Dehumidification System Enhancements

Similar documents
Available online at Energy Procedia 6 (2011) MEDGREEN 2011-LB

Adding More Fan Power Can Be a Good Thing

ASHRAE Standard 90.1 Energy Requirements Wrap-Around Heat Pipes

Air Conditioning Clinic

SIMULATION ANALYSIS OF BUILDING HUMIDITY CONTROL AND ENERGY CONSUMPTION FOR DIFFERENT SYSTEM CONFIGURATIONS USA

Trane CDQ Desiccant Dehumidification

Dedicated Outdoor Air Systems: AHRI 920, ISMRE & ASHRAE 90.1

100% Outdoor Air Dehumidification Methods

Energy-Efficient Makeup Air Units BY HUGH CROWTHER, P.ENG., MEMBER ASHRAE

PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM ENERGY EFFICIENT DEHUMIDIFICATION

Humidity Control & Psychrometrics

Two essential attributes of mechanical systems intended to

Field Test of Combined Desiccant-Evaporator Cycle Providing Lower Dew Points and Enhanced Dehumidification

Principles of Active Desiccant Operation. Presented by Tom Peterson, CEO and Founder. Climate by Design International

Desiccant Cooling with Solar Energy

Humidity Control Design Tips. R. Mark Nunnelly, PE, CxA, LEED AP President

Munters Heat Exchangers

Dehumidification at Part Load

Design Considerations For Dedicated OA Systems BY HUGH CROWTHER, P.ENG, MEMBER ASHRAE; YI TENG MA, ASSOCIATE MEMBER ASHRAE

For an ideal gas mixture, Dalton s law states that the sum of the partial pressures of the individual components is equal to the total pressure.

Design of Divided Condensers for Desiccant Wheel-Assisted Separate Sensible and Latent Cooling AC Systems

ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery. Steven T. Taylor, PE Principal Taylor Engineering

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

Designing Energy Efficient Outdoor Air Systems

AHRI 920 Performance Rating and Comparisons of DX-DOAS Unit Efficiency

Dehumidification for Industrial Coating Applications. By: Jay Kranker Munters MCS

Case Study of an Innovative HVAC System with Integral Dehumidifier. Florida Solar Energy Center Cocoa, Florida

Article Energy Saving Benefits of Adiabatic Humidification in the Air Conditioning Systems of Semiconductor Cleanrooms

Dehumidification: Energy Efficiency Comparisons

Feasibility of Controlling Heat and Enthalpy Wheel Effectiveness to Achieve Optimal Closed DOAS Operation

Achieving Dry Outside Air in an Energy-Efficient Manner

PhEn-602 Pharmaceutical Facility Design. Notes #7 J. Manfredi

S.A. Klein and G.F. Nellis Cambridge University Press, 2011

Efficient energy recovery in AHU. DOHA, Qatar Timo Schreck Enventus AB, Sweden

MSP WRAP-AROUND MULTIPLE SMALL PLATE DEHUMIDIFICATION TECHNOLOGY VS. CONVENTIONAL DEHUMIDIFICATION IN DEDICATED OUTDOOR AIR SYSTEMS (DOAS)

DEHUMIDIFICATION: Ice Arena Application & Product Guide. Design, construct and operate to control indoor humidity in ice rinks

Desiccant Dehumidification in Air Conditioning for a Large Commercial Building

Controlling Wrap-Around Heat Pipes for Systems with Strict Space Humidity Requirements. By Michael O. Davis, PE, August 2015

product application data PERFECT HUMIDITY DEHUMIDIFICATION SYSTEM

Standards and Guidelines. Presented by: Aric Murray December 12, 2014

COMPARING AIR COOLER RATINGS PART 1: Not All Rating Methods are Created Equal

The Basics - B Practical Psychrometrics. Jerry Cohen President Jacco & Assoc.

Relative Humidity in Schools Jim Cummings and Chuck Withers

By MIKE WEST, PHD, PE Advantek Consulting Inc. Melbourne, Fla.

To Keep Docs Cool, Dry and Happy

Section 4 of 6 DOAS Core Technologies

ME 410 MECHANICAL ENGINEERING SYSTEMS LABORATORY MASS & ENERGY BALANCES IN PSYCHROMETRIC PROCESSES EXPERIMENT 3

Heat pump and energy recovery systems

CHAPTER 4. HVAC DELIVERY SYSTEMS

PERFORMANCE OF SOLID DESICCANT COOLING WITH SOLAR ENERGY IN HOT AND HUMID CLIMATE

Evaluation of Mechanical Dehumidification Concepts (Part 2)

System Modeling of Gas Engine Driven Heat Pump

Redesign of Bennett Hall HVAC System

Daikin Blueprint: Delivering Hot Water with a Chiller

Do All DOAS Configurations Provide the Same Benefits?

Active desiccant integration with packaged rooftop HVAC equipment

Benefits Offered by Passive Dehumidification Wheel Speed Control

terminal units only provide sensible cooling, a separate dehumidification system is usually needed.

Air Conditioning for and-humid Climates:

Comparison Simulation between Ventilation and Recirculation of Solar Desiccant Cooling System by TRNSYS in Hot and Humid Area

Impact of Multi-Stage Liquid Desiccant Dehumidification in a Desiccant and Evaporative Cooling-Assisted Air Conditioning System

THE PSYCHROMETRIC CALCULATOR By: Stanley F. Gallos, The Bastian-Blessing Company INTRODUCTION PROPERTIES OF THE RSES CALCULATOR

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

ANALYSIS OF DESICCANT COOLING SYSTEM

Summary of Comments (Washington Revisions November 7, 2000) Update November 27, 2000

Dehumidifying with Dedicated Outdoor Air

Pharmaceutical Facility Design

TDSHS Air Change Requirements and the Basics of Psychrometrics. Presented by: Aric Murray December 06, 2013

Dynamic performance of a novel dew point air conditioning for the UK buildings

SIMULATION ANALYSIS ON THE FRESH AIR HANDLING UNIT WITH LIQUID DESICCANT TOTAL HEAT RECOVERY

Comfort and health-indoor air quality

Recent Advances in Energy, Environment and Economic Development

A/C Cooling Load calculation and measurement

White Paper Dehumidification in Humid Climates - A Theoretical Case Study

ME Mechanical Engineering Systems Laboratory. Experiment 3 - Mass and Energy Balances in Psychrometric Processes

ASHRAE S DOAS WEBCAST: A DEEPER EXAMINATION OF THE ROLE OF HEAT PIPES

Low GWP Refrigerants for Air Conditioning Applications

White Paper. Executive Summary. Overview of Membrane Exchangers CLCH-PRB063A-EN. June 2017

Air Conditioning Clinic. Psychrometry One of the Fundamental Series TRG-TRC001-EN

Don t Turn Active Beams Into Expensive Diffusers

Dehumidification in HVAC Systems

BOOK 1 OVERVIEW RD2XIN INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

Psychrometrics: The Science of Moisture in Air. Presented by Tom Peterson, CEO and Founder. Climate by Design International

Oxyvap Evaporative Cooling Applications

BOOK 1 OVERVIEW RD2XRT INSTALLATION AND OPERATION MANUAL. Table of Contents ABOUT BOOK 1:

Cold Storage Warehouse Dock Parametric Study

HVAC Psychrometric Analysis to Avoid Moisture Problems

HVAC Myths and Realities Trane Engineers Newsletter Live Series

Feasibility study on an energy-saving desiccant wheel system with CO 2 heat pump

Chapter 14, Problem 27.

Review on Waste Heat Recovery Techniques in Air Conditioning Application

Chapter 14 GAS VAPOR MIXTURES AND AIR-CONDITIONING

Energy Consumption Reduction of AHU using Heat Pipe as Dehumidifier

Fundamentals of Psychrometrics. By James L. Murphy, Colorado Building Environments Sales Engineer

HOW IT RELATES TO PERFORMANCE IN REFRIGERATED COMPRESSED AIR DRYERS

By Thomas H. Durkin, P.E., Member ASHRAE, and James B. (Burt) Rishel, P.E., Fellow/Life Member ASHRAE

Small Commercial Business Energy Audits. Recognizing and addressing the special requirements of the small business market segment.

COMMERCIAL HVAC PACKAGED EQUIPMENT. Rooftop Units Level 1: Constant Volume

Optimisation of cooling coil performance during operation stage for improved humidity control

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

Transcription:

2006, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Journal, (Vol. 48, February 2006). For personal use only. Additional distribution in either paper or digital form is not permitted without ASHRAE s permission. Dehumidification System Enhancements By Douglas Kosar, Member ASHRAE A recent report1 has documented the emergence of diverse air-conditioning products with enhanced dehumidifi cation features. The leading issue 2 being addressed with these new cooling systems is the large dehumidifi cation requirement presented by moisture-laden outside air that is mechanically introduced into buildings to meet the increased ventilation rates of ANSI/ASHRAE Standard 62-1989, Ventilation for Acceptable Indoor Air Quality, and its revisions over the last 15 years. The availability of humidity design weather data 3 in the ASHRAE Handbook Fundamentals since 1997 and the ready quantification of outside air dehumidification loads by others 4 has also made it much more straightforward to determine a building s HVAC moisture removal design needs, especially those originating from outside airstreams. However, we are faced with an array of system offerings to apply to our buildings and their dehumidification needs. In this article a conventional DX system along with three other all-electric enhanced dehumidification DX system packages are compared to provide insight into their respective performance capabilities. This insight can be applied by others to better match enhanced dehumidification equipment to appropriate application profiles in different climates and buildings. Conventional DX System Options The simple schematics in Figure 1 lay out a conventional constant vol- About the Author Douglas Kosar is the principal research engineer for the Building Sciences Area at the Energy Resources Center at the University of Illinois at Chicago and the chair of ASHRAE Technical Committee 8.12, Desiccant Dehumidification Equipment and Components. 4 8 A S H R A E J o u r n a l a s h r a e. o r g Fe b r u a r y 2 0 0 6

ume DX cooling system and the following three alternative configurations, all of them based on augmenting the DX cooling coil with the following enhanced dehumidification components: Wraparound heat pipe heat exchanger (HX-DX); Wraparound rotary desiccant dehumidifier (DD-DX); and Rotary desiccant dehumidifier downstream of the cooling coil (DX & DD). The heat pipe heat exchanger DX (HX-DX) cooling system has been available for many years while the latter two systems, as described here, are relatively new. In this first system, the heat pipe literally wraps itself around a DX cooling coil to precool incoming air via heat exchange with cooler exiting air off the coil. This process lowers the dew-point temperature of the air leaving the cooling coil and shifts some coil capacity from sensible to latent effect. In the wraparound rotary desiccant dehumidifier configuration (DD-DX), the rotor uses ducting to wrap itself around the DX cooling coil. It also takes the heat pipe concept one step further by using the moisture cycling desiccant material to also premoisten the incoming air to the coil by transferring water vapor from the nearly saturated cool air exiting the coil. The warmer entering airstream to the rotor before the coil actually performs the function of the dehumidifier regeneration airstream to drive off the moisture collected by the desiccant from the air exiting the coil and deliver a cooler, wetter airstream to the face of the DX cooling coil. This system also is known as the Cromer Cycle. 5 Finally, the rotary desiccant dehumidifier can be placed downstream of the DX cooling coil (DX & DD). Here the rotor is regenerated using a separate condenser waste heat airstream that is then exhausted to the outdoors. In these latter two systems, the unique advantage of the desiccant dehumidifier, especially in the DX & DD system is that its sorption process can produce dew points well into the 32 F (0 C) range and lower possibly, without the freezing coils associated with the conventional condensation process for dehumidification at those dew points. A desiccant dehumidifier basically converts the moisture, or latent load, into sensible heat of the same magnitude. Dehumidification Component and System Models Table 1 lists the specifications 6 for the DX cooling coil system and the enhanced dehumidification components. The critical factor increasing the energy consumption of the enhanced dehumidification systems is the pressure drop of the added component and the resulting additional fan power requirements. All the additional fan energy requirements were calculated assuming a combined fan/motor efficiency of 70%. The small fractional horsepower drive motors for the slow rotating desiccant dehumidifiers are ignored. The DX coil and the heat pipe heat exchanger component models are direct adaptations from the EnergyPlus simulation program. 7 The DX coil is based on the EnergyPlus DX cooling coil model, which uses the rated capacity, SHR, and EER (COP) obtained under ARI Standard 210/240-2005, Unitary Air-Conditioning and Air-Source Heat Pump Equipment, along with curve-fitted performance data for calculations of capacity and COP at off-ari operating conditions. This model is intended for operation between 250 and 500 cfm/ton (to 33.6 to 67.2 L/s. kw) but has demonstrated reasonable performance representations down to 150 cfm/ton (20.2 L/s. kw). Sensible and latent capacity splits are determined using the ARI-rated SHR and the coil dew-point/bypass factor approach. This approach is analogous to the NTU-effectiveness calculations in the EnergyPlus air-to-air generic heat exchanger model that is used to model the heat pipe. These heat exchanger calculations are used in conjunction with ARI Standard 1060-2005, Performance Rating of Air-To-Air Heat Exchangers for Energy Recovery Ventilation Heat Equipment, effectiveness data generated at 100% and 75% of rated airflow to determine performance at airflows between 50% and 130% of the rated airflow. Coupling the EnergyPlus DX and HX models in an iterative spreadsheet allows calculation of their combined performance in the HX-DX system. Through discussions with manufacturers, it has been determined that both the wraparound and condenser waste heat regenerated desiccant dehumidifiers are new Brunauer Type 3 isotherm desiccant rotors, not yet modeled in public domain simulation programs, including EnergyPlus. In the longer term, a finite difference desiccant dehumidifier modeling program is being used to generate these two new performance datasets. These new desiccant dehumidifier models are being generated consistent with the EnergyPlus input/ output structure for ready incorporation into that simulation program at a later date. However, these new Type 3 desiccant dehumidifier models are not yet completed. While those public domain curve fits are under ongoing development by the author, a preliminary curve fit of performance data from a rotor manufacturer selection program 8 for a condenser waste heat (115 F [46 C]) regenerated Type 1 desiccant dehumidifier has been developed. It has been coupled with the EnergyPlus DX model and applied to a spreadsheet that allows calculation of their combined performance in the DX & DD system. Based on interactions with another manufacturer, 9 a DD model based on their actual empirical Type 3 rotor data was coupled with the EnergyPlus DX model in an iterative spreadsheet that allows calculation of their combined performance in the DD-DX system. Fe b r u a r y 2 0 0 6 A S H R A E J o u r n a l 4 9

Figure 1: System schematics and performance at ARI conditions. Component (in System) Description DX 10-ton Nominal System With Four-Row Coil At 3,500 cfm ARI EER = 10.5 SHR = 0.758 Three-Row Heat Pipe (with Various FPI) For 45% Effectiveness At Different cfm/ton With Face Area/fpm Matching DX Coil 4 in. Depth Type 3 Desiccant Dehumidification Rotor with 50/50 Process and Regeneration Face Area Split 4 in. Depth Type 1 Desiccant Dehumidification Rotor with 50/50 Face Area Split Process And Regeneration with 115 F Regeneration Temperature from Condenser Waste Heat Airstream HX (in HX - DX) DD (in DD - DX) DD (in DX & DD) Additional Pressure Drop (in. w.g.) For Face Velocity (fpm) at cfm/ton of 350 250 150 0.67 0.48 0.29 420 300 180 1.40 1.30 1.06 575 530 440 1.51 1.51 1.51 800 800 800 Table 1: Enhanced dehumidification component specifications. 50 ASHRAE Journal ashrae.org February 2006

Dehumidification System Performance Metrics The following commonly used performance metrics from existing HVAC industry rating standards were used to compare the enhanced dehumidification systems: 10 Coeff icient of perfor mance (COP) defines a system's overall efficiency non-dimensionally as total cooling capacity over total energy input; Sensible heat ratio (SHR) defines the fraction of a system s total cooling capacity that is sensible, and, in turn, latent (1-SHR); and Apparatus dew-point (ADP) temperature defines a system's delivered humidity level, which will determine if a system can meet the latent load without increasing airflow more than that required to meet the sensible load. In this article we will make a further distinction by defining the CDP as Coil DP or the dew point temperature leaving the DX cooling coil, and the SDP as the System DP or the dew point leaving the entire system including any enhanced dehumidification component. All three enhanced dehumidification systems rely on the conventional DX cooling coil for the cooling effect, or the actual enthalpy reduction in the system process, while using the additional components to shift some of that coil s capacity from sensible to latent effect and effectively lower its SHR. So the challenge becomes how to most efficiently shift that DX coil capacity from sensible to latent effect. Figure 3 illustrates that shifting process by defining an enhanced dehumidification performance region with a combination of SHR and COP. A conventional DX air conditioner using a COP (including evaporator fan) of 3.08 (EER of 10.5) and SHR of 0.758, which is well within typical ARI rating point performance ranges identified by others for large unitary equipment, 11 is plotted on that figure. The ARI rating is measured at a system inlet condition of 80 F (26.7 C) and 78.6 gr/lb (11.2 g/kg) with a 95 F (35 C) ambient condensing temperature. Note that since no ambient humidity ratio is defined at the ARI rating point, it is assumed to be 110 gr/lb (15.7 g/kg) for DX & DD system using ambient air for desiccant dehumidifier regeneration. The plot shows two lines emanating from that single point. The curved line represents a DX system using free condenser reheat to lower its SHR. Such equipment is offered by all major HVAC equipment manufacturers. As that line nears the vertical COP axis, the performance approaches that of a typical DX dehumidifier (SHR = 0) with a COP of around 0.8. That curve represents a minimum performance level that any enhanced dehumidification system offering must exceed. The dashed horizontal line represents an ideal scenario where the shift of sensible to latent capacity occurs without any loss in COP. No real system can achieve that level of performance by modifying the base DX coil system, which is represented by the single ARIrating data point. However, real systems that approach that level of performance over the lower range of SHRs will define a best practice approach for enhanced dehumidification equipment. The area in Figure 3 bounded by the COP axis, the horizontal ideal performance line, and the free reheat curve defines an enhanced dehumidification performance region. Enhanced Dehumidification System Performance Comparisons Performance at ARI Rating Conditions The four systems and their resulting performance COP, capacity, and CDP/SDP at ARI rating conditions are discussed in the following sections. COP. Against the backdrop of the enhanced dehumidification region, the four systems discussed and their COPs at ARI-rating conditions are plotted for three airflow rates (cfm/ton or L/s. kw levels) in Figure 4. The detailed state point conditions at the inlet and outlet of Advertisement formerly in this space. Fe b r u a r y 2 0 0 6 A S H R A E J o u r n a l 5 1

A DX and DX & DD System Process Paths at ARI Conditions Figure 3: Enhanced dehumidification performance region. B HX-DX System Process Paths at ARI Conditions Figure 4: ARI COP of enhanced dehumidification systems. C DD-DX System Process Paths at ARI Conditions Figure 2: Pyschrometric analysis of state points in Figure 1. each component in the system operating at 350 cfm/ton (47.0 L/s. kw) is delineated in the system schematics of Figure 1. The compilation of data points in Figure 4 infers a current best practice curve for enhanced dehumidification systems using different component augmentations to achieve lower SHRs vs. the DX cooling coil alone. As expected, lowering the airflow rate on the DX cooling coil system (DX) is a logical first step to lowering SHR with little loss in COP. Adding a wraparound heat pipe heat exchanger (HX-DX) or desiccant dehumidifier (DD-DX) provides comparable, additional SHR reductions by precon- 52 ASHRAE Journal ditioning air into the coil with similar COP losses due to the extra fan power requirements. The post DX coil integration of a desiccant dehumidifier using condenser waste regeneration (DX & DD) provides the greatest SHR reduction but with the largest COP penalty. Compared to the other three systems, the SHR trends with lowering airflow rates are reversed for this system in Figure 4. It is typical of a desiccant dehumidifier operation, that even though the leaving humidity level decreases as airflow rate decreases, the capacity (the product of humidity depression and total airflow) decreases. This decrease in dehumidification capacity is coupled with a decrease in the sensible heating from the dehumidifier as well. The resulting increase in sensible capacity and decrease in latent capacity raises overall SHR with lowering airflow rates. A little further psychrometric analysis of the state point conditions in Figure 1 helps explain these results further. When in the 45% effectiveness range, a heat pipe heat exchanger provides about a 12 F (6.7 C) closer dry-bulb temperature approach to the saturation curve from the ARI-rating conditions. On an equivalent enthalpy basis, that closer approach equates to about a 4 F (2.2 C) increase in dew-point depression at the coil. On that portion of the saturation curve that amounts to upwards of a 10 gr/lb (1.4 g/kg) greater depression in the moisture level leaving the coil. In discussions with the manufacturer currently applying wraparound desiccant dehumidifiers, those rotors are selected to cycle about 10 grains of moisture as well, providing about an equivalent depression in moisture level leaving that system. Whereas the heat pipe heat exchanger processes follow a con- ashrae.org February 2006

stant humidity ratio line, the desiccant dehumidifier processes follow essentially a constant enthalpy line. These two process paths for the HX-DX and DD-DX systems are contrasted on the abbreviated psychrometric charts in Figures 2b and 2c. Also in Figure 2a, you will see the two process paths for the DX and DX & DD systems plotted together on a single psychrometric chart. The addition of the desiccant dehumidifier downstream of the DX coil provides more than 15 gr/lb (2.1 g/kg) of additional depression in the moisture level leaving the coil. The commensurate temperature rise is somewhat greater than a constant enthalpy process due to the higher regeneration temperature source and heat carryover effects. This accounts for the additional decline in COP, especially at the higher airflow rates when the dehumidifier capacity is maximized. It should be reiterated here that presently a Brunauer Type 1 isotherm desiccant dehumidifier is being used in this DX & DD modeling. Use of a Type 3 isotherm desiccant dehumidifier resulting from ongoing finite difference modeling is expected to lessen that temperature rise somewhat due to lower heat of adsorption effects. Capacity. Figure 5 plots the capacities of the four systems at the ARI-rating conditions for the same three airflow rates. In general, capacities Figure 6: ARI dew-point temperatures. drop with airflow rates as cold coil based systems realize diminishing returns in total cooling effect with decreasing apparatus dew points. Psychrometrically, as the saturation curve becomes more shallow at lower dewpoint temperatures, less latent effect exists with each drop in dew-point temperature. The DX & DD system is less sensitive to this phenomena since its post coil desiccant dehumidifier with its separate regeneration airstream can drive additional moisture removal via an adsorption process independent of the DX cooling coil. Again the SHR trends are reversed for the post coil desiccant dehumidifier system (DX & DD) compared to the other systems, as explained in the COP section. Coil and System DP (CDP and SDP). It was noted earlier that desiccant dehumidifiers and their adsorption process, have the unique advantage of producing dew points well into the 32 F Figure 5: ARI capacity of enhanced dehumidification systems. (0 C) range and lower, without the freezing coils associated with the conventional condensation process for dehumidification at those dew points. Figure 6 illustrates this point by plotting both the dew-point temperature off the DX coil and that supplied by the entire system. For the DX and HX-DX, system the CDP and SDP are the same. With the addition of a wraparound desiccant dehumidifier to the DX coil in the DD-DX system, it can deliver air at SDP 4 F to 7 F (2.2 C to 3.9 C) lower than the CDP as a result of the adsorption process after the DX cooling coil. Likewise for the DX & DD system, air can be delivered at a SDP 7 F to 11 F (3.9 C to 6.1 C) lower than the CDP as a result of the adsorption process in the downstream desiccant dehumidifier. The concern about freezing cooling coils is exemplified by the values at the lowest airflow rate of 150 cfm/ton (20.2 L/s. kw). The DX coil in the DX, DD-DX, and DX & DD are all operating above a CDP of 40 F (4.4 C), while the DX coil in the HX-DX system is near freezing at 35 F (1.7 C). In fact, the other systems are still operating in a CDP range in which manufacturers may only offer custom DX systems. Generally, packaged DX systems operate at a 45 F (7.2 C) or higher CDP at typical design conditions. The HX-DX system would need to use tilt control or other means to reduce the effectiveness of the heat pipe and raise the DX CDP. This will raise the resulting SHR, but not affect the COP or overall capacity of the HX-DX system. When necessary in the DD-DX system, air can be preheated up to 15 F (8.3 C) with condenser waste heat to false load the system. This will raise the resulting SHR, and significantly lower the COP and overall capacity of the DD-DX system. The DX & DD system with its post coil desiccant dehumidifier typically would use conventional DX-only system controls to prevent a freezing coil. Performance at Other Conditions In addition to ARI conditions, 10 other system inlet conditions were evaluated for the four systems at the three airflow 5 4 A S H R A E J o u r n a l a s h r a e. o r g Fe b r u a r y 2 0 0 6

Figure 7: 100% OA design dry-bulb COP. rates. These 10 other system inlet conditions ranged from 100% outside air (OA) through mixed (50% and 15% OA) air (MA) to 100% return air (RA) at 75 F (23.9 C) and 50% RH. The OA conditions selected were typical of three design ambient conditions for a humid climate: 1. Design dry-bulb (DB) temperature of 94 F (34.4 C) and 110 gr/lb (15.7 g/kg); 2. Design dew point (DP) of 140 gr/lb (20.0 g/kg) and 83 F (28.3 C); and 3. Design latent part load (PL) condition 12 of 110 gr/lb (15.7 g/kg) and 75 F (23.9 C). The complete results are too extensive to report here. Although these results could be condensed in a tabular Figure 8: 100% OA design dry-bulb capacity. format, that presentation would lack the visual clarity and insight offered in a graphical format. Performance results for three additional system inlet conditions are presented in Figures 7 12. Given the similar psychrometrics, the 100% RA and 15% OA operations resulted in performance trends for the four systems that were similar to the ARI rating point operations and, therefore, will not be presented here. Instead, we ll focus on the 50% to 100% OA operations, specifically on the 100% OA conditions. As OA fractions increase to 100% at design DB conditions, the performance trends of the systems relative to one another are maintained for COP and capacity as seen in Figures 7 and 8. Advertisement formerly in this space. 5 6 A S H R A E J o u r n a l a s h r a e. o r g Fe b r u a r y 2 0 0 6

Figure 9: 100% OA design dew-point COP. Figure 10: 100% OA design dew-point capacity. Figure 11: 100% OA design PL COP. The performance of all the systems increases at the much higher system inlet dry-bulb temperature (and higher humidity ratio). The DX & DD system does display distinctive behavior here. Under these operating conditions, this system exhibits modest Figure 12: 100% OA design PL capacity. proportional reductions in latent and sensible capacity with lower airflow rates resulting in little variation in SHR. As OA fractions increase to 100% at design DP conditions, the performance trends of the systems do yield more Advertisement formerly in this space. Fe b r u a r y 2 0 0 6 A S H R A E J o u r n a l 5 7

Advertisement formerly in this space. differentiation in Figures 9 and 10. The HX-DX provides a lower SHR as a result of condensation on the heat pipe prior to the DX cooling coil. Under these operating conditions, each of the DX, HX-DX, and DD-DX systems separately form tight groupings of the different airflow rate data points for COP and capacity vs. SHR as a result of the dominant effect of the much larger moisture loading on these systems. However, the DX & DD system again displays a distinctive behavior here. Under these operating conditions, this system exhibits significantly greater reductions in latent versus sensible capacity with lower airflow rates resulting in large variations in SHR. The cause of this effect, as noted before, is that despite the fact that the DX & DD system achieves a lower DP at a lower airflow rate, the resulting overall moisture removal capacity drops by a greater proportion at a lower airflow rate. Performance results in Figures 11 and 12 for 100% OA at design latent part load conditions are similar in their trends to Figures 9 and 10. Conclusions Augmenting a conventional DX cooling coil with enhanced dehumidification components can substantially increase an integrated system s moisture removal capacity, resulting in a lower SHR that can better match higher latent loading applications. The enhanced dehumidification components evaluated were a wraparound heat pipe heat exchanger, a desiccant dehumidifier also in a wraparound configuration, and a post coil desiccant dehumidifier regenerated by condenser waste heat. These integrated systems provided the ability to reduce typical SHR levels for DX only systems at ARI-rating conditions of 0.75 to below 0.50 in certain enhanced dehumidification systems while limiting losses in COP and capacity. These three alternative systems define a best practices performance that can approach the high performance of an ideal cooling system that can shift its sensible capacity to latent capacity without an efficiency penalty. They far exceed the poor performance of the simple, but less efficient, condenser waste heat reheat approach. Acknowledgments The author thanks the National Center for Energy Management and Building Technologies and the U.S. Department of Energy for their financial support of this research, as well as the Trane Company, Munters Corporation, and the Florida Solar Energy Center for technical assistance during this research. References 1. National Center for Energy Management and Building Technologies. 2005. NCEMBT- 050430-5, Task 6: Integrating Advanced Humidity Control to Reduce Energy Use, Quarterly Report, January March. 2. Kosar D.R., et al. 1998. Dehumidification issues of Standard 62-1989. ASHRAE Journal 40(3):71 75. 3. Harriman, L.G., D. Plager, D.R. Kosar. 1997. Dehumidification and cooling loads from ventilation air. ASHRAE Journal 39(11):37 45. 4. Harriman, L.G., D.G. Colliver, K.Q. Hart. 1999. New weather data for energy calculations. ASHRAE Journal 41(3): 31 38. 5. Cromer, C.J. 1988. Cooling System. U.S. Patent Office, Patent Number 4,719761. 6. National Center for Energy Management and Building Technologies. 2005. NCEMBT- 051031-4, Task 6: Integrating Advanced Humidity Control to Reduce Energy Use, Quarterly Report, July September. 7. U.S. Department of Energy. 2005. EnergyPlus Engineering Reference The Reference to EnergyPlus Calculations. 8. ProCalc 2.14, Proflute AB, Sweden, www.proflute.se. 9. Personal communication, The Trane Company. 10. National Center for Energy Management and Building Technologies. 2005. NCEMBT- 050731-5, Task 6: Integrating Advanced Humidity Control to Reduce Energy Use, Quarterly Report, April June 2005. 11. Amrane K., G.C. Hourahan, G. Potts. 2003. Latent performance of unitary equipment. ASHRAE Journal 45(1):28 31. 12. Harriman, L.G., J. Judge. 2002. Dehumidification equipment advances. ASHRAE Journal 44(8):22 27. 5 8 A S H R A E J o u r n a l Fe b r u a r y 2 0 0 6