Cable Limiters Increase System Reliability Decrease Downtime

Similar documents
SECTION LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES (600 VOLTS AND BELOW)

CHAPTER 20 SERVICE EQUIPMENT

Electrical Essentials corrected calculation slides only

Ordering Key. Dielectric strength

Electric Shock Drowning

Subpanels. Bring Big Amps to Distant Spaces. A subpanel is a secondary breaker box BY CLIFFORD A. POPEJOY

Sundance Spas SPA EQUIPMENT SYSTEM. Installation Instructions. P/N Rev. A

Self-regulating Roof Heat Cable

MODEL EH ELECTRIC BOILER OPERATION AND INSTALLATION INSTRUCTIONS

Toll Free:

Self-regulating Roof Heat and Gutter Trace Cable

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

AF/GF dual-purpose receptacles

GE Industrial Solutions. Residential Electronic Circuit Interrupters

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Corra/Clad MC Cable The contractors cable of choice in place of conduit and wire.

Afci TR Duplex 20A 125V Iv. Features amperage rating. Dimensions and Weight. Descriptions

ASCO Series 185 Power Transfer Switches

Motor Controller AC Semiconductor Motor Controller Type RSBS23..A2V.2C24

SUGGESTED SPECIFICATION For Series 300 Manual Transfer Switches (3MTS)

INSTALLATION INSTRUCTIONS FOR 8330*633* COOL ONLY A/C 8330*635* HEAT READY A/C 8530*63** HEAT PUMP CHILLGRILLE FLUSH MOUNT CEILING ASSEMBLY

8. Multi-Family Residential Buildings

Afci TR Duplex 20A 125V La. Features amperage rating 20. Dimensions and Weight Width 3.3. Long Description

MONITRON II MODEL EH-M2 ELECTRIC BOILER OPERATION AND INSTALLATION INSTRUCTIONS. Four stage electronic control with energy saving and other features.

Dwelling unit feeder/service conductor calculations

Toll Free:

Fusible Shunt. Trip Switch. Operation and Maintenance Manual SOLUTIONS GUIDE

FRP HEATING SYSTEM INSTALLATION, OPERATION & MAINTENANCE MANUAL FRP.IOM.R1

INSTALLATION INSTRUCTIONS FOR 8330*5511 MOUNTING KIT

MODELS B1PA024, 030 AND 036

VENTILATION FAN READ AND SAVE THESE INSTRUCTIONS. MODEL Pro200/Pro300 TABLE OF CONTENTS. Package Contents. General Safety Information

Informational Bulletin on Mobile office Units Prepared by Mark Hilbert May 17, 2017

CORFLEX TYPE MC-HL POWER, CONTROL & INSTRUMENTATION CABLES

ONE- AND TWO-FAMILY DWELLING ELECTRICAL CODE HANDOUT (2015 Michigan Residential Code Effective February 8, 2016)

SMPG3 SNOW MELTING AND DE-ICING POWER DISTRIBUTION AND CONTROL PANEL. For three-phase heating cables PRODUCT OVERVIEW

INSTALLATION INSTRUCTIONS FOR 7330C740 FLUSH MOUNT CEILING ASSEMBLY

SECTION ELECTRICAL GENERAL PROVISIONS

ELECTRONIC FLAME SUPERVISION MULTI-BURNER

ABH BASIN HEATER CONTROLS PACKAGE. engineering data and specifications

HESNI ANNUAL CONFERENCE May 3, 2012 Aramark Conference Center, Downers Grove

Toll Free:

INSTALLATION INSTRUCTIONS FOR 8330*63**, 8530*63** CHILLGRILLE FLUSH MOUNT CEILING ASSEMBLY

PART GENERAL 1.01 SECTION INCLUDES

BGH Series Hot Surface Ignition Control

INSTALLATION INSTRUCTIONS FOR MOUNTING KIT

Ramsey Motion Monitoring Systems

MARATHON HEATER. File # E Made in USA

Photovoltaic (Solar) Array Installation Guide

Machinery Room Electrical Best Practices

Residential Backup Power. Keep the power on

Remote NAC Power Supply D7038

SECTION AUTOMATIC TRANSFER SWITCHES PART 1 - GENERAL

Electrical Safety Through Design. Mersen EP formerly Ferraz Shawmut

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES

Installation and Operation Manual

Flow Factor ~

TECHNICAL GUIDE DESCRIPTION SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS MODELS: HF-07 FEATURES B-0703

HUMIDITY SENSING BATH FAN

AFCI. RECEPTACLEFAQs. What is an arc fault? What causes arc faults?

PLSRR Heat Trace Cable Data Sheet

VENTILATION FAN / LED LIGHT

Engineered Solutions SYSTEMS CUSTOM ENGINEERED TO YOUR SPECIFICATIONS. Fused Coordination Panelboards...ES 2. Fusible Shunt Trip Switch..

SECTION PANELBOARDS. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

Michigan Chapter IAEI Annual Meeting Ann Arbor, Michigan Code Panel Questions December 5 th and 6 th, 2013

MASTER PRESSRE MAINTANENCE CONTROLLER. Models PMCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:

Reliable connections are your main concern Our stars provide crimping that lasts Let s connect. Connection technology and electrical installation

Toll Free:

Your Global Automation Partner. Minimizing Arc Flash Exposure in Industrial Applications. White Paper - W1000

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 8/10/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

Flame Retardant EP/CPE POWER, CONTROL & INSTRUMENTATION CABLES

Where technical minds provide innovative solutions

VENTILATION FAN READ AND SAVE THESE INSTRUCTIONS MODEL 50F / 70F / 70HS TABLE OF CONTENTS. Package Contents 2. General Safety Information 3

Explosion Proof Line Powered Telephone Ringer

Lord Stirling Community School Electrical Systems Existing Conditions & Building Load Summary Technical Assingment#2 Due October 26, 2004

ASSESSING THE HIDDEN DANGERS IN YOUR INDUSTRIAL CONTROL PANELS

Revision: None DCN No. First Issue Date: November 30, 1998 Product: Standard DCT, 120-volts

Installing the Cisco ONS FAP-4 Fuse Alarm Panel

Line Isolation Monitor (LIM) LIM2000plus

AlarmLine Linear Heat Detector

UltraLITE Model ELU Centralized Emergency Lighting Inverter 4.2 KW- 5 KW

32 Tips to Consider Before Purchasing an Electrical Enclosure Air Conditioner TABLE OF CONTENTS INTRODUCTION... 3 TECHNICAL FEATURES 4

OPERATING AND INSTALLATION MANUAL

Tamper & Weather Resistant Receptacles

SECTION AIR COILS

Residential Wiring According to 2011 NEC (Homestudy)

MASTER JOCKEY PUMP CONTROLLER. Model JPCE INSTRUCTION MANUAL. C 2018 Master Control Systems, Inc

Electric Floor Warming Systems Installation and Operation Instructions. Mat Heating Systems and Cable Heating Systems. UL Listed for USA and Canada

A HOMEOWNERS HANDBOOK

Alternative Fuel Fueling Stations

PRODUCTS FOR Wiring Duct Power & Grounding Connectors Fastening Products Control Termination Identification Solutions

ARM SERIES Switching Relays With Priority

Custom Pump Controls. The Custom Controls Solution Provider. A New Generation. Complete Management. Page 2

You work hard on your panel. we work hard in your panel. PRODUCTS FOR

MHCFC4W Chilled/Hot Water Cassette Fan Coil

MHCFC4W Chilled/Hot Water Cassette Fan Coil

MHCFC4W Chilled/Hot Water Cassette Fan Coil

Motor Controller AC Semiconductor Motor Controller Type RSBS23..A2V.2C24..

Second Revision No. 601 NFPA [ Section No [Excluding

Transcription:

Limiters Increase System Reliability Decrease Downtime

Increase system reliability and versatility with Ferraz Shawmut Limiters. Limiters are designed for the protection of low voltage distribution networks, feeders and service entrance cables. Permitted by National Electric Code Article 230.82(1), cable limiters prevent service outages by isolating damaged cables ensuring continuity of customer power. Increase system reliability and versatility with Ferraz Shawmut Limiters. Ferraz Shawmut Limiters Install Ferraz Shawmut cable limiters in underground power distribution systems found in commercial, industrial, and residential applications. limiters are designed for use in both radial and network type underground systems to reduce the hazards of unexpected downtime and maintenance. Ferraz Shawmut offers a full line of both 600VAC and 250VAC cable limiters, with the 600VAC product line being UL Listed for code compliance. Select the proper limiter for your application by choosing from seven available terminal combinations suitable for aluminum or copper wire sizes from 1 AWG up to 1000kcmil. Customer Benefits Limiters offer users an inexpensive solution to prevent costly downtime. Limiters isolate faulty cables and allow the remaining cables to keep your business up and running. Faulty cables can now be pulled and replaced during a scheduled or routine shutdown when power is not needed. Applications and Installation Three common cable limiter applications include: 1. Distribution network systems with three or more cables in parallel per phase Install cable limiters on each end of each cable to allow for isolation of damaged cables. The limiters remove damaged cables from the circuit to maintain service. 2. Commercial and residential applications with multiple customers fed from one transformer Install one cable limiter on the secondary of the utility transformer per cable run. Allow businesses and homes to maintain power if a fault may occur. 3. Secondary Ties Protect circuits that connect two power sources or power supply points to prevent vaporization of cables under short circuit faults.

Three or more Conductors per Phase. For larger ampere rated systems it is common to use several smaller cables in parallel, instead of one large cable, to share a heavier load. For this application Limiters are installed on the secondary of the utility transformer and on the line side of the service entrance disconnect. It is important to install cable limiters on each end of each cable. In most cases the customer hired contractor is responsible for installing limiters at the utility transformer and on the line side of the service entrance disconnect at the building. If one cable experiences a fault, the faulty cable will be isolated from the network allowing the remaining cables to maintain power to the system. The damaged cable can now be replaced during a scheduled shutdown when revenue gain or production is not at risk of downtime. Unexpected power loss can result in lost revenue. Commercial Malls, strip malls, shopping centers, outlets, retail businesses, universities, government facilities, and office buildings are typical customers that benefit from the installation of cable limiters. Protect incoming power to the retail centers power distribution network. Construction work external to the facility is a major cause of damaged cables. Improperly marked dig sites, equipment malfunction and operator error can all result in potentially hazardous electrical faults. Protect commercial developments with cable limiters and prevent potential lost revenues to its tenants. Application Example Utility Transformer Industrial NEC Article 230.82(1) permits the installation of cable limiters on the supply side of the service entrance disconnect. Ensure system reliability, guarantee operation, reduce maintenance costs and prevent unexpected downtime. Benefit from using cable protection in all types of industries such as metal fabrication, wastewater, assembly, electronics, textile, oil and gas, pulp and paper, rubber, steel, aluminum, glass and chemical. OPEN Fault Limiters Ferraz Shawmut cable limiters are designed to withstand harsh environments and will not deteriorate from elements such as age, moisture or environmental surroundings. Ferraz Shawmut limiters are self-contained and self-protecting. Various termination offerings accommodate all types of installations. Service Entrance Limiters Service Entrance Recommended Product: Amp-Trap CP

Secondary Ties. NEC article 450.6(A)(3) states that any secondary tie, 600V or less nominal, shall be equipped with a protective device that will open under short-circuit conditions. Article 450.6(A)(3) permits the installation of a cable limiter as an acceptable method of meeting this requirement. A secondary tie is a point in a circuit where two power sources or power supply points are connected, such as the secondary of two transformers. For example this could be two individual transformers or a bank of transformers operating as a unit. Multiple Services Supplied by a Single Source. Multiple services such as residential developments, apartment buildings, and small commercial buildings consume lighter loads and are often fed from a single transformer. To prevent the entire neighborhood, apartment building or strip mall from experiencing an outage, cable limiters are installed on each cable run to each individual service. In the case of a cable fault, the faulty service will be isolated from the remaining customers. For this application only one cable limiter is required per cable run on the secondary of the utility transformer. Utility Transformer Transformer Transformer Limiter Limiters Overcurrent Protection Service Service Customer Customer Customer Customer Recommended Product: Amp-Trap CP Recommended Product: Amp-Trap CP and 2CL

Amp-Trap CP 600VAC Limiters Approved 600VAC limiters for heavy commercial and industrial applications. Ideal for multiple cable runs per phase. Increase reliability and prevent unexpected downtime. Amp-Trap 2CL 250VAC Limiters Approved 250VAC limiters for light commercial and residential applications. Protect underground cable runs from thermal damage caused by short circuits. UL Listed, File E305297 600VAC, 200kA IR Superior short circuit protection sizes #2 1000kcmil Seven terminal combinations available Copper or Aluminum cable Optional heat shrink or molded rubber boots available Ferraz Shawmut Certified 250VAC, 200kA IR Superior short circuit protection sizes #1 500kcmil Four terminal combinations available Copper or Aluminum Shorter in length than standard 600VAC rated cable limiters Installation information, including crimping tool recommendations, limiter performance characteristics and part numbers is available online at us.ferrazshawmut.com or by contacting your local sales representative.

A relentless pursuit of protection for electrical components, systems and the people who use them. Ferraz Shawmut is an international company manufacturing the widest range of circuit protection solutions in the electrical industry. Drawing on a century of experience and an ongoing commitment to critical research in electrical safety we provide industrial, commercial, and OEM customers with innovative products and technical support teams to increase effectiveness, simplify applications, and enhance productivity. Learn more about our circuit protection solutions at us.ferrazshawmut.com. For more information, visit our website at us.ferrazshawmut.com. USA 374 Merrimac Street, Newburyport, MA 01950 T: 978-462-6662 F: 978-462-0181 Canada 88 Horner Avenue Toronto, Ontario, Canada M8Z 5Y3 T: 416-252-9371 F: 416-252-6572 2008 Ferraz Shawmut. All rights reserved. BR-CL-001