Swegon CASA. duct coils for heating. the supply air

Similar documents
Air heater/cooler in combination with ground source heat pump

Swegon Home Solutions CASA. W3 Smart. Installation, commissioning and maintenance instruction. W3_f_EN-t

Swegon Home Solutions CASA. W9 Smart. Installation, commissioning and maintenance instruction. W9_e_EN-t

CASA. W5 Smart. Installation, commissioning and maintenance instructions. W5_d_EN-t

Series. Suspended air supply units with the air capacity up to 4100 m 3 /h in the sound- and heat-insulated casing with the water heater

Series VENTS VUT R WH ЕС

Swegon Home Solutions CASA. R3 Smart. Installation, commissioning and maintenance instruction. R3_d_EN-t

Silencer Preheater unit Electric post-heating unit Water circulated post-heating unit CO 2 sensor %RH sensor Pressure difference switch LON converter

Swegon CASA W130. Ventilation unit with counter-flow plate heat exchanger HOME VENTILATION

Swegon Home Solutions CASA. W4 Smart. Installation, commissioning and maintenance instruction. W4_c_EN-t

TopMaster Air Handling unit. Technical data

Series VENTS MPA...W. Supply units with the air capacity up to 6500 m 3 /h in the compact sound- and heat-insulated casing with water heater

PRODUCT DATA COMFORT 450 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 450 m 3 /h

Swegon Home Solutions CASA. R2 Smart. Installation, commissioning and maintenance instruction. R2_a_EN-t

Swegon CASA R120. Instructions for installation, operation and maintenance. R120_h_EN-m

PRODUCT DATA COMFORT 600 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 800 m 3 /h

Series VUT PW EC. wool internal heat and sound-insulating layer for VUT PE/PW 350, 600, 1000 units and 50 mm for VUT PE/PW 200, 3000 units.

Primo Hotel. General. Indoor climate units for hotel rooms

CAW Ceiling-mounted fan heaters for hot water

panel filters with filtering class G4. Supply filter F7 can be supplied with the few models.

panel filters with filtering class G4. Supply filter F7 can be supplied with the few models.

Swegon CASA W80 EC, version B

Swegon CASA R120. Ventilation unit with rotary heat exchanger HOME VENTILATION

Contents. Technical Description of the Air Handling Unit General, Specification Function, Functional Sections

NKW. Heater series HEATERS

VEX100 series Air handling units with cross-flow heat exchanger

Heat pump & cooling unit in one

PRODUCT DATA COMFORT 1200 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 1400 m 3 /h

TopMaster Air Handling Unit

CUMULUS CUMULUS. Key figures. Construction. Function Integrated chilled beams

PRODUCT DATA COMFORT 5000 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 5300 m 3 /h

eco PREMIUM ENERGY RECOVERY UNIT» Technical instruction

Topvex SR03, SR04, SR06 Compact Air Handling Unit

Cassette units Model Comfort Circle. - heating - cooling - ventilation

VEX250H with rotary heat exchanger and EXact control system

EC A1/L2 RIS P EKO RIS 400 P E 0.9 EKO 3.0 AIR HANDLING UNITS. Application

Instructions for the BASIC BCRW Fan, Sizes General

Swegon CASA. R85, version B. Instructions for installation, operation and maintenance. R85B_h_EN-m

KOMFORT EC DB Suspended heat recovery air handling units

VEX280H with rotary heat exchanger and EXact control system

OVERVIEW and SYSTEM GUIDE. Swegon CASA. Residential ventilation for optimal operating economy and the greatest comfort.

RIS V. AHU with heat recovery. exchanger. AHU is used for ventilation of houses and other heated areas. Stouch and TPC remote control devices.

Installation Instruction

Swegon Home Solutions CASA. R3 Smart. Installation, commissioning and maintenance instructions. R3_f_EN-t

Supply air unit VEKA Installation & Maintenance

EC A1/L2 RIRS V EKO AIR HANDLING UNITS

DOMEKT. Residential ventilation units

PRODUCT DATA COMFORT 300 TOP BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 325 m 3 /h

PRODUCT DATA COMFORT 450 BY NILAN. Ventilation & passive heat recovery. Passive heat recovery. < 450 m 3 /h

Operation and maintenance instructions

ADAPT Parasol EXb. Installation. Installation Commissioning Maintenance A1, B1

TECHNICAL SPECIFICATION

COMPACT AIR HANDLING UNIT. CompAir RW. Technical Brochure

DK Sparepart Pricelist Air Handling Units with DK specifications. Pingvin XL eco EC DK. Water heating /cooling duct coil

Proper maintenance of tunnel finisher will prolong its life and enable the equipment to produce the best possible quality.

BTBa. FLUSHLINE Ventilated chilled beam for cooling, heating and ventilation. BTBa

Fan coil unit KL. Wall unit Ceiling unit

MAXI CENTRALIZED VENTILATION WITH HEAT RECOVERY

Air Handling Unit. REC Temovex Blue 4 NEW! Experts on indoor climate in low-energy houses

Fan heater SWT Ceiling mounted fan heater with water heat

HRV-IP. Ceiling Type Heat Pump Heat Recovery Unit

RIS V EKO A1/L2 RIS 700 V E L EKO 3.0 AIR HANDLING UNITS. Application

39HX. High-efficiency dual-flow air handling unit PRODUCT SELECTION DATA. Plug & play unit (built-in control) Class A+ across entire range

COMPACT Air & Heat. Contents

Swegon CASA R85. Ventilation unit with rotary heat exchanger HOME VENTILATION

WINDOW YORK TECHNICAL GUIDE. Single package Cooling only and Heat pump. Models YO-YM R407C YO V6 G YO V7 G

Swegon CASA R85, version B

GLOBAL LP. Ceiling-mounted ventilation unit with plate heat exchanger

EC L2. and humidity sensors. All units are supplied tested and ready to install.

Second Revision No. 1-NFPA 17A-2016 [ Section No ] Submitter Information Verification. Committee Statement. 1 of 14 6/22/2016 3:15 PM

Hi-Pres. Self Contained A/C Unit HI-PRES MARINE & OFFSHORE

Complements and Accessories

Danfoss Air Heating Surfaces

AC25. Art.nr:

BACK BAR REFRIGERATION Installation, Operation and Maintenance Instructions

Halton Rex 600 Basic R6B - Active chilled beam

IN LINE MIXED FLOW DUCT FANS AND ELECTRIC HEATER TD-MIXVENT HEATING System

PRODUCT DATA COMBI 300 POLAR BY NILAN. Ventilation with passive & active heat recovery. Active heat recovery. Passive heat recovery.

INSTALLATION AND OPERATING INSTRUCTIONS GN2. HIGH EFFICIENCY CAST IRON BOILER FOR LIQUID and/or GAS FUELS

290 on. 286 on. Comfortable climate with pre-heated, filtered supply air. Fresh air boxes ALB WW MODEL WITH WARM WATER HEATING

EBAC MODEL CD425 ( ) INDUSTRIAL DEHUMIDIFIER OWNER S MANUAL

Novenco Air Handling Units

Heat Recovery Unit HERU. web-version

TopMaster Air Handling unit. Installation instructions

SPECIFICATIONS for AIR CONDITIONING CONTROLLER ZONE CONTROL

USER S MANUAL HSC-14/18/24/24A

FLOWAY. Floway Range. The dual-flow air handling unit with heat recovery guaranteeing an Economical and Durable solution. use.

Installation instruction

Technical documentation Fan coil unit

Original instructions AR

HEATER, AIR CONDITIONING AND VENTILATION

Climaster ZerAx. Eco-designkrav. Climaster ZerAx type ZCN-M guide GB

LONGONI ENGINEERING SRL

KOMFORT EC S5B KOMFORT EC D5B KOMFORT EC S. Heat and Energy Recovery Ventilators

145SE. Vallox. Operating, maintenance and technical instructions

PGDX Rectangular duct coolers with DX coil

Smart Smart IR. Service instruction SALES DATE MANUFACTURED ON (DATE): APPROVAL MARK SOLD. model (check applicable) is recognized as serviceable

238 Series. Industrial/Commercial Electric Unit Heater. Owner s Manual

READ AND SAVE THESE INSTALLATION INSTRUCTIONS

CHH - Active Chilled Beam. Halton CHH. Active Chilled Beam

Transcription:

Swegon CASA the supply air duct coils for heating Instructions for installation, operation and maintenance For design engineers, installation engineers and service personnel SDHW_c_EN m

! Important information Qualified personnel only Only qualified personnel should carry out installation, configuration and commissioning. Freeze protection If there is a risk of freezing, the duct heater is equipped with freeze protection. The freeze protection switches off the ventilation unit s fans and closes an outside air damper if fitted and activates the alarm. The duct coil can burst if the water freezes in the coil, which in turn causes the pipe system to drain and water damage can occur. Important details to consider during installation The coil must be installed in a space where there is a drain. The coil must not be installed directly next to the ventilation unit or a bend in the duct, as the air that passes over the coil will then not remain even resulting in an impaired output. Commissioning The duct connections on the duct coil must be capped during transport, when in storage and during installation. Make sure that the duct coil and the ducts are clean and that there are no loose objects in them before you commission the ventilation system. Ensure that the heating pipes are mounted and insulated and that the venting connections and shut-off valves are mounted. Do not commission the duct coil until all carpentry work that produces large quantities of sanding dust or other impurities has been completed. CWK 125 H 255 B 313 D 125 H D H+8 CWK 160 H 255 B 313 D 160 B CWW 125 K 276 L 356 Leave at least 40 cm service space in front of the door. CWW 160 K 276 L 356 NOTE! The manual s original language is Finnish. 2 www.swegonhomesolutions.com 17-5-2016 Swegon reserves the right to make changes.

1. General Description A separate coil for installation in ducts, uses the water in the heating system. Can be used in the supply air duct for heating the room. Control of heating can be completely transferred to the CASA Smart control technology. 2. Project planning Remember when planning: find out the heating system's temperature and s, as well as the coil s pressure loss in order to size the pump and pipe system. Swegon recommends its own heat pipe system for heating coils. Take into consideration the pressure loss caused by the coil when sizing the airs and selection of the ventilation unit. Remember the shut-off damper that is placed in the outdoor air duct! The damper control signal is taken from the circuit board on ventilation units equipped with Smart control system. 24 VDC, max. 2 W. (ON/OFF.) 3. Installation 3.1. Coil installation in the duct system The duct coil can be mounted in supply air duct. The duct is connected to the duct coil s Ø125 mm or Ø160 mm connection sleeves. The coil is suspended with the help of a shelf or another approved manner. The weight of the coil in an operating state is about 5.5 kg. The ducts are pushed into the sleeves and locked with pop rivets. Keep in mind that the ducts insulation must run right up to the unit. After the duct coil, the supply air duct is thermal insulated using 10 mm thick mineral wool in cold air space (general instruction). 3.2. Water connection The following must be taken into account when connecting the heater/chiller to the pipe system: 1. Push-on couplings must be used for the connection of the heating/cooling coil. Valve connection with threaded couplings: 2-way valve (½" int. g., kvs 0.4) Belimo R3015-P4-S1 2. The duct coil s connection pipes must not be subjected to distortion or bending movements when the connections are made. Counterhold with a tool when assembling the connections. The valve s actuator can be mounted horizontally or so that the actuator is above the pipe lines. 3. Make sure that the unit's expansion forces and the self-weight of the pipe system does not load the coil connections. 4. In order to facilitate venting of the coil, the water is usually led in via the lower tube. The venting valve is generally positioned on the coil or on the highest point of the unit. Heating pipes must be fitted with filters. 5. The heating/cooling coil must be connected so that the pipe system can be drained easily, for example, during repairs, extended periods of downtime or when there is a risk of freezing. 6. Immediately after filling the pipe system with water, you must check that the duct heater and its connections do not leak. A possible leak can cause water damage. The duct heater can be installed horizontally or vertically in the duct with an optional direction of air. 17-5-2016 Swegon reserves the right to make changes. www.swegonhomesolutions.com 3

3.3 Electric and control cables Temperature sensor T4 is mounted in the supply air duct after the coil in the direction of and sensor cable is routed to the unit's circuit board. The temperature sensor is connected to the circuit board s T4 outlet. (If there is already a sensor connected in the terminal T4, remove it.) The heating coil kit includes temperature sensor T4 (604930) with 3 m cable. The cable for freeze protection sensor T6 (included in the heating coil kit) is routed to the coil s return pipe and the sensor is taped to the pipe surface. The temperature sensor (603048) is connected to the circuit board s T6 outlet. The valve motor s control signal and power supply are connected to the circuit board outlet TEMP CTRL OUTPUT, see the figure below. The cable for the room temperature sensor T8 (accessory PRTG) is routed from the circuit board outlet T8 to a suitable location in the home, such as the entrance hall, where sunlight does not penetrate and where the temperature is uniform.! Important! Only a qualified electrician may make the electrical connections. 4. Use Smart-piirikortti TEMP CTRL OUTPUT +24V 0-10V GND 2 3 1 5 BELIMO HRYD24-SR Control of the unit from a Smart control panel. The duct coil s settings can be changed in the menu (Main menu/settings(1234)/temperature Controller). The temperature setting changed in the Main menu (Temperature) with the reset button. Main menu Alarms Temperature Display Diagnostics Weekly programs Information Settings 20 C From the temperature menu on the Smart control panel you can select either: A) Standard supply air temperature level Supply air regulation mode: from the control panel, select External reheating and then select the setting value for the supply air temperature, that the coil strives to produce during the heating season, for example, 20 ºC. B) Room temperature control Temperature Controller Control type Supply air Fresh air limit 8 C Post cooling Ext. afterheat Ext. preheat/cooling The settings window in standard mode, control mode supply air Room air control mode: this function strives to keep the room air at the set value during the heating season. You can set the upper and lower limits via the control panel for the air blown into the room (depending on the heating system temperature.) The heating coil is controlled by the room temperature, according to the options: 1. By a temperature sensor UP1/UP2 included in a CASA Smart control panel. (Control panel 1 or 2) 2. By a separate room temperature sensor T8 (accessory). 3. By unit's internal extract air temperature sensor T3. 4 www.swegonhomesolutions.com 17-5-2016 Swegon reserves the right to make changes.

Temperature Controller Control type Room air Fresh air limit 8 C Supply control min value 16 C Supply controller max value 20 C Room air T3 Post cooling Ext. afterheat Ext. preheat/cooling Room air regulation as the regulation mode Temperature Controller Control type Room air Fresh air limit 8 C Supply control min value 16 C Supply controller max value 20 C Room air T3 Post cooling Ext. afterheat Ext. preheat/cooling 5. Service! Important! Stop the ventilation before servicing. The coil must be cleaned regularly to get full output from of the heater/cooler. The length of the service interval is entirely dependent on the cleanliness of the air, and of how well the filters and unit are maintained in general. The duct coil is easy to clean if you remove the heater/ cooler cover. The inlet side of the coil is cleaned first with a brush, and then you can clean the entire coil with compressed air, water or steam. Blow or rinse dirt away from the outlet side toward the inlet side. Exercise care so that the thin edges of the fins are not damaged. External reheating in operation 17-5-2016 Swegon reserves the right to make changes. www.swegonhomesolutions.com 5

6. Wiring example Venting T6 TV1 M SD1 OUTDOOR AIR SUPPLY AIR SUPPLY AIR DUCT 24 VDC, 2W T1 T3 HX 2*0,5 3*0,5 T4 2*0,5 2*0,5 Modular cable PMK20 T8 Room sensor PRTG Control panel s temperature sensor Room s summer temperature setting e.g. 23 degrees RESET DDC T8 T4 T1 T7 T6 T5 T3 T2 SUPPLY EXHAUST ELECTRIC AFTERHEAT TEMP OUTPUT CO2 INPUT %RH INPUT PUMP CTRL SD1 TV1 6 www.swegonhomesolutions.com 17-5-2016 Swegon reserves the right to make changes.

CASA heating coils for the supply air duct: CASA heating coils ØD mm B mm H mm Øo.d. mm F G mm K mm L mm Pipe system s int. volume I CWW 125 125 313 255 10 175 40 276 356 0.20 5.5 CWW 160 160 313 255 10 175 40 276 356 0.42 5.4 Weight, kg CWW 125 Water temperature In/out 80 ºC/60 ºC In/out 60 ºC/40 ºC In/out 55 ºC/45 ºC Air Air in Air out Power Water Air out Power Water Air out Power Water l/s m 3 /h Pa ºC ºC kw l/s Pa ºC kw l/s kpa ºC kw l/s Pa 25 90 4 0 63.7 2.0 0.02 2.6 45.2 1.4 0.02 1.5 44.9 1.4 0.03 5.1 25 90 4 7.5 65.0 1.7 0.02 1.7 46.0 1.1 0.01 1.0 46.0 1.1 0.03 3.6 25 90 4 15 66.9 1.5 0.02 1.5 46.6 0.9 0.01 0.7 47.0 0.9 0.02 2.5 40 140 10 0 57.4 3.1 0.04 5.9 40.4 2.2 0.03 3.3 40.7 2.2 0.05 11.9 40 140 9 7.5 59.2 2.7 0.03 4.7 42.0 1.8 0.02 2.3 42.4 1.8 0.04 8.5 40 140 9 15 60.9 2.3 0.03 3.6 43.3 1.4 0.02 1.6 43.9 1.5 0.04 5.7 60 210 18 0 52.8 4.1 0.05 9.9 37.1 2.9 0.03 5.4 37.5 2.9 0.07 19.8 60 210 17 7.5 55.1 3.6 0.04 7.7 39.1 2.4 0.03 3.8 39.7 2.4 0.06 14.1 60 210 17 15 57.2 3.1 0.04 5.9 40.9 1.9 0.02 2.5 41.7 1.9 0.05 9.5 CWW 160 Water temperature In/out 80 ºC/60 ºC In/out 60 ºC/40 ºC In/out 55 ºC/45 ºC Air Air in Air out Power Water Air out Power Water Air out Power Water loss air l/s m 3 /h Pa ºC ºC kw l/s kpa ºC kw l/s kpa ºC kw l/s Pa 40 90 9 0 57.8 3.0 0.04 5.7 40.7 2.1 0.03 3.1 40.9 2.1 0.05 11.3 40 90 9 7.5 59.6 2.6 0.03 4.4 42.3 1.8 0.02 2.2 42.6 1.8 0.04 8.1 40 90 9 15 61.2 2.3 0.03 3.4 43.5 1.4 0.02 1.5 44.1 1.4 0.03 5.5 70 250 23 0 50.8 4.6 0.06 12.2 35.6 3.2 0.04 6.6 36.1 3.3 0.08 24.4 70 250 22 7.5 53.2 4.0 0.05 9.5 37.8 2.7 0.03 4.7 38.5 2.7 0.07 17.4 70 250 22 15 55.6 3.4 0.04 7.2 39.8 2.1 0.03 3.1 40.7 2.2 0.05 11.7 100 360 41 0 45.8 5.9 0.07 19.3 32.0 4.1 0.05 10.3 32.7 4.2 0.10 39.0 100 360 40 7.5 48.8 5.1 0.06 15.0 34.7 3.4 0.04 7.3 35.5 3.5 0.08 27.7 100 360 39 15 51.6 4.4 0.05 11.4 37.3 2.7 0.03 4.8 35.1 2.4 0.06 24.0 17-5-2016 Swegon reserves the right to make changes. www.swegonhomesolutions.com 7

www.swegonhomesolutions.com