The Temperature and Relative Humidity Control in Cushing Library

Similar documents
Song Deng, P.E. Assistant Director Energy Systems Laboratory Texas A&M University College Station, TX

Submitted to. Texas A&M University-Corpus Christi The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge

Continuous Commissioning: A Valuable Partner to Retrofit Projects

Computing Services Center

Submitted to. Texas A&M University at Galveston The Texas A&M University System. Submitted by. Yeqiao Zhu Dan Turner David Claridge

Submitted to. Texas A&M University at Commerce The Texas A&M University System. Submitted by. Guanghua Wei Craig Campbell David Claridge Dan Turner

Technical Assignment 3 11/15/04. Executive Summary

Andrea Borowski The Pennsylvania State University University Park, PA November 11, 2002 Consultant: Dr. Bahnfleth Technical Assignment M-3

Civil Engineering Building

Impacts of Optimized Cold & Hot Deck Reset Schedules on Dual Duct VAV Systems - Theory and Model Simulation

Description of All Alternatives Considered-

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

EarthWise System Seminar

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

Appendices. Included in this section are

Auburn University Basketball Arena:

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

Optimizing Electric Humidifier Operation with an Air Side Economizer

Retrocommissioning Findings Summary: Building X #1 Priority: Major Comfort/Control Problems

Implementation of the Laboratory Air Handling Unit Systems (LAHU)

Architectural Alliance Incorporated MDP CONSULTING ENGINEERS, INC N 11th Street Beaumont, TX 77702

Harrington Tower Building

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

HVAC Mandatory Provisions Part II, Page 1

Physical Plant Complex

INTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings

Redesign of Bennett Hall HVAC System

Urbana Free Library HVAC Analysis. Prepared for the Urbana Free Library. Prepared by Paul Boland, P.E., and Nathan Alderman, E.I.T.

Architectural Engineering Senior Thesis Mechanical System Redesign

Continuous Commissioning of Commercial Kitchen and Dining Facilities Case Study

Continuous Commissioning Report

COMcheck Software Version Mechanical Compliance Certificate

ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery. Steven T. Taylor, PE Principal Taylor Engineering

Mechanical Technical Report 3. Mechanical Systems Existing Conditions Evaluation

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

Benefits Offered by Passive Dehumidification Wheel Speed Control

SYNOPSIS. Part-Load Control Strategies for Packaged Rooftop Units. In this issue... Bin Hour Profile Charlotte, NC

Mechanical Systems Existing Conditions Evaluation. Instructor: Dr. Bahnfleth. November 12, Thesis Building Sponsor s: INOVA Fairfax Hospital

Applied Packaged Terminal Air Conditioner with Catalog Top-Mounted Hydronic Heat

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

NON-REVERSING, 100% OUTSIDE AIR HEAT PUMP FOR HEATING AND COOLING

SAMPLE. added benefit of reduced operating costs during low demand periods, such as spring and fall.

Data Aire Mini Ceiling Systems 1, 1.5, 2, and 2.5 ton capacities R-410A. ISO 9001 Certified

Feature Summary. I. System

Technical Report #3 Mechanical Systems Existing Conditions Evaluation

Existing Mechanical System Operation

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney

Continuous Commissioning SM Report. For. Wing 86, Chemistry Complex (Building # 376) Hui Chen Song Deng Homer L. Bruner, Jr., CEM.

ENERGY EFFICIENCY WITH SUPERIOR INDOOR AIR QUALITY

Design Standard. Thermal Systems (Chilled Water and Hot Water Systems) Detailed specifications follow. CHW AND HHW SUPPLY TEMPERATURE RESET

4. OVERVIEW OF MECHANICAL SYSTEM

Improving Control of Dual-Duct Single-Fan Variable Air Volume Systems

Selected Laboratory Energy Efficiency Measures

Job Name Control Systems Description Date

product application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM

Mechanical Compliance Certificate

DEHITMIDlFICATION WITHOUT REHEAT USING FACE AND BYPASS DAMPERS

Technical Assignment 3. Mechanical Systems Existing Conditions Evaluation

A New Approach to Museum HVAC Design ASHRAE TECHNOLOGY AWARD CASE STUDIES

CARRIER edesign SUITE NEWS. Modeling 100% OA Constant Volume Air Systems. Volume 6, Issue 1. Page 1 Modeling 100% OA Constant Volume Air Systems

DX-9100 Applications from Engineering Services

AIR-CONDITIONING SYSTEMS AND APPLICATIONS. Abdullah Nuhait Ph D. King Saud University

TECHNICAL REPORT III Mechanical Systems Existing Conditions

CASE STUDIES OF HIGH HUMIDITY PROBLEMS IN HOT AND HUMID CLIMATES IN THE UNITED STATES

1 Air Handling Units In ICE

DIGI-VAV APPLICATIONS

H3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE / GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNTS. RQ Series.

Achieving Dry Outside Air in an Energy-Efficient Manner

MECHANICAL INFRASTRUCTURE ASSESSMENT FOR VICTOR VALLEY COLLEGE

FAARM-Underground Facility. Conceptual Design Review. Mechanical Systems. Dunham Associates, Inc.

I. Introduction and Arrangement

VERTICAL AHU ENGINEERING SPECIFICATIONS BULLETIN

AHRI 920 & ASHRAE 90.1

Product Data. Features/Benefits. OMNIZONE 50BRN,BZN Water-Cooled and Remote Air-Cooled Indoor Self-Contained Systems. 5 to 20 Nominal Tons

HVAC Controls Upgrades: Requirement Details ( )

TECAM S.A. harmony. 5PZA Direct Expansion. Air Conditioning Equipment Manufacturer. R-410A PRECISION UNIT 2 Ton 6 Ton / 60 Hz. Tecnología Ambiental

Technical Development Program

Summary Comparison of Simulation Program Features

ASHRAE Standard 90.1 Energy Requirements Wrap-Around Heat Pipes

RN/RQ. Series PACKAGED ROOFTOP UNITS, AIR-SOURCE HEAT PUMPS, WATER-SOURCE/ GEOTHERMAL HEAT PUMPS, & OUTDOOR AIR HANDLING UNITS.

MASS AND HEAT RECOVERY SYSTEM SALAH MAHMOUD HINDAWI DIRECTOR HINDAWI FOR ENGINEERING SERVICES & CONTRACTING NEW DAMIETTA, EGYPT

Sequence of Operations (excerpt)

Prescriptions for Critical Healthcare Cx. John D. Villani, P.E. Associate Grumman/Butkus Associates

control sequences model QST / EST Series Table 47: QST / EST Analog Electronic Control Strategies Fan Powered Air Terminals

Shelf Units R-407C. 2, 3, and 4 ton. ISO 9001 Certified

ASHRAE WILL GIVE YOU THE WORLD. This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee

PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM ENERGY EFFICIENT DEHUMIDIFICATION

CONTROLLED CHILLED BEAM PUMP MODULE

COMcheck Software Version Mechanical Compliance Certificate

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

AIR HANDLING SYSTEM RETRO-COMMISSIONING TRENDING ANALYSIS

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available.

HCU Systems for Industrial Applications. Rob Smith National Accounts Manager March 7, 2011

Lynergy Comfort Control SCR Electric Heater Application Guide

APPLICATION GUIDE BEAMS

To Keep Docs Cool, Dry and Happy

Digital Precise Air Control - DPAC

Transcription:

The Temperature and Relative Humidity Control in Cushing Library Chenggang Liu Research Associate Song Deng Assistant Director Homer L. Bruner, Jr., CEM Mechanical Systems Specialist Utilities Office of Energy Management Physical Plant Department W. Dan Turner, Ph.D., P.E. Professor & Director David E. Claridge, Ph.D., P.E. Professor & Associate Director ABSTRACT Cushing Library located on TAMU campus is a special building, which needs precise temperature and relative humidity control, because it stores a number of rare collections and memorial books. There are five air-handling units (AHUs) serving the building. This paper will concentrate the unit, which serves the book stacks. This AHU is a multiple zone, constant air volume (MZCAV) system, with reheat and direct digital control (DDC). It has a standard cooling coil, glycol cooling coil, steam humidifier, and heat recovery. The chilled water to the standard cooling coil is served by the chilled water on the campus. There is a glycol chiller for the glycol cooling coil for added dehumidification ability. Because of programming problems and hardware problems, the relative humidity was t controlling properly. In this paper, the new control program for temperature and relative humidity control is implemented and the energy savings from the new control program is estimated. The temperature and relative humidity are w under control. GENERAL INTRODUCTION The Cushing Library is a 3-story building with a basement. The total floor area is about 36,100 ft 2. The west part of the building is mainly office space, conference rooms and reading areas. The east part of the building contains book stacks with a total area of 10,500 ft 2. This library is a special building, because it stores a number of collections and memorial books, such as historical drawings, paintings and books. Therefore the book stacks need t only precise temperature control but also exacting relative humidity controls. The physical, or more accurately mechanical, properties of cultural materials have been largely humidity (RH). Fluctuations of RH greater than ± 5% are considered responsible for the cracking of wood Table 1. The air handling system performance responsible for the current standard museum environment of around 72 F and 50% ± 5% relative Part/Equipment Name Performance Data Fan Fan CFM 12,500 Total Static (inwg) 6.0 Motor HP 25.0 Standard Cooling Coil EDB / EWB ( F) 72.4 / 62.1 LDB / LWB ( F) 50.5 / 50.2 Total / Sens MBTU/H 424.3/ 296.9 GPM 76.0 EWT /LWT ( F) 45.0 / 56.2 20% Glycol coil EDB / EWB ( F) 50.5 / 50.3 LDB / LWB ( F) 42.8 /42.6 Total / Sens MBTU/H 227.3 / 104.0 GPM 60.0 EWT /LWT ( F) 38.0 / 45.7 Heat Pipes (recovery) Precool Section Reheat Section EDB / EWB ( F) 81.0 / 65.2 42.2 / 41.2 LDB / LWB ( F) 63.9 / 59.2 59.3 / 49.4 Precool/Reheat ( F) 17.1 17.1 Heat Trans MBTU/H 235.1 235.1 Humidifier LBS/H 173.0 Max KW 124.0 Preheat Coil Air CFM 3,200 EAT / LAT ( F) 44 / 104 EWT / LWT ( F) 180 / 160 GPM 26.0 MIN MBTU/H 267 Reheat Coil (TYP of 4) Average Air CFM 3,700 EAT / LAT ( F) 44 / 104 EWT / LWT ( F) 180 / 160 GPM 24.0 MIN MBTU/H 236 Glycol Chiller Total Tons 21.0 Max KW 29 GPM 60 EWT /LWT ( F) 46 / 38 furniture and the flaking of panel and canvas supported paintings. While RH related damage is

clearly established, temperature changes (independent of RH) are a subtler source of considerable damages. The real problem is that low temperature severely embrittles materials such as paints. Rapid change or excessive fluctuation of temperature or RH is ather cause of damage. Before July 2000, the relative humidity of the stacks was t controlling and the humidity alarm has been on for some time. Most of the time the humidity alarm was on, because the relative humidity was too low, around 35%. AIR HANDLING SYSTEM The air-handling unit (AHU), serving the book stacks located on the east part of the building from the basement to the 3 rd floor, is a multiple zone, constant air volume (MZCAV) system, with reheat and direct digital control (DDC). Figure 1 demonstrates the air handling system for the book stacks. The system employs a preheat coil, heat recovery, standard cooling coil, glycol cooling coil, steam humidifier, and zone reheat. The chilled water to the standard cooling coil and hot water to preheat and reheat coils are served by the chilled water and hot water s on the campus. There is a glycol chiller outside of the building for the glycol-cooling coil for added dehumidification ability. The AHU is equipped with heat pipes as a heat recovery system. There is a bypass on the reheat section of the heat pipes. The bypass damper (rmally open) is damper is closed before zone reheats on. Otherwise, the bypass damper will be open. An electrical steam humidifier generates steam for humidification. Table 1 demonstrates equipment performance data. The design airflow rate of the AHU is 12,500 CFM. The air temperature can be reduced from 72.4 F to 50.5 F by the standard cooling coil. The glycol coil has a capacity to treat air from 50.5 F to 42 F for further dehumidification. The heat pipes have a max heat transfer of 235.1 MBTU/H from precool section to reheat section. It results in the max energy saving of 235.1 MBTUH on both reheat and cooling energy usages. The humidifier has a capacity of 173 lbs/hr. Preheat and each zone reheat has a min heating capacity of 267 MBTU/H and 236 MBTU/H respectively. OLD CONTROL SCHEME AND ISSUES Zone temperature and relative humidity were controlled at 65 F and 50% ±5%. The glycol coil served by the glycol chiller is designed for added dehumidification. But according to the chiller control demonstrated in Figure 2, the glycol chiller was on all the time while the AHU was on. It cost unnecessary electricity consumption and hot water consumption, when the standard cooling coil can handle stack temperature and relative humidity by itself. Figure 3 demonstrates chilled water valve, glycol valve and heat pipes bypass damper controls. The Return air Preheat coil Standard cooling coil Heat pipes Glycol coil Outside air Glycol chiller Discharge air Zone reheat (typical of 4) Humidifier Bypass damper Figure 1. Air handling system diagram interlocked with heat pipes damper (rmally closed). When the stacks need reheat, the bypass chilled water control valve and glycol control valve were controlled by two control s separately. The

heat pipes bypass damper was controlled by three control s. This resulted in the zone temperature and relative humidity t controlling properly. For instance, the glycol valve was controlled to maintain max RH at its setpoint of 55% and temperature after the glycol coil at its setpoint of 38 F. When max zone RH was lower than 55% and temperature after the glycol coil is higher than 38 F, the RH control would close the glycol valve to reduce dehumidification, but the temperature control would open the valve to reduce the temperature. This caused the relative humidity to fluctuate. Also the 38 F air temperature setpoint after the glycol coil, point (a) in Figure 6, is the main reason for causing on AHU on chiller pump AHU on proof off chiller pump chiller pump on proof on chiller off chiller Figure 2. Chiller on/off control diagram (old) max RH setpoint (55%) reverse relay chilled water valve max RH the valve full open switch relay glycol valve (60 F) hi/lo lo bypass damper max zone temperature (65 F) temp after standard coil temp after glycol coil (55 F) (38 F) Figure 3. Chiller water valve, glycol valve and heat pipes bypass damper control diagram (old)

the relative humidity too low. For example, when zone temperature is 65 F at its setpoint and humidifier is off when out side air relative humidity is higher than 75%, seeing Figure 4, the zone RH would be around 35%, point (b) shown in Figure 6. In this situation, the RH alarm would be on. When the out side air relative humidity was lower than 75%, the humidifier was commanded to be on to maintain RH at its setpoint. But if the temperature after glycol is 48 F, point (d) instead of 38 F, the humidifier was t commanded to be on. For the chilled water valve, it is very hard or impossible to maintain 55 F after standard coil and 55% of max zone RH under the control of two control s. For the heat pipes bypass damper, the direct control min RH could t maintain zone temperature at its setpoint, because the bypass damper is rmally open. The temperature control should be direct control for the bypass damper to maintain zone temperature at its setpoint. Figure 4 demonstrates the humidifier control. There are five humidity sensors located in room 005, 115, 207, 208, and 305. The humidifier is controlled to maintain minimum zone relative humidity at its setpoint of 45%, when outside air RH is lower than 75%. The humidifier is off, when outside air RH is higher than 75%. When outside air RH is between 70% and 75%, the humidifier is controlled by the control output weighted with linear outside air relative humidity as below. Humidifier = control output *(75 RHoa) / 5 min RH setpoint (45%) humidifier = output RHoa < 70% output Here RHoa is outside air relative humidity. Figure 5 demonstrates zone reheat valve control. The terminal equipment controllers (TEC) control reheat valves to maintain zone temperature at its setpoint of 65 F. This setpoint is as same as the setpoint of the heat pipes bypass damper control. To save heating and cooling energies, the bypass damper humidifier = output(75-rhoa)/5 70<RHoa>75 zone temperature off humidifier setpoint (65 F) TEC reheat valve Figure 4. Humidifier control diagram (old) Figure 5. Zone reheat valve control diagram (old) Figure 6. Zone temperature and RH control point

(70 F) hi / lo lo reverse relay chilled water valve zone max temp max RH setpoint (53%) chw valve full open abd glycol valve open max RH on chiller max RH setpoint (55%) glycol valve off chiller Figure 7. Chiller water valve, glycol valve and chiller control diagram (new) should be closed earlier than the zone reheat valve is open. To say the least, the existing control program was t working. NEW CONTROL SCHEME AND OPERATION For proper room temperature, RH requirements, and energy management, the zone temperature setpoint was increased from 65 F to 68 F for heating and 70 F for coiling. The relative humidity setpoint is 50% ±5%, the same as before. The new setpoints of 68 F and 50% ±5%, point (c) in Figure 6, require discharge air temperature setpoint of 48 F for the glycol coil, instead of 38 F. It reduces electricity consumption of both the glycol chiller and the electrical humidifier. Figure 7 demonstrates the new control scheme for the chilled water valve, glycol valve and chiller. The plant chilled water control valve is modulated to maintain zone-cooling temperature at its setpoint of 70 F and max zone RH at 53% of its setpoint. The humidity setpoint for chilled water valve is 2% lower than the setpoint of 55% for the glycol valve, so that the glycol valve will be open for further dehumidification, after the plant chilled water valve is fully open. The glycol chiller will cycle on, as it is needed. Figure 8 demonstrates the new control scheme of heat pipes bypass damper and zone reheat valve for zone reheat only. The temperature setpoint for heat pipes bypass damper is 69 F, which is 1 F higher than the setpoint of 68 F for the zone reheat valve, so that the reheat valve will be open for further reheat, after the heat pipes bypass damper is fully closed. The relative new control schemes were implemented during commissioning by the Continuous Commissioning (CC SM ) group at the (ESL), Texas A&M University (TAMU). The CC SM process was conducted from January to March 2001, under direction of and in cooperation with the TAMU Physical Plant Energy Office. The performance of the new control program for temperature and humidity control in Cushing Library was observed over a oneyear and a half period. It is functioning well. The temperature and relative humidity of the book stacks are under control and the RH alarm has remained off. Under the old control program, the glycol chiller was on all year around. But with the new control program, the glycol chiller was on only when outside air was hot and humid, from July to September. During the rest of the year, the chiller was off. The estimated electricity saving for the glycol chiller is $12,900 annually. (69 F) (68 F) max zone temperature TEC bypass damper reheat valve Figure 8. heat pipes bypass damper and reheat valve control diagram (new) CONCLUSION The air handling system for the collections and memorial book stacks in Cushing Library was studied and the control schemes are optimized in this paper. The new control schemes for the temperature and

relative humidity control was generated and implemented. Over a year and a half period the new control schemes are functioning well. The temperature and relative humidity of the book stacks were improved and annual electricity saving of $12,900 for the glycol chiller only is estimated. ACKNOWLEDGMENT The work of this paper was sponsored by Texas A&M University, Physical Plant. We greatly appreciate support for this work from the Office of Energy Management and from other members of the Continuous Commissioning Group, Energy Systems Laboratory,. REFERENCE 1. Marion F. Mecklenburg and Charles S. Tumosa. 1999. Temperature and Relative Humidity Effects on the Mechanical and Chemical Stability of Collections, ASHRAE Journal, April 1999, pp. 77-82. 2. C. Liu, W. Dan Turner, David E. Claridge, Song Deng, Homer L. Bruner, Jr. 2002. Result of CC Follow-up in the G. Rollie White Building, Proc. Of the 13 th Symposium on Improving Building Systems in Hot and Humid Climates, pp. 96-102. 3. John Murphy, 2002. Dehumidification performance of HAVC Systems, ASHRAE Journal, March 2002, pp. 23-31. 4. 2001 ASHRAE Handbook, Fundamentals. Chapter 6, Psychometrics.