NORMS AND REGULATIONS FOR AUTOMATIC DOORS & ENTRANCE CONTROLS

Similar documents
STANDARDS UPDATE NOTICE (SUN) ISSUED: March 19, 2018

UL Revision 5. - Commercial Door Installations -

Installer: (Name, address, telephone number)

Sliding Gates White Paper 1 Sliding Gate Safety Third Edition

dhf General Information Automated Gates Guidance for enforcement bodies

Installer: (Name, address, telephone)

Installer: (Name, address, telephone number)

Installer: (Name, address, telephone)

Installer: (Name, address, telephone)

Architectural Specification Sheet

Standards in Security Shutters & Fire Shutters (UK & USA)

Safety Standard for Automatic Residential Garage Door Operators. SUMMARY: The Consumer Product Safety Commission ( Commission or CPSC ) is

GUIDE TO INSTALLATION

Installer: (Name, address, telephone number)

Guide to gate safety legislation and standards

Engineering Specifications

Installer: (Name, address, telephone)

Solar Powered. Solar Powered. Model Installation/Owner s Manual. Solar Powered Vehicular Swing Gate Operator. UL 325 August 2018 Standard

Non-contacting guards

CHAPTER SIX Automatic Gates

Floor Protectors and Wall Shields. Solar Reflectance Roof Covering Materials

Risk assessment and analysis for swing gates

BLG77 Rising Fenced Barrier

FAQs - Codes and Listings

Guide to Gate Safety Legislation & the Machinery Directive

DETEX ARCHITECTURAL SPECIFICATIONS, June 2012 AO19 SERIES HEAVY DUTY LOW-ENERGY ELECTRIC SWING DOOR OPERATOR

Guide to Gate Safety Legislation & the Machinery Directive. In Association with:

Electromagnetic Locking Devices Performance Requirements

Access Control. Total Perimeter Protection Solutions from one Source

Report to Adhoc Health Code change proposal regarding locking arrangements From John Woestman, BMHA

FIRE & LIFE SAFTEY STANDARD

Delayed Action Closer. Mechanical self-closing device that incorporates an adjustable delay prior to the initiation of closing.

ARCHITECTURAL SPECIFICATIONS

Security Considerations for Secure Workplaces

STANDARDS UPDATE NOTICE (SUN) ISSUED: April 26, 2018

ARTICLE II FALSE ALARMS

SENSOR SOLUTIONS FOR DOORS

SAFETY STANDARDS & SOLUTIONS MATERIAL HANDLING & INTRALOGISTICS

Networked Access Control Panel. Installation Guide

Instructions for Use

Specification for Portable Traffic Signal Control Equipment for use at Roadworks

RITTNER FRENCH ASSOCIATES Rittner French Associates / Rittner Products, Inc.

Instructions for Use

Custom options such as housing finishes and design, lid have their presence felt. A combination of sleek, sophisticated

LOCAL AMENDMENTS TO THE INTERNATIONAL FIRE CODE 2006 EDITION

Richardson Fire Department 136 N. Greenville Avenue, Richardson, TX Telephone: Fax:

A guide to the changes between BS 8418:2010 and BS 8418:2015

Fire Department Access and Water Supply

Contents EN :2006+A2:2016 (E)

BEHIND THE LINES. Guarding & Machine Safety. Ian Hansen RotoConsult ARM Annual Meeting ARM Annual Meeting

STANDARD FOR FIRE RATED ROLLING DOOR ASSEMBLIES

OptiStile 400. Non-Barrier Optical Turnstile

FM-17HD & FM-20HD FLOOR MACHINES

Guide Specification Model CTG Automatic Transfer Switch

INTERNATIONAL STANDARD

Installation and Operation Manual

Fire Alarm System Fundamentals

3. Additional driveways may be permitted where determined by the Planning Commission to adequately accommodate traffic or ensure public safety.

ELITE SERIES COMMERCIAL HIGH-TRAFFIC AC SLIDE GATE OPERATOR

OptiStile 220. Swinging Barrier Arm Optical Turnstile

VACAVILLE FIRE PROTECTION DISTRICT 420 Vine Street Vacaville, California (707)

Safety Tips for the Office

TX7130. Conventional Reflective Beam Detector Installation and Operation Manual. TANDA UK Technology Copyright 2015, All right reserved.

Understanding Recognized and Generally Accepted Good Engineering Practices (RAGAGEP) for the Ammonia Industry

Australian Standard. Safeguarding of machinery

CHAPTER 61G15-32 RESPONSIBILITY RULES OF PROFESSIONAL ENGINEERS CONCERNING THE DESIGN OF FIRE PROTECTION SYSTEMS

ISO Acceptance tests for Nd:YAG laser beam welding machines Machines with optical fibre delivery Laser assembly

Florida Building Code Chapter 9 Fire Protection Systems Advanced Course

Report on First Revisions with Statement June 2014 NFPA 101

Across-the-Line SERIES MP300 Combined Manual and Automatic

INFORMATIONAL PUBLICATION SECURITY VS. EXITING... Door Locking Hardware in Schools

FIRE SAFETY DURING CONSTRUCTION, ALTERATION AND DEMOLITION

Florida Building Code 2010

INVESTIGATION FINDINGS III IMPACT OF INADEQUATE VENTILATION AND DISCHARGE SYSTEMS

CM Series. Safety, Technology & Innovation. Description. Approvals. Operation. Applications. Certificate of Conformity

ICS Supersedes CLC/TS 62046:2005. English version

A. AMERICAN ARCHITECTURAL MANUFACTURERS ASSOCIATION (AAMA) 101: Appendix Dissimilar Materials.

SENSOR SOLUTIONS FOR DOORS

ARCHIVE GUARDING OF PAPER BALING PRESSES

Automatic swing door solutions. We make access in life smart and secure.

HIGH-RISE RETROFIT ORDINANCES - NO and NO

SECTION AUTOMATIC TRANSFER SWITCHES

ABLOY DOOR AUTOMATICS Easy access for all types of swing doors

ES 200. Sliding door operator

UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES

TECHNICAL SPECIFICATION

ABLOY DA460 SWING DOOR OPERATOR. Installation and commissioning manual

STANDARDS UPDATE NOTICE (SUN) ISSUED: February 16, 2018

SVENSK STANDARD SS-EN Portar Säkerhetsanordningar för maskindrivna portar Krav och provningsmetoder

EUROPUMP ATEX Guideline Part II

40 TAC Tex. Admin. Code tit. 40, What safety precautions must I follow when children in my care use a swimming pool?

GUARDED STATUS INFORMATION and REQUIREMENTS For OWNERS AND OPERATORS Of REFRIGERATION PLANTS

August 2013 Technical Requirements for Remote Controlled Temporary Traffic Management Signs for use on the Highways Agency Strategic Road Network

Chapter 100 FIRE PREVENTION

3.1 Introduction. 3.1 Introduction

Soft Start Series MP700 Solid State, Reduced Voltage

Instructions for Use

DTS SECURITY P.O.BOX 3399 Base plate-mounting EDENVALE instructions 1610 TELEPHONE

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL. FT-EPB Series. Single Motor

INTERNATIONAL STANDARD

Transcription:

Chapter 5 NORMS AND REGULATIONS FOR AUTOMATIC DOORS & ENTRANCE CONTROLS When writing specifications, considerations should be given to the following: he Door should not form the only entrance/exit to an area, e.g. a person should not be trapped in an area if there is a failure of the power supply to the door. Where this is unavoidable then a user must have access to a manual override facility to operate the door. Adequate space for safe positioning of the drive and its controls must be provided. In particular when the door is to be operated in a Hold to Run mode (User is within sight of the opening and holds the control to enable movement. If the control is released the movement stops), the control station must be sited so the user can see the moving door at all times. A suitable power supply with an isolating facility should be made available in the vicinity of the door. It is important to note that a 3phase power supply is normal for most industrial doors. Information related to special environmental conditions such as dust, temperature, humidity and any explosion risk should be included in the specification. USERS OF DOORS It is important that the user category is clearly defined at the specification stage, to enable the supplier to advise on and quote for the most suitable types of operation/automation and appropriate safety devices. Users are defined according to both UL 325 regulation as well as EN 13241-1 normative. NORMS CURRENTLY IN USE This overview is based on both the International standards UL 325 and EN 13241-1, industrial & garage doors and gates safety in use of power operated doors requirements. This standard sets out the safety goals. To ensure the safety of users, safety devices may need to be provided by the door manufacturer. In order to ensure that the full system will comply with the standard, the manufacturer will require information relevant to the guidelines on application, usage, duty and speed of operation. EN 13241-1 (FOR EUROPEAN MARKETS) UL 325 (FOR NORTH AMERICA MARKETS) Door & Entrance Controls Handbook 5-1

EN 13241-1 (FOR EUROPEAN MARKETS) Industrial, Commercial and Garage Doors and Gates - Product Standard SCOPE This European Standard specifies the performance requirements for doors, gates and barriers for installation in areas in the reach of people, for which the main uses are giving safe access for goods and vehicles accompanied by persons in industrial and commercial premises and in residential garages. These devices may be manually or power operated. Power operated doors may be supplied either as an original power operated door or by the retrospective addition of a drive unit to a previously manually operated door. THE STANDARD DOES NOT APPLY TO: CHAPTERS Horizontally moving doors less than 2,5 m wide and 6,25 m2 area, designed solely for pedestrian use Revolving doors of any size Lock gates and dock gates Doors on lifts Doors on vehicles Armoured doors in banks Doors for animals in zoos Theatre curtains Doors outside the reach of people (e.g. crane gantry fences) EN 12445 Safety in use of power operated doors Test methods EN 12453 Safety in use of power operated doors Requirements EN 12978 Safety Devices for power operated doors and gates Safety requirements for photoelectric sensors both for object/person and for edge detection EN 61496 Safety of machinery Photoelectric sensors Specific requirements for optical behaviour of photoelectric sensors Type D activation Door & Entrance Controls Handbook 5-2

EN 12445 Safety in use of power operated doors Test methods TEST PIECE A (Person or object detection) Size 70 x 30 x 20 cm Hard parallelepiped specimen The three sides (one in each dimension) shall be Reflective Dull black TEST PIECE B (Edge detection) - E.g. Mirror - painted raw wood - Fine grained stainless steel - White gloss paint Size 300 mm long and 50 mm in diameter Half of the surface is reflective The other half of the surface is dull black painted raw wood Two testpieces, one reflective and one of dull black raw wood, can be used TESTING OF VERTICAL SLIDING AND ANY TYPE OF HORIZONTALLY MOVING DOOR Detection active on one side (presence detection with A test piece) Door & Entrance Controls Handbook 5-3

Detection active on both sides (two coupled presence detection) For door leaf greater than 100 mm Testing two coupled presence detection devices Detection of edge sensor installed on the door leaf (presence detection with B test piece) Door & Entrance Controls Handbook 5-4

EN 12453 Safety in use of power operated doors Requirements MINIMUM LEVEL OF SAFEGUARDING The minimum level of safeguarding is derived from the combination of types of users and types of activation of the door. Types of Users Type 1 Type 2 Type 3 A limited group of persons are trained to operate the door and the door is out of public area. A limited group of persons are trained to operate the door and the door is located in a public area. Any person is free to operate the door and the door is in contact with the general public. Types of Activation Type A Type B Type C Type D Type E Hold-to-run pushbutton control Hold-to-run control with key switch or similar Limitation of force according to Annex A, either by force limitation or by safeguarding (edge detection, rubber profile) Detection of the presence of a person or obstacle standing on the floor at one side of the door (Photoelectric sensors) Detection of presence which is designed and installed in a way that in no circumstances can a person be touched by the moving door leaf. The following table underlines the two major safety requirements for photoelectrics Type C Activation and Type D Activation as described in EN 12978. Minimum levels of safeguarding at main edge Type of door activation Types of user Trained Users Trained users Untrained users (no public) (Public) (Type 3) Type 1 Type 2 Hold to run control A B Not possible Impulse activation C or E C or E C and D, or E In sight of the door Impulse activation C or E C and D, or E C and D, or E Out of sight of the door Automatic Control C and D, or E C and D, or E C and D, or E Door & Entrance Controls Handbook 5-5

SENSITIVE PROTECTIVE EQUIPMENT In normal operation PSPE (pressure sensitive protective equipment), ESPE (electro-sensitive protective equipment) and inherent (built into the drive) protective equipment shall be designed so that: When they are in working order, they respond by giving an appropriate output signal(s) # when part of a person is in the detection zone # or when a person applies the activating force at any point within the active area of the safety edge sensing element, # or when closing on a test piece positioned at any angle between 90 and 45 to the direction of the motion if the signal from the sensing unit is within a specified signal range for inherent systems The door controller must stop the door movement for as long as the safety edge is activated or the door is reversed The safety edge must be active at maximum 30 mm from each end of the profile if a single fault occurs in the components between the sensing unit and the door control or in the sensing unit which prevents the control signal from stopping the leaf movement: # either they maintain their protective function if according to category 3 or 4 of EN 954-1(includes self checking functions) # or they are monitored according to category 2 of EN 954-1, with the acceptable deviation that the check of the safety function can be done at the latest at one of the final end positions of the leaf. If a fault is detected, the door must stop or switch to hold-to-run control. Both sensitive protective equipments (PSPE and ESPE) meet the safety requirements for photoelectric sensors both for object/person detection and for edge detection as described in EN 12978 Door & Entrance Controls Handbook 5-6

EN 12978 Safety requirements for Photoelectic sensors both for object / person and for edge detection ELECTRO SENSITIVE PROTECTIVE EQUIPMENT (ESPE) Type D Activation - Object/Person detection (as mentioned in EN 12453) PRESSURE SENSITIVE PROTECTIVE EQUIPMENT (PSPE) Type C Activation Edge detection (as mentioned in EN 12453) * The control signal should activate the Output Signal Switch Device in order to test the sensor performance. This should be done at the latest at one of the final end position of the leaf. Door & Entrance Controls Handbook 5-7

EN 61496 Specific requirements for optical behaviour of Photoelectric sensors Type D activation EFFECTIVE APERTURE ANGLE (EAA) TEST METHOD MIRROR PROTECTIONS EXTERNAL REFLECTIONS Door & Entrance Controls Handbook 5-8

UL 325 (FOR NORTH AMERICAN MARKETS) Door, Drapery, Gate, Louver and Window Operators and Systems SCOPE UL325 is a manufacturer s standard that covers door and gate operators The standard defines minimum requirements for testing a product for safety, safety features and performance, and how the product should be manufactured. A product that contains features, characteristics, components, materials, or systems new or different from those covered by the requirements in this Standard, and that involves a risk of fire, electric shock, or injury to persons shall be evaluated using the appropriate additional component and end-product requirements to determine that the level of safety as originally anticipated by the intent of this Standard is maintained. A product whose features, characteristics, components, materials, or systems conflict with specific requirements or provisions of this Standard shall not be judged to comply with this Standard. Where appropriate, revision of requirements shall be proposed and adopted in conformance with the methods employed for development, revision, and implementation of this Standard, UL325 REQUIREMENTS COVER: Electric operators for doors, draperies, gates, louvers, windows and other opening and closing appliances rated 600 volts or less to be employed in ordinary locations in accordance with the National Electrical Code, NFPA 70. Complete doors, gates, and other such assemblies that include electric opening and closing appliances. Accessories, such as external entrapment protection devices, for use with appliances covered by this standard. Doors and door operators intended for exit use as defined in the Life Safety Code, NFPA 101 and codes such as the BOCA National Building Code, the Standard Building Code, and the Uniform Building Code, are additionally subject to design requirements specific to such use CHAPTERS TEST METHODS REQUIREMENTS USA & CANADA REQUIREMENTS FOR PRODUCT SPECIFICATIONS Door & Entrance Controls Handbook 5-9

TEST METHODS TEST PIECE A (person or object detection) Test piece size 6 x 12 inches The sides shall be painted white The surface may simulate surdaces mentioned below-e.g. Mirror o Fine grained stainless steel o White gloss paint TEST PIECE B (Edge detection) Size 1 7/8 inch in diameter TESTING OF VERTICAL SLIDING AND ANY TYPE OF HORIZONTALLY MOVING DOOR When a photoelectric sensor senses an obstruction as described below that is to be placed on a level surface below the door or gate. The sensor is to be tested with the obstruction at a total of five different locations over the width of the door or gate opening. The locations shall include distances 1 inch from each end, 1 foot from each end, and the midpoint. Door & Entrance Controls Handbook 5-10

The Obstruction is to be centered under the door or gate perpendicular to the plane of the door or gate when in the closed position. An edge sensor shall actuate upon the application of a 15 pound force or less in the direction of the application. For an edge sensor intended to be used on a sectional door, the force is to be applied by the longitudinal edge of a 1-7/8 inch diameter cylinder placed across the sensor so that the axis is perpendicular to the plane of the door. For an edge sensor intended to be used on a one piece door, the force is to be applied so that the axis is at an angle 30 degrees from the direction perpendicular to the plane of the door. The test is to be repeated at various representative points of the edge sensor across the width of the door. Exception: The edge sensor need not be sensitive to actuation 2 inches or less from each end of the intended width of the door opening. Door & Entrance Controls Handbook 5-11

REQUIREMENTS ENTRAPMENT PROTECTION The level of entrapment protection is derived from the combination of types of location and types of Safety Devices. Types of Location Class 1 Class 2 Class 3 Class 4 Residential Commericial or General Public Access Industrial or Limited Access Restricted Access Types of Safety Devices Type A Inherent in Operator Provided in design of the Gate Operator ( 40A, 30A.1.2) Type B-1 Non-contact Photoelectric Sensors or equivalent ( 40A, 30A.1.4) Type B-2 Contact Edge device or equivalent ( 40B, 30A.1.9) also read. 34 Edge sensor Type C Swing Inherent Inherent adjustable clutch (mechanical) ( 40B, 30A.1.12) or pressure relief device (for hydraulics) Type D Constant Contact Manual activation of device which ( 40C, 30A.1.14) stop the unit when button released Type E Audio Alarm Bells, horns, sirens or buzzers at 100dB ( 40C, 30A.1. 16) also read 34A Audio Alarms The following table underlines the major Entrapment protections Types Minimum levels of safeguarding at main edge Protection against entrapment Gate operator category Vehicular Horizontal Slide, Vertical Lift Swing Gate, Vertical Pivot Vertical Barrier (arm) Usage Class Primary Type Secondary Type Primary Type Secondary Type Class 1&2 A B1,B2 or D A or C A, B1, C or D Class 3 A, B1 or B2 A,B1,B2,D or E A, B1 or C A,B1,C,D or E Class 4 A,B1,B2,or D A,B1,B2,D or E A, B1,C or D A,B1,C,D or E Door & Entrance Controls Handbook 5-12

A gate operator utilizing entrapment protection designated Type B1 (refer to the previous Table) by having provision for connection of, or providing with the operator, a non-contact sensor (photoelectric sensor or equivalent) shall, when the sensor is actuated: a) Stop or reverse the gate within a maximum of 2 seconds of sensing an obstruction in both the opening and closing directions, b) Stop the gate upon sensing a second sequential obstruction in the opposite direction while in the process of reversal as described in (a), c) Result in a gate at rest remaining at rest unless a Type D device is actuated, and d) Return to normal operation when the sensor is no longer actuated A gate operator utilizing entrapment protection designated Type B2 (refer to the previous table) by having provision for connection of, or providing with the operator, a contact sensor (edge sensor or equivalent) shall, when the sensor is actuated: a) Stop and initiate the reversal of the gate within a maximum of 2 seconds of sensing an obstruction in any direction. The gate operator shall reverse the gate a minimum of 2 inches (50.8 mm), b) Stop the gate upon sensing a second sequential obstruction in the opposite direction, while in the process of reversal as described in (a), c) Result in a gate at rest remaining at rest, unless a Type D device is actuated, and d) After the sensor is actuated no more than 2 times during a single closing cycle, or once in a single opening cycle, require a renewed intended input (via wired or wireless control or integral control, a loop sensor, a card reader, or a similar device) prior to enabling any automatic activation devices such as a timer or any other maintained input that was present when the reversing function occurred. A gate operator installed in accordance with the manufacturer s instructions utilizing entrapment protection designated Types B1 and B2 (refer to the previous table) as the primary device by having provision for connection of such device, or providing such device with the operator, shall monitor for the presence and correct operation of the device, including the wiring to it, at least once during each open and close cycle. The operator shall function as required in the event the device is not present or a fault condition occurs which precludes the sensing of an obstruction. A fault condition includes an open or short circuit in the wiring that connects the external entrapment protection device to the operator and the device s supply source. Door & Entrance Controls Handbook 5-13

USA & CANADA PRODUCT SPECIFICATIONS There are specific requirements according to both US and Canadian Markets for the Product Certifications. USA: FDDR2.E234263 Door, Drapery, Gate, Louver and Window Operators and Systems - Component CANADA: FDDR8.E234263 Door, drapery, Gate, Louver And window Operators And Systems Certified For Canada E 234263 is file number of Carlo Gavazzi Industri Door & Entrance Controls Handbook 5-14