SPECIFICATION: ECS SERIES CLEAN AGENT FIRE SUPPRESSION SYSTEM

Similar documents
A. NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems 2004 edition.

SPECIFICATION: Kidde Engineered Fire Suppression System Designed for use with 3M Novec 1230 Fire Protection

SPECIFICATION: ARGONITE Engineered Fire Suppression System

FM-200 In-Cabinet Series

SECTION FM-200 FIRE SUPPRESSION SYSTEM

SPECIFICATION: CARBON DIOXIDE ENGINEERED FIRE SUPPRESSION SYSTEM

SPECIFICATION: DRY CHEMICAL FIRE SUPPRESSION SYSTEM FOR INDUSTRIAL APPLICATIONS MODEL IND

Kidde Nitrogen Inert Gas Clean Agent Fire Suppression System

NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code

ENGINEERING SPECIFICATIONS FOR FM-200 CLEAN AGENT INDIRECT PRE-ENGINEERED FIRE SUPPRESSION SYSTEMS

KIDDE WHDR WET CHEMICAL FIRE SUPPRESSION AND INTELLIGENT CONTROL SYSTEM FOR COOKING OPERATIONS WITH ARIES-NET MULTI-LOOP INTELLIGENT CONTROL UNIT

SPECIFICATION: AlarmLine TM INTELLIGENT LINEAR HEAT DETECTION

Hospitals and Major Medical Centers

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH SHP-PRO CONTROL PANEL

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE SHP PRO CONTROL PANEL SYSTEM

SPECIFICATION FOR A TOTAL FLOOD ECARO-25 TM CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE CHEETAH Xi 50 CONTROL PANEL SYSTEM

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPUSLE VALVE, Fike FK AGENT & SHP PRO CONTROL PANEL

SECTION TOTAL FLOODING ECARO-25 CLEAN AGENT FIRE EXTINGUISHING SYSTEM

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi 50 CONTROL PANEL

June 20, 2011 PARTIES INTERESTED IN FIXED CONDENSED AEROSOL FIRE-EXTINGUISHING SYSTEMS

Technical Data. Approvals The 1-1/2 in. to 8 in. (DN40 to DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

DIVISION 21: FIRE SUPPRESSION SYSTEMS SECTION Fire Protection Systems Protecting Cold Storage and Unheated Warehouses

DV-5 Red-E Cabinet Integrated Deluge Fire Protection Package. General Description. Technical Data. Page 1 of 6 AUGUST 2018 TFP1300. Worldwide Contacts

Product Alert September 20, 2012

Technical Data. Approvals The 1-1/2 thru 8 inch (DN40 thru DN200) DV-5 Red-E Cabinets are UL Listed and C-UL Listed with the following system types:

Industrial Dry Chemical Fire Suppression System

Capital Projects Group Fire Extinguishers Specification

D. Reference Standards (Utilize latest editions available):

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPULSE VALVE, FK AGENT & CHEETAH Xi 50 CONTROL PANEL

SPECIFICATION FIKE CLEAN AGENT FIRE SUPPRESSION SYSTEM WITH IMPULSE VALVE, FK AGENT & CHEETAH Xi CONTROL PANEL

Technical Data. Working Pressure Range 20 to 250 psi (1,4 to 17,2 bar)

Worldwide Contacts.

TECHNICAL DATA OBSOLETE

SECTION KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

Design & Construction Standards, Revised January

Superior by Design The Kidde ADS TM FM-200 System

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Deluge Fire Protection Package General Description

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEUMATIC RELEASE 1. DESCRIPTION 2. LISTINGS AND APPROVALS 3.

KITCHEN HOOD AND DUCT FIRE SUPPRESSION SYSTEM

Linear Heat Detection Engineering Specifications

Model DV-5 Red-E Cabinet 1-1/2 thru 8 Inch (DN40 thru DN200), 250 psi (17,2 bar) Integrated Preaction Fire Protection Package General Description

DETECT-A-FIRE Heat Detectors

TECHNICAL DATA. 319a. January 27, 2012

Model DDX Deluge Valve

Data/ Specification Sheet

Badger Universal Control Head

TECHNICAL DATA DOUBLE INTERLOCKED PREACTION SYSTEM WITH ELECTRIC/ PNEU-LECTRIC RELEASE

C E R T I F I C A T E O F C O M P L I A N C E

NITROGEN-GENERATING SPRINKLER CORROSION INHIBITING SYSTEM

ANSUL. Twin-Agent Fire Fighting/Securing Systems Specifications. Models 450/50-B, 450/100-B, 900/100-B INDEX SPECIFICATIONS

Twin-Agent Fire Fighting/Securing Systems Specifications

SECTION FIRE-SUPPRESSION STANDPIPES

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL F SERIES DRY VALVE

CERTIFICATE OF FIRE APPROVAL

SECTION DRY PIPE SPRINKLER SYSTEMS MODEL G SERIES DRY VALVE

SECTION WET-PIPE SPRINKLER SYSTEMS EASY RISER CHECK VALVE

Series ELO-231 Upright and Pendent Sprinklers. Standard Response, Standard Coverage, General Description

special request FACTORY ASSEMBLED UPRIGHT WITH SCREW FIELD ASSEMBLED MODEL S2 SHIELD (SEE INSTALLATION SECTION) WRENCH FLATS *

Series TY-FRL 2.8, 5.6, and 8.0 K-factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description

PRODUCT MANAGEMENT BULLETIN# 171b

WORMALD INTERNATIONAL ELECTRIC VALVE ACTUATOR

TECHNICAL DATA OBSOLETE

Model G5-56 Dry (SIN RA5114) K5.6 (80 metric) Concealed Dry Pendent Sprinkler

Australian Standard. Gaseous fire extinguishing systems AS (Incorporating Amendment No. 1) AS

CHAPTER THREE SPRINKLER SYSTEM AND FM-200 AGENT SYSTEM

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION CLEAN AGENT FIRE SUPPRESSION SYSTEMS

SECTION COMMERCIAL-KITCHEN HOODS

Liberty Township Fire Department Fire Prevention Bureau. Clean Agent Fire Protection Plan Submittal Checklist

Series TY-FRL 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick & Standard Response (Light Hazard) General Description

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright, and Pendent Extended Coverage Light and Ordinary Hazard General Description

WRENCH FLATS NPT 1/2" 7/16" (11,1 mm) NOMINAL MAKE-IN. 1-1/2" (38,1 mm) 2-3/16" (55,6 mm) WRENCH NPT. (12,7 mm) NOMINAL MAKE-IN.

MSC Guidelines for Watermist Fire Suppression Systems Procedure Number: E1-03 Revision Date: 02/16/2017

CLEAN AGENTS Updates to the NFPA 2001 Standard on Clean Agent Fire Extinguishing Systems 2015 Edition

Revision May All designs must be submitted to FM Global for review and approval prior to issuing such for bids.

HORIZON MIRAGE QUICK RESPONSE LARGE ORIFICE CONCEALED PENDENT SPRINKLER VK406 TECHNICAL DATA

UFGS (August 2008) UNIFIED FACILITIES GUIDE SPECIFICATIONS

ESCUTCHEON PLATE SEATING SURFACE. 1-11/16" (42,7 mm) CROSS SECTION

Series EC K-factor Extended Coverage (Light Hazard) Pendent and Recessed Pendent Sprinklers General Description

Sinorix Engineered Fire Suppression Systems For use with Novec TM 1230 Fire Protection Fluid and HFC-227ea

A. Hydraulic calculations shall be prepared in accordance with Chapter 23 of NFPA 13 with the following exceptions:

PRODUCT LISTING DATA SHEET (Active Fire Protection Equipment)

Model JL-14 (SIN RA1812) K14.0 (200 metric) Early Suppression Fast Response Sprinkler

Module 3. Water-Based Suppression Systems (WBSS) Part II: Highlights of Code Requirements

FIRE SUPPRESSION SYSTEM

MICROMATIC STANDARD RESPONSE CONVENTIONAL SPRINKLER VK118 (K5.6) TECHNICAL DATA

SECTION FIRE PUMP AND CONTROLS

Model MBEC-14. Extended Coverage Ordinary & Extra Hazard Horizontal Sidewall Sprinklers for Metal Building Applications. Model MBEC-14 (SIN R6932)

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage

Series TY-FRB 2.8, 4.2, 5.6, and 8.0 K-Factor Upright, Pendent, and Recessed Pendent Sprinklers Quick Response, Standard Coverage General Description

Series TY-FRL 5.6 and 8.0 K-factor Extended Coverage Horizontal Sidewall Sprinklers Quick & Standard Response (Light Hazard)

Model/Sprinkler Identification Numbers

Series EC-11 and EC-14 Sprinklers, 11.2 K and 14.0 K Upright and Pendent Extended Coverage Light and Ordinary Hazard General Description

BOC FS125 The Fire Extinguishing Solution

SECTION FIRE PROTECTION. A. Examine all conditions as they exist at the project, prior to submitting a bid for the work of this section

Model G5 Series Sprinkler Summary. Listings and Approvals. G4/G5 QR Gasket culus QR G4/G5 SR Gasket culus, FM SR G4/G5

SECTION DRY-PIPE SPRINKLER SYSTEMS

Welcome to Argonite fire protection from Ginge-Kerr

TECHNICAL DATA. Factory Mutual Approval is pending for the system as a whole.

Sprinkler Identification Numbers

Transcription:

1. GENERAL SPECIFICATION 1.1. A total flooding, FM-200 fire suppression system, super-pressurized with dry nitrogen shall be installed to meet a minimum design concentration of %, by volume in all designated spaces to be protected. 2. CODES/STANDARDS COMPLIANCE 2.1. The design, installation, testing and maintenance of the above stated FM-200 fire suppression system shall be in accordance to the following codes, standards and regulatory bodies: 2.1.1. NFPA 2001 Standard for Clean Agent Fire Extinguishing Systems 2000 edition. 2.1.2. NFPA 12A Halon 1301 Fire Extinguishing Systems 2.1.3. UL 2166 Standard for Halocarbon Clean Agent Extinguishing System Units 2.1.4. Factory Mutual Approval Guide 2.1.5. ANSI B1.20.1 Standard for pipe threads, General Purpose, 1992 2.1.6. Design and installation practices set forth by system manufacturer 2.1.7. NFPA 70 - NEC National Electrical Code 2.1.8. NFPA 72 National Fire Alarm Code 2.1.9. Requirements of the Local Authorities Having Jurisdiction (AHJ) 2.2. The Fire suppression system must have the following listings and approvals: 2.2.1. FM Approved Factory Mutual Research Center 2.2.2. UL 2166 Listed Underwriters Laboratories Inc. 2.3. The manufacturer shall meet ISO 9001 requirements for the design, production and distribution of the FM-200 fire suppression systems. KIDDE FIRE SYSTEMS 1 www.kiddefiresystems.com

3. SYSTEM DESCRIPTION 3.1. All FM-200, fire suppression equipment and accessories must be manufactured by: Kidde Fire Systems 400 Main Street Ashland, MA 01721 U.S.A. phone: (508) 881-2000 URL: http://www.kiddefiresystems.com 3.2. The manufacturer shall warrant all FM-200, fire suppression system products for 18 months from date of shipment or one (1) full year from the date of installation. 3.3. The system shall be supplied and installed by a factory-authorized, Kidde Fire Systems distributor. The distributor / Installer shall be trained by the manufacturer to calculate / design, install, test and maintain the FM-200 Fire suppression system and shall be able to produce a certificate stating such on request. 3.4. The systems design can be of a Modular, Central storage and or a combination of both. 3.5. The total flooding system shall consist of a Kidde FM-200 Agent Storage Cylinder, Kidde actuation hardware and Kidde ECS series system distribution nozzles attached to a pipe network. 3.6. (OPTIONAL EQUIPMENT) The FM-200 Agent Cylinder shall have the option of a Liquid level indicator. This device will provide a reliable means other than weighing for determining the agent weight with the storage container during normal routine servicing. KIDDE FIRE SYSTEMS 2 www.kiddefiresystems.com

4. COMPONENTS 4.1. FM-200 Cylinder and Valve Assembly 4.1.1. FM-200 shall be stored in a Kidde ECS series Cylinders P/N 90-100XXX- XXX. Operating pressure of the FM-200 shall be at 360 psig @ 70 F. 4.1.2. FM-200 storage cylinders shall be provided with a safety rupture disc. An increase in internal pressure due to high temperature shall rupture the safety disc and allow the contents to vent before the rupture pressure of the container is reached. The contents shall not be vented through the discharge piping and nozzles. FM-200 containers shall be equipped with a pressure gauge to display internal pressures. The gauge shall be an integral part of the equipment and shall be color-coded for fast referencing of pressure readings. 4.1.3. A low-pressure switch shall be provided as standard equipment on all the FM-200 agent containers. A decrease in pressure will cause the normally open contacts to close, indicating a trouble condition at the CIE. The low pressure switch shall be field removable/replaceable while the container is still fully charged 4.1.4. The FM-200 Agent cylinder shall be provided with a safety rupture disc. 4.2. Kidde Actuation hardware 4.2.1. The FM-200 Cylinder valve assembly shall be actuated using a Kidde electric control head, electric / cable control head or lever operated control head. 4.2.2. (OPTIONAL EQUIPMENT): pneumatic actuation of the FM-200 Cylinder valve can be accomplished by using a nitrogen pilot Cylinder Kidde P/N s 877940 or 06-129773-00X KIDDE FIRE SYSTEMS 3 www.kiddefiresystems.com

4.3. Distribution Nozzles 4.3.1. Engineered discharge nozzles for use with the Kidde ECS series system will be made of Brass, Kidde P/N 90-1940XX-XXX 4.3.2. Each nozzle shall be located in the space per the manufacturers guidelines, Nozzles can have either a 180 or a 360-degree discharge pattern. 4.3.3. Each Nozzle discharge pattern shall be available in sizes ranging from _ NPT to 2 NPT. 4.4. Pipe Network 4.4.1. Distribution piping and fittings shall be installed in accordance with NFPA 2001, approved piping standards and FM-200 system manufacturer s requirements. 5. SUBMITTALS 5.1. Engineered Design Drawings 5.1.1. The factory-authorized Kidde Fire Systems Distributor shall provide all required installation drawings per NFPA 2001. 5.2. Flow Calculation Reports 5.2.1. The contractor shall provide the following information in the flow calculation report. 5.2.1.1. Customer Information and Project Data 5.2.1.2. Enclosure Information at a minimum enclosure information is to include Minimum and adjusted design concentrations, Minimum and maximum enclosure temperatures, minimum agent required and volume of enclosures, including non-permeable volume if applicable. 5.2.1.3. Agent information at a minimum agent information is to include Cylinder size and part number, quantity of cylinders, main and / or reserve cylinders, pipe take off direction and the floor loading for agent cylinder. KIDDE FIRE SYSTEMS 4 www.kiddefiresystems.com

5.2.1.4. Pipe network information at a minimum pipe network information is to include pipe type, pipe diameter, pipe length, change in direction or elevation, pipe equivalent length and any added accessory equivalent length. In addition, the following nozzle information shall be provided; number of nozzles and identification of enclosure location, flow rate of associated nozzle, nozzle nominal size, nozzle type and nozzle orifice area. 5.2.1.5. Detailed list of all Pipes and Pipe Fittings designed in the pipe network 5.3. Commissioning Equipment List 5.3.1. The contractor shall provide a commissioning equipment list for each installed FM-200 suppression system. The equipment list shall identify all installed equipment and configurations. 5.4. Test Plan 5.4.1. The contractor / Installer shall submit a test plan which describes how the system equipment and room integrity shall be tested. This shall include a step-by-step description of all tests and shall indicate type and location of test apparatus to be used. At a minimum, the tests to be conducted shall be per NFPA 2001 and any additional supplemental tests required by the AHJ. Tests shall not be scheduled or conducted until the engineer of record approves the test plan. 5.5. Installation Drawings 5.5.1. Four (4) sets of installation drawings for each installed FM-200 suppression system and One (1) set of the calculation report, owners manual and product data sheets shall be submitted to the end-user / owner. 5.5.2. Upon completion of installation and commissioning acceptance, two (2) sets of As-Built installation drawings and One (1) set of the calculation report for each installed FM-200 suppression system shall be given to the owner / end-user for use and reference. KIDDE FIRE SYSTEMS 5 www.kiddefiresystems.com

5.6. Operation and Maintenance Manuals 5.6.1. Two (2) copies of the Kidde ECS FM-200 fire suppression system, Operation and Maintenance Manual shall be submitted after complete installation. 6. SYSTEM INSTALLATION AND COMMISSIONING 6.1. FM-200 Fire Suppression System Equipment 6.1.1. The contractor shall install the system in accordance with the manufacturer s installation, operation and maintenance manual. 6.2. Training Requirements 6.2.1. The contractor shall be certified and trained by the manufacturer on installation, design and maintenance of the Kidde ECS, FM-200 fire suppression systems. 6.3. Routine Maintenance 6.3.1. Routine maintenance shall be performed as recommended by the manufacturer s installation, operation and maintenance manual. At a minimum the routine maintenance will include the following: 6.3.1.1. Visual Check of Pipe network and distribution nozzles per the operation and maintenance manual. 6.3.1.2. Weight and pressure of the FM-200 Agent cylinder per the operation and maintenance manual. 6.3.1.3. Inspect all cylinders and equipment for damage per the operation and maintenance manual. KIDDE FIRE SYSTEMS 6 www.kiddefiresystems.com