JDDT1 - Single Stage Digital Thermostat

Similar documents
Instruction Manual for HX-DX and HX-DXHP Heat Exchangers 3 / 2017

XWA11V. Walk-In Temp / Door /Alarm / Light Module

XWA11V-KIT Walk-In Temp / Door /Alarm / Light Module with Mounting Box and Wiring

Dixell Installing and Operating Instructions release 7.0

DIMENS. MIN TYPICAL MAX A 71.0 (2.795) 71.0 (2.795) 71.8 (2.826) B 29.0 (1.141) 29.0 (1.141) 29.8 (1.173)

Operating Instructions XWA11V XWA11V. Walk-In Temp / Door /Alarm / Light Module

ST Wiring diagram. Product description. Standard temperature controller. Order number

MR4PMUHV Electronic. Temperature/Defrost Control with Relay Pack

Operating Instructions XWA11V. XWA11V-KIT Walk-In Temp / Door /Alarm / Light Module with Mounting Box and Wiring

Oxygen (O2) Single-Point Gas Detection System

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

7-Day. Digital Thermostat. residential. & 2-cool

Two-Channel Gas Controller

Refrigerated air dryers

Analog Room Pressure Monitor RPC Series

PARAGON Commercial Refrigeration Controls

MS4PMUHVT Multi-Stage Electronic Temperature Control with Relay Pack

TCA-9102 Series Surface Mount Temperature Controllers with High and Low Alarm

Label Displayed temperature Pb1 if the P4 parameter is set to 0, 1 or 2, room temperature if the P4 parameter is set to 3, incoming air temperature

5+2 Day. up to HEAT COOL

ER52 - Evaporator Controller

SERIES 101T MOISTURE ANALYZER QUICK START GUIDE

Oakton TEMP 9500 Advanced Multiparameter Controller

Emerson Inspire 1HDEZ Installation Instructions. Thermostat/Interface Equipment Control TROUBLESHOOTING

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.

1 4 DIN Dissolved Oxygen Controller

Sentry LIQUID LEVEL CONTROLLER MODEL 120 OPERATING MANUAL.

Mark 25 Ultrapure Water Conductivity Analyzer

MODEL TSTATBBPB101 PROGRAMMABLE DIGITAL THERMOSTAT. Heat Pump & Heat Cool. Meets California Title 24 Residential USERS INFORMATION MANUAL

Introduction. OM-THA2

Combustible Gas Detection and Control System

WH7016E Thermostat Product Manual

Static Pressure Control

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual

1 For All Programmable Digital Thermostat. Meets Residential California Title 24

GG-EM ENTRANCE MONITOR. Installation and Operation Manual

DIGITAL METERS Large Display Temperature Meters Instruction Manual

CA5000 Liquid CO 2 Freezer Backup System

Carbon Monoxide Transmitter

Sentry LIQUID LEVEL GAUGE MODEL 200 or 200C OWNER MANUAL REV 1.7 SEPT08 PAGE 1 OF 12

MR3CCUHV Temperature/Defrost Control

Owner s Manual. Digital Thermostat. Heat/Cool & Heat Pump 7-Day Programmable S1-THEM22P7S COMMERCIAL. Model HVAC SERVICE PARTS

Single Point Freeze Protection Heat Trace Control TRACON MODEL FPT 130 Installation and Operation Manual

DE20 INSTRUCTION MANUAL

User Manual. Humidity-Temperature Chart Recorder. Model RH520

1 For All Programmable or Non-Programmable. Digital Thermostat. Meets Residential California Title 24

Plug-n-Play Humidity Controller. IHC-200 User Manual. Version 1.3s. Inkbird Tech. Co., Ltd.

Process & TeMPerATUre UniversAl input DigiTAl MeTers

TEMPERATURE CONTROLLER (STANDARD MODEL)

HP727S. Single speed swimming pool heat pump controller Operation manual TABLE OF CONTENTS

For Quick Set-Up go to Page 14

T-32-TS Touchscreen Thermostat. Installation Manual

Series A3 and A4 Differential Pressure Controller

MODEL FPT-130 SINGLE POINT FREEZE PROTECTION HEAT TRACE CONTROL

Sf2+HF2 Sf2 Sf1 + Hf1 Sf1. 1 ON Fan1 enabled (only for XC30CX) 2 ON Fans enabled (only for XC30CX) kpa. Time

AutomationDirect PM24. Microprocessor - Based Process/Temperature Limit Controller. Operator s Manual. Technical Support.

flexibility programmed settings.

RC-2000 Thermostat Installation Instructions

IMPORTANT SAFETY INSTRUCTIONS READ AND FOLLOW ALL INSTRUCTIONS SAVE THESE INSTRUCTIONS

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL

CLEANROOM MONITOR CR3A Network - Installation Instructions

Installation and Operations Manual

THA2 TEMPERATURE/ HUMIDITY/ DEWPOINT ALARM WITH LOGGING CAPABILITY. 99 Washington Street Melrose, MA Phone Toll Free

Owner s Manual. Walk-in Monitoring System 100B. Cooler is Better! TM. Used in UL Listed Door Panel Assemblies

PROCESS & TEMPERATURE UNIVERSAL INPUT DIGITAL METERS

Carrier NON-PROGRAMMABLE DIGITAL THERMOSTAT. Dual Setpoint Thermoglow Backlight No Batteries Required Auto Changeover Locking Keypad

ST710-KHJV.03. Wiring diagram. Product description. Temperature controller. Order number

TMC Temperature Monitoring Control Temperature Range -30 to 250 F (-35 to 120 C)

Follett Performance Plus

Updated: 17/03/2010 ELECTROLUX. CAREL ir33. Quick reference Handbook. Ver. 1.1 Eng. Pag.1/12

FRUIT RIPENING CONTROLLER USER MANUAL SZ-FR INDIA

Product Manual SZ1009

Pipe Freeze Protection Control SCFP-CO-F130 Installation and Operation Manual

DNC-PS700-A10 Differential Pressure Control Meter. Operation and Installation Manual

EC 6-295P220S001. smart guide 2 OPERATION. 2.1 How to turn the instrument ON/OFF. If you have to turn the instrument ON/OFF:

TDF 15 MICROPROCESSOR-BASED DIGITAL ELECTRONIC THERMOCONTROLLER. OPERATING INSTRUCTIONS Vr. 01 (ENG) - cod.: ISTR TECNOLOGIC S.p.A.

TECHNICAL MANUAL CVM 3000 C 5030 CV/04-99 GB

ER65-DRW Controller. Heating Applications. Product Bulletin. Heating Controller

1 For All Programmable Digital Thermostat

Temperature. Table of Contents. Temperature Controllers pgs Indicators/Transmitters pgs Thermometers pgs

TECHNICAL MANUAL CVM 20 C 5005 CV/04-99 GB

XC10CX and XC30CX. Digital controller for CDU management 1. GENERAL WARNING 4. FRONT PANEL COMMANDS 2. GENERAL DESCRIPTION

I2:00 Mo MODEL TSTATBBPB501 PROGRAMMABLE DIGITAL THERMOSTAT. Heat Pump & Heat Cool. Meets California Title 24 Residential USERS INFORMATION MANUAL

Safety & Installation Instructions

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

Programmable Outlet Thermostat. User Manual. Version 1.5s. Inkbird Tech. Co., Ltd.

02/11/2015

UDC1000 and UDC1500 MICRO-PRO SERIES UNIVERSAL DIGITAL CONTROLLERS

EVF815 Installer manual ver. 2.0 Code 144F815E204 EVF815

Model: RT310. Installation Manual

Software Version 2.01 LEVEL MONITOR MODEL 220

RS332N BUTTON OPERATION INTRODUCTION. Installation and Operation Instructions for REMOVING THE THERMOSTAT FROM THE BACKPLATE

Oxygen Monitor Operating Manual

Instruction Manual WARNING

RC-112 Two Speed Heat Pump 3 Stage Heat / 2 Stage Cool With Energy Efficient Control

Instruction Manual PCS-400-XY. Pump Controller. Y=2: 4-20 ma Y=6: 0-10 VDC X=5: 1-5 VDC. 4 Pump Control Relays 1 Alarm Relay 1 Signal Fail

CATALOGUE 2017 ELECTRICAL BOARDS FOR REFRIGERATION

Thermometers and temperature controllers

Contents. FX-1 Operations Manual Micro Air Corporation 124 Route 526 Allentown, NJ 08501

VENSTAR T1070 FAN COIL THERMOSTAT PROGRAMMABLE 2 OR 4 PIPE SYSTEMS OWNER S MANUAL AND INSTALLATION INSTRUCTIONS

Transcription:

JDDT1 - Single Stage Digital Thermostat CAUTION NOTICE: The thermostat must be installed by authorized professionals. It should be located in a place free of vibrations, impacts, and corrosive gases. SET NOTICE: Protective plastic overlay should be peeled off after final installation. WIRING INSTRUCTIONS Wiring diagram is displayed on the inside cover of the unit and in figure 2. The JDDT1 Digital Temperature Switch combines reliability and an installation friendly weatherproof enclosure. Programming parameters can be quickly completed using the front keys. If programing multiple units with identical settings, a configuration key is an available accessory. In order to prevent tampering from unauthorized users, a parameter lock physical jumper and software pass-code security are standard in the unit. The bright, easy-to-read LED display shows the current output status and the temperature measurement. The multiple conduit knockouts on the JDDT1 give flexibility to the installer to determine the best location for the conduit entry. Another installation friendly feature of the JDDT1 is the ability to quickly jumper the line voltage to the common of the output relay using fast tabs. SPECIFICATIONS Probe Range: PTC: -58 to 302 F (-50 to 150 C). NTC: -58 to 230 F (-50 to 110 C). Input: PTC (1000 Ω @ 25 C)/NTC (10KΩ @ 25 C). Output: R1 SPDT Relay Resistive Load: 20A @ 240 VAC Horsepower Rating: R1 2HP @ 240 VAC, 1 HP @ 120 VAC Control Type: On/Off.Control Type: On/Off. Power Requirements: 90 to 255 VAC Power Consumption: 3.6VA. Accuracy: ±1% FS. Display: 3 digits plus sign. Resolution:.1 < 100 ; 1 100. Memory Backup: Non-volatile memory. Ambient Temperature: 32 to 104 F (0 to 40 C). Weight: 1.2 lbs (544 g). Front Protection: NEMA 4X (IP66). Agency Approvals: CE, UL, cul. 2-19/32 [65.53] 6-21/32 [168.91] Figure 1 3-5/8 [92.08] NOTICE: If the length of the probe cables exceed 100 meters, a recalibration adjustment must be made (parameter P1). NOTICE: Avoid installing the probe cables within proximity of power cables. TS2-K PROBE INPUTS Sd1 2 3 7 8 9 10 11 Locked Figure 2 Figure 3 OUT 1 OUTPUTS QUICK START - PROGRAMMING PARAMETERS Unlocked POWER SUPPLY In order to adjust parameter values, parameter lock jumper must be set in unlocked position (see figure 3). Upon startup take note of indicated temperature units, C or F. (Change of temperature units is shown in advanced settings.) Access only to Set Points SP (without software code protection): Press and release SET. Parameter SP appears on the display. Press SET to see the value of the parameter. Modify the value using the UP and DOWN keys. Press SET Key to save the value. Press SET and DOWN to quit programming, or wait 1 minute for the TIMEOUT. ISV1004-15K J&D Manufacturing 6200 Hwy 12 Eau Claire, WI 54701 1-800-998-2398 www.jdmfg.com Page 1/2

ADVANCED - PROGRAMMING PARAMETERS Access to all parameters (software code protected): Press SET for 8 seconds. The access code value 0 is shown on the display. Using the UP and DOWN buttons, set the code (factory-set code is 0). Press SET to confirm the code. If it is correct, the first parameter label will be shown on the display (SP). Move to the desired parameter with the UP and DOWN keys. Press SET to see the value of the parameter. Modify the value with the UP and DOWN keys. Press SET to save and exit parameter list. Press SET and DOWN to quit programming, or wait 1 minute for the TIMEOUT. Resetting the parameter pass code The parameter code can be set to zero by holding the SET key and cycling power to the unit. LED INDICATIONS This indicates that the output is energized or that the compressor is connected. It waits for the programmed minimum stop time of the compressor. This indicates that defrosting is activated. Error Messages In normal operation, the probe temperature will be shown. In case of alarm or error, the following messages will be shown: Er- Memory error. -- Shorted-circuited probe error. oo- Open probe error. PARAMETER DESCRIPTIONS SP = Set Point. Temperature desired to regulate the machine. Can vary from r1 to r2. r0 = Differential. Heating: If temperature is SP then output is OFF. If temperature is < SP - r0 then output is ON. Cooling: If temperature is SP + r0 then output is ON. If temperature is < SP then output is OFF. r1 = Lower Set Point Limit. r2 = Upper Set Point Limit. d0 = Heat or Cooling Control. Ht = heating control, Co = cooling control. d2 = Defrosting Time Remaining, in minutes. If d2 = 0, defrosting will not start. d8 = Interval Between Two Defrostings, in hours. c0 = Minimum Time for Compressor to be OFF. Minimum time for compressor to stop until it can start again. c1 = Continuous Cycle Time. The remaining time for a continuous cold cycle. c2 = ON Time of fault cycle, during probe error. c3 = OFF Time of fault cycle, during probe error. P0 = Selection of Engineering units between F and C. P1 = Ambient Probe Calibration. Offsets temperature in degrees to adjust the ambient probe. H5 = Access Code to Parameters. Factory-set to 0. H6 = Selection of Input Probe Type: PTC or NTC. t0 = Temperature Display Limit. Maximum temperature shown on the display, although the real temperature can be greater. OPERATION IN CASE OF ERROR If the probe or thermostat memory should fail, the compressor will be connected in accordance to the parameters set in C2 and C3. PARAMETER LIST Description Units Range P Set Point Degrees r1 to r2 r0 Differential or hysteresis Degrees 1 to 20 r1 Lower value for set point Degrees -50 to 150 C -50 to 302 F r2 Higher value for set point Degrees -50 to 150 C -50 to 302 F d0 Heating or Cooling Control Option Ht/Co d2 Time for Defrosting Minutes 0 to 59 d8 Interval time between Defrosts Hours 0 to 24 c0 Minimum stop time for compressor Minutes 0 to 59 c1 Continuous cycle time Hours 0 to 24 c2 On time of fault cycle Minutes 0 to 999 c3 Off time of fault cycle Minutes 0 to 999 P0 Engineering Units Option C/ F P1 Ambient Probe Adjustment Degrees -10 to 10 H5 Parameter acess code Number 0 to 99 H6 Probe Input Type Option Ptc/ntc t0 Maximum Temperature on Display Degrees -50 to 150 C -50 to 302 F MAINTENANCE After final installation of the JDDT1 Digital Temperature Switch, no routine maintenance is required. A periodic check of system calibration is recommended. WARRANTY J&D Manufacturing warrants all products are free from defects in materials and workmanship under normal use for the period of one year from date of purchase. Our warranty does not cover normal or regular wear and tear. J&D Manufacturing can repair or replace at our option, any product or part of the product that is found to be defective. Our warranty applies to materials only, and does not include return freight, delivery, loss or damage to personal property, cost of removal or installation, any incidental or consequential damages or labor. This warranty does not apply to products which are misused, abused, altered, improperly installed or subject to negligence. All warranties must be approved through our warranty department. The original purchaser must present a copy of the invoice for the defective product. One year is our standard warranty unless specified on our literature or in the installation instructions or user manuals. ISV1004-15K J&D Manufacturing 6200 Hwy 12 Eau Claire, WI 54701 1-800-998-2398 www.jdmfg.com Page 2/2

SPECIFICATIONS 2-19/32 [65.53] 3-5/8 [92.08] JDDT2 Dual Stage Digital Thermostat 6-21/32 [168.91] Figure 1 SET The JDDT2 Digital Temperature Switch combines reliability and an installation friendly weatherproof enclosure. Programming parameters can be quickly completed using the front keys. If programing multiple units with identical settings, a configuration key is an available accessory. In order to prevent tampering from unauthorized users, a parameter lock physical jumper and software pass-code security are standard in the unit. The bright, easy-to-read LED display shows the current output status and the temperature measurement. The multiple conduit knockouts on the JDDT2 give flexibility to the installer to determine the best location for the conduit entry. Another installation friendly feature of the JDDT2 is the ability to quickly jumper the line voltage to the common of the output relay using fast tabs. Probe Range: PTC: -58 to 302 F (-50 to 150 C). NTC: -58 to 230 F (-50 to 110 C). Input: PTC (1000 Ω @ 25 C)/NTC (10KΩ @ 25 C). Output: R1 SPDT Relay Resistive Load: 20A @ 240 VAC; R2 SPDT Relay Resistive Load: 8A @ 240 VAC, Inductive Load: 3A @ 240 VAC. Horsepower Rating: R1 2 HP @ 240 VAC, 1 HP @ 120 VAC, R2 1 /2 HP @ 240 VAC, 1 /4 HP @ 120 VAC Control Type: On/Off. Power Requirements: 90 to 255 VAC Power Consumption: 3.6VA. Accuracy: ±1% FS. Display: 3 digits plus sign. Resolution:.1 < 100 ; 1 100. Memory Backup: Non-volatile memory. Ambient Temperature: 32 to 104 F (0 to 40 C). Weight: 1.2 lbs (544 g). Front Protection: NEMA 4X (IP66). Agency Approvals: CE, UL, cul. WIRING INSTRUCTIONS Wiring diagram is displayed on the inside cover of the unit and in figure 2. NOTICE: If the length of the probe cables exceeds 100 meters, a recalibration adjustment must be made (parameter P1). NOTICE: Avoid installing the probe cables within proximity of power cables. CAUTION NOTICE: The thermostat must be installed by authorized professionals. It should be located in a place free of vibrations, impacts, and corrosive gases. NOTICE: Protective plastic overlay should be peeled off after final installation. TS2-K Sd2 Sd1 PROBE INPUTS 1 2 3 4 5 6 7 8 9 10 11 Figure 2 OUT 2 OUT 1 OUTPUTS POWER SUPPLY ISV1005-15K J&D Manufacturing 6200 Hwy 12 Eau Claire, WI 54701 1-800-998-2398 www.jdmfg.com Page 1/4

QUICK START - PROGRAMMING PARAMETERS In order to adjust parameter values, parameter lock jumper must be set in unlocked position (see figure 3). Locked Figure 3 Unlocked Upon startup take note of indicated temperature units, C or F. (Change of temperature units is shown in advanced settings.) NOTE: SP1 is temperature setting to control relay 1. SP2 is temperature setting to control relay 2. Access only to Set Points SP1 and SP2 (without code protection): Press SET key. Out1 LED and out1 set point value will flash on the display. Modify the out1 set point value using the UP and DOWN keys. Press SET key to store the out1 set point value and advance to out2 set point value. Modify the out2 set point value using the UP and DOWN keys. Press SET key to store the value and return to home screen. ADVANCED - PROGRAMMING PARAMETERS Access to all parameters (code protected): Press SET for 8 seconds. The access code value 0 is shown on the display. Using the UP and DOWN buttons, set the code (factory-set code is 0). Press SET to confirm the code. If it is correct, the first parameter label will be shown on the display (SP1). Move to the desired parameter with the UP and DOWN keys. Press SET to see the value of the parameter. Modify the value with the UP and DOWN keys. Press SET to store value. Press SET and DOWN to quit programming, or wait 1 minute for the TIMEOUT. Resetting the parameter pass code The parameter code can be set to zero by holding the SET key and turning the controller off then on again. LED INDICATIONS Out1: Indicates relay 1 On or Off as per parameter H2. If H2=, with relay 1 On, LED lit, if H2=inv, with relay 1 On, LED off. It blinks when SP1 is displayed. Out2: Indicates relay 2 On or Off as per parameter H3. If H3=, with relay 2 On, LED lit, if H3=inv, with relay 2 On, LED off. It blinks when SP2 is displayed. Error Messages Under normal operation, the temperature of the probe selected by P4 will be displayed, the following messages may also appear: Err Memory reading error. ErP Error of the probe not shown on the display. AH1 Maximum temperature alarm, probe 1. AL1 Minimum temperature alarm, probe 1. AH2 Maximum temperature alarm, probe 2. AL2 Minimum temperature alarm, probe 2. ooo Open probe. --- Shorted probe. Pressing SET and UP keys simultaneously will display the temperature of the probe not selected by P4 will be displayed. When the probe not selected by P4 is displayed, it alternates its value with message Sd1 or Sd2 depending if it is probe 1 or probe 2. Pressing SET and DOWN keys simultaneously will cancel. The display blinks when waiting for a value confirmation. Silence the Buzzer Pressing the SET and DOWN keys simultaneously silences the buzzer. The message of alarm continues appearing in the display. Resetting Parameters to Factory Values Access parameter H0 as explained in programming parameters. Value 0 will be displayed. Press SET for 8 seconds. Pro will be displayed if they have been setup correctly. Press SET + DOWN to exit setup or wait for 1 minute. Factory Description Units Range Value SP1 Set point 1 Degrees r4 to r6 10.0 SP2 Set point 2 Degrees r5 to r7 10.0 r0 Dependency SP1 to SP2 Option Ind or dep ind r1 Differential for SP1 Degrees 0.1 to 20.0 1.0 r2 Differential for SP2 Degrees 0.1 to 20.0 1.0 r3 Band differential Degrees 0.1 to 20.0 1.0 r4 Lowest value for SP1 Degrees -99.9 to r6-99.9 r5 Lowest value for SP2 Degrees -99.7 to r7-99.9 r6 Highest value for SP1 Degrees r4 to 302 302 r7 Highest value for SP2 Degrees r5 to 302 302 r8 Regulation or Operating Mode Option On1, On2, neu On1 A0 Alarm Differential Degrees 0.1 to 20.0 0.1 A1 Maximum alarm probe 1 A2 Maximum alarm probe 2 A3 Minimum alarm probe 1 A4 Minimum alarm probe 2 A5 Alarm verification time h-m(*) 0.0 to 18.0 18.0 A6 Alarm probe 1 selection Option AHL, Ano, AH, AL AHL A7 Alarm probe 2 selection Option AHL, Ano, AH, AL AHL c0 Minimum relay stop time Minutes 0 to 240 O c1 Operation relay 1 c2 Operation relay 2 c3 Fail Safe Operation relay 1 Option Opn or Clo Opn c4 Fail Safe Operation relay 2 Option Opn or Clo Opn P0 Temperature Units Selection Option C or F C P1 Calibration Probe 1 Degrees -20 to 20 0.0 P2 Calibration Probe 2 Degrees -20 to 20 0.0 P3 Decimal Point Option no or yes yes P4 Probe to be displayed Option sd1 or sd2 sd1 P5 Number of Probes Option 1 or 2 1 H0 Factory Reset Values Option 0 0 H1 Keypad tamper protection Option no or yes no H2 Operation of Out1 LED H3 Operation of Out2 LED H4 Address for serial communication Range 0-999 0 H5 Access code to parameters Range 0-999 0 H6 Probe Type Selection Option Ptc or ntc PTC (*) h-m are data in format XX.Y where XX are hours and Y tens of minutes. ISV1005-15K J&D Manufacturing 6200 Hwy 12 Eau Claire, WI 54701 1-800-998-2398 www.jdmfg.com Page 2/4

PARAMETER DESCRIPTIONS SP1 = Setpoint of relay1. Variable between r4 and r6. SP2 = Setpoint of relay 2. Variable between r5 and r7. r0 = Dependency between SP1 and SP2. Only for mode ONOFF1 Ind=set point for relay 2, SP2. dep=set point for relay 2, SP1+SP2. r1= Differential or hysteresis for relay 1. Temperature differential between ON/OFF of relay 1 in ON/OFF control. r2 = Differential or hysteresis for relay 2. Temperature differential between ON/OFF of relay 2 in ON/OFF control. r3 = Band differential. Temperature differential between ON/OFF of relays 1 and 2 in neutral area control. For relay 1 it is added to SP1 and for relay 2 it is subtracted from SP1. r4 = Lowest value for SP1. r5 = Lowest value for SP2. r6 = Highest value for SP1. r7 = Highest value for SP2. r8 = Regulation or operating mode. Selection of the operating mode. A0 = Alarm differential. It is the temperature differential between the alarm On and Off cycle. A1 = Maximum alarm probe1. Maximum alarm ON when probe 1 higher than SP1+A2 Maximum alarm OFF when probe 1 lower than SP1+A2-A0. A2 = Maximum alarm probe2. Maximum alarm ON when probe 2 higher than SP2+A2 Maximum alarm OFF when probe 2 lower than SP2+A2-A0. A3 = Minimum alarm probe1. Minimum alarm ON when probe 1 lower than SP1-A3 Minimum alarm OFF when probe 1 higher than SP1-A3+A0. A4 = Minimum alarm probe2. Minimum alarm ON when probe 2 lower than SP2-A4 Minimum alarm OFF when probe 2 higher than SP2-A4+A0. A5 = Alarm verification time. Time from the alarm event until it trips. A6 = Alarm probe 1 selection. (See Figure 4). AHL = Maximum and minimum alarm probe 1 enabled. Ano = No alarms probe 1. AH = Maximum alarm probe 1 enabled. AL = Minimum alarm probe 1 enabled. A7 = Alarm probe 2 selection. (See Figure 4). AHL = Maximum and minimum alarm probe 2 enabled. Ano = No alarms probe 2. AH = Maximum alarm probe 2 enabled. AL = Minimum alarm probe 2 enabled. c0 = Minimum relay stop time. Minimum time from the disconnection of a relay until it can be switched on again. c1 = Operation relay 1. Selection between ect or reverse operation for relay 1. c2 = Operation relay 2. Selection between ect or reverse operation for relay 2. c3 = Default operation relay 1. In case of failure of probe 1: opn = relay 1 will remain open. Clo = relay 1 will remain closed. c4 = Default operation relay 2. In case of failure of probe 1 (for all modes excepting ON OFF2) or in case of failure of probe 2 (for mode ON OFF2): opn = relay 2 will remain open. Clo = relay 2 will remain closed. P0 = Temperature scale selection. P1 = Calibration of probe 1. Offset degrees to be added to probe 1. P2 = Calibration of probe 2. Offset degrees to be added to probe 2. P3 = Decimal point. If the displayed value of the probes is desired with decimals or not. P4 = Probe to be displayed. Probe always on the display. The other probe can be seen pressing the keys SET+UP. sd1 = probe 1. sd2 = probe 2. P5 = Number of probes. If P5=1, there is no ONOFF2 mode. If selected, it will operate as ONOFF1. H0 = Reprogramming. Parameter to reprogram the thermostat. H1 = Keyboard protection. To change the settings, enter into parameter and exit again. The protection setting is momentarily released. It switches on again 1 minute after the last time a key was pressed. Yes = Keyboard Protected. No = Keyboard non protected. H2 = Operation of LED OUT1. = On when relay 1 is ON. inv = On when relay 1 is OFF. H3 = Operation of LED OUT2. = On when relay 2 is ON. inv = On when relay 2 is OFF. H4 = Serial communication address. Address for computer connection. H5 = Parameter entry code. Factory set as 0. MAINTENANCE After final installation of the JDDT2 Digital Temperature Switch, no routine maintenance is required. A periodic check of system calibration is recommended. WARRANTY Figure 4 J&D Manufacturing warrants all products are free from defects in materials and workmanship under normal use for the period of one year from date of purchase. Our warranty does not cover normal or regular wear and tear. J&D Manufacturing can repair or replace at our option, any product or part of the product that is found to be defective. Our warranty applies to materials only, and does not include return freight, delivery, loss or damage to personal property, cost of removal or installation, any incidental or consequential damages or labor. This warranty does not apply to products which are misused, abused, altered, improperly installed or subject to negligence. All warranties must be approved through our warranty department. The original purchaser must present a copy of the invoice for the defective product. One year is our standard warranty unless specified on our literature or in the installation instructions or user manuals. ISV1005-15K J&D Manufacturing 6200 Hwy 12 Eau Claire, WI 54701 1-800-998-2398 www.jdmfg.com Page 3/4

OPERATING MODES Mode ON OFF1 (On1) with r0=ind. Relay 1 with c1=. Temperature of probe 1 >= SP1+r1 -->relay 1 ON Temperature of probe 1 <= SP1 -->relay 1 OFF Relay 2 with c2=inv. Temperature of probe 1 <= SP1+SP2-r2 -->relay 2 ON Temperature of probe 1 >= SP1+SP2 -->relay 2 OFF Figure 9 Relay 1 with c1=inv. Temperature of probe 1 <= SP1-r1 -->relay 1 ON Temperature of probe 1 >= SP1 -->relay 1 OFF Figure 5 Mode ON OFF2 (On2) Output 1 works as an independent ON/OFF control (Figure 5 and 6), but output 2 works as follows: Relay 2 with c2=. Temperature of probe 2 >= SP2+r2 -->relay 2 ON Temperature of probe 2 <= SP2 -->relay 2 OFF Relay 2 with c2=. Temperature of probe 1 >= SP2+r2 -->relay 2 ON Temperature of probe 1 <= SP2 -->relay 2 OFF Figure 6 Figure 10 Relay 2 with c2=inv. Temperature of probe 2 <= SP2-r2 -->relay 2 ON Temperature of probe 2 >= SP2 -->relay 2 OFF Relay 2 with c2=inv. Temperature of probe 1 <= SP2-r2 -->relay 2 ON Temperature of probe 1 >= SP2 -->relay 2 OFF Figure 7 Figure 11 Neutral Area Mode (neu) Relay 1 Temperature of probe 1 >= SP1+r3 -->relay 2 ON Temperature of probe 1 <= SP1 -->relay 2 OFF Relay 2 Temperature of probe 1 <= SP1-r3 -->relay 2 ON Temperature of probe 1 >= SP1 -->relay 2 OFF Figure 8 Mode ON OFF1 (On1) with r0=dep. Output 1 works as an independent ON/OFF control (Figure 5 and 6), but output 2 works as follows: Relay 2 with c2=. Temperature of probe 1 >= SP1+SP2+r2 -->relay 2 ON Temperature of probe 1 <= SP1+SP2 -->relay 2 OFF Figure 12 Operation in case of error. If probe 1 fails, the operation is through c3. (See Parameter description.) If probe 2 fails, the operation is through c4. (See Parameter description.) In case of memory failure, both relays will remain open. ISV1005-15K J&D Manufacturing 6200 Hwy 12 Eau Claire, WI 54701 1-800-998-2398 www.jdmfg.com Page 4/4