Test Report No. AJD Date: JUN.09, 2013 Page 1 of 6

Similar documents
Test Report No. AJFS FF Date: OCT.17, 2018 Page 1 of 6

CAN/ULC-S102 Surface Burning Characteristics of "8 mm Fire Rated High Pressure Laminate Phenolic Panel"

CAN/ULC-S102 Surface Burning Characteristics of "ezobord 9 mm (Green)"

CAN/ULC-S102.2 Surface Burning Characteristics of "16 mm Multiwall Polycarbonate"

TEST REPORT. Report No.: D Rendered to: 3M COMPANY St. Paul, Minnesota

CAN/ULC-S102 Surface Burning Characteristics of "Digitally Printed Aluminum Siding" Coated Aluminum

TEST REPORT. Report No.: E Test Date: May 6, Rendered to: FUNDERMAX GMBH A-9300 St. Veit an der Glan, Austria

We Identify and S.T.O.P. Your Noise Problems

SIGMADEK, LTD. FIRE TEST REPORT

ASTM D Horizontal Burning Rate Determination of "Marlon FS 1.5mm Clear" Polycarbonate Sheet

FUNDERMAX GMBH FIRE TEST REPORT

FABRITRAK SYSTEMS, INC. FIRE TEST REPORT

REPORT NUMBER: SAT-001B ORIGINAL ISSUE DATE: February 29, 2016 REVISED DATE:

Report Of Surface Burning Characteristics Tests On PVC Sheeting As Submitted By Jain (Americas) Inc.

Report Of Surface Burning Characteristics Tests On Felt Material As Submitted By Rieke Office Interiors

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Tile-diy LLC

EnviroScape Mural. pre-pasted printable wallcovering material. Choose your GREEN resource from a leading solutions provider.

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Ebrille SRL

Contents: 4. Report of Surface Burning Characteristics Tests on LP FlameBlock/BlazeGuard (30-minute test) Updated April, 2010

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Railtech Ltd.

Report Of Surface Burning Characteristics Tests On Coated Louvered Door Panels As Submitted By Contego International Inc.

TEST REPORT EVALUATION CENTER Intertek Testing Services NA Ltd Brigantine Drive Coquitlam, B.C. V3K 7C1

Report of Surface Burning Characteristics Test on Acoustical Panel

Report Of Surface Burning Characteristics Tests On Samples As Submitted By Textures 3D

Report of Surface Burning Characteristics Tests on Samples As Submitted By Jotun UAE Ltd (LLC)

Report of Surface Burning Characteristics Tests on Skyfold Panel Samples As Submitted By Railtech Ltd

Acoustical Surfaces, Inc.

Report Of Surface Burning Characteristics Tests On Fire Retardant Coating As Submitted By Contego International

RENDERED TO. Radial Engineering Limited 1588 Kebet Way Port Coquitlam, B.C. V3C 5M5

Report of Surface Burning Characteristics Tests on Samples As Submitted By Eco-Sol Ltd

ASTM E84-99 ADHERED SURFACE BURNING CHARACTERISTICS

The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318

RENDERED TO. Laminam S.P.A. Via Ghiarola Nuova Fiorano Modenese Italy

Test Report No. AJHG FB Date: FEB.17, 2015 Page 1 of 13

RENDERED TO Vipco Industries Inc th Avenue SE Calgary, AB T2C 0B3

UL Test Methods for Determining the Combustibility Characteristics of Plastics Used in Semiconductor Tool Construction. General Information

Tech Notes. TESTING PROTOCOL Fire Retardant Gel Coats. INTERPLASTIC CORPORATION Thermoset Resins Divison ISSUE 5

Public Comment No. 2-NFPA [ Section No ]

Test Report: ICL/H18/9039 Rev 1

FIRE RETARDANT ARCHITECTURAL WOOD COATING FIRE SHIELD FS020 FIRE-SHIELD SEALER. FS021 FIRE-SHIELD TOP COAT Available in different gloss

PERFORMANCE TEST REPORT. Rendered to: VELUX America, Inc. PRODUCT: SUN TUNNEL Acrylic Dome

Materials Testing by Gregory Havel

TEST REPORT. Contact No: SAMPLE NOT DRAWN BY OUR LABORATORY. THE RESULTS RELATE ONLY TO THE ITEMS TESTED

C-01 FIRE DECKS AND BULKHEADS

BS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 28 th April Test Sponsor: Tapco Europe Limited

Test Report: ICL/CR15/11/087

BS EN ISO : Fire Tests For Determination Of The Burning Behaviour of Floorings. WF Report Number. Date: 16 th November 2009.

BS EN ISO : 2010

PERFORMANCE TEST REPORT. Rendered to: PALRAM AMERICAS, INC. PRODUCT: Clear Palsun TYPE: Polycarbonate

ASTM E 84 Surface Burning Characteristics of "12 mm Stratificato Panel"

Classification of Fire Performance of Wall and Ceiling Lining Materials

M E M O R A N D U M. Diane Matthews, Administrator, Technical Projects. NFPA 101 First Draft Letter Ballot (A2014)

BS EN ISO : 2010

GUARDIAN FIRE TESTING LABORATORIES, INC.

PERFORMANCE TEST REPORT. Rendered to: EVERBLOCK SYSTEMS, LLC. PRODUCT: Modular Block Product

Forbo Flooring Attn. Mr. A. Tijhof Postbus AA Krommenie. Report. Sponsor : Contractor, manufacturer : Forbo Flooring. Lot. No. : 66869/3877.

Report on Public Input June 2014 NFPA 101

BS EN 13823: A Report To: Contra Vision. Document Reference: Date: 25 th November Issue No.: 1

BS EN ISO 1716: Determination Of The Heat Of Combustion For Building Products

Safety Code Users. Fire Tests for Life SUPPLEMENT 3. Marcelo M. Hirschler FIRE PROPERTIES

BS EN ISO : 2010

Fire Risk and CODE Compliance For Fabric Wrapped Acoustic Panels

Classification of reaction to fire performance in accordance with BS EN : A1: 2009 on Sandwich Panel, WP 50.

Public Comment No. 1-NFPA [ Section No ]

BCTC CARPET TECHNICAL CENTRE

BS 476: Part 3: External Fire Exposure Roof Test. WF Report Number: Date: 13 th October Test Sponsor: Tapco Europe Limited

Title: Indicative fire test. WF Report No: /A. Prepared for: Hoody Speaker Hoods Ltd

NF X : Parts 1, 2, 3, 4 & 5

Resolution: FR-2-NFPA Statement: The new language requires the action completed by NFPA 557 be prepared by a person that is approved.

BS 476: Part 6: 1989+A1:2009

Contact person Date Reference Page Richard Johansson P (2) Fire Research

BS 476: Part 6: 1989+A1:2009

TEST REPORT. NFPA 253 / ASTM E648-14c Standard Test Method for Critical Radiant Flux of Floor-Covering Systems Using a Radiant Heat Energy Source

CERTIFICATE OF APPROVAL No CF 5236 EMVER PAINTS INDUSTRIES LLC

CPD Seminar: Importance of Reaction-to-Fire Properties of Materials: Combustibility, Spread of Flame and Smoke Generation

BS EN : 2001 & IEC :2000

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC

RetardantsInc. The Decision You Make May Save A Life! 123 Columbia Court North Suite 201 Chaska, MN 55318

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

Review Fire Test Report

FACADES AND FIRE The Essential Elements

PRODUCT PERFORMANCE TEST REPORT. Report No.: D Test Date: May 29, Rendered to: Natural Light Energy Systems Phoenix, Arizona

1.0 INTRODUCTION. Shaw Industries Group 2 SwRI Project No c

Contents Page No. Page 1 of Introduction Specimen verification Description of supporting constructions...

IMO Resolution MSC 61 (67) 1996; Annex 1, Part 2. Smoke & Toxicity Test. WF Report Number: Date: 13 th August Test Sponsor:

In Search of Standard Reference Materials (SRMs) for ASTM E05 Fire Standards by. Norman Alvares & Harry Hasegawa

BS EN 13823: A Report To: Durabuild Technologies Pvt. Limited. Document Reference: Date: 22 nd February Issue No.

IEC Method of test defined in IEC / -21 for determining the circuit integrity of electric cables under fire conditions

Report on the Fire Testing of a Roofing System with a Synthetic Underlayment in Accordance with ASTM E a. Trinity ERD Columbia, SC

Heat and Smoke Release of a Ceiling-Installed Speaker

Fire Test Methods ASTM NFPA UL ISO IEC

Ceramic Fiber Heaters

BS EN : Measurements Of Smoke Density Of Electric Cables. WF Report Number. Date: 17 th November Test Sponsor:

CLASSIFICATION OF REACTION TO FIRE PERFORMANCE IN ACCORDANCE WITH EN :2007+A1:2009

IMO Resolution MSC 61(67): Annex 1: Part 2

Ad-hoc IEC Ad-hoc investigation to determine the fire performance of a cable junction box, using the principles of IEC

BS 476: Part 7: 1997 on K-Flex IN Clad Foil. Prepared for: L'Isolante K-Flex Srl Via Leonardo da Vinci, RONCELLO (MB) Italy

Fire Testing of Foams

Flame Retardant Polyethylene Tubing

New European Fire Testing Classification for Construction Products

Transcription:

Test Report No. AJD201302471 Date: JUN.09, 2013 Page 1 of 6 WALER PRECISION MFG. SDN. BHD. NO.2, JALAN CANGGIH 1, TAMAN PERINDUSTRIAN CEMERALNG, 81800 ULU TIRAM, JOHOR, MALAYSIA. The following sample(s) was / were submitted and identified on behalf of the client as: Sample Description: WALL CLADDING PROFILE Type/Style: CP 140 Density: 1.55 Thickness: 13mm Composition: FIBER PVC COMPOSITE Part No.: CP140 / RESCP120612 Supplier: WALER PRECISION MFG. SDN. BHD. Buyer: RESYSTA NORTH AMERICA Manufacturer: WALER PRECISION MFG. SDN. BHD. Country of Origin: MALAYSIA Country of Destination: USA Test Requested: To determine the flame spread index (FSI) and smoke-developed index (SDI) of the sample s surface burning characteristics when it is subjected to the conditions of specified in ASTM E84-12a Standard Test Method for Surface Burning Characteristics of Building Materials Test Results: -- See attached sheet -- Test Period: Sample Receiving Date : MAY.16, 2013 Test Performing Date : MAY.16, 2013 TO JUN.09, 2013 Signed for and on behalf of SGS-CSTC Co., Ltd. Allen Zou Technical Supervisor

Test Report No. AJD201302471 Date: JUN.09, 2013 Page 2 of 6 I. TEST CONDUCTED This test was conducted in accordance with ASTM E84-12a Standard Test Method for Surface Burning Characteristics of Building Materials. II. INTRODUCTION The method, designated as ASTM E84-12a, "Standard Method of Test for Surface Burning Characteristics of Building Materials", is designed to determine the relative surface burning characteristics of materials under specific test conditions. Results are expressed in terms of flame spread index (FSI) and smoke developed index (SDI). The purpose of this test method is to determine the relative burning behavior of the material by observing the flame spread along the specimen. Flame spread and smoke developed index are reported. However, there is not necessarily a relationship between these two measurements. III. TEST PROCEDURE The tunnel is preheated to 150 F, as measured by the floor-embedded thermocouple located 23.25 feet downstream of the burner ports, and allowed to cool to 105 F, as measured by the floor-embedded thermocouple located 13 feet from the burners. At this time the tunnel lid is raised and the test sample is placed along the ledges of the tunnel so as to form a continuous ceiling 24 feet long, 12 inches above the floor. The lid is then lowered into place. Upon ignition of the gas burners, the flame spread distance is observed and recorded every 15 seconds. Flame spread distance versus time is plotted ignoring any flame front recessions. If the area under the curve (A) is less than or equal to 97.5 min ft, FSI = 0.515 A; if greater, FSI = 4900/(195-A). Smoke developed is determined by comparing the area under the obscuration curve for the test sample to that of inorganic reinforced cement board and red oak, arbitrarily established as 0 and 100, respectively. IV. CONDITIONING Prior to testing, the sample was conditioned, To a constant weight at a temperature of 73.4±5 F (23±2.8 C) and at a relative humidity of 50±5%

Test Report No. AJD201302471 Date: JUN.09, 2013 Page 3 of 6 V. SAMPLE DETAILS The details of the tested specimen given below have been prepared from information provided by the sponsor of the test. All values quoted are nominal, unless tolerances are given. Name WALL CLADDING PROFILE Color / Density Brown / About 8.6kg/m 2 Exposed face: The front face MOUNTING METHODS: The specimen was self-supporting and was placed directly on the inner ledges of the tunnel. The specimen consisted of 12 pieces of 175mm wide 1835mm long 13mm thickness and all sections jointed end-to-end. TEST RESULTS FSI SDI 0 45 RATING: The National Fire Protection Association Life Safety Code 101, Chapter 10, Section 10.2.3 Interior Wall and Ceiling Finish Classification, has a means of classifying materials with respect to Flame Spread and Smoke Developed when tested in accordance with NFPA 255, ASTM E84, UL 723 Method of Test of Surface Burning Characteristics of Building Materials. International Building Code, Chapter 8, Interior Finishes, Section 803 Wall and Ceiling Finishes, was classified in accordance with ASTM E 84 or UL 723. Such interior finish materials shall be grouped in the following classes in accordance with their flame spread and smoke-developed indexes.

Test Report No. AJD201302471 Date: JUN.09, 2013 Page 4 of 6 The classifications are as follows: Class A Class B Class C Flame Spread Index 0-25 26-75 76-200 Smoke-developed Index 0-450 0-450 0-450 Since the tested sample received a Flame Spread Index 0 and a Smoke Developed 45, it would meet the requirement of Class A interior Wall & Ceiling Finish Category. OBSERVATIONS Time to ignition (sec) 336 Time to Max. FS (sec) 0 Maximum FS (feet) 0 GRAPHICAL RESULTS: 20 18 16 Flame Spread Chart Test Sample Red Oak Flame Spread Distance (Feet) 14 12 10 8 6 4 2 0 0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5 5.5 6 6.5 7 7.5 8 8.5 9 9.5 10 Time (Minutes) Figure 1 Flame Spread Chart

Test Report No. AJD201302471 Date: JUN.09, 2013 Page 5 of 6 Smoke Developed Chart 100 Test Sample Red Oak 80 Light Absorption (%) 60 40 20 0 0 1 2 3 4 5 6 7 8 9 10 Time (minutes) WARNING: Figure 2 Smoke Developed Chart The use of supporting materials on the underside of the test specimen has the ability to lower the flame spread index from those which might be obtained if the specimen could be tested without such support. These test results do not necessarily relate to indices obtained by testing materials without such support. Testing of materials that melt, drip, or delaminate to such a degree that the continuity of the flame front is destroyed, results in low flame spread indices that do not relate directly to indices obtained by testing materials that remain in place. The test results relate only to the specimens of the product in the form in which were tested. Small differences in the composition or thickness of the product may significantly affect the performance during the test and may therefore invalidate the test results. Care should be taken to ensure that any product, which is supplied or used, is fully represented by the specimens, which were tested. The specimen was supplied by the sponsor and SGS-CSTC ANJI Branch was not involved in any selection or sampling procedure.

Test Report No. AJD201302471 Date: JUN.09, 2013 Page 6 of 6 Photo Appendix: ***End of Report***