Guidance Note. Fire Alarm Detector Applications and Documentation of the Selection

Similar documents
Guidance Note. Guidance Document on Best Practice for Fire Detector Testing/Test Equipment

Guidance on Video Smoke Detection Technology (VSD)

Fact File 48 Guide to BS EN 54-13:2017 Fire Detection and alarm systems:

Guidance Note. Visual Alarm Devices: Conflict between BS 5839 and EN 54-23

Fact File 46 Guidance to recyclers on treatment of domestic ionisation chamber smoke detectors (ICSD)

Guidance Note FIA Application Guidance on BS :2015

BS 5839: Part THE CHANGES

FIA Guidance on Manual Call Point - Protection - False Alarm Mitigation

Environmental Guidance Foam Fire Extinguishers

Watermist Fire Protection of Plant Rooms

Fact File 69 Fire Detection & Alarms

Additional Requirements for Watermist Systems Protecting High-rise Buildings

Fact File 75. Published Document PD CEN/TS 54-32:2015 Fire detection and fire alarm systems

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS Standard

Code of Practice for Design, Installation, Commissioning & Maintenance of Duct Smoke Detector (DSD) Systems

Environmental Guidance Fire Fighting Powder and Powder Fire Extinguishers

Fact File 66. Guide to Beam Smoke Detectors

Fact File 78. Portable Fire Extinguishers under the ADR. Note: This Fact File supersedes Fact File 060 which is withdrawn

Secretary of State determination under article 36 of the Fire Safety Order

Fact File 39 Environmental Guidance

Research into multi-sensor detector capabilities and false alarm reduction

Fire precautions in dwellings

Tudor House, Kingsway Business Park Oldfield Road, Hampton, Middlesex, TW12 2HD Phone: +44 (0) Website: EQUALITY ACT 2010

Fire Alarm Systems Design. incorporating Amendment No.2. a guide to BS5839. Part1:2002

Unwanted Fire Alarms. Marty Ahrens National Fire Protection Association 1 Batterymarch Park Quincy, MA (617)

Farms and Similar Agricultural Facilities

Fact File 15 Ionisation Chamber Smoke Detectors and The Radioactive Material (Road Transport) Regulations 2002

Notifier by Honeywell: SMART Detection. SMART Detection. The Ultimate in False Alarm Technology...Make the SMART choice

False Alarm Management. Graham Simons FIA Technical Manager

Fire Safety Register

Tudor House, Kingsway Business Park Oldfield Road, Hampton, Middlesex, TW12 2HD Phone: +44 (0) Website:

Fire Risk Assessment 2017

SAQCC FIRE D&GS TRAINING SUB COMMITTEE COURSE CURRICULUM

LITTLE BLACK BOOK. of Fire Detection and Alarm Systems

B16008-R0-160RC SERIES-U&C 17/1/07 11:13 AM Page Installation Guide

The Social Accountability International (SAI) Fire Safety Checklist

USER MANUAL 10 YEAR LIFE SMOKE ALARM

AIR CURTAIN GUIDE WHAT IS AN AIR CURTAIN?

Logbook. Precept EN Fire Detection/Alarm Panel. & Precept EN Repeater

5 Key Stages to Risk Assessment

Fire Safety Guidance 2. Health & Safety 4. The following guidance is intended to supplement the QMUL procedures.

For the Design, Installation, Commissioning & Maintenance of Fire Detection and Fire Alarm Systems

Consultant Specification AGILE Wireless Fire Detection System

TX7100. Intelligent Addressable Optical Smoke Detector Installation and Operation Manual. TANDA UK Technology Copyright 2015, All right reserved.

Unit 2 Fire Safety (Zone 1)

False Alarm Management

False Alarm Management

200 SERIES ADVANCED PHOTO/THERMAL/IR DETECTOR PRODUCT SPECIFICATION

Fire Risk Assessment. Do-it-Yourself ekit. Guidance Manual

Early Warning Fire Detection Engineering

Availability, Reliability, False Alarm Resistance Best Practice in Fire Alarm Systems. FIRE PROTECTION OF ROLLING STOCK 2 rd March 2017

Directories. B.1 Keyword Directory B.2 Tables B.3 Figures B.4 End Notes Fire Safety Guide / Siemens Switzerland Ltd

IQ8Quad. The right sensor for every environment. The detection principles of the IQ8Quad detector. Fire detection technology

Multi-Point Peripherals

ED820-24V MODEL INSTRUCTION MANUAL. fire DETECTOR

Where EXCESSIVE reduce the number of ignition sources such as: ACTIONS TAKEN/TO BE TAKEN:-*

Replacing a consumer unit in domestic premises where lighting circuits have no protective conductor

UBS1RF OPTICAL SMOKE ALARM EN 14604:2005/AC:2008 DOP:UBS1RF-001-V1

Datasheet CALYPSO II R. Interlinkable smoke alarm device

For the Design, Installation, Commissioning & Maintenance of Fire Detection and Fire Alarm Systems

Guidance Note. Guidance Document for Testing and Maintaining Self-Contained Emergency Lighting and Luminaires

BS 5839 Part 1 : 2013 Changes. By Don Scott

Dispute over the requirement for fire door signage to hotel suites at 124 Devon Street West, New Plymouth

Facilities and Estates. Hot Works: Standard Operating Procedure. Document Control Summary

Fire Procedures. April 2016

Millfield Schools Fire Risk Prevention Policy

ISO/TS TECHNICAL SPECIFICATION. Fire detection and alarm systems Part 9: Test fires for fire detectors

RELIGIOUS, FESTIVAL & OTHER DECORATIONS - FIRE SAFETY GUIDANCE

ISO INTERNATIONAL STANDARD

The new detector from Rafiki

Loss Prevention Standards

HME09 NATURAL VENTILATION

Health and Safety Policy. Version Author Revisions Made Date 1 Colin Campbell First Draft March 2014

The Route to Third Party Certification

Sandwell Valley School and Sandwell Community Care Trust Training. 150 Birmingham Road, West Bromwich, B70 6QT

A Guide To BS Understanding the selection, spacing and siting of detectors

FIRE RISK ASSESSMENT Self Assessment

Construction Products Regulation (CPR) Update. Graham Simons Technical Manager, FIA

FIRE RISK ASSESSMENT

COMITÉ EUROPÉEN DES ASSURANCES

Wireless Interlink Smoke Alarm + 10 Year Life

FIRE ALARM SOLUTIONS THAT FIT YOUR NEEDS

Fire Safety Logbook. FOLLOW the regulations. MANAGE fire risks. RECORD relevant checks

TYPE 1 FIRE RISK ASSESSMENT REVIEW (NO DESTRUCTIVE AUDIT)

AGT 1 Confined Space. Authorised Gas Tester 1. Scienco Limited. Authorised Gas Tester 1 1

Aspirating Detection System. Protec Aspirating Detection System Atria Design Guide. MED2199 Atria Design Guide Issue 0 Page 1 of 22

British Columbia Building Code 2006 Division B Part 3 Fire Protection, Occupant Safety and Accessibility Section 3.2 Building Fire Safety

Intelligent Detection Devices

Guidance Document on Caravan and Camping Sites Fire Safety Equipment Requirements

SPEED, STABILITY, & RELIABILITY N EW! IntelliQuad TM PLUS Combination Smoke and Carbon Monoxide (CO) Detector

Fire Safety Policy (Communal Areas)

Smoke Alarm and Carbon Monoxide Alarm Installation

LOG BOOK & CERTIFICATES

Type of Fire Alarm Control Panel: System is: Existing OR New If new, provide Electrical Permit Number:

Aspirating Detection System. Protec Aspirating Detection System Lift Shaft Design Guide. MED2198 Lift Shaft Design Guide Issue 0 Page 1 of 23

ISO INTERNATIONAL STANDARD. Fire detection and alarm systems Part 20: Aspirating smoke detectors

Desigo Fire Safety intelligent detectors for complete safety

Radar technology in surveillance

½ CAUTION ½ DANGER. Getting to know the smoke detector. ARGUS Smoke Detector Single. Accessories. Operating instructions. For your safety A B C D E

HEC CAMPUS RESIDENTIAL HOUSING FORM 2017 Summer School Programs

Transcription:

Guidance Note Fire Alarm Detector Applications and Documentation of the Selection

Fire Alarm Detector Applications and Documentation of the Selection INTRODUCTION... 3 FLOW CHART FOR THE SELECTION OF... 4 DETECTOR AND APPLICATION VERIFICATION DETECTOR SELECTION TABLE... 5 NOTES FOR ASSISTANCE WITH COMPLETION... 6 OF THE DETECTOR SELECTION TABLE 2 of 8

INTRODUCTION During the design of a fire system, consideration is given to the fire risk(s) and the false alarm risk(s). Fire detectors are selected depending on the nature of the protected area and the risks associated with it. Often, this involves utilising different fire detector technologies in order to meet the diverse needs of both fire and false alarm in each scenario. Single-sensor detectors (eg optical smoke detector, heat detector) are suited to the of certain fire risks. Selection choices need to be made carefully to optimise the of fire but minimise the occurrence of false alarms. The deployment of multi-sensor detectors means that the system could potentially detect fires earlier and yet avoid troublesome false alarms to a greater extent too. The choices and decisions concerning which detector types to use, are initially made during fire system design but are also sometimes re-visited, and even modified, during commissioning and/or maintenance. They are not always well recorded nor is the rationale behind them. At a later time, for example during a maintenance visit, this can give rise to confusion. A clear understanding of the original reasons behind the choice of detectors and how they are configured is needed, in order to verify continued suitability. Aside from multi-sensor detectors, a visual inspection of a fire detector can often provide sufficient information to a maintenance technician, to allow in-situ functional testing to be undertaken (eg in the case of a smoke detector or a heat detector). However, in the case of multi-sensors, the type of employed within it and its settings, modes or specific configuration which govern its performance to the risk, are not apparent from a visual inspection. This information may not even be available from the CIE. In all cases, however, there remains the need to know the principles and to understand the reason for the choice of that, relative to the risks perceived in the protected area. This document is intended to assist with the task of selecting and clearly recording the type, sensitivity and settings selected for all detectors, including multi-sensor detectors, relating to the perceived risks. A Detector Selection Table is shown below in this document. It is a template to allow the documentation of the main risks and all decisions and reasoning behind the choices made, either during system design or at the time of any subsequent change to the fire. It is intended to assist designers, commissioning engineers and service/maintenance technicians, to keep good records of their choice decisions and rationale. A flowchart is also provided below, which demonstrates the process of detector choice and is provided as a guide for completing the Detector Selection Table. The notes shown after the table give further guidance on its completion, including reference to relevant recommendations within BS 5839-1. 3 of 8

FLOW CHART FOR THE SELECTION OF DETECTOR AND APPLICATION VERIFICATION 4 of 8

Record the responses to the questions in the flowchart in this Detector Selection Table (for guidance on completion of this table, see notes 1-11 below): DETECTOR SELECTION TABLE Protected area/ Predominant use Fire risk(s) 3 False alarm risk(s) 4 Detector type 5 Detector Certificated type of area 1 of area 2 setting 6 mode(s) chosen? 7 Acceptable to interested parties? 8 Fire strategy met? 9 Detector type/ setting choice rationale 10 Comments/ action 11 Hotel bedroom en-suite Hotel bedroom non en-suite Hotel suite Bedroom dormitory style Office cellular Office open plan Kitchen (main) Kitchenette Restaurant/ Canteen Corridor Escape route Reception area Lobby Workshop (clean) Workshop (moderate) Workshop (dirty) Warehouse/ storage Sleeping Cooking Unoccupied Storage nonflammable Storage flammable General office work Meetings Circulation route Escape route Manufacturing Manufacturing (hot works) Assembly white smoke dark smoke changing to flaming Flaming (clean burn) Flaming (dirty) None Steam Toaster Oven usage Cooking Dust Smoking Aerosol spray Hot works Optical Heat (static) Heat (RoR) Ionisation Multisensor: Optical/heat Heat/CO Optical/CO Optical/heat/ CO Optical beam Linear heat ASD Class C ASD Class B ASD Class A Flame Video CO Please detail of detector setting(s) Choose from: Yes No Choose from: Yes No then Choose from: Yes No then Please in detail Details as appropriate 5 of 8

NOTES FOR ASSISTANCE WITH COMPLETION OF THE DETECTOR SELECTION TABLE 1. Protected area should be related to the system category as defined in BS 5839-1:2017, clause 5. In the case of time-related settings (eg day/night mode), a new selection process should be undertaken and recorded for each setting. 2. Anticipated use(s) of the protected area does not need to be an exhaustive list but should cover the main use(s). 3. Risks anticipated in the protected area. This can either be described as the fire type or in terms of the expected causes of fire. Only the main fire risks need to be identified in the Detector Selection Table this need not be an exhaustive list. To assist in completion of the fire risks column in the Detector Selection Table, the following summary of individual sensor performance (as found within point type fire detectors) is provided. It also shows some indication of how a typical multi-sensor detector can be used to improve. EXAMPLE FIRE RISKS Fire risk key: very good = good = moderate = poor = very poor = Fire risk white smoke dark smoke changing to flaming Flaming (clean burn) Flaming (dirty) Example fire(s) Ionisation Optical (scatter) CO Heat Flame Typical multisensor, eg opticalheat* Typical multisensor, eg optical-heat- CO* Electrical fire wood furnishings Waste paper bin fire Burning solvents Burning oils The performances indicated in the above table apply to single-sensor detectors unless otherwise stated. *Multi-sensor detector responses could be a combination of the single-sensor responses, but the behaviour of a multi-sensor will be dependent on the manner in which the sensors are combined within the detector. The combination of sensors within a multi-sensor detector could provide an enhancement to performance overall and cannot be considered to be the linear sum of the individual sensor responses. The response of multi-sensors will not be common across all detector manufacturers, due to differences in construction and internal algorithms. The response of a chosen multi-sensor, including its mode and settings, should be properly understood to ensure that the risks are adequately covered. This table shows some typical examples of multi-sensor responses and does not represent an exhaustive list of all possible sensor combinations and algorithms. 4. Only the predominant false alarm risks need to be identified in the Detector Selection Table this does not need to be an exhaustive list. These should be described in terms of the expected causes of false alarms. See clause 35 of BS 5839-1:2017 for assistance with selection of detector types for the minimisation of false alarms. 6 of 8

To assist in completion of the false alarm risks column in the Detector Selection Table, the following summary of typical causes of false alarms and how individual sensors respond to them is provided. It also shows some indication of how a typical multi-sensor detector can be used to improve false alarm. EXAMPLE FALSE ALARM RISKS False alarm risk key: very good = good = moderate = poor = very poor = False alarm risk Example false alarm cause Ionisation Optical (scatter) CO Heat Flame Typical multisensor, eg opticalheat** Steam Shower or bathroom Smoke Smoking, kitchen/ cooking fumes Dust Warehouse Other particulate Sparks/naked flames Substance ingress High ambient airflow Rapid thermal change Aerosol canister products, artificial smoke Welding Insects Typical multisensor eg opticalheat-co** Airconditioning, open doors/ windows Opening of ovens **Multi-sensor detector responses could be a combination of the single-sensor responses, but the behaviour of a multi-sensor will be dependent on the manner in which the sensors are combined within the detector. The combination of sensors within a multi-sensor detector could provide an enhancement to performance overall and cannot be considered to be the linear sum of the individual sensor responses. The response of multi-sensors will not be common across all detector manufacturers due to differences in construction and internal algorithms. The response of a chosen multi-sensor, including its mode and settings, should be properly understood to ensure that the risks are adequately covered. This table shows some typical examples of multi-sensor responses and does not represent an exhaustive list of all possible sensor combinations and algorithms. 5. See BS 5839-1:2017, clause 21, for further information on types and their selection. 6. Different detector settings may include various response speeds, delays, variations of sensor performance, sensitivity of alarm level, etc. Other risks (eg evacuation strategy/timescales) should be considered when choosing these settings. 7 of 8

7. Some detectors may have modes of operation which are not certificated to the relevant EN 54 standards. These modes should be avoided if at all possible but where such modes are used, that decision should be agreed in writing by all interested parties following a fire risk assessment, noted here and explained in the rationale in the Detector Selection Table. Information concerning noncompliance of a specific mode has to be provided by the manufacturer, by clearly marking the detector or within the associated data (as per EN 54 standards, On-site adjustment of response behaviour). 8. Refer to BS 5839-1, clause 6, for the definition of relevant interested parties. 9. The implications of future changes to the type or setting must be understood and continue to support the Fire Strategy. 10. The reasoning behind decisions concerning the choice of detector technology, type, setting, sensitivity, etc should be given here. 11. Any additional, relevant information concerning the detector selection should be given here, including required or agreed actions. DISCLAIMER The information set out in this document is believed to be correct in the light of information currently available but it is not guaranteed and neither the Fire Industry Association nor its officers can accept any responsibility in respect of the contents or any events arising from use of the information contained within this document. Tudor House, Kingsway Business Park, Oldfield Road, Hampton, Middlesex TW12 2HD Tel: +44 (0)20 3166 5002 www.fia.uk.com 8 of 8