Hydro-Pnuematic Tank Contoller. HTC200 and 300 Series. User Manual

Similar documents
Dryer Master Inc. Dryer Master AM 3. Product Manual

User s Manual. TIGER S EYE E-Series Mark V Jockey. TIGERFLOW Systems, Inc Mint Way Dallas, Texas

ModSync Sequencing System Installation & Operation Manual. For use with Fulton Steam Boilers.

Micro-VPAC IIT LSC - Lift Station Controller. User Manual. Version 1.0.2

Tri-Stack Smart System

Operation Manual. Programmable Logic Controller

MYRIAD TRIPLEX PUMP CONTROLLER INSTRUCTION MANUAL

No part of this publication may be reproduced, stored in an automated data file or made public in any form or by any means, whether electronic,

Intelligent Security & Fire Ltd

Tempered Water Logic Control OPERATION l TROUBLE SHOOTING

MYRIAD DPC DUPLEX PUMP CONTROLLER INSTRUCTION MANUAL VERSION 3.7

Rev Pulse Modulating and Anti- Sweat Control (PMAC II Solo) Installation and Operation Manual

Manual# User s Manual. 200E Series. DCU 210E/208E Diesel Engine Control Unit RP 210E Remote Panel

Oracle Communications Performance Intelligence Center

Pump-Up Controller MODEL 4062

Oakton TEMP 9500 Advanced Multiparameter Controller

Pump-Down Controller MODEL 4052

Avigilon Control Center System Integration Guide

Universal Monitoring System. Model IMEC8A. User Manual Version 1.10 Software version 2.3.1

Subcooling is defined as the point at which liquid is cooled below it s condensing temperature. Example: Refrigerant R404A

Alarm Manager Plug-in

CONsOlIDATOR 4 & 8. MulTI- C h ANNEl CONTROllERs. ConsoliDator 4 Model PD940 ConsoliDator 4 Features. ConsoliDator 8 Features.

Operation manual. Rooftop Packaged Unit

Series A3 and A4 Differential Pressure Controller

GASGUARDIAN Channel Controller OPERATING & INSTALLATION MANUAL

Installation and Operations Manual

AUTOMATION. Operator s Manual RST Series Web Enabled Input Module. Rev. A2, 1/12

Fire detection and alarm system Operating instructions

FLOW CONTROLLER TYPE S/601

ALARM SYSTEM USER S MANUAL Rev

DEIF A/S. Operator s Manual. Basic Gen-set Controller. Display readings. Push-button functions. Alarm handling. Log list C (UK)

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

DEIF A/S. Operator s Manual. Multi-line 2/version 2-GS E (UK) SW version 2.4X.X. Display readings. Push-button functions.

Xtralis VESDA LCD Programmer Quick Reference Guide

Installation and User Instructions

RPM1600 Series Room Pressure Monitors

CASS9000 Standalone FingerPrint Door Access System. User Manual

TWLC - Tempered Water Logic Controller. The Intelligent Control

HS-5100, HS-5200, HS-5400 ANALOGUE ADDRESSABLE CONTROL PANELS. User Manual. Approved Document UI-ELAN-02 Revision 03

Follett Performance Plus

ZERIO PLUS EDA-Z5008, Z5020 & Z5100

Accent User. Version. Rheem. PO Box 146, ABN:

Ice Rink (Single and Dual Configurations) Custom Control Features

Lift Station Level Controller

user manual Document No , Revision 03 November 2015

Isolated Thermocouple Module

Rosemount 4500 Hygienic Pressure Transmitter. Start

OT-FX2 OLED TOUCH for the FX II Touch control panel OPERATOR S MANUAL. Technicold Marine Systems

Browser Manual ProMinent ProMtrac Cooling Tower Water Treatment Controller

Manual# User s Manual. 200 Series. DCU 210/208 Diesel Engine Control Unit RP 210 Remote Panel

Operator's Manual Dielman Rock Island Industrial Dr. St. Louis, MO Tel:(314)

1025, BOUL. MARCEL-LAURIN INSTRUCTION MANUAL FOR WATER COOLED ENVIROCHILL CHILLER. Prepared par Claude Gadoury, P. Eng MTL TECHNOLOGIES INC.

Operator's Handbook. Release 3. Fire Alarm Control Panel, BS-310 / 320 / Operator Panel BS-330. System Program Version 3.8.0

GG-2 2-CHANNEL GAS DETECTION CONTROL PANEL. Installation and Operation Manual

Protégé Eclipse LED Keypad User Manual PRT-KLES

Owner s Manual. Model AC375C Refrigerant Recovery, Recycle, and Recharge Unit

AD-1272 Advanced Thermal Dispersion Probe Airflow Measuring System

CIRRUS PRO. User Manual and Responsibilities ASPIRATING FIRE DETECTOR

User manual and installation guide

Avigilon Control Center 5 System Integration Guide

Guardian II Pipeline Washer B Instruction Supplement

Manual Supplement. Model Number: 8680-N2. Communications Protocol. Contents of this manual supplement include:

Agri-Alert 800EZe. Alarm System. Alarm. System in Standby. Burglary Armed. Online (phone) Green = zone activated Amber = zone bypassed.

NT DUAL CHANNEL DISPLAY. User Guide

SECTION PACKAGED HEAT TRANSFER SYSTEM

OPERATING INSTRUCTIONS. G214 Software - Version 4

CSP-204 CSP-208 CSP-104 CSP-108

Control Panel User Guide (TO BE RETAINED BY THE USER)

Generator Control Unit, GCU 100 Push-buttons LEDs Display and menu structure Display readings Alarm handling and log list

Table of Contents 1. OVERVIEW SYSTEM LAYOUT SPECIFICATIONS FUNCTION... 11

Oakton TEMP 9000 Advanced Thermocouple Controller

MicroTech Series 200 Centrifugal Chiller

Advisor Advanced User Guide

PRESSURA ROOM PRESSURE MONITOR MODEL RPM10 AND RPM20

THX-DL Data Logger USER & INSTALLATION MANUAL V

Beacon 800 Gas Monitor Operator s Manual

STORM PRO Model # - C-4014, C Storm Pro- Instruction Manual V.2. This instruction manual serves as a guide for the Storm Pro.

Refrigeration and Air Conditioning Controls. User s manual. Degree Master Controller in AKC 55 Systems ADAP-KOOL REFRIGERATION AND AIR CONDITIONING

AGRI-ALERT 9600 ALARM SYSTEM USER MANUAL

Advisor Advanced Mobile Application User Manual

Feniex Hammer S Distributed By: Feniex Hammer Instruction Manual / feniex.com

Planning Guide EnviroAlert Monitoring Systems

Nitrogen Dioxide (NO2) Single-Point Gas Detection System

Manual# User s Manual. DCU 410/408 Engine Control Unit RP 410 Remote Panel FW 2.3

AGC 200 Advanced Gen-set Controller OPERATOR S MANUAL

RAM-3500-LCD. Remote Annunciator. Installation and Operation Manual

Instruction Manual Series 17CA3000 Chloralert TM Plus Multi-Gas Detector CAPITAL CONTROLS

PF1000 CONTROLLER. for the. Heateflex Corporation 405 E. Santa Clara St. Arcadia, CA TEL: (626) ; FAX: (626)

MacDonald Steel Limited

This manual explains the features and operations of the VFDC controller which is specifically designed for Pressure Booster Pump Systems.

CELLTROL II BIOREACTOR CONTROL SYSTEM OPERATIONS MANUAL

GLD-30 Gas Leak Detector

Owner s Manual. Model 8800 Universal Communicating Thermostat. Includes Operating Instructions and Warranty Information

User Guide. itec.

General The Dryer Programmer for Windows Computers

Manual Supplement. Product/System Title: Premium Clean Room Monitor. Contents of this manual supplement include:

BD Viper Lysing Heater Manual (for BD Viper System)

Manual. Model GF. Digital Glycol Feeder with MegaTron XS Controller. Installation Maintenance Repair Manual

Chore-Tronics Load Cell Indicator

Falcon-II Next Generation, Air Quality Monitor CO2 & Temperature

Transcription:

Hydro-Pnuematic Tank Contoller HTC200 and 300 Series User Manual

2 Preface This manual explains how to use the Healy-Ruff Hydro-pneumatic Tank Controllers. Copyright (C) 2012 ICS Healy-Ruff. All rights reserved. No part of this publication may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language or computer language, in any form by any means, electronic, mechanical, magnetic, optical, chemical, manual or otherwise, without prior agreement and written permission of ICS Healy-Ruff. Information in this document is subject to change without notice. Trademarks Ethernet is a trademark of Xerox Corporation Micro SD is a registered trademark of SanDisk Corporation icontrol is a registered trademark of Instrument Control Systems, Inc. For user manual updates, contact ICS Healy-Ruff: North Amaerica: Tel: (763) 559-0568 Fax: (763) 559-2187 Web: www.icshealyruff.com Email: sales@icshealyruff.com

LIMITED WARRANTY AND LIMITATION OF LIABILITY 3 ICS Healy-Ruff warrants to the original purchaser that the Micro-VPAC IIT LSC is free from defects in material and workmanship under normal use and service. The obligation of ICS Healy-Ruff under this warranty shall be limited to the repair or exchange of any part or parts which may prove defective under normal use and service within two (2) years from the date of purchase or eighteen (18) months from the date of installation whichever occurs first, such defect to be disclosed to the satisfaction of ICSHealy-Ruff after examination by ICS Healy-Ruff of the allegedly defective part or parts.

4

5 Contents 1. Description of Operation...7 2. How to use the Menus and set Variables in the Micro V-PAC II...7 2.1. Changing Variables... 7 3. Main Screens and Pump Status...8 3.1. Pressure Screens... 8 4. Main Menu Screen...8 4.1. Setpoint Screens... 8 4.2. Alarms... 10 4.3. Setup Screens... 10 4.4. Security... 11 5. Example of how to change the SYSTEM PRESSURE variable...11 6. Useful Data and Formulas...13 7. Installation Diagram...14 8. Panel and Chassis Layout...15

6

7 1. Description of Operation The HTC is a two (2) or three (3) pump hydro-pneumatic tank control with an integral or remote mount float column. A hydro-pneumatic tank is a vessel in which water is maintained within a desired pressure range above atmospheric. The tank is partially filled with water and the remainder of the volume is compressed air. With the water level and the air pressure in the tank at their desired maximum values and the pump(s) and air compressor(s) disabled: as water is withdrawn to supply the demand, the air expands which causes its pressure to be reduced. After withdrawal of a predetermined quantity of water, the pump(s) are started (based on tank pressure) and caused to deliver to the tank the same amount of water which had been removed. The air in the tank will be compressed as the water volume is increased; when the pump(s) are stopped either by electrode or float switch in the float column, the air pressure will be close to or at its desired maximum value. When the pumps stop, system pressure is monitored and air is either added or removed to optimize the system pressure. For instance, systems that utilize vertical turbine well pumps will typically add a column of air to the system every time they start necessitating removal of air when the tank is finished filling. Systems that utilize closed loop booster pumps to fill the tank may need to have air added when the tank is finished filling to replace air which is absorbed by the water. 2. How to use the Menus and set Variables in the Micro V-PAC II When you first power up the HTC, alarms may start to display on the screen. To clear the alarms press the right selection arrow to clear all alarms. 2.1. Navigating Menus key two (2) times then F2 to clear each alarms or F4 A menu lists various options for the user. A menu is easily selected by using the small, white arrow keys +/- located under the display screen to move to the item the user wants to select. When the correct menu item is highlighted, press ENTER to select it. 2.2. Changing Variables A variable is a setpoint that you, the operator, can control. Values such as high pressure limit, whether to alternate pumps, or the time which the system will wait to turn off the lag pump when signaled to stop can all be controlled by the operator and are considered variable. Use the up down navigation arrow keys ( ) to move the cursor to the menu item you want to select; when it is +/- highlighted, press ENTER to select it. After choosing a variable from a menu, for example the System Pressure Set Point or Lead Pump Start, you are shown a screen describing the variable, and that variables current value. Press ENTER and the value in the box will become highlighted, use +/- or numeric keypad to change the value. Press ENTER when you have completed changing the value and the value in the box will no longer be highlighted. Where screens display more than one variable, use +/- to select the desired variable and press ENTER to select. Using the F1 and F5 key, you can move forward and backward through the sub menu selections screens; press the F3 key at any time to be returned to the main menu.

8 3. Main Screens and Pump Status The default screen is the SYSTEM PRESSURE screen. From this screen that operator can navigate to the The Following is a list of sub menu options and the variables they control 3.1. Pressure Screens 1 System Pressure (this is the Main Screen) a Displays tank pressure in pounds per square inch (P.S.I.). 2 Suction Pressure (Option) a Displays Suction pressure in pounds per square inch (P.S.I.). 3 Pump 1 Status a Reports if pump #1 is off, called, running or failed b Reports daily pump #1 run time c Reports daily pump #1 starts d Reset failed pump from this screen 4 Pump 2 Status a Reports if pump #2 is off, called, running or failed b Reports daily pump #2 run time c Reports daily pump #2 starts d Reset failed pump from this screen 4. Main Menu Screen The Main Menu Screen (F3), Consists of the following sub menus: Exit (takes you back to the Main Screen) Set Point Screens Alarm Screens Setup Screens Security Logon Screens 4.1. Setpoint Screens Note: you must be logged on before any changes may be made, see Security in next section. 1 System Pressure Set Point a Stores the user specified pressure setting. To change, press ENTER once. The box around the value will become highlighted, use the numeric keypad to enter the desired system pressure (in P.S.I.). Press ENTER again, the highlighted area will disappear; press F3 to return to the main menu. Press F5 to move to the next sub menu screen. 2 Tank Low Press Alarm a The system pressure level at which you want to be notified that you have low tank pressure. The delay setting allows you to set a time (in seconds); that the system pressure must be below the Low Pressure Alarm set point, in order to cause an alarm. 3 High Pressure C/O Alarm [High pressure cut out alarm]

9 a Pressure at which the High Pressure Alarm shuts down run signals to all pumps. The delay setting allows you to set a time (in seconds); that the system pressure must exceed the High Pressure C/O Alarm set point, in order to cause an alarm. 4 High Pressure C/O Rstr [High pressure cut out restore] a Pressure at which the High Pressure Alarm resets. The delay setting allows you to set a time (in seconds); that the System pressure must be lower than the High Pressure C/O Rstr set point for this amount of time, in order to reset the High Pressure C/O Alarm. Note: The High Pressure C/O Alarm and High Pressure C/O Rstr (restore) settings help to prevent pump short cycling after a High Pressure C/O Alarm. 5 Lead Pump Start a The tank level set point (in feet or PSI) that you want the lead pump to start at. The delay setting allows you to set a time (in seconds); the pump will delay starting when the tank level has reached the lead pump start set point. 6 Lag Pump Start a The tank level set point (in feet or PSI) that you want the lag pump to start at. The delay setting allows you to set a time (in seconds); the pump will delay starting when the tank level has reached the lead pump start set point. 7 Pump Stop Delay a The delay setting allows you to set a time (in seconds); that the pump will run after float column calls for the pumps to stop. There is a separate setting for the lead and lag pumps. 8 Low Suction C/O Alarm [Low Suction Cut Out Alarm] a The lowest pressure (in P.S.I.) allowed on the pump water supply before the V-PAC II turns the pumps off. 9 Low Suction C/O Rstr [Low Suction Cut Out Restore] a The lowest pressure (in P.S.I.) allowed on the pump water supply side before the V-PAC II allows the pumps to turn on again. Note: The Low Pressure C/O Alarm and Low Pressure C/O Rstr (restore) setting help to prevent pump short cycling after a Low Pressure C/O Alarm. 10 Pump Sequence Select 1-2, 2-1, or Auto. For three pump, select 1-2-3, 2-3-1, 3-1-2 or Auto a 1-2 will always call pump #1 as lead and pump #2 as lag, 2-1 will always call pump #2 as lead and pump #1 as lag and Auto will alternate which pump is lead after the lead pump stops. NOTE: Enable Alternation must be set to YES in the Set Up menu for this to function. 11 Pump Fail Delay a Time the system will wait for a run signal after the pump is called to run, before generating a pump fail alarm. There is a separate setting for Pump #1 and Pump #2.

10 4.2. Alarms When the alarm screen comes up with an alarm, read the alarm message and then press the upper left hand arrow next to the display twice. A pop up menu will appear, press F3 to acknowledge the alarm and clear it, or choose one of the other selections. If you chose the alarm screens from the main menu, you can view active alarms on the alarm screen you are taken to or press F5 to go to the alarm history page. The alarm history page will give you a time date stamp of past alarms and alarm acknowledgements. (Approximately 24 entries) 1 High P.S.I. C/O Clear/Alarm a The text on the first line gives you the date, the time the alarm occurred, if it was an alarm (ALM). Or the date and the time the alarm was acknowledged (ACK); the second line tells what the alarm was. 2 Low P.S.I. Clear/Alarm a The text on the first line gives you the date, the time the alarm occurred, if it was an alarm (ALM). Or the date and the time the alarm was acknowledged (ACK); the second tells what the alarm was. 3 Low Suc. C/O Clear/Alarm a Alarm (ALM). Or the date and the time the alarm was acknowledged (ACK); the second tells what the alarm was. 4 Pump 1 Fail Clear/Alarm a The text on the first line gives you the date, the time the alarm occurred, if it was an alarm (ALM). Or the date and the time the alarm was acknowledged (ACK); the second tells what the alarm was. 5 Pump 2 Fail Clear/Alarm a The text on the first line gives you the date, the time the alarm occurred, if it was an alarm (ALM). Or the date and the time the alarm was acknowledged (ACK); the second tells what the alarm was. 4.3. Setup Screens Note: you must be logged on before any changes may be made, see Security in next section. 1 Pressure Transducer Size (In P.S.I.) a Enter the tank pressure level transducer pressure rating by using the keypad. The Micro V-PAC II will calibrate itself. This is a 4 20mA signal. 2 Suction Trans. (In P.S.I.) a Enter the suction pressure transducer pressure rating by using the keypad. The Micro V-PAC II will calibrate itself. This is a 4 20mA signal. 3 Monitor Suction Pressure a Determines if the suction cut-out / restore function will be used. b Select either Yes or No 4 Alternation Enable a Determines if the pumps will alternate. b Select either Yes or No

11 5 Number of Pumps a Select SIMPLEX, DUPLEX or TRIPLEX to set the maximum number of pumps to run at a time. If the the system is setup for a three pump system and DUPLEX is selected for NUMBER OF PUMS, when in Auto, a maximum of two pumps are allowed to run at any time even though there are three pumps int the system. The alternator will alternate through all three pumps but only two pumps are allowed to run at a time. If simplex is selected, then only one pump will run but at the beginning of the next cycle the next pump in the sequence will be called. 6 Pump Fail Enable a Selects if you want to monitor the run status of your pumps. Functions using the Pump Fail Delay Set Point. b Select either Yes or No 7 Air Option 4.4. Security a Select Air Add or Air Vent function. In the rare cases when both air add and air vent are both required to operate; contact ICS Healy Ruff. 1 Setup Screens are in a password protected area in the program that allows the user to set up the parameters for his individual system. Options such as alternation, air add or vent, tank transducer size, and more are included here. 2 To access the Setup and Setpoint screens you must logon on. Press F3 for the MENU and scroll down to Security Logon and press ENTER. The factory default is 00000. Up to five numbers may be entered for a security password. If you change the security logon password make sure you save this number for future access. To keep the default factory password just press Logon and you will be able to make changes. When complete should then logoff in the same manner. 3 To change the password, go to the security screen using the method in step 2 above and logon. Press the F5 key to bring up the password window. Press the ENTER key and the password box entry will be highlighted, enter your password using the keypad and then press ENTER again. If you have entered the correct security password, you will be taken back to the security log on screen. Press F3 to be taken back to the main menu, you will then select Setup Screens again and this time you can access the Setup and Setpoint Screens. 5. Example of how to change the SYSTEM PRESSURE variable 1 From the Main Menu Screen press until SET POINT SCREEN is highlighted, and then press ENTER. 2 SYSTEM PRESSURE SET POINT screen will appear, with the set point value displayed in a box on the screen. Press ENTER, the value will be become highlighted. 3 Use the +/- keys or the numeric keypad to enter the desired pressure the system will be set for. Press ENTER to lock in value, the value will no longer be highlighted. 4 Press F3 to exit and return to Main Menu screen. 5 PRESSURE SCREENS is highlighted. Press ENTER. 6 You are now at the SYSTEM PRESSURE screen.

12

13 6. Useful Data and Formulas Water Data Power Data Q = Flow, in GPM, CFS, etc. 1 BTU = 1 British Thermal Unit H = Head, Feet of Lift of Q = Heat Required to Raise Temperature of 1 lb. of water 1º F 1 MGD = 1 million gallons per day = 700 GPM 1 HP = 33,000 ft-lb/min. 1 ft³ = 1 cubic foot = 7.5 gallons = 42.5 BTU/min. 1 cfs = 1 cubic foot per second = 2545 BTU/hour = 450 GPM = 746 Watts 1 gallon water = 8.33 lbs Pump HP = Water Hp =Water Hp Pressure Pump Eff ep 1 Atmosphere = 14.7 P.S.I. = 34 feet H2O =(GPM) x H = 29.92 inches 3,960 x ep Hg 1 P.S.I. = 2.31 feet H20 = (MGD) x H = 27.72 inches H20 5.7 x ep = 2.03 inches Hg 1 foot w.c. = 1 foot H2O = (CFS) x H =.432 P.S.I. 8.8 x ep 1 inch w.c. = 1 inch H2O =.036 P.S.I. Water HP = GPM (8.33) #/Gal. x feet lift 33,000 ft.#/min. = (GPM) x H 3,960 = (MGD x 700 x 8.33) x feet lift 33,000 = (MGD) x H 5.07 = (CFS x 450 x 8.33) x feet lift 33,000 = (CFS) x H 8.8

14 7. Installation Diagram OPTIONAL AIR ADD AND/OR AIR VENT OPTIONAL ELECTRODE WIRING TO CONTROLLER 2 IPS HOLE REQUIRED FOR OPTIONAL ELECTRODE HOLDER HTC200-300 HYDRO-PNEUMATIC TANK CONTROLLER WITH INTEGRAL FLOAT COLUMN 1 QZ F1 F6 6 3 DEF 4 GHI 9 WXY F9 F10 0 OUTLET TO DISTRIBUTION SYSTEM INLET FROM PUMP INSTALLATION NOTES: This drawing shows both the electrode type and float column type of HTC and supplements the instruction manual. Make a separate tank connection for air add and/or air vent air line and the control pressure tap. Do not use a tee. Air add and air vent lines may be combined. Installation of a vertical tank is the same. FLOAT TYPE 1 Connect float column with 1" ips pipe, with the runs as short as possible. 2 Locate lower pipe tank connection about 1' above the tank bottom or above the sediment line. The connection should be away from the pump inlet and distribution outlet connections to prevent the float from being affected by turbulence. 3 Locate upper pipe close to tank top. 4 If column is separate from control enclosure, install pressure connection and wiring between column and control. ELECTRODE TYPE (OPTIONAL) 1 Locate tip of shorter electrode at the level where the high water level is desired. 2 The longer electrode should be about 1" longer than the short electrode to eliminate false operation due to turbulence and to allow proper resetting. 3 To further avoid turbulence effects, the electrodes should not terminate near pump inlet and distribution outlet connections. ESC MNO 2 ABC F2 7 F7 PRS +/- F3 8F8 TUV F4 ENTER 5 JKL F5

15 8. Panel and Chassis Layout

16 Catalog No. 01283.5_UM_130627-HTC