SINGLE MONITORED INPUT UNIT BN-303

Similar documents
DUAL MONITORED INPUT/OUTPUT UNIT BN-305

DUAL MONITORED INPUT/OUTPUT UNIT BN-305-2

Instructions AutroFlame IR Flame Detector BG-201/BG-21

ADAPTER FOR VENTILATION DUCT BWP-143A-SS (STAINLESS STEEL)

Easy Reliable Flexible. Interactive fire detection system

ZIOU/230 - MAINS IO INSTRUCTION MANUAL

System Description Autroprime Interactive Fire Detection System

AUTROSAFE. An interactive fire detection system for larger vessels

AutroSafe interactive fire detection system AUTROSAFE. An interactive fire detection system for complex installations

AUTROSAFE 4 A new level in interactive fire detection systems

Operator's Handbook. Interactive Fire Alarm System Release 3. Information Panel, BV-320. Protecting life, environment and property...

Mounting Instructions Adapter for ventilation duct BWP-143A-SS, Stainless Steel version

System 800 Addressable Fire Detection & Alarm System

Interface and EOL Modules 8

FEC400 Series. Installation Manual

Input module, input/output modules

ISOSCAN EDS460/490 EDS461/491. Insulation fault locators with control and display function for EDS systems (insulation fault location systems)

1.7. Insulation fault evaluators EDS460/490 EDS461/491

Technical Description Relay Module Flame Detector

System Description AutroMaster V Presentation System

End To End Optical Beam Smoke Detector. Additional Information

Loop units. a wide range covering your basic fire detection needs

FDCIO223 (ES 45) Transponder

Fire Extinguishing Control Panel INSTRUCTION MANUAL. Revision 8/ Instruction Manual Page 1 Revision 8/01.17 of 63

INPUT / OUTPUT MINI MODULES

Not to be distributed outside of FM Approvals and its affiliates except by Customer APPROVAL REPORT. BU-110 and BV-110 Loop Based Displays

Autronica Fire and Security AS ID:

System Design and Engineering AutroSafe Interactive Fire & Gas Detection System (IFG)

Snifter ATEX22 VERSION. User Manual. Distributor

F&G detection system for LNG plants

FDMM01S - FDMM02 - FDMM10- FDMM11S FDMM12 - Input / output mini modules

S200Plus Triple Infra Red Flame Detector Triple Waveband Infra-Red Flame Detection

Installation, Operating and Maintenance Manual

Input/Output Modules Data Sheet

Conventional Fire Alarm System 2014 V1.2

Release 4. System Description. AutroSafe Interactive Fire Detection System. 116-P-ASAFE-SYSTEMD/EGB Rev. H, , Autronica Fire And Security AS

2000 Series Sensors Installation Guide

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

Insulation fault evaluator EDS460-DG

ISOSCAN EDS460-DG. Insulation fault locator for DC IT systems with high system leakage capacitances

Snifter. User Manual. Distributor

Standard detectors. General information. Product Sheet Detec on

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

System Description AutroMaster ISEMS - Integrated Safety and Emergency Management System

FEC403EN Installation Manual

IMQ SPA scope as CertAlarm CCB and RTL. Last update: 12th June 2017

SOUNDER CONTROL MODULE SCM-AS4

Input module, input/output module

Operator's Handbook. Release 3. Fire Alarm Control Panel, BS-310 / 320 / Operator Panel BS-330. System Program Version 3.8.0

FR-4000 & FR-8000 Fire Alarm Monitor Installation Manual

JK e-solutions ApS FS12. Control and Monitoring system for Fixed Aerosol Fire Extinguishing Systems. Installation and Service Manual R11

Панели. Autroprime. Технические характеристики

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

Interface Modules for SENTRI

1.7. Insulation fault evaluators EDS460/490 EDS461/491

Multi-Gas-Controller MGC2

Consultant Specification AGILE Wireless Fire Detection System

FC330A-ECO Auto-addressing analogue 1-Loop fire detection panel

FC330A-ECO1 Auto-addressing analogue 1-Loop fire detection panel

An introduction to... Sigma

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

Control and Indicating Equipment

PROFIBUS-PA Display RID 261 PROFIBUS-PA

MINERVA S200Plus. Fire Detection. Triple Waveband Infra-Red Flame Detection. Features: Minerva S200PLUS

Motorised Infrared Optical Beam Smoke Detector. User Guide

AutroVoice voice alarm system AUTROVOICE VOICE ALARM. Loud and clear information

INDEX 1- Introduction The Control Pane...7l 4.1- The Control Panel 1 and 2 Loops The Control Panel 4 and 8 Loops...

Motorised Infrared Optical Beam Smoke Detector. User Guide

ETNC24-FC-BAC-PIR-01 Owner s manual & Technician Settings

OilSET-1000 (12 VDC)

DC1136, DC1131-AA, DC1134-AA, DC1136-AA Input / Output modules

LAE10 LFE10. Use. Series 02

QA16 Addressable Panel Programming Manual V3.07.3

FPX103C Auto DUAL LOOP AUTO/MANUAL FIRE CONTROL PANEL Iss 1.0

AU MX Digital Loop Card Installation Instructions

LM80031 Issue H. Installer s Handbook

E N G L I S H FIRE ALARM ASPIRATION SENSING TECHNOLOGY QUICK INSTALLATION GUIDE ADDRESSABLE FAAST LT MODELS MI-FL2011EI, MI-FL2012EI AND MI-FL2022EI

Danfoss gas detection unit Type GD Heavy Duty

MINERVA MX. 800 Series Ancillary Equipment

SecuriSens LIST Product Catalogue 2015

5, SE GÅNGHESTER,

IT system floor-standing distribution

Public Safety DAS Annunciator Panel

Analogue addressable devices

BS-316. Gas detection control panel up to 16 inputs. Installation operation manual

Dual Point General Purpose Heat Trace Control TRACON MODEL GPT 230 Installation and Operation Manual

OilSET Installation and Operating Instructions. Oil Separator Alarm Device

DC1154 / DC1154-AA / DC1156-AA / DC1157-AA Input / Output modules

Planning Instructions MEW01776 Revision -

AutroFlame X33AF. Addendum. Multi-spectrum IR flame detector. Protecting life, environment and property...

AL600ULADA. NAC Power Extender. Installation Guide

Esmi Sense FDP Fire detection panel with ALC2 loop controller

ICS Regent. Fire Detector Input Modules PD-6032 (T3419)

Shortform Configuration Guide

CONTROL DEVICE SLIDETRONIC HD

Installation Handbook. Interactive Fire Alarm System Release 3. Operator Panel, BS-330. Protecting life, environment and property...

KSUF CONTROL AND MONITORING UNIT. Description. Installation Designed for wall installation.

isopv425 and AGH420 Ground Fault Detector for Ungrounded Solar Arrays < 100 kw And Isolation Tester Prior to Array Startup (Grounded and Ungrounded)

MODEL GPT-130 SINGLE POINT HEAT TRACE CONTROL THERMOSTAT

MX43. Analog and digital controller. 4 or 8 lines / 16 to 32 detectors max. Highly versatile controller. Cost savings on wiring installation

Transcription:

SINGLE MONITORED INPUT UNIT BN-303 Interactive fire detection system Product Datasheet Features Interactive For interfacing switches and 3rd party detectors with relay outputs to Autronica s interactive fire detection systems Multi function unit: Function selected by switch setting 1 non-isolated input: on/off function with end-ofline monitoring With SelfVerify function for reduced maintenance/testing and increased reliability on input for critical alarm functions Short-circuit isolator of detection loop in each unit Automatic addressing Proven technology Wall mounted Designed to meet the requirement of the major maritime classification societies Approved according to EN 54-17 and EN 54-18 Product overview The Single Monitored Input Unit BN-303 has been designed for use with Autronica s fire detection systems, Autroprime (version 1.1.0 or newer) and AutroSafe (version 4.3.1 or newer), and includes the SelfVerify function. This function ensures the highest grade of reliability and reduces the need for manual testing because the panel is able to continuously and automatically check all units that include this function. Note: External devices attached to this interface unit require a separate power source (they can not be powered by the detection loop). SelfVerify: The unit s ability to initiate alarm is regularly checked. Function Options / Switch Settings The internal DIP switch S1 selects the function performed by the BN-303. For location of the DIP switch, refer to circuit board drawing on the next page. Refer to detailed descriptions of each function on this datasheet (Descriptions of function options A-E). The available functions include: Function A Alarm condition signalling input Function B Pre Alarm condition signalling input unit Function C Fault condition signalling input Function D Uncommitted input unit Function E Pre Alarm and Alarm condition signalling input unit with configurable input delay Function F Fault, Pre Alarm and Alarm condition signalling input 116-P-BN303/CGB, Rev. A, 2015-06-05 Protecting life, environment and property

Technical Specification Dimensions (mm) 112 x 110 x 50 Weight (g) 192 Housing material Colour Mounting Power Voltage Peak current consumption (during communication) Average current consumption Polyamide Light grey Wall mounting, 100mm bolt space Unit connects to AL_Com only Supplied from detection loop 359μA <60μA Temperature range -25 to +70 C Humidity Degree of protection Membrane glands: PG glands (PG-13,5): Communication loop Cable terminals Cable requirements AL_Com Maximum input cable length Maximum cable capacitance Response time Threshold Approvals 10% - 95% RH (non-condensing) IP54 IP67 Autronica Loop Communication protocol (Al_Com) Max 2.5mm² single core wires Refer to specification for Autroprime or AutroSafe 10m, non-shielded or shielded. End termination 2kohms +/-5% 10nF <= 1 second Short-circuit: 0-235 Ω Activate: 260-1000 Ω Normal: 1200-4800 Ω Open circuit: 5400- Ω See Autronica s website 0333 Autronica Fire and Security AS, N-7483 Trondheim 08 0333-CPR-075249 EN 54-17:2005 Short circuit isolators EN 54-18:2005 Input/output devices Product name Part number Description BN-303 116-BN-303 Single monitored input unit 6571-011.6020 116-6571-011.6020 Membrane gland TSS M20, grey Optional 6571-011.1920 116-6571-011.1920 Gland IP67 6531-006.1920 116-6531-006.1920 Backnut for gland Autronica Fire and Security AS Tel.: +47 90 90 55 00 E-mail: info@autronicafire.no www.autronicafire.com Page 2

Dimension (mm) Connectors Terminal Description 1 AL_Com In (+) 2 AL_Com In (-) 3 AL_Com Out (+) 4 AL_Com Out (-) 5 Input (+) 6 Input (common) Connectors and DIP switches on circuit board Autronica Fire and Security AS Tel.: +47 90 90 55 00 E-mail: info@autronicafire.no www.autronicafire.com Page 3

Descriptions of connection options Input configuration A Class 1 N.O. 910 Ohm Input configuration B Class 2 N.C. 910 Ohm Input configuration C Class 3 N.O. Input configuration D Class 4 N.C. Figure 1 The electrical connection options for the input to the unit are shown in Figure 1. The various electrical input configurations allow a user to select under what condition the unit will be triggered to provide a signal the fire alarm system indicating the selected condition. Autronica Fire and Security AS Tel.: +47 90 90 55 00 E-mail: info@autronicafire.no www.autronicafire.com Page 4

The four different behaviours can be configured by DIP switch 5 and 6 in order to be able to monitor different setups of the input contact (s). (Switch 7 and 8 are not used). (See location of DIP switch S1 on the circuit board drawing) Input configuration A activates when the contacts are closed. This arrangement also allows the unit to monitor for an electrical wiring fault in the form of an open or short-circuit, between the contacts and the unit, either before or during activation. OFF OFF Normal Open contact with activate resistor, fault monitored for open and short-circuit. Input configuration B activates when the contacts are opened. This arrangement allows the unit to monitor for an electrical wiring fault in the form of an open or short-circuit, between the contacts and the unit, either before or during activation. OFF ON Normal Closed contact with activate resistor, fault monitored for open and short-circuit. Input configuration C activates when the contacts are closed. This arrangement allows the unit to monitor for an open circuit fault in the electrical wiring before activation. A short-circuit in the wiring will trigger the unit. ON OFF Normal Open contact without activate resistor, fault monitored for open circuit. Input configuration D activates when the contacts are opened. This arrangement allows the unit to monitor for an open circuit fault in the electrical wiring during activation. ON ON Normal Closed contact without activate resistor, fault monitored for open circuit. Autronica Fire and Security AS Tel.: +47 90 90 55 00 E-mail: info@autronicafire.no www.autronicafire.com Page 5

Descriptions of function options (See location of DIP switch S1 on the circuit board drawing) Function A OFF OFF OFF OFF Function: Alarm condition signaling input. Fire alarm push buttons Flame, heat or beam detectors with relay contacts Function B ON OFF OFF OFF Function: Pre Alarm condition signaling input. Manual input for Pre Alarm Pre Alarm input from a detector with relay output Function C OFF ON OFF OFF Function: Fault condition signalling input. Monitoring of associated equipment for faults Monitoring of detectors with relay contacts Autronica Fire and Security AS Tel.: +47 90 90 55 00 E-mail: info@autronicafire.no www.autronicafire.com Page 6

Function D ON ON OFF OFF Function: Uncommitted input. Applications: A typical application is monitoring of the power fault contact in the power supply or a fire pump. This unit can be used for: Monitoring of water level detection systems Monitoring of smoke control damper systems Monitoring of extinguishing systems General Alarm Push Button (GAPB) Function E OFF OFF ON OFF Function: Delayed Alarm condition. Configurable delays for entering Pre Alarm and Alarm condition. The default timer value is: 10 seconds before entering Pre Alarm condition. 20 seconds before entering Alarm condition. Sprinkler contacts, etc. Function F ON OFF ON OFF Function: Fault, Pre Alarm and Alarm condition. Applications include: Fire detectors with two-level output (Pre Alarm and Alarm). Autronica Fire and Security AS Tel.: +47 90 90 55 00 E-mail: info@autronicafire.no www.autronicafire.com Page 7