Performance Comparison of R32, R410A and R290 Refrigerant in Inverter Heat Pumps Application

Similar documents
Experimental Research On Gas Injection High Temperature Heat Pump With An Economizer

Experimental Study About An Amount Of Oil Charge On Electric Driven Scroll Compressor For Electric Vehicle

Effects of Flash and Vapor Injection on the Air-to- Air Heat Pump System

Figure 1: Schematic of internal heat exchanger vapor-injection cycle

Introduction of Transcritical Refrigeration Cycle Utilizing CO2 as Working Fluid

R32 Compressor for Air conditioning and Refrigeration applications in China

Control Method Of Circulating Refrigerant Amount For Heat Pump System

The Innovative Green Technology for Refrigerators Development of Innovative Linear Compressor

Experimental Study on Match for Indoor and Outdoor Heat Exchanger of Residential Airconditioner

Air-Cooled Heat Exchanger Performance for R410A

Low GWP Refrigerants for Air Conditioning Applications

Lower GWP Refrigerants Compared to R404A for Economizer Style Compressors

Purdue e-pubs. Purdue University

Performance of R-22, R-407C and R-410A at Constant Cooling Capacity in a 10

Development of R744 Two Stage Compressor for Commercial Heat Pump Water Heater

The Development Of High Efficiency Air Conditioner With Two Compressors Of Different Capacities

Refrigeration Cycle And Compressor Performance For Various Low GWP Refrigerants

System Using Exhaust Heat from Residential GHPs

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

Comparison Of Hermetic Scroll And Reciprocating Compressors Operating Under Varying Refrigerant Charge And Load

Experimental Study on the Performance and Oil Return Characteristics of Multi-Split Air- Conditioning System for Medium Size Building

Performance Evaluation of Heat pump System using R32 and HFO-mixed Refrigerant in High Ambient Temperature.

Study of R161 Refrigerant for Residential Airconditioning

Development Of 2-Cylinder Rotary Compressor Series For Light Commercial Use With R410A

Performance Characteristics and Optimization of a Dual-Loop Cycle for a Domestic Refrigerator- Freezer

Evaluation and Optimization of System Performance using HFO-mix Refrigerants for VRF and Mini-split Air-Conditioner

Design and Research of the Digital VRV Multi- Connected Units With Three Pipes Type Heat Recovery System

Performance Investigation of Refrigerant Vapor- Injection Technique for Residential Heat Pump Systems

Development and Performance Measurements of a Small Compressor for Transcritical CO2 Applications

Experimental Investigation on Condensation Performance of Fin-and-Flat-Tube Heat Exchanger

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) â Summary of Phase II Testing Results

Performance Characteristics of Air-Conditioner Under Tropical Ambient Condition

High Efficiency R-134a Compressor for Domestic Refrigerator

Drop-in Testing of Next-Generation R134a Alternates in a Commercial Bottle Cooler/Freezer

Compressor Capacity Control: A New Direction

Improving Heating Performance of a MPS Heat Pump System With Consideration of Compressor Heating Effects in Heat Exchanger Design

Compressor Capacity Control

Low Global Warming Refrigerants For Commercial Refrigeration Systems

Modelling of an Integrated Supermarket Refrigeration and Heating System Using Natural Refrigerants

Higher Efficiency, Lower Sound, and Lower Cost Air Conditioning Compressors: Part 1 Efficiency

Development of an Open Drive Scroll Compressor for Transportation Refrigeration

The Design Of A New Generation Of Twin Screw Refrigeration Compressors

Hunting Phenomena Of Automotive Air Conditioning Systems With Variable Displacement Compressor

Effect of Modification in Refrigerant Passage of an Automotive Air Conditioning Compressor

Comparison of Energy Efficiencies of Commercial Refrigeration Direct and Indirect Systems

Performance of CO2 Cycles with a Two-Stage Compressor

Selection of a refrigeration oil for the R32 refrigerant and evaluation of the compressor reliability

The Effect of the Ventilation and the Control Mode on the Performance of a VRV System in Cooling and Heating Modes

Load Sharing Strategies in Multiple Compressor Refrigeration Systems

Purdue e-pubs. Purdue University. T. Hamada Mitsubishi Heavy Industries Ltd. N. Nishiura Mitsubishi Heavy Industries Ltd.

A study of high efficiency CO2 refrigerant VRF air conditioning system adopting multi-stage compression cycle

Development of a Transient Simulation Model of a Freezer Part II: Comparison of Experimental Data with Model

Design and Research of the Commercial Digital VRV Multi-Connected Units With Sub-Cooled Ice Storage System

Systematic Study of the Solution Properties of Low Global Warming Potential R-404A Replacement Refrigerant Blends with Various Polyol Ester Lubricants

Development of a Novel Structure Rotary Compressor for Separate Sensible and Latent Cooling Air-Conditioning System

Numerical Evaluation of Performance Curves of a High Frequency Microcompressor

Experimental Study of Fouling Performance of Air Conditioning System with Microchannel Heat Exchanger

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Analysis of Oil Pumping in the Hermetic Reciprocating Compressor for Household Refrigerators

Performance Comparisons Of A Unitary Split System Using Microchannel and Fin-Tube Outdoor Coils, Part I: Cooling Tests

Noise Reduction Technology With Porous Metal for Refrigerant Two-Phase Flow Through the Expansion Valve

Conceptual Design of a Better Heat Pump Compressor for Northern Climates

An Experimental Investigation Of Oil Retention Characteristics In CO2 Air-Conditioning Systems

Performance Characteristics of a Refrigerator- Freezer with Parallel Evaporators using a Linear Compressor

Behavior of R410A Low GWP Alternative Refrigerants DR-55, DR-5A, and R32 in the Components of a 4-RT RTU

Effects of Frost Formation on the External Heat Transfer Coefficient of a Counter-Crossflow Display Case Air Coil

Some Modeling Improvements for Unitary Air Conditioners and Heat Pumps at Off-Design Conditions

System Modeling of Gas Engine Driven Heat Pump

Comparison of the High Side vs

Performance Characteristic and Optimization of a Simultaneous Heating and Cooling Multi Heat Pump

Sub-Critical Operation of the CO2 Expander/ Compressor

AHRI Low Global Warming Potential Alternative Refrigerants Evaluation Program (Low-GWP AREP) Summary of Phase I Testing Results

Enhancement of the Separate Sensible and Latent Cooling Air-Conditioning Systems

HSPF Calculation of a System Allowing Switching Between a Single-Stage to a Two-Stage Compression System

Application of two hybrid control methods of expansion valves and vapor injected compression to heat pumps

Experimental Investigation on the Performance of Ground-source Heat Pump with the Refrigerant R410A

Dynamic Simulation of Liquid Chillers

Experimental Investigation of a New High Temperature Heat Pump Using Water as Refrigerant for Industrial Heat Recovery

Experimental Investigation of Closed Loop Oscillating Heat Pipe as the Condenser for Vapor Compression Refrigeration

Geothermal ORC Systems Using Large Screw Expanders

Characterization of Thermal Processes in Scroll Compressors

Investigation of Evaporator Performance with and without Liquid Overfeeding

Experimental Study on the Thermal Behavior of a Domestic Refrigeration Compressor during Transient Operation in a Small Capacity Cooling System

A Performance-Enhancing Additive for Vapor- Compression Heat Pumps: Additional Test Results

Alternative Refrigerants For Household Refrigerators

An Investigation Into The Influence Of Improved Refrigeration Cycle And Refrigerants On An Energy Efficient Domestic Refrigerator

Performance Evaluation of the Energy Efficiency of Crank-Driven Compressor and Linear Compressor for a Household Refrigerator

Application Considerations of Line-Break, Internal Protectors

Experimental comparison of a cascade refrigeration system operating with R744/R134a and R744/ R404a.

Investigation, Analysis and Solution of Higher Noise of Heat Pump Water Heater

Effect of the Use Pattern on Performance of Heat Pump Water Heater

Comparison of Performance of a Residential Air- Conditioning System Using Microchannel and Finand-Tube

Performance Evaluation of a Plug-In Refrigeration System Running Under the Simultaneous Control of Compressor Speed and Expansion Valve Opening

Numerical Study on the Design of Microchannel Evaporators for Ejector Refrigeration Cycles

Tribology Characteristics of HFO and HC Refrigerants with Immiscible Oils - Effect of Refrigerant with Unsaturated Bond -

Experimental Study Of An Ejector Refrigeration System

Visualization of Evaporatively Cooled Heat Exchanger Wetted Fin Area

Low GWP Refrigerants for Air Conditioning and Chiller Applications

HEAT PUMPS WITH HYDROCARBONS AS REFRIGERANTS FOR SMALL RESIDENTIAL BUILDINGS

A New Control Approach for a Direct Expansion (DX) Air Conditioning (A/C)System with Variable Speed Compressor and Variable Speed Supply Fan

Transcription:

Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 Performance Comparison of R32, R410A and R290 Refrigerant in Inverter Heat Pumps Application Supharuek Konghuayrob Siam Compressor Industry, Thailand, supharuekk@siamcompressor.com Kornvalee Khositkullaporn Siam Compressor Industry, Thailand, kornvaleek@siamcompressor.com Follow this and additional works at: http://docs.lib.purdue.edu/iracc Konghuayrob, Supharuek and Khositkullaporn, Kornvalee, "Performance Comparison of R32, R410A and R290 Refrigerant in Inverter Heat Pumps Application" (2016). International Refrigeration and Air Conditioning Conference. Paper 1577. http://docs.lib.purdue.edu/iracc/1577 This document has been made available through Purdue e-pubs, a service of the Purdue University Libraries. Please contact epubs@purdue.edu for additional information. Complete proceedings may be acquired in print and on CD-ROM directly from the Ray W. Herrick Laboratories at https://engineering.purdue.edu/ Herrick/Events/orderlit.html

2049, Page 1 Performance Comparison of R32, R410A and R290 Refrigerant in Inverter Heat pumps application. Supharuek Konghuayrob 1*, Kornvalee Khositkullaporn 2 Siam Compressor Industry CO., LTD. 87/10 Moo2 Sukhumvit Rd., Tungsukhla Sriracha Chonburi Thailand 20230 Tel: +66-38-490900#643, Fax: +66-38-493821 1 E-mail: supharuekk@siamcompressor.com 2 E-mail: kornvaleek@siamcompressor.com *Corresponding Author ABSTRACT Since low GWP matter rise up in the market, all heat pump manufacturers are searching for the refrigerants which are attractive for environment reasons. R290 is one of the player. It has a negligible GWP but it is flammable and dangerous to apply in commercial and split type of Heat pump application. In other words, R290 has been designated for Monobloc heat pump only. Thus, R32 is an alternative refrigerant for cooling application. Flammability of R32 is 80% burning velocity less than R290 and slightly flammable when compared with R410A. Although, R32 discharge gas temperature is around 20 C higher than R410A and this can damage compressor s motor at some heat pump condition especially at high compression zone. However, Discharge superheat control (DSH) concept could be implemented in the experiment to keep temperature of discharge gas within limit of 120 C. From the results, R32 has better heating performance 6% for BTW and 12% in ATW application when compared with both R410A and R-290. Consider to the refrigerant properties, the changing of R410A to R32 can keep compressors stoke volume. Meanwhile 57% stoke volume increasing of R290 must be implemented to keep the same capacity level, Consequently R32 is the candidate refrigerant for heat pump application when DSH control has been applied. 1. INTRODUCTION Due to environmental reasons the heat pump manufacturer interested in GWP matter. Apart from the GWP reduction, the system s efficiency is also important. R32 is one of the candidates to make an environmentally - friendly heat pump because the lower GWP is one of the characteristics of R32. However, when focusing on discharge temperature of R32, this might be a problem if it is applied in heat pump application because of discharge temperature characteristic

2049, Page 2 As the high pressure shell type compressor can compress some small liquid portion at suction side (SSH = 0), the changing of expansion valve control from suction superheat to discharge superheat can be possible. This can also control discharge temperature lower than compressor s limitation. Therefore, the changing of control by discharge superheat with electronic expansion valve (EEV) can be applied with high pressure shell type compressor which using R32 in heat pump application. By discharge superheat control concept, not only we can find the benefit of efficiency improvement but we can also apply R32 in heat pump application without the over limit problem of discharge temperature. 2. SYSTEM CONFIGURATION The schematic diagram of heat pump with discharge superheat (DSH) control is shown in Figure 1. The system used electronic expansion valve (EEV) to control discharge superheat (DSH) by using Pd and Td for refrigerant flow adjustment. Figure 1 : The schematic diagram of heat pump with DSH control. Figure 2 : The schematic diagram of heat pump with SSH control. Figure 2 shows the system used suction superheat control (SSH). Thermostatic expansion valve (TXV) controls suction superheat by using Ps and Ts at ~5 K (R410A). SCOP of the system can be calculated by equation (1) SCOP = Q H/Q HE (1) Q H is the reference annual heating demand, calculated as equation (2) Q H = PD*HH (2)

2049, Page 3 Discharge superheat is calculated by Td and Pd as equation (3) DSH = Td-Tsat (at Pd) (3) Figure 3 shows P-h diagram with DSH which can be calculated from equation 3. Figure 3: P-h diagram Suction superheat was calculated by Ts and Ps as equation (4) SSH = Ts Tsat (at Ps) (4) This experiment considered 3 refrigerants. The focusing refrigerants were R410A, R290 and R32. All of them have different properties as shown in table 1. Table 1 : Refrigerant properties comparision.

2049, Page 4 3. EXPERIMENTAL UNIT AND TESTING CONDITION 3.1 Type of testing unit There are several types of heat pump unit in the market. This experiment only focused on the most famous heat pumps in the market that concern with environmental policy and efficiency standard following SCOP regulation at average zone. 3.1.1 Brine to water heat pump. For experimental unit for Brine to water heat pump, the evaporator and condenser were plate heat exchangers. The compressor was a high pressure shell type hermetic scroll compressor. Expansion valve control was controlled by discharge superheat. Environmental temperature was around 30 C. The testing condition follow EN14825 is shown in Table 2. Table 2 : Test temperature for Brine to water heat pump : Under floor heating 3.1.2 Air to water heat pump. For experimental unit for Air to water heat pump. The condenser was a plate heat exchanger. The evaporator was an air type heat exchanger. The compressor was a high pressure shell type hermetic scroll compressor. Expansion valve control was controlled by discharge superheat. The testing condition follow EN14825 is shown in Table 3. Table 3 : Test temperature for Air to water heat pump : Under floor heating 3.2 Type of compressor Inverter driven scroll compressor with high pressure shell type was fixed with this experiment. There are different stroke volume but almost the same capacity level at rated condition. The specification is shown in table 4.

2049, Page 5 Table 4 : Specifiaction of refrigerant compressor comparision 4. TEST RESULTS 4.1 Refrigerant charge amount The suitable refrigerant charge amounts compared between each refrigerant were confirmed at various compression ratio (Pd/Ps), from the shown results when discharge superheat control was implemented, refrigerant charge amount by discharge superheat control was increased when compared with suction superheat control up to 6.3% for R32, 13.5% for R290 and 10.9% for R410A. 4.1.1 Brine to water heat pump Figure 4-6 show the refrigerant charge amount by varying compressor s compression ratio. (Pd/Ps) Figure 4: Testing result of BTW Heat Pump with R290 Figure 5: Testing result of BTW Heat Pump with R32

2049, Page 6 Figure 6: Testing result of BTW Heat Pump with R410A Figure 7: Refrigerant quantities at design condition for BTW Figure 7 shows the suitable refrigerant quantities of Brine to water at design condition follow SCOP regulation. 4.1.2 Air to water heat pump Figure 8-10 show the refrigerant charge amount by varying compressor s compression ratio (Pd/Ps). Figure 8: Testing result of ATW Heat Pump with R290 Figure 9: Testing result of ATW Heat Pump with R32

2049, Page 7 Figure 10: Testing result of ATW Heat Pump with R410A Figure 11: Refrigerant quantities at design condition for ATW Figure 11 shows the suitable refrigerant quantities of Air to water at design condition follow SCOP regulation. 4.2 Discharge superheat set point The optimum DSH value was related with Compression ratio (Pd/Ps) of compressor as shown in figure 12-13. Figure 12: Discharge superheat set point for BTW Heat Pump Figure 13: Discharge superheat set point for ATW Heat Pump 4.3 Discharge temperature When discharge superheat control was applied, the discharge temperature could be controlled under the compressor limit at 120 C by expansion valve adjustment. Figure 14-15 show the relation between compression ratio (Pd/Ps) and discharge temperature of R410A, R290 and R32 when they were controlled by discharge superheat.

2049, Page 8 Figure 14: Test result of discharge temperature with discharge superheat control for BTW Figure 15: Test result of discharge temperature with discharge superheat control for ATW Figure 16 17 show the relation between compression ratio (Pd/Ps) and discharge temperature of R410A, R290 and R32 when they were controlled by suction superheat. At high compression ratio condition, discharge temperature of R32 was over than compressor limitation. Figure 16: Test result of discharge temperature with suction superheat control for BTW Figure 17: Test result of discharge temperature with suction superheat control for ATW 4.4 Unit performance When discharge superheat control was applied, R32 was comparable with another alternative refrigerant in heat pump application without any restriction of high discharge temperature. The comparison of performance follow EN14825 in average zone is shown in figure 18 19.

2049, Page 9 Figure 18: Performance comparison of BTW heat pump when discharge superheat control has been applied Figure 19: Performance comparison of ATW heat pump when discharge superheat control has been applied Figure 20 shows SCOP in average zone, from the testing results, R32 could improve 6% of SCOP when compared with R410A in Brine to water system, and 12% improvement in Air to water system. Meanwhile, R290 cannot improve SCOP level when compare with R410A Figure 20: SCOP comparison in average zone 5. CONCLUSION In this experiment, it was shown that the performance comparison between R410A R290 and R32 in heat pump application, which were controlled expansion device by discharge superheat. 1. For Brine to water system, the SCOP improvement of R32 when compared with R410A is 6% and 12% for Air to water system. 2. SCOP of R290 is same level as R410A in Brine to water system and 6% of SCOP lower than R410A in Air to water system. 3. The stroke volume of compressor, which was using R32 could be reduced when compared with the same capacity level of compressor which using R410A. 4. R32 can be applied in heat pump application when discharge superheat control has been implemented.

2049, Page 10 NOMENCLATURE SSH Suction Superheated Subscripts DSH Discharge Superheated d Discharge HCOP Heating Coefficient of Performance s Suction SCOP Seasonal coefficient of performance sat Saturated BTW Brine to Water H reference annual heating demand ATW Air to Water HE seasonal electricity consumption HP EEV TXV P T PD Q HH Heat Pump Electronic Expansion Valve Thermostatic Expansion Valve Pressure (MpaG) Temperature (Celsius) Design load for heating (kw) Power (kwh) Equivalent active mode hours for heating (hrs) REFERENCES Willbert F.Stoecker / Jerold W.Jones. (1982). Refrigeration and Air Conditioning, Chapter 13, Expansion Devices, McGraw-Hill Inc, P.260-280 Stavros DIMAS. (2007). Establishing the ecological criteria for the award of the Community eco-label to electrically driven, BTW&ATW HP Testing Condition, P. 4-5 Siam Compressor Industry. (2002). General Specification of Scroll Compressor, VHIK-71676 revised F, Maximum Discharge Temperature, P.2 Tanawitayakorn Wasan / Phrajanpanich Paisarn / Siwapornphaisarn Supot. (2012). Heat Pump Efficiency Improvement by Discharge Superheated Control, International Refrigeration and Air Conditioning Conference at Purdue 2012, P.2 Siam Compressor Industry. (2010). Discharge Superheat Control Guideline, TDCS10D045 revise A, P.1