UNIVERSITY OF ALASKA FAIRBANKS DIVISION 25- INTEGRATED AUTOMATION DESIGN STANDARDS SECTION INTEGRATED CONTROL OF FACILITY LAB FUME HOODS

Similar documents
AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

1.1 DESCRIPTION A. The purpose of this section is to specify Division 23 responsibilities in the commissioning (Cx) process.

High Plume Blowers Suggested Specification Section (Master Format 1996) Suggested Specification Section (Master Format 2004)

SECTION AIR DUCT ACCESSORIES

SECTION SEQUENCE OF OPERATION FOR HVAC CONTROLS PART 1 GENERAL

LABORATORY DESIGN HANDBOOK

15900 HVAC INSTRUMENTATION AND CONTROLS

SPECIFICATIONS - DETAILED PROVISIONS Section Magnetic Flowmeters C O N T E N T S

HVAC Controls Upgrades: Requirement Details ( )

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available.

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

Selected Laboratory Energy Efficiency Measures

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

HVAC Controls Upgrades: Requirement Details ( )

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

City of Duluth Festival Center 04/25

MD and Its Impact on Lab Facilities

INSTRUMENTATION AND CONTROL DEVICES FOR HVAC

Guide Spec Summary. Option List. Date: 05/21/2001. EarthWise VAV Terminal Units Full Spec. Prepared by: Phone Number: Prepared for:

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

SEQUENCE OF OPERATIONS

TESTING, ADJUSTING AND BALANCING

DTW Master Specification Section EMCS: Start Up, Verification and Commissioning

SECTION FUNCTIONAL PERFORMANCE TESTING (FPT) PROCEDURES - CONSTRUCTION MANAGER EDITION

A. American National Standards Institute (ANSI) : Establishes requirements applicable to certifying direct gas-fired heaters.

CONTENTS AUTOMATIC TRANSFER SWITCHES

Case Study: Furman University Charles H. Townes Center for Science. Michael K. Mantai, PE, CCP President System WorCx

Linear Floor Heaters

************************************************************************************************************************

A. American National Standards Institute (ANSI): Establishes requirements applicable to certifying direct gas-fired heaters.

RAMAPO COLLEGE OF NEW JERSEY CCA0803 PHASE II HOUSING REHABILITATION 2012

ADDENDUM No: 3 JOSEPHINE COUNTY BUILDING OPERATIONS DEPARTMENT. February 29, NO CHANGE: March 8, 2012 / NOT LATER THAN 2:00 PM

DIVISION 23 - HVAC HVAC

SECTION PLUMBING/HVAC FINAL TESTING, ADJUSTING AND BALANCING

Virginia Tech Standards for Building Automation System

UCDMC CAMPUS STANDARDS & MASTER SPECIFICATIONS DIVISION 23 HEATING, VENTILATING AND AIR CONDITIONING (HVAC)

CHEMICAL FUME HOOD PROGRAM

Integrated Automation Instrumentation & Terminal Devices

DIVISION 23 HEATING, VENTILATING AND AIR CONDITIONING (HVAC)

DIVISION 23 HEATING, VENTILATING AND AIR CONDITIONING (HVAC)

Building Automation System (BAS) Design Criteria

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC

SECTION INTEGRATED AUTOMATION COMMISSIONING

Lab Design shall comply with the UC Lab Safety Design Manual located at: LABORATORY FUME HOODS

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

PHYSICAL FACILITIES Consultant s Handbook Division 01 General Special Requirements for Laboratories. Page 1 of 6

UC DAVIS Campus Design Guide DIVISION 11 - EQUIPMENT

SECTION COMMERCIAL-KITCHEN HOODS

SECTION DIRECT GAS-FIRED INDUSTRIAL HEATING AND VENTILATING UNITS

Direct Fired Heater Model AD Specification

10+ HVAC Troubleshooting Tips for Healthcare Facilities Jerry Hirsch JCI Facility O&M Performance Development Manager.

SECTION AIR COILS

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC

THERMA FUSER SIDEWALL LINEAR VAV DIFFUSER

COMcheck Software Version Mechanical Compliance Certificate

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION AUTOMATIC TRANSFER SWITCHES

A. Section Instrumentation and Control Devices for HVAC. B. Section Building Automation Systems(BAS) for HVAC

UNIFIED FACILITIES GUIDE SPECIFICATIONS

DIVISION 23 HEATING, VENTILATING AND AIR CONDITIONING (HVAC)

TLW Therma-Fuser Linear Sidewall Thermally Powered VAV Diffuser

Civil Engineering Building

See Part II for additional information regarding Indoor Pollutant Reduction and Control, Energy Efficiency, etc.

Integrated Automation

COMcheck Software Version Mechanical Compliance Certificate

Union County Vocational - Technical Schools Scotch Plains, New Jersey

DACC Health Sciences Building Air Handler Assessment/Study

San Marcos Building Standards PART 1 - GENERAL 1.1 SUMMARY

NATIONAL INSTITUTES of HEALTH FUME HOOD TESTING PROTOCOL. For CONSTANT VOLUME FUME HOODS

************************************************************************************************************************

Copyright 2003 and 2005 by The American Institute of Architects (AIA) Modified by MSU Physical Plant / Engineering and Architectural Services

CONTENTS. B. System Design and Performance Requirements

SECTION DIGITAL, ADDRESSABLE FIRE-ALARM SYSTEM

A. General: Refer to paragraph entitled "SUBMITTAL" in Section Include the following data:

THE IMPACT OF FACILITY HVAC SYSTEMS ON BIOLOGICAL SAFETY CABINETS

Glossary of Terms Laboratory & Fume Exhaust Fans

Updated: September 12, 2018 DIVISION INTEGRATED AUTOMATION. INTEGRATED AUTOMATION Page 1 of INTEGRATED AUTOMATION

Fan Selection. and Energy Savings

UFGS (February 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION DUCTWORK

Fire Smoke Damper Actuator Replacements SECTION COMMISSIONING OF HVAC

1.03 RELATED SECTIONS: The following sections contain requirements that relate to this section.

control sequences model QST / EST Series Table 47: QST / EST Analog Electronic Control Strategies Fan Powered Air Terminals

Chilled Water DOAS Fan Powered Terminal Units

B. System Design and Performance Requirements

SECTION (15900) - INSTRUMENTATION AND CONTROL FOR HVAC

SECTION TESTING, ADJUSTING AND BALANCING

SECTION CLIENT-SERVER INFORMATION / DATABASE INTEGRATION

DWYER INSTRUMENTS, INC. P.O. BOX 373 MICHIGAN CITY, INDIANA 46360, U.S.A. Series 670 Hood Monitor. Bulletin AV-670

Louvers & Dampers April Product Guide Specification SECTION COMBINATION FIRE SMOKE DAMPERS

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

Fume Hood Safety TYPES OF FUME HOODS

SECTION TESTING, ADJUSTING, AND BALANCING FOR HVAC

Florida Department of Transportation

AIRFLOW MEASUREMENT AND CONTROL PRODUCT CATALOG. Phone: 877-4GNTROL ( ) - Internet: GreenTrol.com. r1f

BES-TECH TECHNOLOGY & SYSTEM INTEGRATION

Technical Assignment 3 11/15/04. Executive Summary

Electric Duct Heaters. IDHB & IDHC Series

Transcription:

PART 1 - GENERAL 1.01 General: A. Laboratory ventilation system will ensure the health and safety of laboratory occupants. B. Room pressurization control will utilize airflow tracking to vary the volume of supply air into a space and fume hood/general exhaust air out of the space to maintain both minimum ventilation and airflow balance. The Building Management System (BMS) will control temperature and humidity. C. Supply and exhaust airflows will be controlled by a stand alone control system that is interconnected to the BMS. D. Designer will provide complete fume hood control sequence of operations in 23 09 93. 1.02 Codes and standards: Refer to CODES AND STANDARDS in Design Standards Section IIe 1.03 Performance: A. Provide 100% field testing per ASHRAE 110 and meet 4.0AI0.05 containment of tracer gas. B. Average fumehood face velocity = 100 fpm +/- 10% at all times and specifically at 18 inch sash height. No point will be lower than 80 fpm or higher than 120 fpm. C. Response time: Meet or exceed ASHRAE 110. D. Flow rates within 10% of set point at all times. E. Electrical signaling response must transpire and stabilize within one second after completion of sash movement. Resultant sash opening airflow rate must stabilize within five seconds. 1.04 Room pressurization with fume hoods A. Use venturi valves or single blade dampers, high speed actuators and volumetric offset control to maintain room pressurization. B. Laboratory control system to continuously determine the supply airflow and the exhaust airflow. C. Laboratory ventilation system to maintain proper room pressurization polarity regardless of any change in room/system conditions such as the raising and lowering of any or all fume hood sashes or rapid changes in duct static pressure. 25 51 00-1

D. Fail air control valves to last position upon loss of control or power. 1.05 Room pressurization without fume hoods A. Single-blade dampers and non-high speed actuators may be used, in which case pressurization control will be by Siemens Building Technologies only. 1. Single-blade dampers will be specified under Division 23 2. Designer will consider flow feedback system in VAV areas to meet needs of user. 1.06 Air change rate: Designer to provide calculations indicating the design ACH for each lab. 1.07 Laboratory sound criteria to be established by designer. UAF Facilities Services suggests levels not exceed NC55. PART 2 - PRODUCTS 2.01 General: Basic fume hood control system will include devices such as fume hood sash sensor, fume hood monitor, air terminal devices, control panels and all associated low voltage wiring, pneumatic tubing and all necessary accessories to implement an integrated system as specified. A. Laboratory fume hood controls approved manufacturers: Phoenix Controls Corporation and Siemens Building Technologies. Alternate Brand Request or Substitution Request required. 1. Fully integrated, stand-alone controls system 2. Closed or open loop control. Averaging sensors, through the wall sensors or airflow crosses may not be used for airflow tracking. 3. Device sound levels and pressure losses comparable to listed manufacturers. 4. Manufacturer must provide evidence of at least five years experience in fully integrated laboratory fume hood control and instrumentation work and evidence of similar installations in last two years. 5. Manufacturer must have technical/service personnel within the State of Alaska. 6. Manufacturer must demonstrate periodic calibration and maintenance requirements of equipment B. All laboratory fume hood control equipment to be of a single manufacturer. 25 51 00-2

C. Manufacturer will include costs for any interconnectivity to UAF BMS that is beyond requirements stated in this section. 1. Manufacturer will provide all requirements for control air, control and power wiring. 2.02 Control/Alarming devices: Provide devices to accomplish the following functions: A. Maintain room pressurization by varying airflow in a linearized manner using volumetric tracking. B. Maintain constant fume hood face velocity as sash is raised and lowered. C. Modify room ACH to accommodate changes in conditions and heating/cooling needs. D. Provide fume hood user with face velocity readout, airflow alarm and emergency/purge function. E. Measure sash position and provide precise, instantaneous values to controller. 2.03 Air terminal devices: A. Provide linear flow performance characteristics with sufficient turndown to ensure that all airflows specified can be maintained. B. Use only venturi type air valves or approved single blade dampers, pressure independent over the specified differential static pressure operating range. Minimum 16 gauge. spun aluminum. Refer to Division 23 for further information. C. Minimum airflow control accuracy: +/- 5% of actual reading over the entire rated airflow range of each device. D. Factory calibrated in accordance with NIST to specific requirements of project. E. Components suitable for non-corrosive, corrosive or highly corrosive airstreams. 2.04 Submittals: O&M Manual will be reviewed at Submittal period and returned to manufacturer for update. Resubmit as Project O&M Manual. Conform to Division 01 requirements. O&M Manual to include: A. Valve Schedule B. Schematic diagram including depictions of all major equipment/devices. 1. Labels with device name, project device number and manufacturer part numbers. 2. Indicate mechanical and electrical interconnections to related equipment/devices. 25 51 00-3

3. List room locations. Typical installations may be depicted as long as associated room numbers are listed. 4. All drawing title blocks will include manufacturer location/contract information and project information including Project Name/Number. C. Wiring diagrams 1. Include major internal and external connections. D. Sequence of Operations: Reproduce from Contract Documents. E. Equipment Parts List and Products Data. F. Maintenance methods. 2.05 Interconnectivity: Interface with UAF campus Building Management System. A. Manufacturer will provide and install necessary devices and wiring terminating at UAF BMS panels provided by Siemens Building Technologies. BMS control panel locations will be indicated on construction drawings. SBT will terminate industry standard fume hood control system wiring in SBT panels. B. Minimum interface: (4) hardwired points: 1. Temperature override. 2. CFM output. 3. Emergency override alarm. 4. Low fume hood flow alarm. PART 3 - EXECUTION 3.01 Control panels: Mount controllers, relays, switches, etc. in enclosed control panels, in a readily accessible location and in close proximity to control devices. 3.02 Designers will indicate fume hood control system power supply provisions on contract documents. Coordinate power requirements with Siemens Building Technologies and Division 26. Require fume hood controls installer to be responsible for any needs other than those depicted. 3.03 Controls contractor shall be responsible for providing all power services required under this section. Installation shall conform with the Division 26 specifications. 25 51 00-4

3.04 Quality: A. Manufacturer s system to be 100 percent field tested and installed in accordance with ASHRAE 110. B. A qualified, independent testing company to perform fume hood tests on each hood to determine face velocity, airflow patterns and response times. 3.05 Warranty: A. The manufacturer to review the system for proper installation and warrant the system for parts and labor for one year after installation. The manufacturer to include one visit at the end of the warranty period to confirm that the system is operating as commissioned. B. Manufacturer to calibrate fume hood controls, pressure transmitters and air sensors at the end of the warranty period. A written report to be submitted detailing the results and any work that was done. Calibration per ASHRAE 111 or AMCA 210. END OF SECTION 25 51 00-5