DET-TRONICS. SPECIFICATION DATA Eagle Quantum Premier Fire and Gas Detection / Releasing System APPLICATION FEATURES

Similar documents
DET-TRONICS SPECIFICATION DATA. Eagle Quantum EQ2200UVHT For Use With C7050B Continuous Duty High Temperature UV Flame Detector DESCRIPTION

Instructions. Eagle Quantum Premier Fire and Gas Alarm Control System and Automatic Releasing for Pre-Action and Deluge Systems

Annex to: IECEx ULD U Issue. No. 2 Manufacturer: Detector Electronics Corporation Electrical apparatus: Eagle Quantum Premier system Modules

Safety Manual. Eagle Quantum Premier SIL 2 Rated Fire & Gas System. 7.2 Rev: 8/

SAFETY MANUAL. X2200 UV, X9800 IR, X5200 UVIR SIL 2 Certified Flame Detectors

The Most Versatile Flame Detectors in the World. Optical Flame Detection Solutions

The Most Versatile Flame Detectors in the World. Optical Flame Detection Solutions

Safety Manual. Eagle Quantum Premier SIL 2 Rated Fire & Gas System. 9.1 Rev: 9/

INSTRUCTIONS. Eagle Quantum Premier (EQP) Addressable Smoke & Heat (ASH) Module EQ3750ASH. 5.1 Rev: 4/

Industrial Grade Gas Detection Detecting The Difference

Instructions R8471J Gas Controller for use with Model OPECL Open Path Eclipse IR Gas Detector 1.1 1/

SAFETY MANUAL. Multispectrum IR Flame Detector X3301

Multi-Spectral, Digital, Infrared Electro-Optical. FSC Model No. s. Unitized, Two Stage, Quick Response Flame Detectors.

Specification/ Data Sheet

Instructions Infrared Hydrocarbon Gas Detector PointWatch Eclipse Model PIRECL /

Instructions Det-Tronics Standard Gas Panel. 1.1 Rev: 10/

Industrial Grade Gas Detection

SAFETY MANUAL. PointWatch Eclipse Infrared Hydrocarbon Gas Detector Safety Certified Model PIRECL

Addendum HART Communication with the X2200 UV Flame Detector 1.1 4/

Combustible and Toxic Gas Detection Solutions. Performance and Safety Beyond Compliance

FM Approved Fire & Gas Detection System

Detectors-Transmitters for Flammable, Toxic Gases and Oxygen. Non-intrusive operation via intrinsically safe infrared remote control.

Combustible and Toxic Gas Detection Solutions. Performance and Safety Beyond Compliance

For Complete Fire and Gas Solutions

TTSIM-2 TRACETEK SENSOR INTERFACE MODULE WITH LCD AND RELAY INSTALLATION/OPERATION INSTRUCTIONS

DET-TRONICS INSTRUCTIONS. Infrared Hydrocarbon Gas Detector PointWatch Eclipse Model PIRECL APPLICATION OPERATION OVERVIEW

THERMAL BUILDING SOLUTIONS EN-TraceTekTTSIM1A-IM-H /16

Instructions. Infrared Hydrocarbon Gas Detector PointWatch Eclipse Model PIRECL Rev: 3/

Commercial and Light Industrial Fire Alarm Control Panel

Danfoss gas detection units

PEGAsys. Multi-Loop Intelligent Suppression Control System FEATURES DESCRIPTION. Effective: March 2007 K

IR4000. Point Infrared Combustible Gas Detection System. The Reliable and Flexible Safety Solution That s Low Maintenance

Industrial Grade Gas Detection

AEGIS FEATURES DESCRIPTION. Conventional Fire Alarm-Suppression Control Unit. Effective: March Programmable Relays

APPLICATION BULLETIN COMBUSTION TURBINE FACILITIES. Overview

DET-TRONICS INSTRUCTIONS. Infrared Hydrocarbon Gas Detector. PointWatch Eclipse Model PIRECL APPLICATION OPERATION OVERVIEW

GAS DETECTORS. When every second counts

Fire and Gas Monitoring Panel ST7-HV

5New features & EXtreme design, now with HART Protocol and DuraSource Technology. Ultima X Series Gas Monitors

SIL 2. Ultima X Series Gas Monitors CERTIFIED

SUPREMATouch. Modular Fire & Gas Detection System

Instructions Infrared Hydrocarbon Gas Detector PointWatch Eclipse Model PIRECL Rev.10/

TTSIM-1A. TraceTek Sensor Interface Module with Relay. Installation/Operation Instructions. Installation Items (not supplied) Tools Required.

APPLICATION DATA SHEET

Dependable Solutions for Gas Detection

FireSystem 2000 Commercial and Light Industrial Fire Alarm Control Panel

Model D12-IR. Digital Gas Transmitter...

SUPREMATouch. Modular Fire & Gas Detection System

incontrol Systems Inc. Flame and Gas Detection

TYPE CM-2201 NELSON SINGLE POINT CIRCUIT MANAGEMENT SYSTEM

Two-Channel Gas Controller

INFRARED PRODUCTS FOR MONITORING SMOKELESS FLARES, PILOTS, AND FLAME INTENSITY

Integrating Fire and Gas Safety with Process Control Systems:

SEC 2000 Millenium Infrared Gas Detector

DATA SHEET CHEETAH XI 50 INTELLIGENT SUPPRESSION CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

Products and performance

CHEETAH XI INTELLIGENT SUPPRESSION CONTROL SYSTEM

LC150 VIEW-AT-A-GLANCE PUMP CONTROL-TELEMETRY UNIT

MX43. Analog and digital controller. 4 or 8 lines / 16 to 32 detectors max. Highly versatile controller. Cost savings on wiring installation

Self-contained and intrinsically safe wireless stand-alone multi-point gas detector.

DATA SHEET CYBERCAT 254 INTELLIGENT FIRE ALARM CONTROL SYSTEM DESCRIPTION APPROVALS: SYSTEM OPERATION. Form No. D

Dräger REGARD -1 Control System

Dräger Polytron 7000 Fixed gas detector

LMV52 Control. Specifications. Document No. LV February 3, Product Description. Sample Specification

YOUR PARTNER IN FIRE & GAS DETECTION

Analog and digital controller. 4 or 8 lines / 16 to 32 detectors max. Highly versatile controller. Cost savings on wiring installation

Recalibrate the way you look at gas detection

GasGard 100 Control System

Danfoss gas detection units

SAFEYE XENON 700. Hydrocarbons and ethylene detection. Heated optics. 10-year Warranty for the Xenon flash bulb. SIL 2 according to IEC 61508

Dräger Polytron Fixed Gas Detector. Dräger Polytron 5700 Infrared DrägerSensor PIR 7000 to detect combustible gases and vapors

MX43. Analog and digital controller. 4 or 8 lines / 16 to 32 detectors max. Highly versatile controller. SIL1 reliability. Gas Detection Control Panel

Across-the-Line SERIES MP300 Combined Manual and Automatic

Instructions. Explosion Proof Smoke Detector U Rev: 9/

Instructions Dual Spectrum Infrared Flame Detector PM-5MPX. 4.1 Rev: 8/

Safety Instrumented Fire & Gas Systems

4100U City and Relay Cards Installation Instructions

SafEye OPEN-PATH GAS DETECTION SYSTEM XENON 700. We INVENTED it... We PERFECTED it! Patent No. US 5,281,816; US 6,061,141; EP

Multi-Gas-Controller MGC2

LMV51 Control. Specifications. Document No. LV February 7, Product Description. Sample Specification

PWGSC Ontario MULTIPLEX FIRE ALARM SYSTEM Sect Region Project Page 1 Number R

Instructions

MINERVA. Marine. Fire Detection. MX T2000 Panel Range. Features: MINERVA Marine Panel Range

OLCT 700 & 710. Certifications FIXED GAS DETECTION. Better detection. Better protection.

Danfoss gas detection unit Type GD Heavy Duty

Digital Gas Transmitters with Auxiliary Inputs & Control. PolyGard 2 DC6

Dräger Flame 2100 Flame Detection

Soft Start Series MP700 Solid State, Reduced Voltage

30.45 Electric Release PDRP-2001

Case Study. INTEGRATING Fire & GAS SAFETY WITH PROCESS CONTROL SYSTEMS

Instructions Model MIR MSHA Approved IR Gas Detector 3.1 7/

LifeAlarm Fire Alarm Control Panels

Nanotechnology Metal Oxide Semiconductor (NTMOS) H 2 S Gas Sensor

NGC-40 Advanced Heat-Tracing Control System

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

Detection, Protection, Innovation

GAS PLUS ALARM SYSTEM

NETWORK FIRE ALARM CONTROL PANEL. Features

Dräger Polytron Pulsar 2 Open Path Gas Detector

Transcription:

DET-TRONICS SPECIFICATION DATA Eagle Quantum Premier Fire and Gas Detection / Releasing System APPLICATION Eagle Quantum Premier is a configurable, distributed, intelligent safety system providing flame and/or gas detection, along with alarm signaling, notification, extinguishing agent release, and/or deluge operation. All system components are integrated together on a fault tolerant digital communication network. The system is ideally suited for harsh industrial applications that require a hazardous location rated protection system. Typical applications include: Refineries and chemical plants Offshore platforms Pipelines and liquid gas storage Automotive applications Turbines / generators / compressors Aircraft / vehicle maintenance facilities Hazardous manufacturing processes Alternative fuel bus facilities. FEATURES Hazardous location certification, including ATEX, for field devices Fire detection and alarm Fire suppression control Gas detection and alarm Distributed architecture Extensive diagnostics Device calibration data and event logging Programmable logic Real time clock Four-line, 20 character alphanumeric display LED status indicators Fault tolerant communication loop Up to 60* intelligent addressable field devices NFPA/CEC/CENELEC/CE Approvals pending Designed in accordance with ANSI/NFPA 72 National Fire Alarm Code. Detector Electronics Corporation 2002 8/02 90-1150

CONFIGURABLE INPUTS AND OUTPUTS (FIRE OR GAS) FIRE DETECTION NOTIFICATION AND RELEASING CIRCUITS DRY CONTACT INPUTS CONFIGURABLE OUTPUT POINTS CONTACT CLOSURE DEVICES 8 CHANNEL DCI/O MODULE UV DETECTOR UV/IR DETECTOR IR DETECTOR INITIATING DEVICE CIRCUIT AGENT RELEASE MODULES FIRE SUPPRESSION (SOL) UNSUPERVISED INPUTS AND OUTPUTS NETWORK EXTENDER 8 DRY CONTACT INPUTS 8 RELAY OUTPUT POINTS SIGNAL AUDIBLE MODULES HORNS & BEACONS DIGITAL COMMUNICATION UNITS ECLIPSE GAS DETECTOR EQP CONTROLLER POWER SUPPLY MONITOR COMBUSTIBLE, TOXIC, POINTWATCH OR OTHER 4-20 MA INPUT CONTROLNET (OPTIONAL INTERFACE) FUTURE EXPANSION CAPABILITIES ONBOARD SERIAL INTERFACE SYSTEM POWER BATTERY CHARGER AC POWER INPUT GAS DETECTION SIGNALING LINE CIRCUIT (SLC) HARDWIRED I/O SERIAL INTERFACE RS-232 RS-485 (FUTURE) CONFIGURATION PC MODBUS INTERFACE Figure 1 Block Diagram of the Eagle Quantum Premier System + + A2114 SYSTEM DESCRIPTION The Eagle Quantum Premier system is a third generation hazard protection system that is designed for fire and gas detection and initiation of alarm/trouble notification and suppression. The system utilizes modularized field devices on a digital communication loop. All the detection, re-action, and notification activities are coordinated through a centralized Controller. See Figure 1. The Eagle Quantum Premier system has the flexibility to utilize any combination of Eagle Quantum Premier field devices. The system can be a total gas detection system, a total fire detection system, or a combination of both fire and gas detection. All devices and operating parameters are configured through the Controller. Third party devices can be integrated into the system either through dry contact closure inputs (using IDCs/DCIOs) or through 4 to 20 ma inputs (using DCUs). Through its centralized control unit, the Eagle Quantum Premier system provides an open architecture in which systems can be tied together to share information. PLC, DCS and human/machine interface (HMI) systems can communicate directly with the Eagle Quantum Premier system through supported communication protocols. The controller supports up to two optional communication boards, along with a built-in RS-485 Modbus interface. An optional two port ControlNet board is also available. The Eagle Quantum Premier Controller displays current information about the system. Twelve LEDs are provided to indicate when an alarm or fault condition exists. The four line 20-character vacuum florescent display (VFD) shows the current status of the system. Alarm and trouble conditions are easily identified, along with the associated device tagname. The Eagle Quantum Premier system provides operational flexibility through custom designed user logic programs in the controller. Over 50 different types of logic gates are available to allow the system to be optimized for nearly any application. 2

Eagle Quantum Premier Controller 24 vdc nominal, 18 to 30 Vdc. 10% overvoltage will not cause UNSUPERVISED OUTPUTS (8 Relays) Dry Contact Rating: 1 ampere at 30 Vdc maximum. SPDT normally open/normally closed contact, configurable for normally energized or de-energized (de-energized is the default mode). TROUBLE OUTPUT SPDT normally open/normally closed contact. Non-configurable, normally energized only. The microprocessor-based Controller continuously monitors the field devices on the Signaling Line Circuit (SLC) and performs the logic functions needed to generate the appropriate output(s). The Controller performs both fixed and user programmable logic operations. Fixed logic controls the faceplate displays and relay outputs (alarm, trouble and supervisory) per ANSI/NFPA 72. Fixed logic also activates built-in annunciation circuits, consisting of both visible and audible alarms. Programmable logic allows the Controller to be customized to perform a variety of complex logic operations. Using Det-Tronics S3 Software, the Controller can be programmed using logic gates to implement crosszone monitoring, voting, or timed operations that might be needed in a fire suppression system. The Controller also has provisions for communications with external devices and software. An optional ControlNet board is available for monitoring Eagle Quantum Premier s system status. RELAY RESPONSE TIME Output relays actuate in <0.1 second after acknowledging an alarm command message. UNSUPERVISED INPUTS (8 Channels) Two state input (on/off). User selectable normally open or normally closed contact (N.O. is the default). Operating: 40 F to +185 F ( 40 C to +85 C). Storage: 40 F to +185 F ( 40 C to +85 C). Excluding communication port optional modules. HUMIDITY RANGE 0 to 95% RH, non-condensing. DIMENSIONS L: 10.75 inches W: 5.25 inches D: 2.15 inches. MOUNTING DIN rail or panel mount. Signaling Line Circuit (SLC) Devices The SLC is a fault tolerant, two wire, digital communication network, arranged in a loop that starts and ends at the Controller. In its base configuration, the SLC supports up to 60 intelligent field devices spread over a distance of up to 2000 meters (up to 10,000 meters using Network Extenders). Devices on the network can consist of a variety of flame and gas detectors, as well as other input and output devices. Each device on the SLC contains both the hardware and software necessary to isolate and re-route communication in the event of a network wiring fault. When a problem occurs somewhere within the network wiring, the Controller annunciates the fault, while the fault isolation circuitry in the affected nodes isolates the section of the network where the fault has occurred. Communication is thereby ensured and will continue over the network. See Figure 2. A single open or short on the SLC will not affect system communication between the field devices and the Controller. System communication to all field devices will continue until the wiring problem can be repaired. SLC OUTPUT Digital communication, transformer isolated (78.5 kbps). CONDUIT ENTRIES All SLC devices are available with 3/4 inch NPT or M25/M20 conduit entries. SLC DEVICES Can consist of any combination of the following: DC I/O Module, X3301 IR Flame Detector, UVIR Flame Detector, UV Flame Detector, Initiating Device Circuit, PointWatch Eclipse, Digital Communication Unit, Agent Release Module, Signal Audible Module, Network Extender, Power Supply Monitor. NODE 3 NODE 6 NODE 2 PATH A PATH B NODE 7 EQP NODE 1 NODE 8 CONTROLLER A2115 NODE 4 NODE 5 WIRING FAULT Figure 2 Communication with a Wiring Fault on the SLC 3 90-1150

8 Channel Digital Communication Input/Output (DC I/O) Module 24 vdc nominal, 18 to 30 Vdc. 10% overvoltage will not cause Operating: 40 F to +185 F ( 40 C to +85 C). HUMIDITY RANGE 0 to 95% RH, non-condensing. The DC I/O module provides 8 channels that are configurable as either digital inputs or outputs, with or without supervision. When configured as an input, a channel can accept fire detection devices such as heat detectors, unitized flame detectors, or any dry contact closure input device. DIMENSIONS DIN Rail Mount: L: 5.2 inches W: 4.5 inches D: 2.1 inches. Panel Mount: L: 5.2 inches W: 4.5 inches D: 1.8 inches. When configured as an output, a channel can initiate notification devices (horns and strobes) or release suppression agents (or deluge). X3301 Multispectrum IR Flame Detector OPERATING VOLTAGE 24 volts dc nominal (18 Vdc minimum, 32 Vdc maximum). Hazardous location ratings from 55 C to +125 C available on extended temperature model. The X3301 detects the presence of fire by monitoring three different frequencies of the IR spectrum. The X3301 provides unsurpassed detection of fires from light to heavy hydrocarbon fuels combined with the highest degree of false alarm rejection. When a fire is detected, a fire alarm message is immediately sent to the Controller. The device is equipped with both automatic and manual optical integrity (oi) test capability. Status is indicated by a multi-colored LED that is visible on the detector s faceplate. Class I, Div. 1, Groups B, C and D; Class II, Div. 1, Groups E, F, and G; Class I, Div. 2, Groups A, B, C and D (T4); Class II, Div. 2, Groups F and G (T4); NEMA/Type 4X. CENELEC: Standard Temperature Model CE: 0539 II 2 GD EEx de IIC T5 T6 DEMKO 01 ATEX 130204 T6 (Tamb = 55 C to +60 C). T5 (Tamb = 55 C to +75 C). Extended Temperature Model 0539 II 2 GD EEx d IIC T4 T6 DEMKO 01 ATEX 130204 T6 (Tamb = 55 C to +60 C). T5 (Tamb = 55 C to +75 C). T4 (Tamb = 55 C to +125 C). 4

UV/IR Flame Detector 24 Vdc nominal, 18 to 30 Vdc. 10% overvoltage will not cause Storage: 40 F to +185 F ( 40 C to +85 C). The EQ2200UVIR** Flame Detector provides reliable fire protection in applications where the use of either UV or IR detectors alone can result in false alarms. The device combines both a UV and an IR sensor in a single detector and requires simultaneous response of both sensors to generate a fire alarm. This enables it to respond to a real fire while ignoring potential false alarm sources such as arc welding, x-rays, or hot vibrating objects. The microprocessor based detector is equipped with advanced fault detection and diagnostic capabilities, status indicator LEDs, and software selectable options. Class I, Division 1, Groups B, C, & D. Class I, Division 2, Groups A, B, C and D. Class II, Division 1, Groups E, F, & G. Class II, Division 2, Groups F and G. CENELEC: Standard Temperature Version EEx d IIB +H2 T6 (Tamb = 40 C to +75 C). EEx d IIB +H2 T5 (Tamb = 40 C to +90 C). Extended Temperature Version EEx d IIB +H2 T4 (Tamb = 55 C to +125 C) UV Flame Detector and High Temperature UV Flame Detector 24 Vdc nominal, 18 to 30 vdc. 10% overvoltage will not cause EQ2200UV Storage: 67 F to +185 F ( 55 C to +85 C). The EQ2200UV** UV Flame Detector utilizes the UV spectrum to detect the presence of fire, and is equipped with both automatic and manual optical integrity (oi) test capability. The detector is equipped with a special arc rejection feature that enables it to prevent nuisance fire alarms caused by UV from shortduration electrical arcs or electrostatic discharge, while maintaining the ability to reliably detect the UV given off by a flame. Typical applications that benefit from arc rejection logic include electrostatic coating processes and uncontrolled environments where transient UV sources can be present, such as many typical outdoor applications. The EQ2200UVHT High Temperature UV Flame Detector is rated for continuous duty high temperature applications, such as turbine compartments, enclosures, generator rooms, etc. where ambient temperatures can continuously exceed +75 C (+167 F), up to +125 C (+257 F). It consists of an electronic module that is used with a high temperature rated UV detector. The two devices are mounted in separate enclosures and can be separated up to 20 feet (6 meters) using high temperature rated shielded cable within conduit. EQ2200UVHT Electronic Module: UV Detector: Storage: 40 F to +167 F ( 40 C to +75 C). 40 F to +257 F ( 40 C to +125 C). 67 F to +185 F ( 55 C to +85 C). Class I, Division 1, Groups B, C, and D. Class I, Division 2, Groups A, B, C, and D. Class II, Division 1, Groups E, F, and G. Class II, Division 2, Groups F and G. CENELEC: UV Flame Detector Standard Temperature Version EEx d IIB +H2 T6 (Tamb = 40 C to +75 C). Extended Temperature Version EEx d IIB +H2 T4 (Tamb = 40 C to +125 C) UVHT Detector Electronic Module CE 0539 II 2 G UV Detector EEx d IIB +H2 T4 (Tamb = 55 C to +125 C) EEx d IIB +H2 T5 (Tamb = 55 C to +90 C) EEx d IIB +H2 T6 (Tamb = 55 C to +75 C) 5 90-1150

EQ2200IDC Initiating Device Circuit and EQ2200IDCSC Initiating Device Circuit Short Circuit The EQ2200IDC Initiating Device Circuit (IDC) accepts two dry contact inputs for use with devices such as relays, pushbuttons, key switches, etc. The IDC supports ANSI/NFPA 72 Class B Style B supervised input circuits. When an input is activated, an alarm message is immediately sent to the Controller. The EQ2200IDCSC (IDCSC) Initiating Device Circuit Short Circuit is similar to the IDC, but supports ANSI/NFPA 72 Class B Style C supervised input circuits. 24 Vdc nominal, 18 to 30 Vdc. 10% overvoltage will not cause Class I, Division 1, Groups B, C, and D. Class I, Division 2, Groups A, B, C, and D. Class II, Division 1, Groups E, F, and G. Class II, Division 2, Groups F and G. PointWatch Eclipse The PointWatch Eclipse is a diffusion based, infrared combustible gas detector that provides continuous, fixed monitoring of flammable hydrocarbon gases, with programmable alarm setpoints from 5 to 60% Lower Explosive Limit (LEL). The Eclipse is capable of detecting hundreds of flammable hydrocarbon vapors. 24 Vdc nominal. Operating range is 18 to 32 Vdc. Ripple cannot exceed 0.5 volts peak-to-peak. Operating: 40 C to +75 C ( 40 F to +167 F). Storage: 55 C to +85 C ( 67 F to +185 F). Class I, Div. 1, Groups C & D (T4). Class I, Div. 2, Groups A, B, C & D (T4). CENELEC: EEx d e [ib] IIC T6 (Tamb 40 C to +40 C) EEx d e [ib] IIC T5 (Tamb 40 C to +50 C) EEx d e [ib] IIC T4 (Tamb 40 C to +75 C). Stainless Steel: Model PIRECLx4. EQ2200DCU and EQ2200DCUEX Digital Communication Unit The EQ2200DCU / EQ2200DCUEX Digital Communication Unit (DCU) digitizes a 4-20 ma analog signal and transmits the value as a process variable to the Controller. The DCU is approved for use with a variety of Det-Tronics sensors including catalytic combustible gas sensors, the PointWatch IR gas detector, and the H 2 S electrochemical sensor. The DCU will also accept other sensors with a linear 4 to 20 ma output signal. Non-intrusive calibration can be performed by one person. 24 Vdc nominal, 18 to 30 Vdc. 10% overvoltage will not cause Class I, Division 1, Groups B, C and D. Class I, Div. 2, Groups A, B, C, and D. Class II, Division 1, Groups E, F, and G. Class II, Div. 2, Groups F and G. 6

EQ2500ARM Agent Release Module RELEASE OUTPUT RATING 2 amperes at 30 Vdc maximum. 24 Vdc nominal. The EQ2500ARM Agent Release Module (ARM) provides agent release capability to the Eagle Quantum Premier system. The device is located on the SLC and is controlled by programmable logic in the Controller. The agent release module is designed to monitor and control two output circuits, which are energized together. It is compatible with a variety of solenoid or initiator based suppression systems. The release circuit (including the solenoid coil) is supervised for open circuit conditions. If an open circuit occurs, a trouble condition will be indicated. Class I, Division 1, Groups B, C, and D. Class I, Div. 2, Groups A, B, C, and D. Class II, Div. 1, Groups E, F, and G. Class II, Div. 2, Groups F and G. EQ2500SAM Signal Audible Module OUTPUT RATING 2 amperes at 30 Vdc maximum. 24 Vdc nominal. The EQ2500SAM Signal Audible Module (SAM) provides two indicating circuits for controlling UL Listed 24 Vdc polarized audible/visual indicating appliances. Each output circuit is independently programmable to allow annunciation of separate events. The outputs operate in the reverse polarity fashion when activated. Each output delivers up to 2 amperes at 24 Vdc. The Signal Audible Module is located on the SLC and is controlled by programmable logic in the Controller. Each output circuit is supervised for open and short circuit conditions. If a wiring fault occurs, a trouble condition will be indicated. Class I, Division 1, Groups B, C, and D. Class I, Div. 2, Groups A, B, C, and D. Class II, Div. 1, Groups E, F, and G. Class II, Div. 2, Groups F and G. 7 90-1150

F EQ2400NE Network Extender 18 to 30 Vdc. Operating: 40 F to +167 F ( 40 C to +75 C) The EQ2400NE Network Extender allows for expansion of the communication network. The base system can accommodate up to 60 nodes and up to 2,000 meters of wiring. By adding the appropriate number of network extenders, this can be increased to 246* network devices and up to 10,000 meters of wiring. Class I, Division 1, Groups B, C, & D. Class I, Div. 2, Groups A, B, C and D. Class II, Div. 1, Groups E, F, & G. Class II, Div. 2, Groups F and G. NEMA / Type 4X. EQ2100PSM Power Supply Monitor EQ2110PS, EQ2130PS AND EQ2175PS POWER SUP- PLIES Selectable for 120, 208 or 240 Vac input power, ±10%. INPUT FREQUENCY 60 Hz ±5% standard, 50 Hz ±5% optional. The EQ2100PSM Power Supply Monitor supervises the system power supply and reports any detected power related trouble to the Controller. EQ2200IDCGF Initiating Device Circuit Ground Fault INPUT CURRENT EQ2110PS: 4 amps at 120 Vac (60 Hz) EQ2130PS: 11 / 6 / 6 amps at 120 / 208 / 240 Vac* EQ2175PS: 24 / 15 / 12 amps at 120 / 208 / 240 Vac*. *Specify 50 Hz or 60 Hz. Operating: +32 F to +122 F (0 C to +50 C) Storage: 40 F to +185 F ( 40 C to +85 C). EQ2100PSM POWER SUPPLY MONITOR 24 Vdc nominal, 18 to 30 Vdc. The EQ2200IDCGF Initiating Device Circuit Ground Fault module monitors for system ground faults. Operating: +32 F to +122 F (0 C to +50 C) EQ2200IDCGF IDC GROUND FAULT Same as EQ2200IDC. NOTES: * For the initial release only, the EQP system is limited to 60 field devices. All subsequent releases will support up to 246 field devices. ** EQ2200UV and EQ2200UVIR will be replaced by new UV and UV/IR Flame Detectors after 1/1/03. For complete specification or certification information, refer to the Specification Data sheet for each individual device. ControlNet is a trademark of ControlNet International. REGISTERED BY UL AND BSI ISO 9001 REGIS T E RE D FIR M NO. A2305 REGIS T E RED NO. IRM 25826 Detector Electronics Corporation 6901 West 110th Street Minneapolis, Minnesota 55438 USA Operator: (952) 941-5665 or (800) 765-FIRE Customer Service: (952) 946-6491 Fax (952) 829-8750 http://www.detronics.com E-mail: detronics@detronics.com Specifications subject to change without notice.