EVALUATION ON PERFORMANCE OF PHOTOELECTRIC SMOKE DETECTORS IN THE ZONE DETECTION SYSTEM

Similar documents
J. R. Qualey III, L. Desmarais, J. Pratt Simplex Time Recorder Co., 100 Simplex Drive, Westminster, MA 01441

Optimization of Sensitivity Characteristics of Photoelectric Smoke Detector to Various Smokes

AN ANALYSIS OF THE PERFORMANCE OF RESIDENTIAL SMOKE DETECTION TECHNOLOGIES UTILIZING THE CONCEPT OF RELATIVE TIME

A Method for Fire Detecting by Volume and Surface Area Concentration Based on Dual Wavelengths

Available online at ScienceDirect. Procedia Engineering 135 (2016 )

THE EFFECT OF HEAT LOAD ARRANGEMENT ON THE PERFORMANCE OF RADIANT PANELS

RADIATION BLOCKAGE EFFECTS BY WATER CURTAIN

Developing a Fire Test Strategy for Storage Protection Under Sloped Ceilings

UL268 7 th challenge with single infrared smoke detector

Characterising the smoke produced from modern materials and evaluating smoke detectors

Experimental Study on Response Sensitivity of Smoke Detectors in High Flow Velocity

Evacuation Hazards in Crowded Subway Stations

Evaluation on Combustion Characteristics of Finishing Materials for Exterior Walls

Fire Protection as the Underpinning of Good Process Safety Programs

Warehouse Protection of Exposed Expanded Group-A Plastics with Electronic Sprinkler Technology

DETERMINATION OF SMOKE QUANTITIES TO BE USED FOR SMOKE DETECTION PERFORMANCE GROUND AND FLIGHT TESTS

InstrumentationTools.com

ZONE MODEL VERIFICATION BY ELECTRIC HEATER

PREDICTING SMOKE DETECTOR ACTIVATION USING THE FIRE DYNAMICS SIMULATOR

Investigation of the Potential Use of Blue Light in Forward Scattering Optical Smoke Chambers to Detect all UL217 Fires in the New Standard

Simulation of Full-scale Smoke Control in Atrium

Simple Equations for Predicting Smoke Filling Time in Fire Rooms with Irregular Ceilings

Comparison of Different Sensory Outputs on the Driving Overtake Alarm System

The Study of Evacuation Times from the Multiplex Theatres

A Numerical study of the Fire-extinguishing Performance of Water Mist in an Opening Machinery Space

CHOOSING A FIRE VENTILATION STRATEGY FOR AN UNDERGROUND METRO STATION

Using Smoke Obscuration to Warn of Pre-Ignition Conditions of Unattended Cooking Fires

Recent BRANZFIRE enhancements and validation

A Comparison of Aspirated Smoke Detectors

ANALYSIS OF SMOKE MOVEMENT IN A BUILDING VIA ELEVATOR SHAFTS

Chapter 17, Initiating Devices

Available online at ScienceDirect. Procedia Engineering 84 (2014 )

Evaluation of the NFPA 72 Spacing Requirements for Waffle Ceilings

A Comparison of Carbon Monoxide Gas Sensing to Particle Smoke Detection in Residential Fire Scenarios

Simulation of Evacuation Process in a Supermarket with Cellular Automata

Effect of Contamination on the Sensitivity of Optical Scatter Smoke Sensors

FIRE DYNAMICS IN FAÇADE FIRE TESTS: Measurement, modeling and repeatability

Laser Technology Smoke Detector

STACK EFFECT IN LIGHT WELL OF HIGH RISE APARTMENT BUILDING

SMOKE ALARM SUMMIT Technological Advances in Smoke Alarms Richard Roberts Honeywell Fire Safety Industry Affairs Manager

Smoke Alarms. Rev. A Copyright 2011 James D Peisker

for family composition, time allocation of people, ownership and specification of home appliances. This paper first presents the simulation procedure

Results from a Full-Scale Smoke Alarm Sensitivity Study

THE NEXT GENERATION IN VISIBILITY SENSORS OUTPERFORM BOTH TRADITIONAL TRANSMISSOMETERS AND FORWARD SCATTER SENSORS

Study of Numerical Analysis on Smoke Exhaust Performance of Portable Smoke Exhaust Fan

Research on Decision Tree Application in Data of Fire Alarm Receipt and Disposal

CAN THE CONE CALORIMETER BE USED TO PREDICT FULL SCALE HEAT AND SMOKE RELEASE CABLE TRAY RESULTS FROM A FULL SCALE TEST PROTOCOL?

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland

Unwanted Fire Alarms. Marty Ahrens National Fire Protection Association 1 Batterymarch Park Quincy, MA (617)

Evaluation on Residential Energy Efficiency Programs Using the City-Scale End-Use Simulation Model

Smoke Detector Testing

Chapter 2 Background. 2.1 VID Technology

LEARNING SPECIAL HAZARD DETECTION TYPES

An experimental study of the impact of tunnel suppression on tunnel ventilation

Experimental Study on the Effects of Compression Parameters on Molding Quality of Dried Fish Floss

CFD Analysis of Fire Characteristics on Subway Junction Station

Guidance Note. Guidance Document on Best Practice for Fire Detector Testing/Test Equipment

Impact on Smoke Alarm Performance Considering New Nuisance and Fire Tests

RESEARCH ON THE MAIN CRITERIA OF DECISION-MAKING FACTORS THAT AFFECT CONSUMERS' PURCHASE OF RESIDENTIAL FIRE ALARMS

STUDY FOR SAFETY AT A RELATIVELY SHORT TUNNEL WHEN A TUNNEL FIRE OCCURRED

SCHULTE & ASSOCIATES Building Code Consultants 880D Forest Avenue Evanston, IL /

Comparative Study of Technological Trend between DAIKIN and Panasonic in the Field of Air Conditioner

K.F. Fong *, C.K. Lee, T.T. Chow

Thermal Comfort with Convective and Radiant Cooling Systems

Intelligent Detection Devices

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

Smoke Alarm Research at NIST

CerberusTM. PRO intelligent protection. A comprehensive fire protection system. Answers for infrastructure.

Potential Impact of New UL Fire Test Criteria

Induction heating with the ring effect for injection molding plates

TSI AEROTRAK PORTABLE PARTICLE COUNTER MODEL 9110

Smoke Alarms: Comparing the Differences in Response Times and. Nuisance Alarms. Chris Kasperczyk. University of Cincinnati.

Structure Improvement and Flow Field Analysis of Condenser in Freeze drying Equipment

Automatic Detection of Defects on Radiant Heaters Based on Infrared Radiation

FIRE PROTECTION FOR NON-STORAGE OCCUPANCIES WITH HIGH CEILING CLEARANCES

The Science Behind Water Mist Protection of Typical Building Hazards

PASSIVE AND ACTIVE FIRE PROTECTION OF THE AIR HEATED SOLAR HOUSES

Reducing the Carbon Footprint of Existing Domestic Heating: A Non-Disruptive Approach

Modeling of Ceiling Fan Based on Velocity Measurement for CFD Simulation of Airflow in Large Room

A STUDY ON THE DEVELOPMENT OF A DEODORIZATION UNIT FOR THE TOILET BIDET

Keywords: Fire detection, smoke alarm, nuisance, UL 217, polyurethane foam

A Study on Improvement of Fire Protection Systems based on Failure Characteristics accodrding to Yearly Variation in Old Commercial Buildings

Cerberus PRO intelligent fire protection. A comprehensive portfolio of innovative and industry-leading technology.

Performance evaluation of an innovative fan-coil unit: Low-temperature differential variable air volume FCU

Experimental study on heat transfer characteristics of horizontal concentric tube using twisted wire brush inserts

A Simulation Study on the Energy Efficiency of Gas-Burned Boilers in Heating Systems

Validation of a Smoke Detection Performance Prediction Methodology. Volume 3. Evaluation of Smoke Detector Performance

Fire Risks of Loviisa NPP During Shutdown States

FALSE ALARM ACTIVITY IN THE U.S. 2012

WATER MIST FIRE PROTECTION SYSTEMS FOR INDUSTRIAL CABLE TUNNELS AND TURBINE HALLS

The effect of write current on thermal flying height control sliders with dual heater/insulator elements

Design Procedure for a Liquid Dessicant and Evaporative Cooling Assisted 100% Outdoor Air System

ARCHITECT AND ENGINEER SPECIFICATIONS

WHEREAS, the City of Albany has adopted a Fire Prevention Regulations in the form of Chapter XI of the Albany Municipal Code; and

Fire Dynamics Simulation and Evacuation for a Large Shopping Center (Mall), Part II, Evacuation Scenarios

Numerical Simulation of Ventilation Efficiency in Commercial Kitchen

5B-3 6th Asia-Oceania Symposium on Fire Science and Technology 17-20, March, 2004, Daegu, Korea

Dr. Daniel T. Gottuk Joshua B. Dinabug SUPDET 2014

RESEARCH TECHNICAL REPORT. SMART Sprinkler Protection for Highly Challenging Fires Phase 1: System Design and Function Evaluation

INDOOR CLIMATE IN HEATING CONDITION OF A LARGE GYMNASIUM WITH UNDER-FLOOR SUPPLY/RETURN SYSTEM

Transcription:

EVALUATION ON PERFORMANCE OF PHOTOELECTRIC SMOKE DETECTORS IN THE ZONE DETECTION SYSTEM Hui-Pei Chang 1, San-Ping Ho 2*, Chao-Shi Chen 3,Tsung-Ming Wu 4,Chin-Feng Chen 5 and Cheng-Wei Wu 6 1 Department of Resources Engineering, National Cheng Kung University, Tainan City, Taiwan, R.O.C. 2 Department of Occupational Safety and Health, Chang Jung Christian University, Tainan City, Taiwan, ROC 3 Department of Resources Engineering, National Cheng Kung University, Tainan City, Taiwan,R.O.C. 4 Chia Tai Fire Protection Co., Ltd., Tainan City, Taiwan, R.O.C. 5 Graduate School of Engineering Science and Technology, National Yunlin University of Science and Technology, Yunlin,Taiwan, R.O.C. 6 Department of Resources Engineering, National Cheng Kung University, Tainan City, Taiwan,R.O.C. ABSTRACT Most people believe that detector actuation time increases with the age of a device, but the current test results suggest otherwise. According to government requirements, the standard actuation time limit for photoelectric smoke detectors is 60 seconds or less in the zoned detection system; however, this experiment discovered that new detectors all exhibited actuation times between 10 and 15 seconds. The actuation time of the detectors decreased with the age of the devices. The current study also determined that if the actuation time was 4 seconds or less, then the detector should be replaced because of the high chance of false alarms. In short, detectors with actuation times between 4 and 15 seconds are ideal and should be viewed as the standard for fire safety equipment. In addition, replacing detectors every 6 years in a zoned system is suggested by this research, which found a greater chance of false alarms after 6 years of detector use. KEYWORDS Detector Actuation Time, Smoke Actuation Test, Fire Safety Equipment, False Alarm 1. INTRODUCTION Smoke detectors are commonly used devices for detecting fires; however, instances of false alarm signals are higher among smoke detectors than other types of fire detectors, and cause fire alarm systems to frequently be shut off. These systems eventually lose efficacy, and in cases of real fires, factories are brought to an instant operational stop and suffer enormous losses. Taiwan DOI:10.5121/civej.2017.4104 33

recently promulgated a law requiring fire safety equipment maintenance. Under the law, specialized technicians conduct annual inspections and evaluations, during which they ensure the working condition of this equipment. Therefore, the methods used to evaluate the fire safety equipment must be correct for the desired results to be achieved. The Standard for Validation of Fire Alarms (National Fire Agency 2012) divides smoke detectors into two groups, namely ionization- and photoelectric-type detectors, according to their actuation principles. However, code 72 of the National Fire Protection Association (2013) does not classify the various types of smoke detectors. Instead, a test using gasoline, polystyrene, wood, or newspaper as fuel is performed; as long as the detectors are sensitive to smoke within the specified range under UL 268 testing standards, they are considered to be qualified detectors. In a gray smoke scenario, gasoline or polystyrene is used as fuel to produce a flaming fire with an acceptable smoke concentration of 1.6%/m to 12.5%/m; conversely, in a black smoke scenario, wood or newspaper is used as fuel to simulate a smoldering fire with an acceptable smoke concentration of 5.0%/m to 29.2%/m. Standards for the evaluation of smoke detector performance in Taiwan follow the regulations for automated fire alarms from chapter 10 of the Standard for Maintenance Registration and Operation on Fire Safety Equipment (National Fire Agency 2011). Similar to Japanese requirements, the optimal procedure for evaluating the performance of the detectors is the smoke actuation test, which requires smoke detectors to activate within 60 seconds (Fire and Disaster Management Agency 2006). Additionally, conducting overall inspections should include a smoke sensitivity test. Among modern smoke detectors, photoelectric types are more commonly used. These devices act upon the light scattering principle, which means that the light beam and the photoelectric receivers are perpendicular when no smoke is present; thus, the photoelectric receivers are prevented from sensing the light. However, once smoke enters the chamber, the light beam scatters into the path of the photoelectric receivers. The resulting changes in electrical resistance increase the electric current; when this is detected by the circuit switch, the circuit sends a fire warning (Chen 2013). Overall, photoelectric detectors are more sensitive to smoldering fires but less sensitive to flaming fires. However, Litton (2009) determined that adjusting the ratio of the ionization chamber signal to the optical scattering signal can markedly improve the detectors sensitivity to flaming fire. Bjӧrkman et al. (2002) revealed that the actuation principle for smoke detectors can be represented using the convective-diffusion equation. The factors that affect the time needed for smoke detectors to activate can be divided into four categories: detector sensitivity, time delay, smoke speed, and smoke density. Because the interiors of smoke detectors form a maze, the characteristic length to activation varies; much of the research presented in the SFPE Handbook of Fire Protection Engineering (DiNenno et al. 2002) discusses the range of these lengths. Fergusion (1976) described the false alarm signal rate of automated fire alarms. Among these devices, false alarms are the most commonly encountered problem, followed by errors involving mishandling the central control unit, central receiver, or alarm device; faulty wiring; and other problems. The rate at which false alarms occurred for a smoke detector compared with an actual fire alarm was 15:1 for rate-of-rise detectors, 11:1 for fixed temperature detectors, 14:1 for 34

photoelectric detectors, and 25:1 for ionization detectors. Lack (1973) similarly found the rate of false alarms to be 11.1:1 for heat detectors and 14.1:1 for smoke detectors. Chen et al. (2012) improved the aerosol generator to produce different-sized particles that could promote the smoke detector test. Elsewhere, To and Fong (2013) determined that multisensors effectively increase the accurate detection of a fire detector from 80% to 90%. The aforementioned research reveals that, when applied to the smoke detector actuation time test, the current requirement standard is inaccurate and cannot be used to locate degraded detectors early through only periodic tests. An improved requirement standard is provided in this research and can be the criterion for modern fire detection. 2. RESEARCH METHODS 2.1 Experiment Setup The smoke testers (model FTG 012) used to conduct this experiment were manufactured by Japan Nohmi Bosai Ltd. These testers come with a cap to cover the smoke detector to prevent genuinely activating the device while smoke is being produced for the simulation experiment. This model of smoke testers uses fuel gas (tetrafluoroethane (see Figure. 1)) and a smoke generator, and can be applied to both ion and photoelectric smoke detectors. The smoke testers enabled examination of both the performance and actuation times of smoke detectors. Additionally, smoke sensitivity testers were used to prevent drastic changes in the sensitivity of the smoke detectors, which can be impeded from sending fire warnings after long periods of use. Oil smoke sensitivity testers (model BG99103K, Japan Panasonic Corp.) were used in this experiment. The smoke concentration value required for activation is represented as a voltage (V), with higher values corresponding with actuations that occurred at higher concentrations. The exterior of the tester is shown in Figure. 2. Figure1.Smoke tester and fuel gas can Figure2.Exterior of smoke sensitivity tester 35

2.2 Experiment Methods Four units of photoelectric smoke detectors from both of the two most common brands of smoke detectors used in Taiwan, identified as A and B, were selected as samples. To determine the actuation times of the smoke detectors, the smoke testers were activated for 1, 3, 6, 9, and 12 seconds, with their response times recorded; the results were used as a reference for the accuracy of the smoke testers. A sketch of the method used to test the smoke testers is presented in Figure. 3. The smoke actuation test and smoke sensitivity tests were performed on the samples by using the smoke tester and smoke sensitivity tester, respectively. Three categories of smoke detectors were examined: (1) the latest products by brands A and B; (2) detectors used for 1 8 years in ordinary occupancies; and (3) detectors that had a history of false alarms. Figure.3 Method used to test sample via smoke tester 36

3. RESULTS AND DISCUSSION 3.1 Teston Accuracy of Smoke Testers This experiment used smoke testers to test the latest products made by brands A and B. The results, presented in Figure.4, show that activating the smoke tester over various periods of time had no visible influence on the actuation times of the smoke detectors. This was an unexpected finding because the longer the smoke tester is used, the denser the concentration of the smoke becomes and the earlier the actuation of the detector should be. Further investigating the results revealed that the actuation times were influenced by how the testing gas was released. Normally, the gas stored in a fuel gas can is in a liquid state. When it interacts with the external room-temperature air, it forms a jet that causes turbulence inside the cap of the smoke tester. This jet makes it challenging for the testing gas to penetrate the chamber; thus, the released gas concentration has limited influence on the actuation time of the smoke detectors. In the future, smoke detector inspections should note that when fuel gas-powered smoke testers are used to conduct a smoke actuation test, the tester does not need to be activated for long for the smoke detector to actuate. Continual activation only increases the cost of the experiment, with no benefit. Figure. 4 Test results of brand A and B smoke testers 37

3.2 Analysis on Relationship between Actuation Time and Years of Usage This research examined brand A and B detectors that had periods of use from 1 to 8 years, which is the second series of tests, and comparison between the two are shown in Figure. 5. Fig. 6 compares the detectors which have a history of false alarms, which is the third series of tests; all detectors underwent the smoke actuation test and activated at different times. For the second series of tests, results indicated that the smoke detectors used for more than 6 years tended to have faster actuation times, which contradicts the common belief that older devices are slower to activate. The smoke detectors with a history of false alarms, the third series of tests, all actuated after interacting with smoke for approximately 3 seconds (Fig. 6). As shown in Fig. 5, brand A devices that had been used for 1 6 years had an average actuation time of more than 4 seconds. Comparing the two actuation times revealed that critical values existed for triggering a false alarm in the detectors. When the smoke actuation test was conducted after 4 seconds, no false alarms occurred; however, the chance of a false alarm occurring when actuation was conducted after less than 4 seconds was extremely high. This suggests that if the actuation times of the smoke detectors are 4 seconds or less, then the frequency of false alarms increases and the detectors should be replaced to prevent false alarms. Figure. 5 Actuation times of brand A and B detectors under different years of use 38

Figure. 6 Actuation times of detectors with false alarm history 3.3 Analysis on Relationship between Smoke Sensitivity and Years of Usage This experiment also examined brand A and B detectors over varying periods of use, and conducted the smoke sensitivity test on them. No drastic changes to the smoke sensitivity were observed, regardless of the length of time the detector had been used, although the values remained in a certain range (see Fig. 7). These results were distinct from those obtained from the smoke actuation test, in which actuation times declined as usage years increased. Clearly, the increased age of smoke detectors had no direct influence on their sensitivity but had a considerable effect on the actuation times of the devices. Thus, setting regulations for the smoke sensitivity of detectors in Taiwan or Japan does not seem necessary; however, conducting smoke actuation tests on detectors is a practical method to obtain accurate results on the working condition of detectors. Figure. 7 Smoke sensitivity values of brand A and B detectors under different 39

4. CONCLUSION In this study, smoke tests and smoke sensitivity tests were conducted on smoke detectors from two brands that had been used for varying periods of time. The actuation times were lower in the detectors that had been used for 6 years. By contrast, the smoke sensitivity of the detectors did not drastically change with detector age, but rather stayed within a certain range regardless of time. In conclusion, the actuation time of a detector, rather than its sensitivity, dictates its performance. This experiment also indicated that not all the regulations outlined in the Standard for Maintenance Registration and Operation on Fire Safety Equipment manual are appropriate. Specifically, restricting the eligible actuation time to 60 seconds appears unreasonable for photoelectric detectors. The two latest products from brands A and B exhibited upper actuation time limits of 10 15 seconds, with the most likely time for false alarms occurring at approximately 3 seconds. Therefore, functional standards of photoelectric smoke detectors should have 4 and 15 seconds set for the lower and upper limits, respectively, and prime detector operation should be considered as lasting approximately 6 years. ACKNOWLEDGEMENTS The authors acknowledge Chia Tai Fire Protection Co., Ltd. for the use of its facilities and for its aid in supplying detectors of varying ages. REFERENCES [1] Bjӧrkman J, Baroudi D, Latva R, Tuomisaari M, Kokkala M (2002) Determination of dynamic model parameters of smoke detectors. Fire Saf J 37:395 407. doi:10.1016/s0379-7112(01)00058-3 [2] Chen HY (2013) Explanation on installment standards for fire safety equipment in various areas, 6th edn. Tingmao Publish Company, R.O.C. (In Chinese) [3] Chen N, Ma X, Dong W (2012) Experimental study on the testing environment improvement of fire smoke detectors. ProcEng 45:610 616.doi:10.1016/j.proeng.2012.08.211 [4] DiNenno PJ, Drysdale D, Beyler CL, Walton WD, Custer RLP, Hall JR, Watts JM (2002) SFPEhandbook of fire protection engineering 3rd edn. National Fire Protection Association, Quincy [5] Fergusion A (1976) The reliability of automatic fire detection equipment. Edinburgh Univ. [6] Fire and Disaster Management Agency (2006) Standard for inspection on fire safety equipment and inspection report format. Fire and Disaster Management Agency, Ministry of Internal Affairs and Communications, Japan (In Japanese) [7] Lack H (1973) Economics of fire protection with fire detectors. Fire Technol 9(1):56 64. doi:10.1007/bf02624841 [8] Litton CD (2009) Laboratory evaluation of smoke detectors for use in underground mines. Fire Saf J 44:387 393. doi:10.1016/j.firesaf.2008.08.008 [9] National Fire Agency (2011) Standard for maintenance registration and operation on fire safety equipment. National Fire Agency, Ministry of the Interior, R.O.C. (In Chinese) [10] National Fire Agency (2012) Standard for validation of fire alarms. National Fire Agency, Ministry of the Interior, R.O.C. (In Chinese) [11] National Fire Protection Association (2013) NFPA 72 National fire alarm and signaling Code 2013 edn. National Fire Protection Association, Quincy [12] To H, Fong N (2013) Investigation of the performance and improvement of optical smoke detectors. ProcEng 62:985 993. doi:10.1016/j.proeng.2013.08.152 40