Medical Gas Inspections and Maintenance Programs. HESNI Annual Conference NIU Conference Center May 10-11, 2018 Presented by Mathis Carlson

Similar documents
4/18/2017. *2012 edition of NFPA 99 has gone through a major overhaul. *This document is now a Code.

Course Outline. Course Introduction Purpose of the course Course Overview Program Outline Instructor Information

NFPA 99 for Facility Managers

There are many changes to NFPA 99 from 1993 to 2015, but we want to concentrate on the changes made from 2012 to 2015, and we need to know a little

Medical Gas Training ASSE 6010 Installer & ASSE 6020 Inspector Courses Available

27th Annual AHCA Seminar

WHAT S NEW IN NFPA

WHAT S NEW IN NFPA

The Impact the Reference Standards in the 2012 Edition of NFPA 101 have on the Operation of Health Care Facilities: NFPA 80 and 99

AMENDMENTS TO THE BUILDING AND FIRE CODE FOR THE CITY AND COUNTY OF DENVER

Compliance w/ the 2012 Life Safety Code

NFPA Overview and 2000 to 2012 Update. Sharon S. Gilyeat, P.E. - Principal. Koffel Associates, Inc. MD, MA, NC, CT, IN

MAINTENANCE AND TESTING OF FIRE SPRINKLER SYSTEMS

Public Safety in the Healthcare Facility

The Healthcare Environment Update

TOPICS IN CODE ENFORCEMENT

2017 Accreditation Updates

Life Safety Code NFPA 10 NFPA 13 NFPA 25 NFPA 72 NFPA 90A NFPA 110 NFPA 99 THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #7

Riverside County Fire Department Office of the Fire Marshal Market St., Ste. 150, Riverside, CA Ph. (951) Fax (951)

Today s Webcast starts at 1:00 p.m. Eastern. You will not hear audio until the Webcast begins

THE 2012 EDITION OF THE LIFE SAFETY CODE HOSPITAL EDITION SESSION #6

Life Safety Code Comparison

4.2.1 Policies & Procedures. Adds wording that the LSO shall REQUIRE approved written procedures on

BUILDING, FIRE, AND LIFE SAFETY CODE ENFORCEMENT AND CERTIFICATION OF INSPECTORS FOR HEALTH FACILITIES LICENSED BY THE STATE OF COLORADO

Interim Life Safety Measures. Healthcare Construction Certificate - Level 1

DEPARTMENT OF PUBLIC SAFETY DIVISION OF FIRE PREVENTION AND CONTROL

Center for Clinical Standards and Quality /Survey & Certification Group

COURSE SYLLABUS HVAC AND MECHANICAL CONSIDERATIONS FOR PART 3 BUILDINGS CORRESPONDENCE COURSE

Developing a Healthcare Facility Fire Door Inspection Program

Public Safety [661] Chapter 226, Liquefied Petroleum Gas, Amended for Application within the State of Iowa

5.07 Air Replenishment Systems

Prepublication New Text Jan 2018 Changes to Environment of Care and Life Safety Chapters

Applicable To Employees of the Gundersen St. Joseph s Hospital laboratories and Gundersen Tri-County Hospital laboratories.

DEPARTMENT OF PUBLIC SAFETY. Division of Fire Prevention and Control 8 CCR

Iowa State Fire Marshal

FACILITY MANAGEMENT DEFICIENCIES IN ACUTE CARE SETTINGS

S a n F r a n c i s c o F i r e D e p a r t m e n t B u r e a u o f F i r e P r e v e n t i o n & I n v e s t i g a t i o n 1 of 8 P a g e

Today s Webcast starts at 1:00 p.m. Eastern. You will not hear audio un=l the Webcast begins

Are You Prepared? The impending impact of Code on Servicing Security Systems

UNIFIED FACILITIES GUIDE SPECIFICATIONS

First Aspen Federal Regulation Set: K LSC 2000 Health Existing

EC Standard & NFPA 110 (EPSS) Documentation Best Practice. 1: Division Team Mission

ASHE Advocacy Team. Q4 ASHE Advocacy Liaison Webinar 12/7/16 12/7/16. Tim Adams, FASHE, CHFM, CHC Director of Leadership Development

Changes to the 2018 Joint Commission Comprehensive Accreditation Manual for Hospitals (CAMH)

Field Guide for Healthcare Facilities

D. Reference Standards (Utilize latest editions available):

Design & Construction Standards, Revised January

OUR MISSION. OUR MISSION is to promote secure

Changes to Environment of Care, Equipment Management, and Life Safety Chapters Related to Life Safety Code Updates

Are there any policies regarding outlets that contain USB ports?

NFPA Fire Inspector I Study Guide

NFPA CODE TESTING & INSPECTION. Requirements & Recommendations for. Licensed Florida Hospitals, Ambulatory Surgery Centers,

Other EC and LS documents may be requested by surveyors, as needed, throughout the survey.

LIFE SAFETY COMPLIANCE: ADAPTING TO THE 2012 LIFE SAFETY CODE

FACILITY MANAGEMENT DEFICIENCIES IN CRITICAL ACCESS HOSPITALS (CAH)

Smoke Management in Operating Room Renovations

DENVER AMENDMENT PROPOSAL 2015 INTERNATIONAL CODES

LIFE SAFETY & FIRE PREVENTION MANAGEMENT PLAN

NFPA Impacts Training presentation for: AlaSHE Spring 2017 Conference David Stymiest, Senior Consultant, Smith Seckman Reid, Inc.

Laboratory Enclosed Scroll Air Compressor System with Premium NFPA Controls

CARBON DIOXIDE SYSTEMS FOR BEVERAGE DISPENSING PERMIT REQUIREMENTS

M E M O R A N D U M. Please do not vote negatively because of editorial errors. However, please bring such errors to my attention for action.

Title: BFST1505 Syllabus

Ch. 569 FIRE AND SAFETY SERVICES 28 CHAPTER 569. FIRE AND SAFETY SERVICES GENERAL PROVISIONS INTERNAL DISASTER PLAN EVACUATION DRILLS

1.0 Basic Principles and Practices of Propane Performance-Based Skills Assessment 2016

2018 Joint Commission Standards What s New in the EC/LS/UM GASHE Annual March Meeting Lake Blackshear Resort

Overview Alliance Medical Gas Corporation is a privately held organization that was founded on January 1, 1996 with the vision to be a single-source,

FIRE SAFETY SURVEY REPORT AMBULATORY SURGICAL CENTERS (ASC) & END STAGE RENAL DISEASE (ESRD) MEDICARE

New DATE OF BLDG. PERMIT OR PLAN APPROVAL: SURVEYOR (SIGNATURE) TITLE OFFICE DATE REVIEW AUTHORITY OFFICIAL (SIGNATURE) TITLE OFFICE DATE

Danilo B. Concepcion, CBNT, CCHT-A Operations Manager St. Joseph Hospital Renal Services

Medical Gas and Vacuum Systems

FHCA 2014 Annual Conference & Trade Show

PORTABLE FIRE EXTINGUISHERS

Changes to Environment of Care and Life Safety Chapters Related to Life Safety Code Updates

This policy may also be used for routine work orders that are Life Safety in nature and cannot be completed within 45-days.

10/25/2018. Facilitators. Emergency Preparedness &Life Safety Code for Administrators. Participant Guide

Candy Easterling K-063. Adequate and Reliable Water Supply for the Sprinkler System. CITY WATER or WATER TANK for Sprinkler System

Health Chapter ALABAMA STATE BOARD OF HEALTH ALABAMA DEPARTMENT OF PUBLIC HEALTH ADMINISTRATIVE CODE

Beth Israel Deaconess Medical Center BIDMC Manual

B. The Facility Emergency Planners and Alternate Planners will successfully complete the in-house DJJ Fire Prevention course.

PRIVATE ALARM CONTRACTOR LICENSURE EXAMINATION INFORMATION

LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS

Life Safety Code Potpourri

Update all extract references to NFPA documents (including NFPA 72) in Chapter 3 and related annex material to the latest editions.

Changes to NFPA 101A 2013 Edition for Health Care Facilities

EC 5.10 FIRE PREVENTION MANAGEMENT

INDEX 100 GENERAL 101 PURPOSE 102 EXEMPTION, VACUUM CONDITION 103 EXEMPTION, VAPOR PRESSURE

Scroll Medical Air Compressor with Premium NFPA Control Panel

ISHRAE. Guideline document to ISO Version 1 Feb Indian Society of Heating, Refrigerating and Air Conditioning Engineers

Copyright Information

Renovation Program. Renovation Program GENERAL

June 2018 Safety Meeting Fire Extinguishers Part I

3/20/2017. The Impact & Implications of NFPA 652 NFPA s Newest Combustible Dust Standard. Jason Reason. Jason Reason

GEORGIA DEPARTMENT OF CORRECTIONS Standard Operating Procedures

PQS Independent type-testing protocol

ARTICLE 25. FUEL GAS CODE

NFPA Edition Review

Elevator Emergency Equipment Instructor s Guide

Building Codes & Standards for Healthcare. Healthcare Construction Certificate - Level 1

Transcription:

Medical Gas Inspections and Maintenance Programs HESNI Annual Conference NIU Conference Center May 10-11, 2018 Presented by Mathis Carlson

Mathis Carlson I have worked for the last 15+ years in the Medical Gas industry. I maintain my medical gas verifiers, instructors, and maintenance cards, along with additional credentials and plumbing licenses. I serve on the Board of Directors for the Medical Gas Professional Healthcare Association as the Vice President of Membership. I currently am employed by Medical Technology Associates as the area supervisor over Illinois, Wisconsin, Indiana and Michigan. I also oversee all of our training programs nationwide. I can be reached at 773-762-9287 or MathisC@mtausa.com

Inspections and Maintenance 1. Who is the authority over my hospital? CMS? Who are they? 2. NFPA 99-2012 Healthcare Facilities Code 3. What will my Life Safety Surveyor look for? 4. When should an inspection be performed? What should be included in my inspection program? 5. Medical Gas maintenance Programs Code requirements Qualifications for maintenance personnel

Who governs my hospital?

CMS Who are they? Centers for Medicare and Medicaid Services CMS is a Federal program, however it is State Administered, so each state sets it s own guidelines based around the Conditions of Participation (CoP) CMS determines funding reimbursements to healthcare entities providing treatment for Medicare and Medicaid patients CFR Title 42: Public Health Within Title 42 we have Chapter IV: Centers for Medicare & Medicaid Services Department of Health and Human Services

CMS Who are they? 871 pages of regulations Contains NUMEROUS sections such as: Governing Body Nursing Administration Quality Control Laboratory Services PHYSICAL ENVIRONMENT

Code Adoption for Healthcare Organizations Effective July 5, 2016 CMS adopted the 2012 edition of the NFPA 99 Healthcare Facilities Code All applicable CMS deemed status accreditation firms such as: Joint Commission, included in January 9, 2017 standards update

Code Adoption for Healthcare Organizations DNV-GL, included in December 2016 standards update AOA/HFAP, included in February 2017 standards update CIHQ, included in July 2017 standards update We will focus on the NFPA 99-2012 edition to align with CMS standards.

NFPA 99: Healthcare Facilities Code

Applicability Applies to all Health Care Facilities, excluding home health and veterinary.(1.3.1) Construction and equipment requirements apply to NEW construction and NEW equipment, except as modified in individual chapters. (1.3.2) ONLY the altered, renovated, or modernized portion of an existing system, or individual component, shall be required to meet the installation and equipment requirements stated in this code. (1.3.2.1)

Applicability An existing system that is not in strict compliance with the provisions of this code shall be permitted to be continued in use. Unless the authority having jurisdiction has determined that such use constitutes a distinct hazard to life. (1.3.2.3, 5.1.1.4)

NFPA 99 Chapter 5: Medical Gas and Vacuum Systems Chapter 4: Fundamentals NFPA 99 changed from an occupancy based system to a risk based system. 4 categories

NFPA 99 Chapter 4 Categories 1. Systems in which failure is likely to cause major injury or death. 2. Systems in which failure is likely to cause minor injury. 3. Systems in which failure is likely to patient discomfort. 4. No impact Categories determined by a FACILITY PERFORMED risk assessment

So what will our Life Safety Surveyor look for? (LSS) In a short amount of time the LSS is trying to check the following items in the healthcare organization: Compliance with all applicable CMS, Accreditation Agency, State and/or local codes and standards. That all buildings and building systems are installed and maintained according to all applicable codes. Patient and employee safety and best practices.

So what will our Life Safety Surveyor look for? (LSS) Documentation that defines all of the processes listed above, as well as how they are to be performed. Records that show all of the processes were performed according to the established and adopted procedures. A document is some type of instruction or mandate as to how the system or process will operate. A record is maintained to establish proof of conformity to the document and/or process.

So what will our Life Safety Surveyor look for? (LSS) Remember: If you didn t document it, you might as well have not done it. If there is no record of something being done, it is assumed that it was not done.

Documentation Your documentation and records should be in a format that insures all of the following: 1. ANYONE that has to display the information to the LSS can do so easily and efficiently. Remember that it may not be you that will be presenting and explaining the reports to the LSS. 2. You only want to display the pertinent information. 3. You want to minimize the time that it takes the LSS to understand your programs and how they are run.

Documentation 4. You want the staff to be able to efficiently review the documents for accuracy. 5. Confidence leads to success. The more confident you are in your documentation and processes, the easier this review is. The document review is typically the first thing done in a survey. Don t let it set a bad tone for the rest of the process. Fill in all the blanks! Blank spaces or fields lead to questions. Make sure that inventories are accurate. When adding or removing a device, remember to account for that process.

Documentation Have all follow-up documentation (Work orders, re-inspection forms etc.) for any repairs Have an accurate index or table of contents. This will help your staff find their way through the documentation easily and be confident in their answers. Use clear plain language. Make sure that you are using the correct version of the code for your facility/agency. For example, TJC will be on NFPA 99 2012 while a VA hospital will be on NFPA 99 2018.

Documentation Separate required deficiencies from suggestions and/or recommendations. Only place a code required item in the deficiencies list. If a newer code has a different requirement, place it in the suggestions list rather than deficiencies. If your facility is with DNV-GL the equipment calibration records for all test equipment MUST be included with your documentation. Always a good idea to have this.

Documentation Place the deficiencies near the front of the report. Place repair tickets, work orders and/or other supporting documentation for corrections there after. Immediately inform any facility staff that need to know about any deficiencies critical to the operation of the facility. DO NOT wait until the LSS finds them in the documentation review of the survey. Play it safe notify via e- mail or in writing so that there is a record.

How often should I be testing and inspecting my medical gas systems? The Joint Commission EC.02.05.09 states In a timeframe defined by the hospital, the hospital inspects, tests, and maintains critical components of the piped medical gas and vacuum systems.

How often should I be testing and inspecting my medical gas systems? DNV-GL PE.8, SR.3 The Utility Management System shall develop maintenance, testing and inspection processes for critical utilities. PE.8, SR.4 The Utility Management System shall contain a process to address medical gas systems and HVAC systems. (example negative pressure isolation rooms)

How often should I be testing and inspecting my medical gas systems? NFPA 99 2012 Edition 5.1.14.2.2.2* Inspection Schedules. Scheduled inspections for equipment and procedures shall be established through the risk assessment of the facility and developed with consideration of the original equipment manufacturer recommendations and other recommendations as required by the authority having jurisdiction. *indicates additional information in the annex

How often should I be testing and inspecting my medical gas systems? 5.1.14.2.2.3 Inspection Procedures. The facility shall be permitted to use any inspection procedure(s) or testing methods established through its own risk assessment.

How often should I be testing and inspecting my medical gas systems? NFPA 99 2012 Edition 5.1.14.4.4 Central supply systems for nonflammable medical gases shall conform to the following: (1) They shall be inspected annually. (2) They shall be maintained by a qualified representative of the equipment owner. (3) A record of the annual inspection shall be available for review by the authority having jurisdiction.

How often should I be testing and inspecting my medical gas systems? 5.1.14.4.5 A periodic testing procedure for nonflammable medical gas and vacuum and related alarm systems shall be implemented. 5.1.14.4.6 Whenever modifications are made that breach the pipeline, any necessary installer and verification test specified in 5.1.12 shall be conducted on the downstream portions of the medical gas piping system.

How often should I be testing and inspecting my medical gas systems? NFPA 99 2012 Edition 5.1.14.4.8 Audible and visual alarm indicators shall meet the following requirements: (1) They shall be periodically tested to determine that they are functioning properly. (2) Records of the test shall be maintained until the next test is performed. 5.1.14.4.9 Medical surgical vacuum station inlet terminal performance, as required in 5.1.12.3.10.4, shall be tested as follows: (1) On a regular preventive maintenance schedule as determined by the facility maintenance staff.

How are inspection intervals defined? The Joint Commission Every 36 months/every 3 years = 36 months from the date of the last event, ± 45 days Annually/every 12 months/once a year/every year = 1 year from the date of the last event, ± 30 days Every 6 months = 6 months from the date of the last event, ± 20 days Quarterly/every quarter = every 3 months, ± 20 days Monthly/30-day interval/every month = 12 times per year, once per month Every week = once per week

How are inspection intervals defined? CMS, DNV-GL, HFAP, and CIHQ Annually: once per year as close as possible to 365 days between actions. Quarterly: once every three months as close as possible to 90 days between actions. Monthly: once a month as close as possible to 30 days between actions. Weekly: once a week close as possible to 7 days between actions. Daily: once a day as close as possible to 24 hours between actions.

What should be included in a Medical Gas Inspection? 5.1.14.2.3.1 General. The elements in 5.1.14.2.2.2 through 5.1.15 shall be inspected or tested as part of the maintenance program as follows: (1)*Medical air source: (a) Room temperature (b) Shaft seal condition (c) Filter condition (d) Presence of hydrocarbons, (e) Room ventilation (f) Water quality, if so equipped (g) Intake location (h) Carbon monoxide monitor calibration (i) Air purity (j) Dew point

What should be included in a Medical Gas Inspection? A.5.1.14.2.3.1(1) Additional inspections for medical air sources include the following: (1) Aftercoolers (condition, operation of automatic drains) (2) Operating pressures (cut-in, cut-out, and control pressures) (3) Electrical operation (4) Receiver elements (auto/manual drain, sight glass, pressure gauge) (5) Pressure regulators (condition) (6) Dryer (operation, outlet dew point, condition, housekeeping) (7) Dew point calibration (8) Housekeeping around compressors

What should be included in a Medical Gas Inspection? (2)*Medical vacuum source exhaust location (3) WAGD source exhaust location A.5.1.14.2.3.1(2) Additional inspections for medical vacuum sources and WAGD sources include the following: (1) Operating vacuum (cut-in, cut-out, and control pressures) (2) Electrical operation (3) Receiver elements (manual drain, sight glass, vacuum gauge) (4) Housekeeping around pump

What should be included in a Medical Gas Inspection? (4)*Instrument air source filter condition A.5.1.14.2.3.1(4) Additional inspections for instrument air sources include the following: (1) Aftercoolers (condition, operation of drains) (2) Operating pressures (cut in, cut out, and control pressures) (3) Electrical operation (4) Receiver elements (auto/manual drain, sight glass, pressure gauge) (5) Pressure regulators (condition) (6) Housekeeping around compressors

What should be included in a Medical Gas Inspection? (5)*Manifold sources (including systems complying with 5.1.3.5.10, 5.1.3.5.11, 5.1.3.5.12, and 5.1.3.5.13), as follows: (a) Ventilation (b) Enclosure labeling

What should be included in a Medical Gas Inspection? A.5.1.14.2.3.1(5) Additional inspections for manifold sources include the following: (1) Cylinder leads (condition) (2) Cascade (switching from one header to another) (3) Source valve (labeling) (4) Relief valves (discharge location and condition) (5) Leaks (6) Security (door or gate locks and signage) (7) Housekeeping around manifolds

What should be included in a Medical Gas Inspection? (6) Bulk cryogenic liquid source inspected in accordance with NFPA 55, Compressed Gases and Cryogenic Fluids Code (7) Final line regulation for all positive pressure systems delivery pressure

What should be included in a Medical Gas Inspection? (8)*Valves labeling A.5.1.14.2.3.1(8) Additional inspections for zone valves include the following: (1) Locations (relationship to terminals controlled) (2) Leaks (3) Labeling (4) Housekeeping around valve

What should be included in a Medical Gas Inspection? (9)*Alarms and warning systems lamp and audio operation A.5.1.14.2.3.1(9) Additional inspections for alarms include the following: (1) Dew point monitor (operation and calibration) (2) Carbon monoxide monitor (operation and calibration) (3) All local alarms on medical air, vacuum, WAGD, manifolds, medical support gas sources (verify presence of required alarms, perform electrical test, test lag alarm) (4) Locations (visible to staff) (5) Housekeeping around alarms

What should be included in a Medical Gas Inspection? (10) Alarms and warning systems, as follows: (a) Master alarm signal operation (b) Area alarm signal operation (c) Local alarm signal operation

What should be included in a Medical Gas Inspection? (11)*Station outlets/inlets, as follows: (a) Flow (b) Labeling (c) Latching/delatching (d) Leaks A.5.1.14.2.3.1(11) An additional inspection for station outlets/ inlets is a general condition (noninterchangeable indexing).

What should be included in a Medical Gas Inspection? Booms Known in the code as Manufactured Assemblies Employing Flexible Connection(s) Between the User Terminal and the Piping System. Nonstationary booms and articulating assemblies, other than head walls utilizing flexible connectors, shall be tested for leaks, per manufacturer s recommendations, every 18 months or at a duration as determined by a risk assessment. (5.1.14.2.3.2(A))

What should be included in a Medical Gas Inspection? The system pressure to nonstationary booms and articulating arms shall be maintained at operating pressure until each joint has been examined for leakage by effective means of leak detection that is safe for use with oxygen. (5.1.14.2.3.2(B)) Safe working condition of the flexible assemblies shall be confirmed. (5.1.14.2.3.2(C)) D.I.S.S. connectors internal to the boom and assemblies shall be checked for leakage. (5.1.14.2.3.2(D))

What should be included in a Medical Gas Inspection? Leaks, if any, shall be repaired (if permitted), or the components replaced (if required), and the equipment retested prior to placing the equipment back into service. (5.1.14.2.3.2(E)) Additional testing of nonstationary booms or articulating arms shall be performed at intervals defined by documented performance data. (5.1.14.2.3.2(F))

Maintenance Programs NFPA 99 2012 edition requires that facilities have a documented maintenance program. 5.1.14.2.1* General. Health care facilities with installed medical gas, vacuum, WAGD, or medical support gas systems, or combinations thereof, shall develop and document periodic maintenance programs for these systems and their subcomponents as appropriate to the equipment installed.

Maintenance Programs NFPA 99 2012 edition requires that facilities have a documented maintenance program. 5.1.14.2.2.4 Maintenance Schedules. Scheduled maintenance for equipment and procedures shall be established through the risk assessment of the facility and developed with consideration of the original equipment manufacturer recommendations and other recommendations as required by the authority having jurisdiction.

Maintenance Programs 5.1.14.4.7 Procedures, as specified, shall be established for the following: (1) Maintenance program for the medical air compressor supply system in accordance with the manufacturer s recommendations (2) Facility testing and calibration procedure that ensures carbon monoxide monitors are calibrated at least annually or more often if recommended by the manufacturer

Maintenance Programs (3) Maintenance program for both the medical surgical vacuum piping system and the secondary equipment attached to medical surgical vacuum station inlets to ensure the continued good performance of the entire medical surgical vacuum system (4) Maintenance program for the WAGD system to ensure performance 5.1.15* Category 1 Maintenance. Facilities shall have a routine maintenance program for their piped medical gas and vacuum systems.

Maintenance Programs 5.1.15 is not exactly what I would call specific as far as a maintenance program requirement. So Let s look at the annex for some more clarification A.5.1.15 Medical gas and vacuum systems should be surveyed at least annually for the items that follow and deficient items corrected. Survey of medical air and instrument air sources should include, but not be limited to, the following:

Maintenance Programs (1) Dew point monitor (operation and calibration) (2) Carbon monoxide monitor (medical air only) (operation and calibration) (3) Aftercoolers (condition, operation of drains) (4) Operating pressures (cut-in, cut-out, and control pressures) (5) All local alarms (verify presence of required alarms, perform electrical test, test lag alarm)

Maintenance Programs (6) Receiver elements (auto drain, manual drain, sight glass, pressure gauge) (7) Filters (condition) (8) Pressure regulators (condition, output pressure) (9) Source valve (labeling) (10) Intake (location and condition) (11) Housekeeping around compressors

Maintenance Programs Survey of the medical vacuum and the WAGD source(s) should include, but not be limited to, the following: (1) Operating vacuum (cut-in, cut-out, and control pressures) (2) All local alarms (verify presence of required alarms, perform electrical test, test lag alarm) (3) Receiver elements (manual drain, sight glass, vacuum gauge) (4) Source valve (labeling) (5) Exhaust (location and condition) (6) Housekeeping around pump

Maintenance Programs Survey of the medical gas manifold source(s) should include, but not be limited to, the following: (1) Number of cylinders (damaged connectors) (2) Cylinder leads (condition) (3) Cascade (switching from one header to another) (4) All local alarms (verify presence of required alarms, perform electrical test, test all alarms)

Maintenance Programs (5) Source valve (labeling) (6) Relief valves (discharge location and condition) (7) Leaks (8) Security (door or gate locks and signage) (9) Ventilation (general operation, housekeeping) (10) Housekeeping around manifolds

Maintenance Programs Survey of medical gas area alarms should include, but not be limited to, the following: (1) Locations (visible to staff) (2) Signals (audible and visual, use test function) (3) Activation at low pressure (4) Housekeeping around alarm Survey of medical gas master alarms should include, but not be limited to, the following: (1) Locations (visible to appropriate staff) (2) Signals (audible and visual, use test function) (3) Activation at low pressure (4) Housekeeping around alarm

Maintenance Programs Survey of medical gas area alarms should include, but not be limited to, the following: (1) Locations (visible to staff) (2) Signals (audible and visual, use test function) (3) Activation at low pressure (4) Housekeeping around alarm

Maintenance Programs Survey of medical gas outlet/inlets should include, but not be limited to, the following: (1) Flow and function (2) Latching/delatching (3) Leaks (4) General condition (noninterchangeable indexing)

The facility should retain a written or an electronic copy of all findings and any corrections performed.

So who can perform maintenance? 5.1.14.2.2.5 Qualifications. Persons maintaining these systems shall be qualified to perform these operations. Appropriate qualification shall be demonstrated by any of the following

So who can perform maintenance? (1) Training and certification through the health care facility by which such persons are employed to work with specific equipment as installed in that facility Potential Benefits Shorter training, as there is not a set hour requirement Training on the specific equipment that is inside the building Easier to work around staffing, schedules, rotations Lower cost by not having to pay course instruction costs

So who can perform maintenance? Potential Issues If you have one maintenance person covering various buildings, a separate training for each building would be required Opens the training program for review in a survey, was it really sufficient? New equipment, or replaced equipment.new training What will it cost the facility to develop and document the training program Manufactures recommendations would be referenced, and those recommendations may require manufactures training at a high cost

So who can perform maintenance? (2) Credentialing to the requirements of ASSE 6040, Professional Qualification Standard for Medical Gas Maintenance Personnel Potential Benefits Path of least resistance, universal card covers everything and all buildings Nationally recognized credential Won t be questioned or reviewed in a survey

So who can perform maintenance? Potential Issues No equipment or facility specific training Depending on the credentialing agency, either a 24 or 32 hour course plus an exam Difficult especially for small facilities to pull staff off of work assignments for a week Tuition and testing costs as well as potential travel costs

So who can perform maintenance? (3) Credentialing to the requirements of ASSE 6030, Professional Qualification Standard for Medical Gas Systems Verifiers