DX AIR CURTAIN. SensAir

Similar documents
CLIMATE SEPARATION SOLUTION. SensAir

CLIMATE SEPARATION SOLUTION. SensAir

INDUSTRIAL AIR CURTAIN. IndAC 2

Energy-efficient heat source provides comfort in large rooms

Optimal work climate with open doors. Industrial air curtains Model IndAC

CASSETTE UNIT. Comfort Circle

The green and friendly entrance. Comfort air curtains Model CA 2

COLD STORE AIR CURTAIN MAT

Easily maintained air curtain. Comfort air curtains Model DoorFlow

CHILLED ROOM AIR CURTAIN. IsolAir

INDUSTRIAL AIR CURTAIN. IndAC 2

COMFORT AIR CURTAIN. DoorFlow

Strong partners in innovative climate technology. Comfort Air Curtains Model CA DK for Daikin VRV-system

Cassette units Model Comfort Circle. - heating - cooling - ventilation

AIR CURTAIN GUIDE WHAT IS AN AIR CURTAIN?

Manual Comfort Air Curtain

VRV The total solution. Integrated Climate Control

Enriching Environments

X-Stream Air Natural Ventilation kits are predominantly designed for self-installation. Suitable for ventilating existing and new build applications.

Recessed. Air Curtain. Fig 1. Recessed air curtain

SPECIFICATION GUIDE FLEXAIR. Possibility to add auxiliary heaters: Gas, Electrical Heater, Hot Water Coil Possibility to add Heat Recovery Module

Manual. Industrial Air Curtain Model IF. English. Version 1.1

Premium Efficiency Heat Recovery Unit. D-AHU Modular L. Air Handling Units

SPECIFICATION GUIDE NEOSYS. Air-cooled Liquid Chiller for outdoor installation (NAC) Nominal cooling capacity: 200 to 460 kw

DAIKIN Air Handling Unit Modular

The CAB & DAB Air Curtains

BRT C/H Series PACKAGED AIR TO AIR UNITS COOLING / HEATING APPLICATIONS OUTDOOR INSTALLATION. Ver. 1.01

Daikin Applied UK Technically better... D-AHU Modular R. Air handling units. Compact air handling unit with heat recovery wheel

Original instructions AR

INCORPORATION & INSTALLATION INSTRUCTIONS. For incorporating a heat pump control system by others

T-RECESSED RANGE AIR CURTAINS INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

Primo Hotel. General. Indoor climate units for hotel rooms

New rooftop series UATYQ-ABAY1 AFC2Y1 AFC3Y1. Extensive option package included in all models. ErP. years warranty. compliant 2018

WOLF WARM AIR CURTAIN

TopVent Design Handbook

3 rd Generation of VRV. The professional solution for your professional project

NOZ2. Multi-Directional Heating & Cooling Solutions

PHV-RECESSED RANGE AIR CURTAINS INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS

Fan Coil Range HYDRONIC TERMINALS

Billa Palaca, Split. Integrated refrigeration and climate control meets modern HVAC demands within an ancient building.

HP RECESSED HEAT PUMP RANGE AIR CURTAINS INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS. For use with Mr Slim Outdoor Units

AIR CURTAINS. Air curtains with integrated control panel and remote control. Air curtains without heating, with electric heating or water heating

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

The ultimate fresh air solution.

AC25. Art.nr:

Reinventing Energy Efficiency

CHILLED BEAM CASSETTE IQ STAR LYRA

energy efficient air curtains technical data and controllers

LV SERIES SINGLE-ZONE HEATING & COOLING SYSTEMS

Keep looking you ll never find me. VRV IV heat pumps for indoor installation

39HX. High-efficiency dual-flow air handling unit PRODUCT SELECTION DATA. Plug & play unit (built-in control) Class A+ across entire range

Daikin s Policy. and Comprehensive Actions on the Environmental Impact of

VRF HP HEAT PUMP RANGE AIR CURTAINS INSTALLATION, OPERATION & MAINTENANCE INSTRUCTIONS. For use with City Multi (VRF) systems

Dunham Bush Air Cooled Screw Chiller AFVX B 6SR Series

Ceiling air diffuser INDULTHERM INDULTHERM-e

EPCE00-10B. Powerful. air cooled. Hydronic systems EUWA*40-200K(A)X

LV SERIES SINGLE-ZONE HEATING & COOLING SYSTEMS

Flexible & Innovative. Cooling Solutions

INFO. Compact DUAL. GADC Air Cooler for HFC and CO 2. Dual discharge air cooler with and without integrated condensation water pump.

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 21 to 39 kw

Hood Depot Internatioonal, Inc., Phone S. Powerline Road, Deerfield Beach, FL

CHGV AIR COOLED WATER CHILLER WITH HYDRAULIC EQUIPMENT AIR / WATER 47 to 78 kw

NEOSYS. AIR TO WATER LIQUID CHILLER kw. AIR TO WATER HEAT PUMP kw. lennoxemea.com

Arena Centar, Zagreb. Delivering energy-efficient climate control for Croatia s premier shopping centre

Galletti IWC THE HYDRONIC CASSETTE UNIT PAR EXCELLENCE A guide to choosing Create value to design better

Cooling and heating systems. Static cooling ceiling system SKS-5/3 for visible installation

Regulations covering Heating and Ventilation equipment in Schools

Fully Flat Cassette Design & Genius in one

Static cooling ceiling system SKS-4/3 DS 4094 E /1. Technical Selection


Daikin VRV Systems Plugin VE2012 User Guide

CMA TECHNICAL MANUAL CONDENSING UNITS FOR OUTDOOR INSTALLATION O L S A F RA N

Blower-YEFB-020-3R-1maxVel

ART-U 1-4 kw. Design fan coil unit with a minimum depth of 10 cm only and BLDC motor. Fan coil ART-U PLUS. Design-driven innovation NEW

HIWARM kw. Air-water system with external and internal BLDC unit. Total heat recovery multi-purpose units HIWARM PLUS

Mitsubishi System Technologies:

TOTAL HEAT RECOVERY MULTI-PURPOSE HEAT PUMPS

30GH Air-Cooled Liquid Chillers 30GH Nominal cooling capacity kw

DUCTED UNITS EBH EDS INTEGRATED COMFORT SYSTEMS

EHH SERIES DRAW THROUGH FAN COILS CFM

FHE FHE. Dehumidifiers for radiant cooling systems with heat recovery. Versions

Rosemex Products 96 VENTILATION CLIMATAIR COMPARTMENT AIR HANDLING UNITS

Technical documentation. ComfoAir XL The latest generation of ventilation units with heat recovery

Technical Information HXV - HRV Ventilation

Daikin VRV Sizing & Simulation Plug-in User Guide

Fan Coil Unit 1. BOSCH Climate Fan Coil Unit

Whole Home Heat Recovery Ventilation

Leadership, Innovation, Advanced Technology Synergise Here!

Küba SG commercial

Reinventing Energy Efficiency WARMNESS.

Güntner Info GVX. with microox technology kw. Always a step ahead: microox condenser system with maximum installation flexibility

BTBa. FLUSHLINE Ventilated chilled beam for cooling, heating and ventilation. BTBa

AIR CURTAIN T SURFACE MOUNTED RANGE

AIR HANDLING UNITS ASSET REFERENCE: DESIGN AHU 1 AHU 2

lindab we simplify construction LindabIndoorClimateSolutions Product overview Airborne Solutions

PRODUCT DATA COMPACT P - SERIES BY NILAN. Sanitary hot water production. Heating. Ventilation < 300 m 3 /h. Passive heat recovery.

THE ULTIMATE ROOFTOP SOLUTION

SLS 1202 to With or without total heat recovery. u Air Cooled Screw Chillers. 262 to 916 kw. Engineering Data Manual

KLIMA Active Chilled Beams

Water cooled VRV IV W-series

Transcription:

DX AIR CURTAIN SensAir

Biddle and Daikin Complete climate system Since 2006 Biddle and Daikin have joined forces to provide a complete climate system for shops and public buildings. By combining Biddle air curtains with the highle efficient Daikin heat pump systems, a lot of energy is saved and comfort in the building is optimum. Maximum comfort Both visitors and personnel can enjoy maximum comfort during the whole year, under all weather conditions. This is the result of the efficient climate separation created by Biddle air curtains, while heat pump systems heat, cool or ventilate to provide a comfortable indoor climate. Integrated air conditioning solutions The advantage of combining air curtains with heat pumps and heat recovery is that climate separation, heating, cooling and ventilation are combined in one system. Considerable savings on energy costs can be made as compared with traditional systems; this means that the payback time is very short, generally about 1.5 years. The stable indoor climate due to efficient climate separation reduces heat loss through the doorway and also increases the efficiency of the Daikin systems. A Daikin heat pump is very efficient and saves up to 40% of energy costs as compared with a high-efficiency central heating boiler. A Biddle air curtain in combination with Daikin s heat pump systems is the ultimate energy-saving solution for cooling, heating, ventilation and climate separation and means that other energy generators, such as a central heating system, are not required. Daikin climate systems Biddle air curtains can be installed plug&play to various Daikin climate systems. Heat pump/heat recovery: for heating and/or cooling a building. The heat released from cooling systems (residual heat) is recycled for the Biddle air curtain. Conveni-pack: a unique total solution for refrigerated storage and air conditioning, where energy consumption is reduced to a minimum as up to 100% of the heat is recovered from cooling equipment and used to heat the area. This is without additional costs.

SensAir DX air curtains A new wave in climate separation SensAir air curtains are the ideal solution for retailers and other end-users to combat the issue of climate separation across their outlet or office building doorway. The importance of accessibility to attract customers in the retail sector is well-known, but with this free form of access through open door trading, cold draughts and high-energy bills are often the consequence. High comfort and energy efficient The SensAir technology has been improved to deliver greater comfort for all, whether it is in a supermarket, high street store or office building. The SensAir air curtain, does not act as a barrier in the place of a door, its prime role is to reduce the amount of warm air leaving the building and condition the incoming air to a comfortable temperature. BSRIA and Biddle research produced documented evidence proving that air curtains operate best with specific velocities and air volumes. The SensAir air curtain satisfies these needs by delivering the right air flow and temperature at the right time automatically, reducing energy loss. Furthermore it is the only commercially available air curtain of its kind that now offers a unique air damper system to improve efficiency, by controlling the outlet velocity. Intelligent auto-active control and monitoring The auto-active control is the next generation of controls. Knowing that manual control of air curtains often leads to the incorrect setting the inclusion of the automatic CHIPS (Corrective Heating & Impulse Prediction System) technology ensures the most appropriate setting at any moment in time. The i-sense in the discharge grille measures the indoor and outdoor temperatures active in the door opening resulting in accurate data. This auto-active control has been demonstrated to produce energy saving savings of up to 75% when compared with a manually controlled air curtain. Biddle has an extensive range of control options: the b-touch control panel, remote monitoring of comfort and energy performance and connecting to a BMS is easy through the standard integrated Modbus connection. Benefits Energy efficient and high comfort - improved accuracy of temperature data collection - correct settings are adjusted actively and automatically - comfortable inside climate and inviting appearance - low sound level Intelligent control and monitoring - self-regulating: auto-active control - remote monitoring: b-connect - Modbus: integrated as standard Installation & maintenance-friendly - easy to assemble and set up (b-touch) - ready-to-use, integrated control Complete customized solution - customer specific styling possible - suitable for various heat sources

SensAir and Daikin Energy-efficient climate concept Biddle and Daikin supply a complete plug & play climate concept. Within this energy-efficient climate concept two different versions are available: the SRV and SRQ models. Complete SRV air curtain climate system The climate system consisting of the SensAir air curtain, model SRV (1), Daikin VRV outdoor unit (2) and indoor units (3) supplies heating, cooling, ventilation and climate separation in one energy-efficient installation. By heating and cooling at the same time the heat extracted from the cooling systems can be extracted for the air curtain, thus resulting in considerable reduction in energy costs. This integrated climate system is energy efficient, has a quick payback time and provides a comfortable indoor climate. Standalone SRQ air curtain heat pump The SensAir air curtain, model SRQ (1), is available in combination with a Daikin ERQ heat pump (2). The heat pump provides the heating energy required for climate separation in the doorway. The heating and cooling in the building are controlled separately (3). Considerable energy savings are obtained by connecting the SensAir to a heat pump: up to 40% as compared with a high-efficiency boiler and even 73% as compared with an electric air curtain. This climate solution is sustainable, energy saving and creates a pleasant indoor climate. The SensAir is also available as a hybrid DX version Constant heating with hybrid SensAir The hybrid SensAir consists of a DX and an additional electric heating element. First maximum use is made of the available heat from the DX. If necessary, the electric element switches on automatically so that the required discharge temperature can be achieved continuously. In cold weather the electric element switches on automatically if the outdoor unit is not adequate to supply the capacity required. The electric element also supplies the heating required during the defrosting cycle. In this way climate separation is always guaranteed.

SensAir auto-active control Intelligent control and monitoring There are an extensive range of control options; touchscreen control (b-touch), remote operation and integration with a Building Management System (BMS). It is possible to monitor the energy performance and comfort levels remotely by means of the b- connect monitoring module. Connecting to a BMS is easy through a standard Modbus Protocol connection, whilst it is also possible to communicate via BACnet. All SensAir devices are fitted with Biddle's innovative auto-active control, the next generation of controls. Auto-active control Generally, installing an air curtainis typically set to operate at a mid-speed setting and rarely adjusted. This results in the air curtain continually operating at a single air volume, velocity and temperature. However, as internal and external conditions constantly vary this means the air curtain will only be operating at the optimum setting some of the time, and for the rest of the time will be on either too high or too low a setting. The automatic CHIPS (Corrective Heating & Impulse Prediction System) technology ensures the most appropriate setting at any moment in time. The i-sense in the discharge grille measures the indoor and outdoor temperatures active in the door opening resulting in accurate data. This process ensures that the SensAir is always functioning correctly and yields an ideal, energy-efficient indoor climate without interference of the user. b-touch control panel A revolutionary combination of technologies SensAir s auto-active control combines no fewer than four renowned Biddle technologies. The revolutionary patented i-sense infrared technology collects all temperature-related data in the doorway. CHIPS technology translates this information into the correct setting, whilst the adaptable discharge width (Controlled Air strength technology) and the patented rectifier create the perfect climate separation. Benefits Combination SensAir - Daikin - Sustainable climate solution - Integrated climate system possible - Extensive control options - Extremely low energy consumption - Low investment costs (no central heating needed) - Optimal comfort - Low CO -emission 2 You will find more information regarding SensAir s commercial advantages in a separate brochure.

SensAir selection Air curtain selection Selecting the right air curtain is crucial in order to ensure the SensAir works optimally. An air curtain performs properly when it completely shields the doorway and is strong enough to heat the cold air streaming in from outside to acomfortable temperature. 1. Installation height Selecting an air curtain is a simple process, achieved by taking installation height (floor to bottom of unit) and door width into account (see adjacent diagram and selection table). 2. Natural ventilation The volume and temperature of the incoming outside air are hard to measure because the climatic circumstances around the doorway are constantly changing. Structural issues also influence capacity requirements. The following guidelines generally apply when it comes to choosing your device: Favourable: indoor shopping centre, sheltered shops Normal: moderate direct wind attacks, no open doors facing each other, ground floor Unfavourable: on a corner or square, several floors, open staircases Selection table Proper installation In order to guarantee proper functioning, the distance between the air curtain and the door should be as small as possible, whilst the curtain itself should be at least as wide as the doorway. situation favourable normal unfavourable type door height (cm) S < 240 < 220 - M < 280 < 250 < 220 L < 330 < 300 < 280 XL < 400 < 350 < 320 Simulation tool Biddle has developed a simulation tool to help you select the right air curtain: VACP (Visual Air Curtain Performance). Biddle has specific advice for all doorway scenarios. For more information, please contact Biddle s sales department.

SensAir possibilities A suitable solution for every situation The SensAir has endless possibilities. The SensAir creates optimum climate separation in all doorways and is also suitable for Daikin systems. There is a solution available for many monitoring and control options. Example type code: SRV S-100-DK-80-F SRV = SensAir with Daikin VRV SRQ = SensAir with Daikin ERQ Capacity S = Small (200-240 cm) M = Medium (220-280 cm) L = Large (250-330 cm) XL = Extra Large (300-400 cm) Length (cm) 100-150 - 200-250 DX = Refrigerant R410a DXE = DK + Electrical heating Capacity index 80-100 - 125-140 - 250 Model F = Free hanging model R = Recessed model C = Cassette model For every door width Doors wider than 250 cm are covered by placing multiple units next to each other. Control options Auto-active control with b-touch control panel b-connect monitoring module Modbus communication Daikin DX: Direct expansion SRQ S-100 not available Standard colours Traffic white (RAL 9016) with accent end panels in silver grey (RAL 9006) Silver grey (RAL 9006) Other RAL classic colours available on request Customer specific styling The inlays in the end panels are supplied in grey and white as standard. The removable inlays in the end panels can also be styled specifically if required (e.g. colour and logo). For the water, electrical, hybrid and ambient versions a separate brochure is available. End panels with styled inlays

SensAir delivery and accessories Delivery and accessories i-sense Technologies i-sense infrared technology to collect accurate temperature data in the door opening CHIPS technology to adjust the settings automatically Controlled air strength technology for the best downward penetration Rectifier technology to reach the floor at the lowest possible speed DX version For a complete installation of model SRV or SRQ several additional components to be delivery by Daikin are necessary. Standard delivery Modbus communication Air filters Ceiling mounting brackets Duct connections R-model (ducts not included) b-touch control panel Accessory set for auto-active control b-touch control panel Two Biddle low voltage cables: 1 x 5 m, 1 x 25 m Two end panels (model F) end panels - 2 colours Optional b-connect monitoring module Filter sensor Wall mounting brackets: standard and design Threaded rod covers Door contact switch External outdoor sensor Installation possibilities Wall mounting brackets M8 threaded rods (see also - threaded rod covers)

SensAir connections Electrical connections The SensAir is delivered as standard with the b-touch control panel and i-sense infrared technology. It is also possible to specify the optional b-connect monitoring module or communicate via Modbus, the latter of which is a standard feature on all units. 1. i-sense infrared technology 2. b-touch control panel 3. b-connect monitoring module 4. Modbus communication

SensAir DX specifications Specifications Casing The casing is made of zinc plated sheet steel, and has an inspection panel in the bottom. The inlet grilles are made of anodised aluminium with fixed fins. The inlet module and the end panels as well as the casing are, as a standard, supplied in silver grey (RAL 9006) or traffic white (RAL 9016). The end panels of the white SensAir have a grey inlay. Other RAL casing colour finishes are available for an additional charge. Motor / Fan assembly The air curtain is equipped with two or more (depending on type) dual-inlet, vibration free suspended centrifugal fans. Each fan is driven by arotor motor on bearings, which are seal for life and no maintenance is required. The fan casing and the impeller are made of zinc coated plate steel. The motors, as standard, are fitted with thermal contacts. These thermal contacts break the circuit of the motor when the maximum permissible motor temperature is exceeded. Heating coil DX: made up of 3/8" copper tubes and aluminium fins. The fluid connection is 9.52 mm, and the gas connection is 16 mm (with 100, S/M-150 & 200, S-250), 19 mm (with M-250, L/XL-150) or 22 mm (with L-200 en 250). Hybrid: a combination of DX with an electrical stitched wire heating element. Connections To connect DX units to the mains supply, they come with a fixed cable (approx. 2 m long) with a moulded, earthed plug. The connection for Daikin units and the connector plate are fitted on the top of the unit. The mains cable for electrical heating must be connected within the unit. The top of the unit has a cable gland for feeding through the feeder cable. A 5-core cable (3 phases + earth + neutral) is required for proper connection.

SensAir DX explanation of technical data Explanation technical data Because of the auto-active control of the SensAir DX air curtain the outlet temperature varies at all speeds, depending on the situation. The maximum heating capacity of the DX air curtains is the same as the heating capacity in the highest fan speed. Selection Daikin outdoor unit To determine the correct Daikin outdoor unit for model SRV, you need to add together the capacity indexes of all the indoor units. Sound The sound data is based on the direct field, in a situation with an open door and a sound absorbing ceiling. The sound data for different situations can be determined by adding the adjacent values to the table values. Closed door Acoustical "hard" ceiling + 1 à 2 db(a) + 2 à 3 db(a) Deviating distances and several units next to each other can be calculated with the table below. Data from the 1 m unit, measured at a distance of 3 m, is the basic assumption. The factors apply to all types of air curtains. Correction factors for sound pressure in db(a) Note distance (m) total unit length (m) 1 1,5 2 2,5 3 3,5 1 +9.5 +11.3 +12.6 +13.5 +14.3 +15.0 2 +3.5 +5.3 +6.5 +7.5 +8.3 +9.0 3 0 +1.8 +3.0 +4.0 +4.8 +5.4 4-2.5-0.7 +0.5 +1.5 +2.3 +2.9 5-4.4-2.7-1.4-0.5 +0.3 +1.0 The SRQ S-100 unit is not available.

SensAir technical data DX heating SRV S-100-DK nominal unit length m 1 door height m 2-2.4 max. input current (1 phase) A 0,88 max. fan power kw 0,2 max. specific fan power W/l/s 0,63 max heating capacity kw 7,8 capacity index 80 weight casing style F / R / C kg 52/62/60 air volume m³/h 440 600 680 880 1010 1130 heating capacity kw 3,6 4,7 5,2 6,4 7,1 7,8 sound pressure level at 3m db(a) 27 33 37 42 46 48 SRV/Q S-150-DK nominal unit length m 1,5 door height m 2-2.4 max. input current (1 phase) A 1,32 max. fan power kw 0,3 max. specific fan power W/l/s 0,63 max heating capacity kw 9,7 capacity index 80 weight casing style F / R / C kg 73/89/84 air volume m³/h 660 910 1020 1320 1520 1700 heating capacity kw 4,9 6,2 6,8 8,2 9 9,7 sound pressure level at 3m db(a) 28 35 39 43 47 50

SensAir technical data DX heating SRV/Q S-200-DK nominal unit length m 2 door height m 2-2.4 max. input current (1 phase) A 1,76 max. fan power kw 0,39 max. specific fan power W/l/s 0,63 max heating capacity kw 12,6 capacity index 100 weight casing style F / R / C kg 88/109/103 air volume m³/h 880 1210 1360 1770 2020 2260 heating capacity kw 6,4 8,1 8,9 10,6 11,7 12,6 sound pressure level at 3m db(a) 30 36 40 45 49 51 SRV/Q S-250-DK nominal unit length m 2,5 door height m 2-2.4 max. input current (1 phase) A 2,2 max. fan power kw 0,49 max. specific fan power W/l/s 0,63 max heating capacity kw 17,3 capacity index 140 weight casing style F / R / C kg 113/139/131 air volume m³/h 1100 1510 1700 2210 2530 2830 heating capacity kw 8,5 10,9 12 14,5 16 17,3 sound pressure level at 3m db(a) 31 37 41 46 50 52

SensAir technical data DX heating SRV/Q M-100-DK nominal unit length m 1 door height m 2.2-2.8 max. input current (1 phase) A 1,25 max. fan power kw 0,27 max. specific fan power W/l/s 0,63 max heating capacity kw 9,7 capacity index 80 weight casing style F / R / C kg 59/69/67 air volume m³/h 490 740 880 1180 1310 1530 heating capacity kw 3,9 5,6 6,4 8 8,6 9,7 sound pressure level at 3m db(a) 25 34 39 45 50 53 SRV/Q M-150-DK nominal unit length m 1,5 door height m 2.2-2.8 max. input current (1 phase) A 1,87 max. fan power kw 0,4 max. specific fan power W/l/s 0,63 max heating capacity kw 11,7 capacity index 80 weight casing style F / R / C kg 81/97/92 air volume m³/h 730 1100 1320 1780 1960 2300 heating capacity kw 5,3 7,2 8,1 9,9 10,6 11,7 sound pressure level at 3m db(a) 26 35 40 47 51 54

SensAir technical data DX heating SRV/Q M-200-DK nominal unit length m 2 door height m 2.2-2.8 max. input current (1 phase) A 2,49 max. fan power kw 0,54 max. specific fan power W/l/s 0,63 max heating capacity kw 15,2 capacity index 100 weight casing style F / R / C kg 101/122/116 air volume m³/h 970 1470 1750 2370 2610 3070 heating capacity kw 6,9 9,4 10,6 12,9 13,8 15,2 sound pressure level at 3m db(a) 28 37 42 48 53 56 SRV/Q M-250-DK nominal unit length m 2,5 door height m 2.2-2.8 max. input current (1 phase) A 3,12 max. fan power kw 0,67 max. specific fan power W/l/s 0,63 max heating capacity kw 21,1 capacity index 140 weight casing style F / R / C kg 125/151/143 air volume m³/h 1210 1840 2190 2960 3270 3840 heating capacity kw 9,2 12,7 14,5 17,8 19 21,1 sound pressure level at 3m db(a) 29 38 43 49 54 57

SensAir technical data DX heating SRV/Q L-100-DK nominal unit length m 1 door height m 2.5-3.3 max. input current (1 phase) A 3,03 max. fan power kw 0,57 max. specific fan power W/l/s 0,66 max heating capacity kw 17,1 capacity index 125 weight casing style F / R / C kg 72/85/83 air volume m³/h 1010 1440 1710 2240 2680 3140 heating capacity kw 7,6 10,1 11,4 13,8 15,5 17,1 sound pressure level at 3m db(a) 33 40 43 48 53 56 SRV/Q L-150-DK nominal unit length m 1,5 door height m 2.5-3.3 max. input current (1 phase) A 4,55 max. fan power kw 0,86 max. specific fan power W/l/s 0,66 max heating capacity kw 25,6 capacity index 200 weight casing style F / R / C kg 106/124/121 air volume m³/h 1510 2160 2560 3360 4020 4720 heating capacity kw 11,4 15,1 17,1 20,7 23,2 25,6 sound pressure level at 3m db(a) 34 41 44 50 54 58

SensAir technical data DX heating SRV/Q L-200-DK nominal unit length m 2 door height m 2.5-3.3 max. input current (1 phase) A 6,07 max. fan power kw 1,15 max. specific fan power W/l/s 0,66 max heating capacity kw 32,3 capacity index 250 weight casing style F / R / C kg 134/159/155 air volume m³/h 2010 2880 3410 4480 5360 6290 heating capacity kw 14,9 19,5 22 26,4 29,5 32,3 sound pressure level at 3m db(a) 36 43 46 51 56 59 SRV/Q L-250-DK nominal unit length m 2,5 door height m 2.5-3.3 max. input current (1 phase) A 7,58 max. fan power kw 1,44 max. specific fan power W/l/s 0,66 max heating capacity kw 34,4 capacity index 250 weight casing style F / R / C kg 167/199/193 air volume m³/h 2520 3610 4270 5600 6700 7860 heating capacity kw 16,9 21,8 24,3 28,7 31,7 34,4 sound pressure level at 3m db(a) 37 44 47 52 57 60

SensAir technical data DX heating SRV/Q XL-100-DK nominal unit length m 1 door height m 3-4 max. input current (1 phase) A 5,02 max. fan power kw 1,03 max. specific fan power W/l/s 0,94 max heating capacity kw 19,6 capacity index 125 weight casing style F / R / C kg 76/89/87 air volume m³/h 1170 1580 2030 2720 3370 3950 heating capacity kw 8,5 10,8 12,9 15,7 17,9 19,6 sound pressure level at 3m db(a) 38 42 47 52 57 62 SRV/Q XL-150-DK nominal unit length m 1,5 door height m 3-4 max. input current (1 phase) A 7,53 max. fan power kw 1,54 max. specific fan power W/l/s 0,94 max heating capacity kw 29,2 capacity index 200 weight casing style F / R / C kg 112/130/127 air volume m³/h 1750 2370 3050 4090 5060 5920 heating capacity kw 12,8 16,2 19,3 23,4 26,7 29,2 sound pressure level at 3m db(a) 39 44 48 54 59 63

SensAir technical data DX heating SRV/Q XL-200-DK nominal unit length m 2 door height m 3-4 max. input current (1 phase) A 10,04 max. fan power kw 2,05 max. specific fan power W/l/s 0,94 max heating capacity kw 36,4 capacity index 250 weight casing style F / R / C kg 143/168/164 air volume m³/h 2330 3170 4060 5450 6740 7890 heating capacity kw 16,7 20,9 24,7 29,7 33,6 36,4 sound pressure level at 3m db(a) 41 45 50 55 60 65 SRV/Q XL-250-DK nominal unit length m 2,5 door height m 3-4 max. input current (1 phase) A 12,55 max. fan power kw 2,57 max. specific fan power W/l/s 0,94 max heating capacity kw 38,3 capacity index 250 weight casing style F / R / C kg 176/208/202 air volume m³/h 2920 3960 5080 6810 8430 9870 heating capacity kw 18,8 23,2 27,1 31,9 35,6 38,3 sound pressure level at 3m db(a) 42 46 51 56 61 66

Free hanging model SensAir dimensional sketches

Recessed model SensAir dimensional sketches

Cassette model SensAir dimensional sketches

SensAir dimensional sketches Wall suspension brackets Standard Design Threaded rod covers Size H is the distance between unit and ceiling. This size needs to be communicated on the order.

SensAir dimensional sketches Connections DX

Dimensional sketches Index The corresponding numbers in the dimensional sketches are explained below: 3 - Air inlet grille with filter 20 - Connection plate 35 - Ducts are not supplied 43 - Finishing sections supplied separately 36 - Eye bolt M6 12 - Pipework 87 - Threaded rod covers (position is flexible) 17 - Connection Daikin units 46 - Fluid connection 49 - Gas connection 50 - Gland Explanation dimensional sketches Models Free hanging: by removing the end panels, the units are easy to interlink. Cassette: daylight opening if cover moldings are used in a suspended ceiling = (A+8) x (C+8) mm. Recessed: daylight openings if cover moldings are used: - for air discharge (A+8) x (D+8) mm - for air inlet: (A+8) x (I+8) mm If the recessed model is to be built into a cove, it is also available in a design that has no inlet air plenum or flexible ducts. To prevent bad air from let in, the cove will need to be air-tight. Wall suspension brackets and threaded rod covers Size H is the distance between unit and ceiling. This size needs to be communicated on the order. Material threaded rod covers: zink coated plate steel, painted, standard colour RAL 9016 and RAL 9006. Note All dimensions are in mm. SensAir 2500 mm units have 3 suspension brackets. All other sizes have 2 suspension brackets.

Notes Notes

Notes Notes

Biddle bv P.O. Box 15 9288 ZG Kootstertille The Netherlands T +31 (0)512 33 55 55 E info@biddle.nl I www.biddle.nl