SECTION ROTARY SCREW WATER CHILLERS. B. Removal of Existing Refrigerant in Existing Chiller:

Similar documents
SECTION ROTARY SCREW WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

SECTION CENTRIFUGAL WATER CHILLERS Vibration Isolation Pumping Equipment (HVAC) Induced Draft Cooling Tower

A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590, latest edition, and ARI certification program.

1.2 REFERENCES - comply with the following codes and standards:

SECTION CHILLERS

SECTION REFRIGERATION EQUIPMENT. A. Section Includes: Refrigeration equipment for insulated cold storage rooms including necessary accessories.

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

SECTION AIR COOLED WATER CHILLERS

SECTION ROTARY-SCREW WATER CHILLERS

.2 Section Waste Management and Disposal.

Call us today! (800)

Call us today! (800)

SECTION REFRIGERATION. 1. Reciprocating Compressors (Hermetic). 2. Reciprocating Compressors (Open Drive). 3. Water Cooled Condensing Units.

Call us today! (800)

SECTION PACKAGE AIR COOLED WATER CHILLER PART 1 GENERAL 1.01 SECTION INCLUDES. A. Chiller package. B. Charge of refrigerant and oil.

DTW Works Master Specification Version 2006 Issued 2006/08/01 Section15621 Packaged Reciprocating Water Chillers Page 1 of 5

Date: August 21, Proposal Number: G Engineer: Payment Terms: Net 30 Days

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION REFRIGERATION

60Hz. R134a HXWC SERIES. 205 to 560 Tons. Products That Perform...By People Who Care WATER-COOLED SEMI-HERMETIC SCREW COMPRESSOR WATER CHILLERS

Exclusively published and distributed by Architectural Computer Services, Inc. (ARCOM) for the AIA

Liebert CSU3000 Chiller

Multi-Institutional Academic Health Science & Research Center Evansville, IN

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

SECTION CENTRIFUGAL WATER CHILLERS

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

SECTION WATER-SOURCE UNITARY HEAT PUMPS

60 TON AIR-COOLED CHILLER. Call us today! (800) PA-ACCTR-60 GENERAL DIMENSIONS ELECTRICAL DATA 60 TON AIR-COOLED CHILLER FEATURES

CONTENTS. B. System Design and Performance Requirements

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

SECTION SPLIT-SYSTEM AIR-CONDITIONERS

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION PACKAGED WATER CHILLERS

SECTION PACKAGED COMPRESSOR AND CONDENSER UNITS

A. Section includes Factory Packaged, Modular units, providing cooling and heating for air distribution systems.

30GN FLOTRONIC II AIR-COOLED CHILLERS

Product Data. Features/Benefits. 19XB Positive Pressure Storage System

Modified by MSU Physical Plant / Engineering and Architectural Services

30GT FLOTRONIC AIR-COOLED CHILLERS

SECTION AIR COILS

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS

SECTION AIR-COOLED SPLIT SYSTEM AIR CONDITIONING UNITS

Technical Development Program

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

MAC N-407 Air-Cooled Chiller

SECTION AIR COOLED WATER CHILLER

PITTSBURG STATE UNIVERSITY. HVAC and BUILDING AUTOMATION SYSTEM STANDARDS

SECTION HEATING BOILER FEEDWATER EQUIPMENT

SECTION AIR COOLED WATER CHILLERS (LESS THAN 150 TONS)

AIR HANDLING UNITS Vibration Isolation Air Filtration Equipment Ductwork.

MACH N-407 Heat Pump Air-Cooled Chiller

30GXN,R AIR-COOLED LIQUID CHILLERS WITH COMFORTLINK CONTROLS 50/60 Hz

BuildingName The Description of the Project P DOCUMENTS

DUNHAM-BUSH. Request for start-up and commissioning of Dunham-Bush chillers (Water Cooled or Air Cooled) and Condensing Units.

SECTION PLUMBING EQUIPMENT

Construction Standards Page

Product Chillers A P P L I C AT I O N S

A. Section includes split-system air-conditioning units consisting of separate evaporator-fan and compressor-condenser components.

Installation Operation Maintenance

SECTION AIR COILS

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: HVAC Standards

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

A. Product Data: Include rated capacities, operating characteristics, furnished specialties, and accessories.

Chiller Manufacturer should have been manufacturing chillers utilizing magnetic bearing, oil free technology for more than 10 years.

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-120HE-03 Air-Cooled Chiller

Update In Progress. Division 23 Heating, Ventilation, and Air Conditioning Page Section FLUID SYSTEMS EQUIPMENT PART 1 GENERAL

As a standard, heat exchangers are provided with flange water connections (BS Standard Table E). All evaporator are supplied fully insulated.

PACKAGED AIR COOLED Product Data Catalog

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS - CUSTOM

HORIZONTAL FIRE TUBE BOILERS Piping (HVAC) Pumping Equipment (HVAC).

NEW CHILLER SCHEDULE

SECTION AIR HANDLING UNIT

SECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings.

Precise Temperature Control; Compact Footprint

LABORATORY AIR COMPRESSORS AND VACUUM PUMPING SYSTEMS

TITAN SERIES Complete Central Chiller & Pump Tank Package 20 to 70 Tons 20 F to 70 F

WCOX B Water-Cooled Packaged Chillers with Helical Rotary Compressors

Design and Construction Standards SECTION PLUMBING EQUIPMENT

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

WATER-TUBE POOL HEATERS

AIR COOLED PACKAGED CHILLER

RECORD SUBMITTAL COVER SHEET

TECHNICAL. Series 18. Pump Packages

WATER-TUBE POOL HEATERS

APPLICATION MANUAL FOR SCU SERIES COMPRESSOR UNITS AND SWU SERIES WATER COOLED CONDENSING UNITS

INTRODUCTION. Special Applications of Package Air Conditioners. Instant Cooling Requirement in Wedding Ceremonies

SECTION PACKAGED HEAT TRANSFER SYSTEM

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

SECTION DOMESTIC WATER PRESSURE BOOSTING SYSTEMS (VFD) PART 1 - GENERAL 1.1 SUMMARY

Page 1 of Relevant Provincial Jurisdictional legislation.

SECTION FAN COIL UNITS

SECTION FIRE PUMP AND CONTROLS

DIVISION FINNED WATER-TUBE BOILERS

1.1 This section applies to air handling units for HVAC Systems.

PhiloWilke Partnership Addendum No. 2 A/E Project No April 2016

SECTION PLUMBING EQUIPMENT

Union County Vocational - Technical Schools Scotch Plains, New Jersey

SECTION AIR HANDLING UNITS WITH COILS. 1. Central Station Air Handling Units. 1. Section Basic Mechanical Requirements.

Transcription:

SECTION 15684 ROTARY SCREW WATER CHILLERS PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 15240 - Vibration Isolation. 2. 15540 - Pumping Equipment (HVAC). 3. 15711 - Induced Draft Cooling Tower. B. Removal of Existing Refrigerant in Existing Chiller: 1. Notify M-DCPS Project Manager and the appropriate M- DCPS Maintenance Satellite Supervisor at least 3 working days (72 hours) before starting the removal of the existing chiller, to allow refrigerant removal by M-DCPS Air-conditioning Department. 2. Refrigerant will remain the property of M-DCPS. 1.02 REFERENCES A. Air-conditioning and Refrigeration Institute (ARI) - Standard 550/590-98, latest edition, and ARI certification program. 1.03 SUBMITTALS A. Shop Drawings and product data in compliance with the chiller performance specifications. 1. Shop Drawings shall contain equipment performance, physical data, piping connections, needed valves, needed strainers, needed external wiring and controls required for a complete system. 2. Shop Drawings shall show chiller s computer operating performance rating to match M-DCPS specific project operating conditions and KW/TON requirements. The computer performance chart shall show compliance with ARI 550/590-98 Integrated Part Load Value/Non-standard Part Load Value (IPLV/NPLV) over the range of 100 percent load to 25 percent part load. 3. Ratings shall be based on the water temperatures and flow rates as scheduled. Project No. SPECIFICATION GUIDELINES 15684-1

4. Computer rating sheets shall be signed off by an authorized chiller manufacturer representative. 5. Centrifugal water chiller shall be ARI 550 certified and performance rated according to ARI Standard 550-92 and stated on the rating sheets. B. Provide 2 complete overhaul, service, installation, maintenance, and parts manuals for the chiller. Deliver 1 set to M-DCPS project manager for M-DCPS Document Control and one set to the appropriate M-DCPS Maintenance Satellite Supervisor and receive a letter back stating that manuals were received. Manuals shall be originals only. Photocopies are not allowed. C. Before starting work, submit a current, legible copy of the following required documentation from the Environmental Protection Agency (EPA): ****** ***** **** *** ** * ** *** **** ***** ****** NOTE TO SPECIFIER: The following is mandatory for refrigerant recovery or addition since August 1993. ****** ***** **** *** ** * ** *** **** ***** ****** 1. EPA Technician UNIVERSAL CERTIFICATE of COMPLETION according to 40 CFR Part 82, subpart F. 2. EPA Refrigerant Recycling 1 Recovery Equipment Affidavit. 1.04 QUALITY ASSURANCE A. Regulatory Requirements (EPA): 1. All air-conditioning technicians on job site shall have EPA certification: According to EPA Section 608, Clean Air Act Amendments of 1990, individuals who service, repair, or dispose of air-conditioning and refrigeration equipment, including in-house service personnel, installers, contractor employees, and anyone else who performs installation, maintenance, or repair of HVAC refrigeration equipment shall be EPA certified. 2. Contractor shall be licensed by Miami-Dade County or the State of Florida as a mechanical or airconditioning contractor. A copy of the qualifier s license shall be included as part of required documents. 3. Contractor shall supply copies of current Certificates Project No. SPECIFICATION GUIDELINES 15684-2

of Competency from Miami-Dade County for all airconditioning personnel on job site. 4. Refrigerant Recycling/Recovery Equipment: According to EPA Section 608, Clean Air Amendments of 1990, owners of refrigerant recycling or recovery equipment, including contractors and others responsible for HVAC equipment serving, shall submit EPA form OMB #2060-0256 signed by the owner/responsible company officer, and sent to the appropriate EPA office. Recovery equipment will be made available for inspection by M-DCPS Project Manager before use can take place. B. Certification: Chiller shall be ARI Certified. C. Water Chillers shall be manufactured in a facility registered by Underwriters Laboratories, Inc. (UL) to the International Organization for Standardization ISO 9000 Series Standards for quality. D. The entire water chiller assembly shall be leak tested to at least 375 psig with a tracer gas mixture. There shall be no leaks greater than 0.5 oz/year of refrigerant. E. The water chiller energy efficiency shall be at least 0.67kW/ton. 1.05 WARRANTY A. Chiller manufacture shall have available local service representative with a 50 mile radius of the job site on a permanent basis and provide 5 year parts, refrigerant, oil, and labor warranty from date of chiller start up. Date of shipment warranty shall not supersede the 1 year start up warranty. PART 2 PRODUCTS 2.01 MANUFACTURERS AND REFRIGERANTS A. Rotary Screw Water Chiller: 1. Carrier. 2. McQuay. 3. Dunnham-Bush. 4. York. 5. Trane. Project No. SPECIFICATION GUIDELINES 15684-3

B. Refrigerants 1. HCFC - 22. 2. HFC - 134A. 3. HFC - 407A. 4. HFC - 410A. 5. Other M-DCPS accepted HFC refrigerant. 2.02 MAINTENANCE A. Warranty Period Service and Maintenance: Manufacturer of Chiller shall perform the following: 1. Start up of chiller according to manufacturer s required procedures. 2. A 2 hour running performance test and log signed by the installing contractor and manufacturer s representative. 3. A running log of chiller performance four, eight, and eleven months after start up. 4. On the eleventh month, a refrigerant leak test, and oil and oil filter change, and a complete test of all testable controls for calibration and operation. 5. The manufacturer shall change oil filter free of charge immediately after any oil pressure drop that occurs during warranty period due to metal filings and other trash left in chiller during manufacturing. 6. Manufacturer shall be responsible for refrigerant loss during the 1 year warranty period, unless loss is caused by M-DCPS personnel. 7. During all log reading, any loss of performance because of condenser or evaporator tube fouling, strainer being plugged, tower performance, or pump performance shall be reported to M-DCPS Project Manager for correction. 2.03 WATER CHILLER A. Chiller manufacture shall protect all areas for chiller with insulation to insure that there is no condensate dripage on to floor with a 100 degree F, 95 percent relative humidity chiller room. 1. Areas to be protected are cooler, cooler tube sheets, compressor suction piping, compressor, and motor. All areas that could condensate shall be protected with insulation. Project No. SPECIFICATION GUIDELINES 15684-4

2. Insulation design shall allow for service access and removal of all covers for servicing. 3. Insulation shall be 3/4" or greater. 4. Insulation shall have a thermal conductivity K value of 0.28 BTY in./hr-ft 2 -degree F. 5. Insulation material shall comply with UL 94, classification 94HBF. 2.04 WATER CHILLER DESIGN AND INCLUDED ITEMS A. Furnish the cooler having a minimum capacity as shown on the Construction Document schedule. 1. Cooling water of 44.0 degrees F. when supplied with condenser water at 85.00 degrees F. at full load power, input shall not exceed the maximum KW/TON requirements as noted. 2. The KW/TON shall comply with FPL Commercial/Industrial Energy Conservation Program Standards. 3. The cooler shall be 1-pass selected for 0.0001 fouling factor and a maximum liquid pressure drop of 13.0 feet. 4. Waterside shall be designed for 150 psig working pressure. 5. The condenser shall be 2-pass selected for 0.00025 fouling factor and maximum liquid pressure drop of 22.0 feet. 6. Waterside shall be designed for 150 psig working pressure. 7. Power shall be supplied to the compressor motor at 480 volts/3 phase/60 cycle and controls at 115 volts/1 phase/60 cycle. B. Unit shall be completely factory packaged including evaporator, condenser, compressors, lubrication system, refrigerant metering system, microcomputer control center, factory mounted and wired started, and all interconnecting unit piping and wiring. 1. Unit shall be factory charged with oil. 2. Refrigerant shall be shipped inside the unit, fully charged. 3. Water chiller manufacture shall supply the water flow safety pressure differential controls for the cooler and condenser. 2.05 COMPRESSORS Project No. SPECIFICATION GUIDELINES 15684-5

A. The packaged chiller shall be furnished with a positive displacement rotary screw compressors as required of the oil injected type. B. Compressor shall include an integral oil separation system, oil sump, and oil filter. 1. The oil temperature shall be controlled during operation to maintain proper oil temperature throughout the lubrication system. 2. An electric oil heater shall be supplied to maintain oil temperature during shut down period. C. Compressor shall be equipped with a variable hydraulically operated slide valve and shall provide capacity modulation from 100 percent to 20 percent capacity. 1. The compressor motor may be a variable frequency drive. 2. If the compressor motor provided is an open type, additional water chiller room ventilation shall be provided to insure the room temperature does not exceed 104 degrees F. D. The package chiller shall be equipped with a flash economizer cycle and oil return system from the evaporator to each compressor. Chiller compressor shall have a positive means of oil equalization. E. Compressor bearings shall be Anti Friction Bearings Manufacturers Association (AFBMA) Class 5 or superior. 2.06 STANDARD CHILLER FITTINGS A. Standard fittings to be provided are: 1. Flash economizer. 2. Check valve on vapor injection line. 3. Cooler sight glasses for checking refrigerant charge. 4. Manual ball valve on condenser drain line for charge isolation. 5. Oil return jet pump (eductor). 6. Oil return filter drier. 7. Valves to isolate compressors for repair. 8. Compressor discharge line check valves. 9. Refrigerant metering system to evaporator. 2.07 COMPRESSOR MOTOR STARTERS Project No. SPECIFICATION GUIDELINES 15684-6

A. Motor starter shall be a reduced voltage wye-delta, solidstate, or a solid state variable frequency drive. 1. Starter shall be UL listed. 2. The starter can be water chiller mounted. 3. Provide a NEMA I enclosure for the starter. B. Electrical components provided shall be: 1. Contactors. 2. Circuit breakers. 3. Single point power connection. 4. 115 volt control transformer. 5. Current transformers for control panel. 6. Three-phase over/under voltage, phase loss/reversal/ imbalance protection. 7. Three-phase voltage meter. 8. Three-phase ammeter. 2.08 MICROPROCESSOR CONTROL PANEL A. The microprocessor control panel shall have a LED display and compressor manual reset button. The computer system is to do the following functions on screw compressor chillers: 1. Capacity control of compressor (manual or automatic). 2. Staging of compressors based on leaving chilled water temperature. 3. Compressor current limiting. 4. Ramp loading mode. 5. Compressor start delays. 6. Automatic under voltage relay. 7. Anti-recycle delay timer. 8. Low pressure safety with computer alarm. 9. High pressure safety with computer alarm. 10. Freeze pressure safety with computer alarm. 11. Solid state compressor motor overloads and temperature protection. 12. High oil temperature protection. 13. Chilled water reset and EMS control interlock. An analog input is to be available for the Board supplied chilled water reset based on a 4 to 20 MA signal. An interlock shall be provided for the Board supplied contacts to control starting and stopping the chiller. 14. A communication post shall be provided to communicate with a terminal or printer. The speed of the communications (BAUD-RATE) can be set from 300-1200. Project No. SPECIFICATION GUIDELINES 15684-7

2.09 COOLER A. Cooler shall be of the shell and tube, designed for 300 psig working pressure on the refrigerant side and be tested at 450 psig. 1. Fabricate shell from rolled carbon steel plate with fusion welded seams. 2. Use carbon steel tube sheets, drilled and reamed to accommodate the tubes. 3. Provide intermediate tube supports spaced no more than 4 feet apart. 4. The refrigerant side shall be designed, tested, and stamped according to American Society of Mechanical Engineers (ASME) Section VIII - Division 1 code for unfired pressure vessels. 5. Tubes shall be high efficiency, internally enhanced type. 6. Each tube shall be roller expanded into the tube sheets providing a leakproof seal, and be individually replaceable. 7. Water velocity through the tubes shall not exceed 12 fps. Liquid level sight glasses shall be located on the side of the shell to aid in determining proper refrigerant charge. 8. The evaporator shall have a refrigerant relief device to meet the requirements of the ASHRAE 15 Safety Code for Mechanical Refrigeration. B. Water boxes shall be removable to allow tube cleaning and replacement. 1. Stubout water connections having Victaulic grooves shall be provided. 2. Water boxes shall be designed for 150 psig design working pressure and be tested at 225 psig. 3. Vent and drain connections with plugs shall be provided on each water box. 2.010 CONDENSER A. Packaged chiller unit shall have 1 condenser common to each compressor. 1. Condenser shall be of the shell and tube type, designed for 300 psig working pressure on the refrigerant side Project No. SPECIFICATION GUIDELINES 15684-8

and be tested at 450 psig. 2. Shell shall be fabricated from rolled carbon steel plate with fusion welded seams. 3. Use carbon steel tube sheets, drilled and reamed to accommodate the tubes. 4. Provide intermediate tube supports spaced not more than 4 feet apart. 5. The refrigerant side shall be designed, tested, and stamped according to the ASME Boiler and Pressure Vessel Code, Section VIII - Division 1 code for unfired pressure vessels. 6. Tubes shall be high efficiency, internally enhanced type. 7. Each tube shall be rolled, providing a leak proof-seal and be individually replaceable. 8. Water velocity through the tubes shall not exceed 12 fps. 9. The condenser shall have a refrigerant relief device to meet the requirements of the ASHRAE 15 Safety Code for Mechanical Refrigeration. 10. Condenser Coils: a. Copper or Aluminum Plate Fins: Mechanically bonded to copper tubes. b. Protect fins against hail damage on coils for 20 tons or greater. c. Fin Coating: Heresite or Bronze Glow epoxy coating. B. Water boxes shall be removable to allow tube cleaning and replacement. 1. Provide stubout water connections having Victaulic grooves. 2. Water boxes shall be designed for 150 psig design working pressure and be tested at 225 psig. 3. Vent and drain connections with plugs shall be provided on each water box. PART 3 EXECUTION 3.01 INSTALLATION A. Unload and install the chiller. B. Provide vibration isolators as recommended by the chiller manufacturer. Project No. SPECIFICATION GUIDELINES 15684-9

3.02 FIELD QUALITY CONTROL A. Training: The water chiller manufacturer shall provide a factory trained representative to perform instructional training on the maintenance, operation, troubleshooting, and repair on the water chiller including the microprocessor control system. 1. Manufacturer shall provide manuals for start-up, operation, maintenance, and parts and microprocessor computer water chiller program CD for up to 10 technicians. After the classroom instructions are completed, the manuals shall remain with the technicians. 2. Training aids such as a slide presentation and simulator may be required. 3. Training duration shall be 8 hours on the job, "handson" training on the installed and operational chiller unit the second day. 4. Training days shall be consecutive. 5. Location of classroom type instruction shall be the delivery address of the chiller unit. 6. The cost of the manuals, program CD, training, and all cost of the training section shall be included in the cost of the water chiller. B. Use 2 venturi flow metering devices sized for the specified evaporator and condenser gpm. The accuracy of this venturi shall be +1 percent. 3.03 START-UP, MAINTENANCE, AND REPAIR A. The water chiller manufacturer shall provide a factorytrained technician: 1. To perform the start-up procedures as outlined in the start-up manual. 2. To troubleshoot and repair as outlined in the operation and maintenance manual. 3. To perform all the tasks of maintenance as specified and as outlined in the operation and maintenance manual. Project No. SPECIFICATION GUIDELINES 15684-10

END OF SECTION Project No. SPECIFICATION GUIDELINES 15684-11