RVL480. Heating Controller

Similar documents
RVL481. Heating Controller. including d.h.w. heating

RVL479. Heating Controller. for use with a partner unit

RVL470. Heating Controller. Use. Functions. Series B

RVL472. Heating Controller. Building Technologies HVAC Products. Series C. including d.h.w. heating

RVP310. Heating Controller. Building Technologies HVAC Products

Heating Controller for 2 heating circuits, d.h.w. and boiler, communicating

RVP331. Heating Controller for 2 heating circuits, d.h.w. and boiler. Building Technologies HVAC Products

Heating and D.h.w. Controller RVL482 Basic Documentation

RVL471 Heating and Domestic Hot Water Controller Basic Documentation

RVL471. Heating controller. G2524en. Installation Instructions. 1 Installation. 2 Commissioning

PRELIMINARY EDITION

District heating controller

District heating controller

RVP360 and RVP361 Heating controllers for 2 heating circuits and d.h.w. Basic Documentation

RVP340 Heating controller for 1 heating circuit RVP350 and RVP351 Heating controllers for 1 heating circuit and d.h.w. Basic Documentation

Use. Functions. Key function. Other functions

G a

RVD120, RVD140 Controllers for district heating and d.h.w. Basic Documentation

District Heating Controller

District heating controller for two heating circuits and d.h.w. according to Siemens specifications:

RVL47. Heating Controller. Installations Instructions. Installation

Room Units and Sensors for Use in Heating Plants. Siemens Building Technologies HVAC Products SIGMAGYR. Type summary

Operating Instructions

Operating Instructions Heating Controllers RVL479, RVL480, RVL481, RVL482

QAW70. Room Unit. Siemens Building Technologies HVAC Products. for use with heating controllers

Operating Instructions

Heating Controller. Building Technologies HVAC Products. Synco 700

QAW70. Room Unit. Building Technologies. for use with heating controllers

Boiler Sequence Controller

Room thermostat with Auto Timer, Option External Input

Room thermostat with 24-hour time switch and large LCD

RDJ10. Room temperature controller with 24-hour time switch and large LCD. For heating systems

ProCon 16, 31, 47 & 75. RVA 63 Boiler and Circuit Controller Commissioning Data.

RVA /109. Heating Circuit ZONE Controller. Instructions for the INSTALLER

RDJ10. Room temperature controller with 24-hour time switch and large LCD. For heating systems

Room thermostat with Auto Timer, Option External Input

Room Temperature Controller

Room Temperature Sensor

QAA Room Unit for Boiler Control with OpenTherm Interface Basic Documentation. Siemens Building Technologies Landis & Staefa Division

Room thermostat with Auto Timer, Option External Input

RVA Heating Circuit or Primary Controller Basic Documentation. Siemens Building Technologies Landis & Staefa Division

Room Unit. Building Technologies SYNERGYR

Immersion Temperature Controller

Self-learning Room Temperature Controller

Semi flush-mount room thermostats

Central apartment unit

Room temperature controller with large LCD. Non-programmable, for heating or cooling systems

ProCon 16, 31, 47, 75, 77 & HT. RVA 46. Zone Controller Commissioning Data.

QAF64.2-J QAF64.6-J. Frost detector. for use on the air side

Room thermostat with Auto Timer, independent DHW

Wireless room thermostat with LCD

RDH10. Room temperature controller with large LCD. Non-programmable, for heating or cooling systems

Room thermostats with LCD for wall mounting

Heating Controller. Synco 700

Room Temperature Controllers

ECL Comfort V a.c. and 24 V a.c.

G2484. Installation. - Control panel (in the panel front, on the inner wall, or on a DIN rail)

Digital Room Thermostat for Heating Applications with 7-Day Time Program

RVA Cascade Controller for modulating gas-fired Boilers Basic Documentation

ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys Designed in Denmark

M116 / M450 USER AND MAINTENANCE MANUAL FOR MODULATING-CONTROL BOILER WITH GAS BURNER EQUIPPED FOR NATURAL GAS. Type : B23 ATLANTIC 2000

Self-learning Room Temperature Controller

Room Temperature Controller

REA22 Room Temperature Controller

Room Temperature. for 2-pipe fan coil units for compressors in DX type equipment

Central apartment unit with QAX913 consumption data acquisition

Semi flush-mount room thermostat

ECL Comfort V a.c. and 24 V a.c.

Room thermostat with Auto Timer, Option External Input

ECL Comfort 210 controller, Remote Control Units ECA 30 / 31 and Application keys

Room thermostats with LCD RDD100..

Room Temperature Controller

No. Icon Name Function

ProCon Boiler Controller Commissioning Quick Reference Guide

RVS46.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55.. Albatros 2 Zone controller User Manual. Building Technologies HVAC Products

INSTRUCTION FOR THE USER THC V E OIL BLU

RVS43.. RVS63.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55.. Albatros2 Boiler controllers User manual. Building Technologies HVAC Products

Control solutions Biofloor

Flush-mounted room thermostats

Smart Thermostat RDS110

The ECL Comfort 110 is a universal 1-circuit controller for use in district heating substations and district heating systems as well as boilerbased

Synco 900 Operating instructions

Universal Dimmer N 528D01, 2 x 300VA, AC 230 V 5WG DB01

QAF63.2 QAF63.6. Frost sensors for use on the air side. Building Technologies HVAC Products

Room thermostat with independent DHW control

Main Features. Functions. with automatic ignition and control functions for the heating and domestic hot water circuit

Semi flush-mount room thermostat with KNX communications For VAV heating and cooling systems

Synco 900 Operating Instructions. Edition 1.0 Controller series 1 CE1B2707en Building Technologies HVAC Products

Local Process Bus LPB

P20. ECL Comfort. User's Guide. Installer's Guide. ECL Comfort P20. User's Guide. Installer's Guide *VI7BD502* *087R8014* *087R8014* *VI7BD502*

Use. For 2-pipe fan coils

Room Temperature Sensors

Room Unit for Boiler Control QAA User manual. Building Technologies. With OpenTherm Interface

ECL Comfort 110, application 116

DT92 WIRELESS DIGITAL ROOM THERMOSTAT FEATURES PRODUCT SPECIFICATION SHEET

Room Temperature Controller with LCD

RVS43.. RVS63.. AVS75.. AVS37.. QAA75.. QAA78.. QAA55.. Albatros2 Boiler controller User Manual. Building Technologies HVAC Products

Weather compensated flow temperature control of heating and boiler systems

Control Thermostat / Thermal Reset Limit Thermostat Combination of electromechanical TR and TW

- Data Brochure Universal Reset Module 422

Transcription:

2 540 Heating Controller RVL480 Multifunctional and communicating heating controller for use in residential and non-residential buildings. Suited for heating circuit control, boiler temperature control or precontrol. Suited for heat source systems like burners or district heat. 6 preprogrammed plant types. Operating voltage AC 230 V Use Types of buildings: Multi-family houses Single-family houses on-residential buildings Types of plants: Heating zones equipped with their own boilers Heating zones with district heat connection Combined plants consisting of heat generation and several heating zones Types of heating systems: Radiator, convector, underfloor and ceiling heating systems, radiating panels Functions Heating zone control Weather-dependent flow temperature control through control of the valve in a heating zone Weather-dependent flow temperature control through control of the burner in a heating zone Weather-dependent flow temperature control through control of the valve in the primary return of a heating zone with district heat connection (transfer station) CE12540en 20.05.2008 Building Technologies

Pre-control Operating modes Load-dependent control of the main flow temperature through control of the valve in the main flow; demand for heat via data bus Load-dependent control of the boiler temperature through control of the burner; demand for heat via data bus Load-dependent control of the secondary flow temperature through control of the valve in the primary return of a district heat connection; demand for heat via data bus Automatic mode Automatic changeover from ORMAL to REDUCED temperature, and vice versa, according to the weekly program, automatic changeover to holiday mode, demand-dependent control of heating system (ECO function) Setback mode Continuous heating to the REDUCED temperature, with ECO function Comfort mode Continuous heating to the ORMAL temperature, no ECO function Protection Manual operation o control, circulating pumps in service Frost protection is ensured in all operating modes. Other functions Optimization functions Protective functions Remote control Commissioning aids Communication functions Ordering When ordering, please give type reference RVL480. The controller is supplied complete with Operating Instructions and Installation Instructions. Sensors and, if required, room unit, actuator and valve must be ordered as separate items. Product documentation Type of documentation Document no. Part no. Basic Documentation P2540 Installation Instructions (languages: de, en, fr, G2540 74 319 0617 0 nl, sv, fi, da, it, es) Operating Instructions (languages: de, en, fr, B2540 74 319 0616 0 nl, sv, fi, da, it, es) CE Declaration of Conformity T2540 Environmental Declaration E2540 Equipment combinations Suitable Flow and return temperature: all sensors with sensing elements LG-i 1000, for example: Strap-on temperature sensor QAD22 Immersion temperature sensors QAE212 and QAP21.3 Room temperature: Room unit QAW50 Room unit QAW70 Room temperature sensor QAA24 2/9

Outside temperature: Outside sensor QAC22 (LG-i 1000 sensing element) Outside sensor QAC32 (TC 575 sensing element) Suitable actuators Communication ote All electromotoric and electrohydraulic actuators for 3-position control made by Siemens. The controller is capable of communicating with: All units with LPB capability made by Siemens SYERGYR OZW30 central unit (from software version 3.0) The heating controller RVL480 cannot be used as partner unit for the RVL469! Technical design Plant types Heating circuit control: 1 Heating circuit control with mixing group Precontrol: 4 Precontrol with mixing group, heat demand signal via data bus B9 A6/B5 2540S01 2540S04 2 Heating circuit control with boiler 5 Precontrol with boiler, heat demand signal via data bus 2540S02 B9 A5/B6 E2 2540S05 3 Heating circuit control with heat exchanger 6 Precontrol with heat exchanger, heat demand signal via data bus B9 A6/B5 2540S03 1 1 2540S06 A6 Room unit E1 Boiler or heat exchanger B1 Flow or boiler sensor E2 Load (space) B5 Room sensor LPB Data bus Return sensor (primary circuit) M1 Circulating pump or boiler pump 1 Return sensor (secondary circuit) 1 Controller RVL480 B9 Outside sensor Y1 Heating circuit mixing valve / 2-port valve Working principle The RVL480 offers 6 different plant types that are ready programmed in the controller. When commissioning the system, the respective plant type must be entered. This activates all functions that are required for the configured plant type. The standard settings are practice-oriented. All functions not required for the selected plant type will not be shown and are disabled. 3/9

Enduser settings With weather-dependent control, the flow temperature is controlled in function of the prevailing outside temperature via the heating curve. Its basic setting is made with the little bar on the front of the unit or on an operating line. The room temperature can be readjusted with the knob. In addition, following can be entered by the enduser: Room temperature set values for ORMAL heating, REDUCED heating and frost protection/holidays Weekly switching program and a maximum of eight holiday periods per year Operating mode Time of day and date Temperature acquisition Flow temperature: with LG-i1000 sensor Outside temperature: with LG-i1000 or TC 575 sensor; the RVL480 identifies the type of sensor used. With interlinked controllers, it is also possible to define the source of the outside temperature Room temperature: with a room temperature sensor or a room unit or both (averaging) Space heating The room temperature is included in the control. It can be acquired with a sensor or simulated by a room model with an adjustable building time constant. When using a sensor, the effect on the control can be adjusted. It is also possible to limit the maximum room temperature The heating is switched on and off depending on demand (ECO function). It is switched off when the amount of heat stored by the building mass is sufficient to maintain the required room temperature. In that case, the controller takes into account the development of the room temperature and the building's heat storage capacity. It is possible to set two heating limits, one for ORMAL heating and one for REDUCED heating The control is optimized. Switching on, heating up and shutting down are controlled such that, during occupancy times, the required room temperature is always maintained. At the end of each occupancy period, the heating will be shut down (circulating pump) until the room temperature set value for the non-occupancy time is reached (quick setback, can be disabled). During heating up, the room temperature set value can be boosted (boost heating). It is possible to set maximum limits for the heating up time and for early shutdown 3-position control 3-position control operates as weather-dependent or load-dependent flow temperature control. P-band and integral action time are adjustable. The flow temperature is controlled via the regulating unit (control or slipper valve). Minimum and maximum limitation of the flow temperature as well as maximum limitation of the rate of set value rise are adjustable. 2-position control 2-position control operates as weather-dependent or load-dependent boiler temperature control. The boiler temperature is controlled through cycling of the single- or 2- stage burner (direct burner control). 2-stage operation is enabled when the release limit is reached, and disabled when the reset limit is reached. The limits can be adjusted. When there is no demand for heat, the boiler will either be shut down or maintained at the minimum temperature limit (selectable). Both minimum and maximum limitation of the boiler temperature are adjustable. 4/9

District heat Minimum limitation of return temperature Locking functions Time switch Remote control ote on QAW70 Passing on the heat demand signal Communication Error messages and flow temperature alarm Other functions The secondary flow temperature is controlled via the valve in the primary return, either weather- or load-dependent. Maximum limitations act on the: primary return temperature, whereby the following selections can be made: type of compensation (local outside sensor or bus signal), slope of limit curve, and start of compensation difference of primary return and secondary return temperature (DRT) Minimum stroke limitation (Y min function) prevents measuring errors in connection with heat metering when flow rates fall below a certain level. The integral action time of the limit functions is adjustable. Minimum limitation of the return temperature acts with both 3-position control and loaddependent control of the boiler temperature and helps prevent flue gas condensation. On the software side, all settings can be locked to prevent unauthorized readjustments. The district heat settings can be locked on the hardware side. The RVL480 has one weekly time switch for entering the daily occupancy times. Each day can accommodate 3 occupancy times, whereby each weekday may have different occupancy times For entering a maximum of eight holiday periods, the RVL480 is equipped with a yearly time switch featuring automatic summer- / wintertime changeover Changeover of operating mode with the QAW50 room unit Overriding the major controller functions with the QAW70 room unit Selection of another (programmable) operating mode with an external switch Preselection of a fixed flow temperature set value with an external switch. Type of set value (fixed or minimum) and flow temperature can be selected The day of the week is set automatically with the date by the controller; an adjustment from the room unit QAW70 is not possible. The heat demand signal can be passed on via the scalable DC 0 10 V output (corresponding to 0 x C). The value of x can be adjusted in the range of 30 130 C. Communication with other devices is effected via the data bus and allows: Signaling of heat demand to the heat generator Exchange of locking and enforced signals Exchange of measured values such as outside temperature, return temperature, flow temperature and of clock signals Reception of heat demand from the SYERGYR OZW30 central unit (from software version 3.0) Exchange of error messages Error message in the event of sensor, data bus or room unit faults Flow temperature alarm; adjustable is a period of time during which the flow temperature may stay outside the set limits; an error message is given when the time has elapsed Display of parameters, actual values, operational statuses and error messages Simulation of outside temperature Relay test; all relays can be controlled manually Sensor test; all measured values of the sensors can be displayed Testing the contacts connected to terminals H1 M, H2 M, H3 M and H4 M Outside temperature-dependent frost protection for the plant; a minimum flow temperature is maintained, its set value and the response threshold can be adjusted Pump overrun time to prevent buildup of heat Periodic pump run (pump kick) to prevent seizing of the pump in the summer Controller hours run meter 5/9

For more detailed information on communication with LPB, refer to the following documents: Data sheet Basic System Data LPB: 2030 Data sheet LPB: 2032 Mechanical design 1 8 2540Z03 9 2 10 3 4 5 6 11 12 13 7 1 Operating mode buttons (selected button is lit) 2 Display (LCD) 3 Buttons for operating the display: Prog = selection of operating line + = adjustment of displayed value 4 Button for Close heating circuit mixing valve or burner stage 2 O/OFF in manual operation 5 Button for Open heating circuit mixing valve in manual operation 6 Button for manual operation 7 LEDs for: Manual operation / Heating circuit mixing valve opens / burner stage 1 O / Heating circuit mixing valve closes / burner stage 2 O Pump runs 8 Sealing facility in the cover 9 Info button for the display of actual values 10 Setting slider for flow temperature setpoint at an outside temperature of 5 C 11 Setting slider for flow temperature setpoint at an outside temperature of 15 C 12 Setting knob for readjustment of room temperature 13 Fixing screw with sealing facility The RVL480 is comprised of controller insert, which accommodates the electronics, the power section, the output relays and on the front all operating elements, and the base, which carries the connection terminals. The operating elements are located behind a lockable transparent cover. The operating instructions can be inserted in the transparent cover. All values are read in the display (LCD) featuring background lighting. The controller insert is secured to the base with two screws, one of which can be sealed. The cover can also be sealed. The RVL480 can be fitted in 3 different ways: Wall mounting (on a wall, in the control panel, etc.) Rail mounting (on a top hat rail) Flush panel mounting (control panel door, etc.) 6/9

Analog operating elements Digital operating elements Buttons for selecting the required operating mode Info button Direct adjustment of the heating curve with the help of the SIGMAGYR setting facility Knob for manual readjustment of the room temperature 3 buttons for manual operation and manual positioning commands The entry or readjustment of all setting parameters, activation of optional functions and reading of actual values and statuses is made according to the operating line principle. An operating line with an associated number is assigned to each parameter, each actual value and each function that can be selected. One pair of buttons is used to select an operating line and one pair to readjust the display. otes Engineering Commissioning The wires of the measuring circuits carry extra low voltage, those to the actuator and the pump carry AC 24 230 V The local electrical regulations must be complied with Sensor cables must not be run parallel to mains carrying cables for loads such as actuator, pump, burner, etc. (insulation class II E 60730) The plant type must be selected When used in district heat plants, the district heat parameters can be locked Disposal In terms of disposal, the RVL480 are classified as electronic scrap conforming to the European Directive 2002/96/EG (WEEE) and must not be disposed of as domestic waste. The relevant national legal requirements must be complied with and the units must be disposed of through the relevant channels. Local and currently valid legislation must be observed. Warranty When using the RVL480 together with third-party devices not specifically mentioned, correct functioning must be ensured by the user. In that case, Siemens will assume no responsibility for service and warranty. 7/9

Technical Data Power supply Output relays Rated operating voltage AC 230 V (±10 %) Frequency 50 Hz Power consumption (no external load) max. 7 VA Supply line fusing 10 A Switching capacity AC 24 230 V Switching current Y1/K4, Y2/K5, Q1 AC 0.02 2 (2) A Rated current of ignition transformer max. 1 A (max. 30 s) Switch-on current of ignition transformer max. 10 A (max. 10 ms) Permissible cable lengths to sensors and room unit Copper cable 0.6 mm Copper cable 0.5 mm 2 Copper cable 1.0 mm 2 Copper cable 1.5 mm 2 20 m 50 m 80 m 120 m Connection terminals Communication by wire Screw terminals for wire section up to 2.5 mm 2 Bus protocol / type LPB Bus loading characteristic E 6 Backup Standards Backup of controller clock -conformance to EMC directive Immunity Emissions Low voltage directive Safety 12 h 2004/108/EC E 61000-6-1 / -2 E 61000-6-3 / -4 2006/95/EC E 60730-1 / E 60730-2-9 Protective data Dimensions Safety class II to E 60730 Degree of protection (cover closed) IP42 to E 60529 Degree of contamination 2 to E 60730 refer to Dimensions Weight Unit (net) 1.1 kg Colors Environmental conditions Controller insert Light grey RAL 7035 Terminal base Pigeon blue RAL 5014 Operation Transport E 60721-3-3 E 60721-3-2 Storage E 60721-3-1 Climatic conditions class 3K5 class 2K3 class 1K3 Temperature 0 +50 C 25 +70 C 20 +65 C Humidity <95 % r.h. <95 % r.h. <95 % r.h. (non-condensing) (non-condensing) Mechanical conditions class 3M2 class 2M2 class 1M2 Use above sea level max. 3000 m above sea level 8/9

Connection diagrams Low voltage L LPB A6 B9 B1 D1 D2 B M B M - DC 0...10 V + S1 S2 B5 1 Y1 B M B M B M AC 230 V L DB MB A6 MD B9 B1 M Ux M H1 H2 B5 M 1 H4 H3 M 1 2540A01 Mains voltage Left: Connections for plant types 1, 3, 4 and 6 (valve or district heat) Right: Connections for plant types 2 and 5 (boiler with a 2-stage burner) L L AC 230 V L F1/F4 F2/F5 F3 Y1/K4 Y2/K5 Q1 1 AC 230 V L F2/F5 Y2/K5 F1/F4 Y1/K4 F3 Q1 1 Y1 Y2 Y1 M1 F1 F2 1. M1 2540A02 2. E1 2540A03 A6 Room unit LPB Data bus B1 Flow or boiler sensor M1 Heating circuit or boiler pump B5 Room sensor 1 Controller RVL480 Return sensor (primary circuit) S1 Remote control operating mode 1 Return sensor (secondary circuit) S2 Remote control flow temperature setpoint B9 Outside sensor Ux Heat demand output E1 2-stage burner Y1 Actuator of heating circuit with contact for minimum F1 Thermal reset limit thermostat stroke limitation F2 Manual reset safety limit thermostat * Wire link for locking the district heat parameters Dimensions 35 ±0.3 E 60715 139 1.5 95 (42.5) 2540M01 144 16.4 15.3 144 26 26 26 26 144 4.5 14 max. 3 18 max. 8 max. 5 M16 22 106 50 39 39 35 36 29 138 +1 0 E 50262 IEC 61554-144 144 36 72 106 108 138 +1 0 Dimensions in mm 2008 Siemens Switzerland Ltd Subject to alteration 9/9