Instlltion Instructions Outside Humidity nd Temperture Sensor Importnt: Retin these instructions Contents 1 Unpcking...1 2 Instlltion...1 3 Fult Finding...4 4 Mintennce...5 5 Disposl...8 1 Unpcking Instlltion Instructions TG200992 2 InstlLtion 1 Ø 105 mm, 4.13" Dimensions 2 Mounting Requirements 196 mm, 7.72" 55 mm, 2.16" 20 mm, 0.78" Ø 5 mm, 0.2" 1.5 mm, 0.06" 80 mm, 3.15" 69.5 mm, 2.74" 94 mm, 3.7" 122 mm, 4.8" c d e f g mient limit -40 C (-40 F) +60 C (+140 F) mesurement -30 C (-22 F) +50 C (+122 F) H O 2 0 %RH 100 %RH Protection: IP65 Instlltion Instructions TG200992 Issue 3, 25/02/2010 1
Instlltion Instructions 2 Instlltion (continued) 2 Mounting Requirements (continued) B1 < L1 h i j k L1 > 1 m, 1 yd L2 B2 < L2 3 Mount Rdition Shield Either on wll 44 mm (1.73 ) Or on mst mst Ø 57 to 68mm (2.25 to 2.68 ) 2 holes Ø 6 mm (0.24 ) 2 wllplugs S6 nd 2 screws 4.2x38 provided U olt ssemly provided 68 mm (2.68 ) 4 Remove Cover Cution: This unit contins sttic sensitive devices. Suitle nti-sttic precutions should e tken throughout the opertion to prevent dmge to the units. BS EN100015/1 Bsic Specifiction: protection of electrosttic sensitive devices. 2 Instlltion Instructions TG200992 Issue 3, 25/02/2010
Instlltion Instructions 2 Instlltion (continued) 5 Attch Sensor to Bckplte 6 Insert Cle through Glnd M16 glnd 7 Wire to Controller 2 nlogue input chnnels 8 Fit Cover IQ1 & IQ2 V+ RH T Tp C (+24V) IN C IN } humidity } temperture linked for current (I) linked for thermistor (T) erth (ground) screens t IQ end V+ RH T Tp 0 (0V) N (in) + (+24V) 0 (0V) N+1 (in) + (+24V) N N+1 IQ3 humidity temperture linked for current (I) linked for thermistor (T) erth (ground) screens t IQ end 9 Fit Sensor Assemly to Shield in two positions Instlltion Instructions TG200992 Issue 3, 25/02/2010 3
Instlltion Instructions 2 Instlltion (continued) 10 Configure IQ 1 3 1 3 or IQ Configurtion Mnul 90-1533 IQ3 Configurtion Mnul TE200768 11 Set up IQ Sensor Types It is recommended to use SET (Softwre Tool) for the setting of the sensor type module. For ll IQ2 series controllers with firmwre version 2.1 or greter, or IQ3 series controllers, the following SET Unique Sensor References should e used: Humidity :Humidity I Temperture :Thermistor HTOT ( C) Thermistor HTOT F ( F) Alterntively enter scling mnully s defined in tles elow. For ll other IQ contriollers see Sensor Scling Reference Crd TB100521A Temperture (thermistor) (-30 to +50 C, -22 t0 122 F) Units: C F Y Input type 1 (therm V) E Exponent 3 U Upper 55 131 L Lower -35-31 P Points 11 x Ix Ox 1 2.641 50 122 2 3.470 40 104 3 4.460 30 86 4 6.663 10 50 5 7.668 0 32 6 8.102-5 23 7 8.482-10 14 8 8.807-15 5 9 9.078-20 -4 10 9.299-25 -1 11 9.476-30 -22 Humidity (current) (0 to 100 %RH) Y Input type 2 (curr ma) E Exponent 3 U Upper 100 Lower 0 P Points 2 x Ix Ox 1 4 0 2 20 100 12 Test System T H IQ 3 Fult Finding Fults Possile Cuses Remedies Long response time Filter polluted Replce filter Complete filure No power supply Check power supply nd cle Humidity reding too high Condenstion on sensor proe Dry proe nd replce filter if necessry 4 Instlltion Instructions TG200992 Issue 3, 25/02/2010
Instlltion Instructions 4 Mintennce Over time, the sensing element my ecome covered in dust. The dust cn e removed using compressed ir. Under no circumstnces should wter or clensing gents e used on the sensing elements. It is recommended tht the ccurcy of the sensor is verified every 12 months. If the sensor flls outside the quoted ccurcy, replce the filter nd reclirte s shown elow. The clirtion chmer nd clirtion liquids will need to e purchsed from specilist clirtion equipment supplier. 1 Remove Sensor Assemly from Rdition Shield in two positions 2 Remove Cover Cution: This unit contins sttic sensitive devices. Suitle nti-sttic precutions should e tken throughout the opertion to prevent dmge to the units. BS EN100015/1 Bsic Specifiction: protection of electrosttic sensitive devices. 3 Replce Filter unscrew See Section 5, Disposl 7 2, 9 d c ACC/HTO/FILTER Cution: Do not touch humidity sensing element Instlltion Instructions TG200992 Issue 3, 25/02/2010 5
Instlltion Instructions 4 Mintennce (continued)) 4 Preprtion 5 Locte Buttons Keep sensor nd humidity chmer in sme room for 4 hours efore. Plce proe in humidity chmer 30 mins efore. Keep temperture constnt during clirtion. push uttons 7 2, 9 clirtion LED 6 Two Point Clirtion For clirtion over whole working rnge Strt clirtion t lower humidity point. Difference etween the two points should e >30%RH Low Humidity Clirtion 1. Remove lid from the clirtion chmer nd clen chmer thoroughly. 2. Insert one of the cloths provided with the clirting liquid. Pour clirting liquid (35%RH) onto the fric. Refit lid nd screw tightly. 3. Insert proe into sensor perture of chmer nd tighten collr to provide ir tight sel round the proe. Wit 30 min. 4. Press Down pushutton for 3 s to strt. LED will illuminte. 5. Press Up or Down pushutton to djust mesured vlue in 0.1% steps. 6. Either: Press Up pushutton for 3 s to stop. Clirted vlue is stored. LED is extinguished. Or: Press Down pushutton for 3 s to exit clirtion without storing vlue. LED is extinguished. High Humidity clirtion 7. Remove lid from the clirtion chmer nd clen chmer thoroughly. 8. Insert one of the cloths provided with the clirting liquid. Pour clirting liquid (80%RH) onto the fric. Refit lid nd screw tightly. 9. Insert proe into sensor perture of chmer nd tighten collr to provide ir tight sel round the proe. Wit 30 min. 10. Press Up pushutton for 3 s to strt. LED will illuminte. 11. Press Up or Down pushutton to djust mesured vlue in 0.1% steps 12. Either: Press Up pushutton for 3 s to stop. Clirted vlue is stored. LED is extinguished. Or: Press Down pushutton for 3 s to exit clirtion without storing vlue. LED is extinguished. 7 One Point Clirtion For clirtion over limited rnge out single point This clirtion gives decresed ccurcy over reminder of working rnge Single Point Humidity Clirtion 1. Remove lid from the clirtion chmer nd clen chmer thoroughly. 2. Insert one of the cloths provided with the clirting liquid. Pour clirting liquid (35%RH or 80%RH) onto the fric. Refit lid nd screw tightly. 3. Insert proe into sensor perture of chmer nd tighten collr to provide ir tight sel round the proe. Wit 30 min. 4. Either: (If chmer humidity >50%RH.) Press Up pushutto for 3 s to strt. LED will illuminte. Or: (If chmer humidity <50%RH.) Press Down pushutton for 3 s to strt. LED will illuminte. 5. Press Up or Down pushutton to djust mesured vlue in 0.1% steps 6. Either: Press Up pushutton for 3 s to stop. Clirted vlue is stored. LED is extinguished. Or: Press Down pushutton for 3 s to exit clirtion without storing vlue. LED is extinguished. 6 Instlltion Instructions TG200992 Issue 3, 25/02/2010
Instlltion Instructions 4 Mintennce (continued 8 Replce Cover 9 Fit Sensor Assemly to Shield in two positions 10 Test System IQ T H Instlltion Instructions TG200992 Issue 3, 25/02/2010 7
Instlltion Instructions 5 Disposl WEEE Directive: At the end of their useful life the pckging nd product should e disposed of y suitle recycling centre. Do not dispose of with norml household wste. Do not urn. Plese send ny comments out this or ny other Trend technicl puliction to techpus@trendcontrols.com 2010 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Mnufctured for nd on ehlf of the Environmentl nd Comustion Controls Division of Honeywell Technologies Sàrl, Z.A. L Pièce, 16, 1180 Rolle, Switzerlnd y its Authorized Representtive. Trend Control Systems Limited reserves the right to revise this puliction from time to time nd mke chnges to the content hereof without oligtion to notify ny person of such revisions or chnges. Trend Control Systems Limited Alery House, Springfield Rod, Horshm, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fx:+44 (0)1403 241608 www.trendcontrols.com Trend Control System USA 6670 185 th Avenue NE, Redmond, Wshington 98052, USA. Tel:(425) 869-3900 Fx:(425) 869-8445 www.trendcontrols.com 8 Instlltion Instructions TG200992 Issue 3, 25/02/2010