FACILITIES PLANNING STUDY RIVER VALLEY SCHOOL DISTRICT Arena Elementary School 314 Willow St. Arena, WI 53503 7 South Dewey Street Eau Claire, Wisconsin 54701 715.83.1605 sdsarch.com
ARENA General Overview Note: Property lines have been approximated Site Acreage: Approx. 5. Acres Parking Stalls: 19 Building Area:,575 GSF Construc on: Masonry/CMU ES Director: Mr. Jaime Hegland Associate Director: Mr. Brian Krey Students: 111 GSF/Student: 03 Grades: K through 5th Paved Area P.1 Descrip on: General Parking Type: Asphalt Net Area: Approx. 10,810 SF Ra ng: Paved Area P.3 Descrip on: Play Ground Type: Asphalt Net Area: Approx. 5,310 SF Ra ng: Paved Area P. Descrip on: Play Ground Type: Asphalt Net Area: Approx. 5,60 SF Ra ng: P.3 P.1 P. * See the final page of Chapter 1 for ra ng system of paved surfaces. Chapter Page
Site Analysis 1 3 4 5 6 7 4 8 3 4 1 5 1 Code/Safety Issue Site photos Chapter Page 3
ARENA Building Construction, Remodels and Additions Year 195 1968 Project Scope Addi on Addi on Area 7,560 SF 15,015 SF Legend 1 Founda on: Cast-In-Place Exterior Shell: Brick Cavity Wall / Concrete Block R-VALUE: 1.79 Interior: Concrete Block Founda on: Concrete Block Exterior Shell: Brick Cavity Wall R-VALUE: 3.15 (5.5 if filled with vermiculite) Interior: Concrete Block 1 Chapter Page 4
Roof Analysis Legend BSPM (Ballasted Single Ply EPDM) ASPM (Adhered Single Ply EPDM) R.4 R.5 Roof Area R.1 Roof Type: ASPM Net Area: 1,495 SF Year Installed: Unknown Condi on: Average Roof Area R. Roof Type: ASPM Net Area: 1,140 SF Year Installed: Unknown Condi on: Average Roof Area R.4 Roof Type: ASPM Net Area: 5,485 SF Year Installed: 01 Condi on: Very Good Roof Area R.5 Roof Type: ASPM Net Area: 9,710 SF Year Installed: 1984 Condi on: Poor R.3 Roof Area R.3 Roof Type: ASPM Net Area: 5,55 SF Year Installed: Unknown Condi on: Average R. R.1 Roof photos Chapter Page 5
ARENA Room Assignments and Building Use Legend Classroom/Instruc on Athle cs Administra on/conference Food Service Music/Arts Circula on TITLE 1 General/Support KITCHEN 5TH GRADE 4TH GRADE 3RD GRADE COMPUTER LAB IMC ND GRADE 1ST GRADE ART & MUSIC STORAGE NURSE WORK OFFICE TOILET TOILET MECH ND GRADE KINDERGARTEN 1ST GRADE MULTIPURPOSE WORK/ LOUNGE/ RESOURCE RESOURCE STORAGE PE OFFICE TOILET TOILET STORAGE Chapter Page 6
1 3 4 1 3 4 1 3 4 1 3 4 1 3 4 1 3 4 1 3 4 9 8 1 3 4 5 6 7 8 9 Floor Plan Analysis Damaged/worn flooring Restroom is not ADA compliant Damaged/worn cabinets/casework Damaged/worn ceiling Damaged/worn plumbing fixtures No Ves bule at building entrance Damaged/Worn doors Corridor is being used as a Work Room No visual/secure control of the Main Entrance from the Office 8 10 1 3 4 1 3 4 1 3 4 13 1 9 11 6 7 6 7 6 Interior Photos Code/Safety Issue Safety/Health Issue ADA/Accessibility Issue Program Related Problem Area Chapter Page 7
ARENA Mechanical Analysis AC Control Air Compressor Exhaust Fan AH Air Handling Unit Fin Tube Heat B CH Boiler Cabinet Unit Heater KH GS Kitchen Hood Gas Service UV UV UV MS UV UV UV UV CR CV ED Condensate Return Sta on Convector Exhaust Duct MS Mini-Split P Pump UH Unit Heater UV Unit Ven lator KH CH CH 1) Corridors are u lized as return air plenums. ) Gymnasium air handling units are not properly accessible. CV ED CV ED CV CV ED CV CV CH 3) The classrooms are served by hea ng only unit ven lators and the gym is served by two hea ng only air handling units. The air handling units are past or nearing the end of their useful life. Unit ven lators are nearing the end of their useful life. AH CH CR AC 14 B UV UV CV UV 4) Steam boilers provide the heat for the building. The boilers, condensate return sta on, valves and accessories are past or nearing the end of their useful life. AH *not being used AH Underground Fuel Oil Tank CH Steam/Condensate through tunnel system Code or Safety Issue Photos Chapter Page 8
UT*pole mounted Electrical Analysis P K D PS TP 16 D P B P M P E FA 15 EM P A D Data Center EM Electric Meter FA Fire Alarm Control Panel MC Master Clock MS Main Service P Panel PS Paging System SS Security System UT U lity Transformer TP Phone/Data Termina on Port 1) Automa c ligh ng control is not present in all required areas of the building. ) Emergency egress ligh ng does not appear to be adequate for egress paths. LIGHTING 3) Ligh ng generally consists of fluorescent recessed and wall mounted fixtures that are in good working condi on. 4) Some recent ligh ng upgrades appear to have taken place. These include exterior LED wall mounted ligh ng and fluorescent P G high bay ligh ng in the gym. POWER 5) Electrical panels in the building are generally in working condi on, but appear to be over 50 years old and are past their expected useful lives. FIRE ALARM 6) The exis ng fire alarm single zone system is in working condi on, but appears to be over 50 years old and is past its expected useful life. Code/Safety Issue Photos Chapter Page 9
ARENA Plumbing Analysis Site Sep c AB Acid Neutralizing Basin CP Circula on Pump GS Gas Service GI Grease Interceptor LS Li Sta on S Water So ener SP Sump Pump WH Water Heater WS Water Service GS GI PLUMBING WH 1) The domes c water is so ened by a Hellenbrand, model H-1S, water so ener and heated by a single Rheem, 500 MBH, gas fired water heater. The plumbing equipment appears to be past or nearing the end of their useful life. SP WS S WH 17 FIRE PROTECTION ) The building is not provided with fire protec on. Code/Safety Issue Photos Chapter Page 10
Photographs 1 09-9-015 09-9-015 3 09-9-015 4 09-9-015 5 09-9-015 6 09-9-015 7 09-9-015 8 09-9-015 9 09-9-015 10 09-9-015 11 09-9-015 Chapter Page 11
ARENA Photographs 1 09-9-015 13 09-9-015 14 11-0-015 15 11-0-015 16 11-0-015 17 11-0-015 Chapter Page 1