5 5 46,4 20,0 49,3 20,1 53,8 20,4 35,0 15,5 34,4 18,2 6 51,5 23,2 54,8 23,4 59,7 23,6 38,9 18,0 38,1 21,1 7 60,0 25,4 63,9 25,5 69,6 25,8 45,3 19,7 44,5 23,0 8 65,7 29,1 69,9 29,3 76,2 29,7 49,6 22,6 48,7 26,5 10 80,4 34,7 85,5 35,0 93,2 35,4 60,7 27,0 59,5 31,5 11 93,8 39,8 99,8 40,1 108,8 40,5 70,9 30,9 69,5 36,1 12 106,0 45,1 112,8 45,4 123,0 45,9 80,1 35,0 78,5 40,9 13 118,4 50,5 125,9 50,9 137,3 51,4 89,4 39,2 87,7 45,9 15 135,0 57,0 143,6 57,4 156,6 58,1 102,0 44,3 100,0 51,8 18 149,8 62,6 159,4 63,0 173,7 63,7-5 113,1 48,6 111,0 56,8 20 172,9 74,5 183,9 75,0 200,5 75,9 130,5 57,8 128,1 67,7 23 208,5 90,5 221,8 91,2 241,7 92,2 157,4 70,3 154,4 82,2 27 240,4 97,6 255,7 98,3 278,7 99,3 181,5 75,7 178,1 88,6 30 264,5 120,8 281,4 121,7 306,7 123,0 199,7 93,8 195,9 109,7 36 303,6 124,7 323,0 125,6 352,0 126,9 230,7 99,7 226,3 116,6 41 351,8 150,3 374,3 151,4 408,0 153,1 264,8 117,3 259,7 137,1 46 407,7 180,0 433,7 181,4 472,7 183,3 307,8 139,8 302,0 163,5 52 460,3 203,2 489,7 204,7 533,8 206,9 347,6 159,0 341,0 186,0 60 529,0 225,6 562,7 227,2 613,4 229,7 399,5 187,5 391,8 219,3 = Cooling capacity ; = power input; Hc= heating capacity Correction factors for Silent version: Cooling capacity: 0,95; Power input: 1,055 Correction factors for freecooling version: Cooling capacity:0,97 Power input:1,02 Correction factors for ethylen glicol percentage and for difference temperature of water at inlet-outlet, see at end of chapter cooling main value; heating main value 42

SA-H-N Outlet water temperature ( C) Outlet water temperature ( C) 5 7 10 40 45 50 Hc Hc Hc 38 40 5 44,7 22,0 47,6 22,4 51,9 22,9 38,0 15,5 37,3 18,2 36,5 20,8 6 49,7 25,5 52,8 25,9 57,6 26,5 42,2 18,0 41,4 21,1 40,6 24,1 7 57,9 27,9 61,6 28,4 67,2 29,0 49,2 19,7 48,3 23,0 47,3 26,4 8 63,4 32,1 67,4 32,6 73,5 33,3 53,9 22,6 52,8 26,5 51,8 30,3 10 77,5 38,3 82,5 38,9 89,9 39,8 65,9 27,0 64,6 31,5 63,3 36,1 11 90,5 43,8 96,3 44,5 104,9 45,5 76,9 30,9 75,4 36,1 73,9 41,4 12 102,3 49,7 108,8 50,4 118,6 51,6 86,9 35,0 85,2 40,9 83,6 46,9 13 114,2 55,7 121,5 56,5 132,4 57,8 97,0 39,2 95,1 45,9 93,3 52,5 15 130,2 62,8 138,5 63,8 151,0 65,3 110,6 44,3 108,5 51,8 106,4 59,3 18 144,5 68,9 153,7 70,0 167,5 71,6 0 122,7 48,6 120,4 56,8 118,0 65,0 20 166,7 82,1 177,4 83,3 193,3 85,3 141,6 57,8 138,9 67,7 136,2 77,5 23 201,1 99,7 213,9 101,3 233,1 103,6 170,8 70,3 167,5 82,2 164,3 94,1 27 231,8 107,5 246,6 109,1 268,8 111,7 196,9 75,7 193,2 88,6 189,4 101,4 30 255,1 133,1 271,4 135,2 295,8 138,3 216,7 93,8 212,5 109,7 208,4 125,6 36 292,8 137,3 311,5 139,4 339,5 142,7 250,2 99,7 245,4 116,6 240,7 133,5 41 339,3 165,6 361,0 168,2 393,5 172,1 287,2 117,3 281,8 137,1 276,3 157,0 46 393,2 198,3 418,3 201,4 455,9 206,1 334,0 139,8 327,6 163,5 321,2 187,2 52 446,9 223,9 475,5 227,3 518,2 232,6 377,1 159,0 369,9 186,0 362,7 212,9 60 507,8 248,5 540,2 252,3 588,8 258,2 433,3 187,5 425,1 219,3 416,8 251,1 5 43,1 23,5 45,9 23,9 50,0 24,5 56,8 16,5 55,7 19,3 54,7 22,1 6 47,9 27,3 50,9 27,7 55,5 28,4 63,1 19,2 61,9 22,4 60,7 25,7 7 55,8 29,8 59,4 30,3 64,7 31,0 73,6 21,0 72,2 24,5 70,8 28,1 8 61,1 34,3 65,0 34,8 70,9 35,6 80,6 24,1 79,0 28,2 77,5 32,3 10 74,8 40,9 79,5 41,5 86,7 42,5 98,5 28,7 96,6 33,6 94,8 38,5 11 87,3 46,8 92,8 47,6 101,2 48,7 115,0 32,9 112,8 38,5 110,6 44,0 12 98,6 53,1 104,9 53,9 114,3 55,1 129,9 37,3 127,5 43,6 125,0 49,9 13 110,1 59,5 117,1 60,4 127,6 61,8 145,1 41,8 142,3 48,9 139,5 55,9 15 125,6 67,1 133,6 68,2 145,6 69,8 165,5 47,2 162,3 55,1 159,2 63,1 18 139,3 73,6 148,2 74,8 161,5 76,5 7 183,6 51,7 180,1 60,5 176,6 69,3 20 160,8 87,7 171,0 89,1 186,4 91,1 211,9 61,6 207,8 72,0 203,8 82,5 23 193,9 106,6 206,2 108,2 224,8 110,7 255,5 74,8 250,6 87,5 245,8 100,2 27 223,5 114,8 237,8 116,6 259,2 119,3 294,6 80,7 289,0 94,3 283,4 108,0 30 245,9 142,2 261,6 144,5 285,2 147,8 324,1 99,9 318,0 116,8 311,8 133,8 36 282,3 146,7 300,3 149,0 327,4 152,5 374,3 106,2 367,2 124,2 360,1 142,2 41 327,2 177,0 348,1 179,7 379,4 183,9 429,7 124,9 421,5 146,1 413,3 167,2 46 379,1 211,9 403,3 215,2 439,6 220,2 499,6 148,9 490,1 174,1 480,6 199,3 52 430,9 239,2 458,4 243,0 499,7 248,6 564,1 169,3 553,3 198,1 542,6 226,8 60 489,6 265,6 520,9 269,7 567,7 275,9 648,2 199,7 635,9 233,5 623,6 267,4 = Cooling capacity ; = power input; Hc= heating capacity Correction factors for Silent version: Cooling capacity: 0,95; Power input: 1,055 Correction factors for freecooling version: Cooling capacity:0,97 Power input:1,02 Correction factors for ethylen glicol percentage and for difference temperature of water at inlet-outlet, see at end of chapter cooling main value; heating main value 43

SA-H-E Outlet water temperature ( C) Outlet water temperature ( C) 5 7 10 40 45 50 Hc Hc Hc 32 35 5 47,3 15,3 50,4 14,5 54,9 15,5 31,1 12,6 6 53,9 17,4 57,4 17,5 62,6 17,7 35,5 14,4 7 61,0 19,9 64,9 20,1 70,7 20,3 40,1 16,5 8 68,9 22,9 73,3 23,0 79,9 23,3 45,3 18,9 10 79,7 25,5 84,8 25,7 92,4 26,0 52,4 21,1 11 92,9 30,3 98,8 30,5 107,7 30,9 61,1 25,1 12 108,9 34,1 115,8 34,4 126,3 34,8 71,6 28,2 13 121,4 39,9 129,1 40,2 140,7 40,6 79,8 33,0 15 140,0 44,7 149,0 45,0 162,4 45,5 92,1 36,9-10 18 156,3 50,7 166,3 51,1 181,2 51,6 102,8 41,9 20 175,9 57,1 187,2 57,5 204,0 58,2 115,7 47,2 23 205,2 62,3 218,3 62,8 238,0 63,4 134,9 51,5 27 241,5 80,0 256,9 80,6 280,0 81,4 158,8 66,1 30 277,0 89,3 294,7 90,0 321,2 91,0 182,2 73,9 36 309,0 106,8 328,8 107,6 358,3 103,8 203,2 88,3 41 355,1 121,1 377,7 122,0 411,7 117,7 233,5 100,1 46 401,7 135,1 427,3 136,1 465,8 131,3 264,1 111,7 52 463,5 158,7 493,1 159,9 537,5 154,2 304,8 131,2 5 45,0 16,1 47,9 16,2 52,2 16,4 34,0 12,6 33,4 14,7 6 51,3 18,3 54,6 18,5 59,5 18,7 38,8 14,4 38,0 16,8 7 58,0 21,0 61,7 21,1 67,3 21,4 43,8 16,5 43,0 19,3 8 65,5 24,1 69,7 24,3 76,0 24,5 49,5 18,9 48,6 22,1 10 75,8 26,9 80,6 27,1 87,9 27,4 57,2 21,1 56,2 24,7 11 88,4 31,9 94,0 32,2 102,5 32,5 66,7 25,1 65,5 29,3 12 103,6 36,0 110,2 36,2 120,1 36,6 78,2 28,2 76,7 33,0 13 115,5 42,1 122,8 42,4 133,9 42,8 87,2 33,0 85,5 38,6 15 133,2 47,1 141,7 47,4 154,5 47,9 100,6 36,9 98,7 43,2-5 18 148,7 53,5 158,2 53,8 172,4 54,4 112,3 41,9 110,1 49,0 20 167,4 60,2 178,1 60,6 194,1 61,3 126,4 47,2 124,0 55,2 23 195,2 65,7 207,7 66,2 226,4 66,9 147,4 51,5 144,6 60,3 27 229,8 84,3 244,4 84,9 266,4 85,8 173,5 66,1 170,2 77,4 30 263,6 94,1 280,4 94,8 305,6 95,9 199,0 73,9 195,3 86,4 36 294,0 112,6 312,8 113,4 341,0 116,0 222,0 88,3 217,8 103,3 41 337,8 127,7 359,4 128,6 391,7 131,6 255,1 100,1 250,3 117,1 46 382,2 142,4 406,6 143,4 443,2 146,8 288,6 111,7 283,1 130,7 52 441,1 167,3 469,2 168,5 511,4 172,4 333,1 131,2 326,7 153,5 = Cooling capacity ; = power input; Hc= heating capacity Correction factors for Silent version: Cooling capacity: 0,95; Power input: 1,055 Correction factors for freecooling version: Cooling capacity:0,97 Power input:1,02 Correction factors for ethylen glicol percentage and for difference temperature of water at inlet-outlet, see at end of chapter cooling main value; heating main value 44

SA-H-E Outlet water temperature ( C) Outlet water temperature ( C) 5 7 10 40 45 50 Hc Hc Hc 40 45 5 41,2 18,9 43,9 19,2 47,8 17,7 36,9 12,6 36,2 14,7 35,5 16,9 6 47,0 21,6 50,0 20,0 54,5 20,2 42,0 14,4 41,2 16,8 40,4 19,3 7 53,1 24,7 56,5 22,9 61,6 23,2 47,5 16,5 46,6 19,3 45,7 22,0 8 60,0 28,4 63,8 26,3 69,5 26,6 53,7 18,9 52,7 22,1 51,6 25,3 10 69,4 31,7 73,8 29,4 80,4 29,7 62,1 21,1 60,9 24,7 59,7 28,3 11 80,9 37,6 86,0 34,9 93,8 35,2 72,4 25,1 71,0 29,3 69,6 33,6 12 94,8 42,4 100,8 39,3 109,9 39,7 84,9 28,2 83,2 33,0 81,6 37,8 13 105,7 49,5 112,4 45,9 122,5 46,4 94,6 33,0 92,8 38,6 91,0 44,2 15 121,9 55,4 129,7 51,4 141,4 52,0 109,1 36,9 107,1 43,2 105,0 49,5 0 18 136,1 62,9 144,7 58,4 157,8 59,0 121,8 41,9 119,5 49,0 117,2 56,2 20 153,2 70,9 163,0 65,7 177,6 66,4 137,1 47,2 134,5 55,2 131,9 63,2 23 178,7 77,3 190,1 71,7 207,2 72,5 159,9 51,5 156,9 60,3 153,9 69,0 27 210,2 99,2 223,7 92,1 243,8 93,0 188,2 66,1 184,6 77,4 181,1 88,6 30 241,2 110,8 256,6 102,8 279,7 103,9 215,9 73,9 211,8 86,4 207,7 98,9 36 269,0 132,5 286,2 122,9 312,0 137,7 240,9 88,3 236,3 103,3 231,7 118,3 41 309,1 150,3 328,9 139,4 358,4 156,2 276,7 100,1 271,5 117,1 266,2 134,1 46 349,7 167,6 372,0 155,5 405,5 174,2 313,1 111,7 307,1 130,7 301,1 149,6 52 403,6 196,9 429,3 182,7 468,0 204,6 361,3 131,2 354,4 153,5 347,5 175,7 5 37,4 22,1 39,8 22,5 43,4 19,1 55,2 13,4 54,2 15,7 53,1 18,0 6 42,6 25,2 45,3 21,5 49,4 21,8 62,9 15,3 61,7 17,9 60,5 20,5 7 48,2 28,9 51,2 24,7 55,8 24,9 71,1 17,5 69,8 20,5 68,4 23,5 8 54,4 33,1 57,9 28,3 63,1 28,6 80,3 20,1 78,8 23,5 77,3 27,0 10 62,9 37,0 66,9 31,6 73,0 31,9 92,9 22,5 91,1 26,3 89,4 30,1 11 73,3 43,9 78,0 37,5 85,0 37,9 108,3 26,7 106,2 31,2 104,2 35,7 12 86,0 49,5 91,5 42,3 99,7 42,7 127,0 30,1 124,5 35,2 122,1 40,3 13 95,8 57,9 102,0 49,4 111,1 50,0 141,5 35,1 138,8 41,1 136,1 47,1 15 110,6 64,8 117,6 55,3 128,2 55,9 163,3 39,3 160,2 46,0 157,1 52,7 7 18 123,4 73,5 131,3 62,8 143,1 63,5 182,2 44,7 178,7 52,2 175,3 59,8 20 138,9 82,8 147,8 70,7 161,1 71,5 205,1 50,3 201,2 58,8 197,3 67,3 23 162,1 90,3 172,4 77,2 187,9 78,0 239,3 54,9 234,7 64,2 230,2 73,5 27 190,7 116,0 202,9 99,0 221,1 100,1 281,6 70,4 276,2 82,4 270,9 94,3 30 218,8 129,5 232,7 110,6 253,7 111,8 323,0 78,6 316,9 92,0 310,7 105,3 36 244,0 154,8 259,6 132,3 283,0 160,9 360,3 94,0 353,5 110,0 346,6 125,9 41 280,4 175,6 298,3 150,0 325,1 182,4 414,0 106,7 406,1 124,7 398,2 142,8 46 317,2 195,9 337,4 167,3 367,8 203,5 468,3 119,0 459,4 139,1 450,5 159,3 52 366,1 230,1 389,4 196,5 424,5 239,1 540,5 139,8 530,2 163,5 519,9 187,2 = Cooling capacity ; = power input; Hc= heating capacity Correction factors for Silent version: Cooling capacity: 0,95; Power input: 1,055 Correction factors for freecooling version: Cooling capacity:0,97 Power input:1,02 Correction factors for ethylen glicol percentage and for difference temperature of water at inlet-outlet, see at end of chapter cooling main value; heating main value 45

SA-C-N Evaporating temperature ( C) 0 2 3 4,5 6 8 10 5 45,8 18,8 49,0 17,7 50,6 19,0 53,0 19,1 55,3 19,2 58,5 19,3 61,7 19,5 6 53,6 21,0 57,3 21,1 59,2 21,2 62,0 21,3 64,8 21,4 68,5 21,6 72,2 21,7 7 59,1 23,9 63,2 24,1 65,2 24,2 68,3 24,3 71,4 24,5 75,5 24,6 79,6 24,8 32 8 65,7 27,4 70,3 27,6 72,6 27,7 76,0 27,8 79,4 28,0 84,0 28,2 88,5 28,4 10 80,4 32,7 86,0 32,9 88,8 33,0 92,9 33,2 97,1 33,4 102,7 33,6 108,3 33,9 11 93,4 37,4 99,9 37,7 103,1 37,8 108,0 35,8 112,8 36,2 119,3 36,8 125,8 37,4 12 106,0 42,4 113,4 42,7 117,1 42,9 122,6 40,6 128,1 41,1 135,5 41,7 142,8 42,3 13 118,4 47,5 126,6 47,8 130,7 48,0 136,9 45,5 143,0 46,0 151,2 46,7 159,4 47,5 15 134,9 53,4 144,2 53,8 148,9 54,0 155,9 51,2 162,9 51,8 172,3 52,6 181,6 53,3 18 152,4 57,5 163,0 57,9 168,3 58,1 176,2 55,1 184,2 55,7 194,7 56,6 205,3 57,4 20 171,7 69,4 183,7 69,9 189,6 70,1 198,5 66,5 207,5 67,2 219,4 68,3 231,3 69,3 23 208,5 85,1 222,9 85,7 230,2 86,0 241,0 81,5 251,9 82,5 266,3 83,7 280,8 85,0 27 242,2 92,1 259,0 92,7 267,4 93,1 280,0 88,2 292,6 89,2 309,4 90,6 326,2 92,0 30 272,9 111,0 291,8 111,8 301,3 112,3 315,5 106,4 329,7 107,6 348,6 109,3 367,5 110,9 5 43,6 19,8 46,6 19,7 48,1 20,0 50,4 20,1 52,7 20,2 55,7 20,4 58,7 20,5 6 51,0 22,1 54,5 22,3 56,3 22,3 59,0 22,5 61,6 22,6 65,2 22,8 68,7 22,9 7 56,2 25,2 60,1 25,4 62,1 25,5 65,0 25,6 67,9 25,8 71,8 26,0 75,7 26,1 35 8 62,6 28,9 66,9 29,1 69,1 29,2 72,3 29,3 75,6 29,5 79,9 29,7 84,3 29,9 10 76,5 34,4 81,8 34,7 84,5 34,8 88,4 35,0 92,4 35,2 97,7 35,4 103,0 35,7 11 88,9 39,4 95,0 39,7 98,1 39,9 102,7 40,1 107,3 40,5 113,5 41,2 119,7 41,8 12 100,9 44,7 107,9 45,0 111,4 45,2 116,6 45,4 121,9 45,9 128,9 46,6 135,9 47,4 13 112,6 50,1 120,5 50,4 124,4 50,6 130,2 50,9 136,1 51,5 143,9 52,3 151,7 53,1 15 128,3 56,3 137,2 56,7 141,7 56,9 148,4 57,2 155,0 57,9 163,9 58,8 172,8 59,7 18 145,0 60,6 155,1 61,0 160,1 61,3 167,7 61,6 175,2 62,3 185,3 63,3 195,3 64,2 20 163,4 73,1 174,7 73,6 180,4 73,9 188,9 74,3 197,4 75,2 208,7 76,3 220,1 77,5 23 198,4 89,7 212,1 90,4 219,0 90,7 229,3 91,2 239,7 92,2 253,4 93,6 267,2 95,1 27 230,4 97,0 246,4 97,7 254,4 98,1 266,4 98,6 278,4 99,8 294,4 101,3 310,3 102,8 30 259,6 117,0 277,7 117,9 286,7 118,3 300,2 119,0 313,7 120,3 331,7 122,2 349,7 124,0 5 39,9 23,1 42,7 23,4 44,0 21,7 46,1 21,8 48,2 21,9 51,0 22,1 6 46,7 25,7 49,9 24,1 51,5 24,2 54,0 24,4 56,4 24,5 59,6 24,7 7 51,4 29,4 55,0 27,5 56,8 27,6 59,5 27,8 62,1 27,9 65,7 28,1 40 8 57,2 33,6 61,2 31,5 63,2 31,6 66,2 31,8 69,1 32,0 73,1 32,2 10 70,0 40,1 74,8 37,6 77,3 37,7 80,9 41,5 84,6 42,0 89,4 42,6 11 81,3 45,9 86,9 43,0 89,8 43,2 94,0 47,6 98,2 48,1 103,9 48,8 12 92,3 52,1 98,7 48,8 101,9 49,0 106,7 53,9 111,5 54,5 117,9 55,4 13 103,1 58,3 110,2 54,7 113,8 54,9 119,2 60,4 124,5 61,1 131,7 62,0 15 117,4 65,6 125,6 61,5 129,6 61,7 135,7 67,9 141,9 68,7 150,0 69,7 18 132,7 70,6 141,9 66,2 146,5 66,4 153,4 73,1 160,3 73,9 169,5 75,1 20 149,5 85,2 159,9 79,8 165,1 80,1 172,8 88,2 180,6 89,2 191,0 90,6 23 181,5 104,5 194,1 97,9 200,4 98,3 209,8 108,2 219,3 109,5 231,9 111,1 27 210,8 113,0 225,5 106,0 232,8 106,3 243,7 117,1 254,7 118,4 269,3 120,2 30 237,6 136,3 254,1 127,8 262,3 128,2 274,6 141,2 287,0 142,8 303,5 145,0 = Cooling capacity ; = power input; Hc= heating capacity Correction factors for Silent version: Cooling capacity: 0,95; Power input: 1,055 Correction factors for freecooling version: Cooling capacity:0,97 Power input:1,02 Correction factors for ethylen glicol percentage and for difference temperature of water at inlet-outlet, see at end of chapter cooling main value; 46 heating main value

SA-C-E Evaporating temperature ( C) 0 2 3 4,5 6 8 10 5 43,9 15,1 47,0 14,2 48,5 15,3 50,8 15,4 53,1 15,4 56,1 15,6 59,2 15,7 6 50,1 17,2 53,5 17,4 55,3 17,4 57,9 17,5 60,5 17,6 64,0 17,7 67,4 17,9 7 56,7 19,7 60,7 19,9 62,7 19,9 65,6 20,1 68,6 20,2 72,5 20,3 76,4 20,5 32 8 65,2 22,7 69,7 22,8 72,0 22,9 75,4 23,0 78,8 23,2 83,3 23,3 87,8 23,5 10 74,3 25,3 79,5 25,5 82,1 25,6 85,9 25,7 89,8 25,9 94,9 26,0 100,1 26,2 11 86,4 30,0 92,4 30,2 95,4 30,4 99,9 30,5 104,4 30,7 110,4 30,9 116,4 31,1 12 101,3 33,8 108,3 34,1 111,9 34,2 117,1 34,4 122,4 34,6 129,4 34,8 136,4 35,1 13 112,9 39,5 120,8 39,8 124,7 40,0 130,6 37,9 136,4 38,3 144,3 38,9 152,1 39,5 15 131,0 44,3 140,0 44,6 144,6 44,8 151,4 42,4 158,2 42,9 167,3 43,6 176,4 44,2 18 146,1 50,3 156,3 50,6 161,4 50,8 169,0 48,2 176,6 48,7 186,7 49,5 196,8 50,2 20 164,5 56,6 175,9 57,0 181,7 57,2 190,2 54,2 198,8 54,9 210,2 55,7 221,6 56,5 23 191,9 61,7 205,2 62,2 211,9 62,4 221,9 59,2 231,8 59,8 245,1 60,8 258,5 61,7 27 225,8 79,3 241,5 79,8 249,3 80,1 261,1 75,9 272,8 76,8 288,5 78,0 304,2 79,2 30 259,7 88,5 277,7 89,2 286,7 89,5 300,2 84,8 313,8 85,8 331,8 87,1 349,8 88,4 5 41,8 15,9 44,7 15,9 46,2 16,1 48,3 16,2 50,5 16,3 53,4 16,4 56,3 16,5 6 47,6 18,2 50,9 18,3 52,6 18,4 55,1 18,5 57,6 18,6 60,9 18,7 64,2 18,8 7 54,0 20,8 57,7 20,9 59,6 21,0 62,4 21,1 65,2 21,3 69,0 21,4 72,7 21,6 35 8 62,1 23,9 66,4 24,1 68,5 24,1 71,7 24,3 75,0 24,4 79,3 24,6 83,6 24,8 10 70,7 26,7 75,6 26,9 78,1 27,0 81,8 27,1 85,4 27,2 90,3 27,4 95,2 27,6 11 82,2 31,6 87,9 31,9 90,8 32,0 95,1 32,2 99,3 32,3 105,0 32,6 110,7 32,8 12 96,4 35,7 103,1 35,9 106,4 36,1 111,4 36,2 116,5 36,7 123,1 37,2 129,8 37,8 13 107,4 41,7 114,9 42,0 118,6 42,1 124,2 42,4 129,8 42,9 137,3 43,5 144,7 44,2 15 124,6 46,7 133,2 47,0 137,6 47,2 144,0 47,4 150,5 48,0 159,2 48,7 167,8 49,5 18 139,1 53,0 148,7 53,4 153,5 53,6 160,8 53,8 168,0 54,5 177,6 55,3 187,3 56,1 20 156,6 59,6 167,4 60,1 172,8 60,3 181,0 60,6 189,1 61,3 200,0 62,3 210,8 63,2 23 182,6 65,1 195,3 65,6 201,6 65,8 211,1 66,2 220,6 66,9 233,3 67,9 245,9 69,0 27 214,9 83,5 229,8 84,2 237,2 84,5 248,4 84,9 259,6 85,9 274,5 87,2 289,4 88,5 30 247,1 93,3 264,3 94,0 272,8 94,3 285,7 94,8 298,5 95,9 315,7 97,4 332,8 98,9 5 38,3 18,6 40,9 18,9 42,2 17,5 44,2 17,6 46,2 17,6 48,9 17,8 6 43,6 21,2 46,6 19,8 48,1 19,9 50,4 20,0 52,7 20,1 55,7 20,3 7 49,4 24,2 52,8 22,7 54,5 22,8 57,1 22,9 59,7 23,0 63,1 23,2 40 8 56,8 27,8 60,7 26,1 62,7 26,2 65,6 26,3 68,6 26,5 72,5 26,6 10 64,7 31,1 69,2 29,1 71,4 29,2 74,8 29,4 78,2 29,5 82,7 29,7 11 75,2 36,9 80,5 34,6 83,1 34,7 87,0 38,2 90,9 35,1 96,1 35,3 12 88,2 41,5 94,3 38,9 97,4 39,1 102,0 43,0 106,6 43,5 112,7 44,2 13 98,3 48,6 105,1 45,5 108,5 45,7 113,7 50,3 118,8 50,9 125,6 51,6 15 114,0 54,4 121,9 50,9 125,9 51,1 131,8 56,3 137,7 56,9 145,6 57,8 18 127,2 61,7 136,1 57,8 140,5 58,0 147,1 63,9 153,7 64,6 162,5 65,6 20 143,2 69,5 153,2 65,1 158,1 65,4 165,6 72,0 173,1 72,8 183,0 73,9 23 167,1 75,8 178,7 71,1 184,5 71,3 193,1 78,5 201,8 79,4 213,4 80,6 27 196,6 97,3 210,2 91,2 217,1 91,6 227,3 100,8 237,5 102,0 251,2 103,5 30 226,1 108,7 241,8 101,9 249,6 102,2 261,4 112,5 273,2 113,8 288,8 115,6 = Cooling capacity ; = power input; Hc= heating capacity Correction factors for Silent version: Cooling capacity: 0,95; Power input: 1,055 Correction factors for freecooling version: Cooling capacity:0,97 Power input:1,02 Correction factors for ethylen glicol percentage and for difference temperature of water at inlet-outlet, see at end of chapter cooling main value; heating main value 47

Correction factors for ethylene glycol content Weight percentage of glycol % 0 10 20 30 40 50 Freezing point ( C) 0-3,6-8,8-15,7-24,86-37,13 Minimum outlet water temperature allowed ( C) 5,5 1,9-3,3-10,2-19,4-31,6 Cooling capacity correction factor (dt=5 C) 1,000 0,993 0,985 0,978 0,970 0,963 Correction factors for differential water temperature IN-OUT Differential water temperature (Inlet - Outlet) C 3 4 5 6 7 8 9 10 Cooling capacity correction factor 0,970 0,985 1,000 1,008 1,016 1,024 1,032 1,040 The technical data in this document are not binding. Rigel Impianti S.r.l. keeps rights to make any technical modifications at any time without notice due to its improvement process. 48

DIMENSIONAL DRAWINGS Unit SA sizes 5, 5-E 6, 6-E 7, 7-E, 8 5 TOP 49

Unit SA sizes 8-E, 10, 10-E, 11, 11-E, 12, 12-E, 13, 13-E, 15 6-TOP, 7-TOP, 8-TOP, 10-TOP, 11-TOP, 12-TOP 50

Unit SA sizes 15- E, 18, 18-E, 20 13-TOP, 15-TOP, 18-TOP 51

Unit SA sizes 20-E, 23 52

Unit SA sizes 23-E, 27, 27-E, 30 20-TOP, 23-TOP 53

Unit SA sizes 30-E, 36, 36-E, 41 27-TOP, 30-TOP 54

Unit SA sizes 41-E, 46, 46-E, 52, 52-E, 60 36-TOP, 41-TOP, 46-TOP 55

Unit SA sizes 60-E 52-TOP 56

SPACE FOR UNIT INSTALLATION 57

Notes..................................................................................................................

Cold Innovation Zona Industriale Padule - 06020, Gubbio (PG) - Italy Tel. +39 075 929 11 13 Fax +39 075 929 92 94 info@coldinnovation.it

VENERUCCI 0214