ZM2 OPERATING AND MAINTENANCE INSTRUCTIONS

Similar documents
ZX1e ZX2e ZX5e. Document No Issue 01 user manual

Syncro AS. Analogue Addressable Fire Control Panel. User Manual

6100 SINGLE LOOP DIGITAL ADDRESSABLE FIRE ALARM CONTROL PANEL

Fire Alarm Control Panel. System Maintenance and Log Book

Operating instructions SENTRI4 Control panel based Fire detection and alarm system

one Operating instructions SenTRI ONE panel-based Fire detection and alarm system

Operating instructions Vigilon panel and Network node Fire detection and alarm system

Installation, Operating and Maintenance Manual

ID2000. operating manual

Algo-Tec 6500/6600 INTERACTIVE ADDRESSABLE FIRE CONTROL SYSTEM

3500 CONVENTIONAL FIRE ALARM CONTROL PANEL

3200 NON-ADDRESSABLE FIRE ALARM CONTROL PANEL

SYSTEM 3400 ANALOGUE ADDRESSABLE FIRE DETECTION. (with Devices) Operating Manual Version 3.3X Issue 2 September 1996

Intelligent Security & Fire Ltd

ZSC100 Gas Detection and Alarm System Controller

XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM CONTROL PANEL. user manual and log book. approved document no. DFU Rev 1

D8024, D9024, D10024 Analog Fire Alarm Control Panels Programming Guide

Control Panel User Guide

Fire detection and alarm system Operating instructions

PNC 1000 SERIES 2, 4, 8 Zone Fire Alarm Control Panel

Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels

Control Panel User Guide (TO BE RETAINED BY THE USER)

Operating manual and Log book for the range of 1,2,4 and 8 zone fire Control and Repeat panels

user manual and log book XFP NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM CONTROL PANEL

System 800 Addressable Fire Detection & Alarm System

QS1 Technical Reference Manual P/N REV 05 REB 14FEB13

Operator's Handbook. Release 3. Fire Alarm Control Panel, BS-310 / 320 / Operator Panel BS-330. System Program Version 3.8.0

2) This manual covers Fire and General Alarm systems. The differences are described in the appropriate sections.

SYSTEM 5000 USER MANUAL

user manual Document No , Revision 03 November 2015

INTELLIGENT FIRE TECHNOLOGY. Twinflex and Multipoint V3. User Guide (TO BE RETAINED BY USER) Issue 3

PAT E N T System 88. COMPLIES WITH Singapore Standard : SS CP10 : 2005 British Standard : BS EN54-2 : 1998 BS EN54-4 : 1998 REV.00

FIRE FIRE. 4100U Fire Alarm. Operator's Manual. Technical Manuals Online! -

The supplier and installer of the system should be approved by the local civil defence authority.

Simplex Panel Interface Guide

The EN54 Part 2 & 4 Fire System

ViewMatrix. Software for Online Monitoring & Control of Matrix2000 Conventional Fire Alarm Panels. Version: 2.0 Revision: 0.1

Operator s Manual Part: InfoAlarm Product: 4100U, 4100ES Rev. B

ZP2 Series Operation Manual

Logbook. Precept EN Fire Detection/Alarm Panel. & Precept EN Repeater

QS1 Technical Reference Manual P/N REV 05 REB 14FEB13

Document No Issue 4 user manual

RESET + Password Enter (During Auto Speed Procedure) Maintenance Timeout or after TEST + RESET + DISABLE (No Need for Device to Initialize)

Fire detection and alarm

Control Panel User Guide

HS-5100, HS-5200, HS-5400 ANALOGUE ADDRESSABLE CONTROL PANELS. User Manual. Approved Document UI-ELAN-02 Revision 03

ZERIO PLUS EDA-Z5008, Z5020 & Z5100

M800, M800iD Plus, M1000 and M3000. User's Guide

Master Code Arming Auto-Bypass Option - Home-Away Arming Entry Delay Off Arming

Operator's Handbook. Interactive Fire Alarm System Release 3. Information Panel, BV-320. Protecting life, environment and property...

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

Summary of Keypad Main User Commands

Intelligent Security & Fire Ltd

USER MANUAL & MAINTENANCE GUIDE OG OO

AFP-300/400 OPERATORS MANUAL INTELLIGENT FIRE DETECTION AND ALARM SYSTEM SOFTWARE VERSION 2.2 REVISION AUS 3

Scimitar user manual & log book. Petersfield Business Park, Bedford Rd, Petersfield, Hampshire GU32 3QA Tel: Fax:

Conventional Fire System. BiWire Flexi Fire Panel EFBW8ZONE-FLEXI / EFBW4ZONE-FLEXI / EFBW2ZONEFLEXI User Manual

The EN54 Part 2, 4 and 13 Fire System

QSC Technical Reference Manual P/N REV 05 REB 14FEB13

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

ZP3 Operator & Maintenance Manual Version 1

Laptop / PC Programming Manual

HARDWIRED CONTROL PANELS

PEGAsys. Multi-Loop Intelligent Suppression Control System FEATURES DESCRIPTION. Effective: March 2007 K

FTEN1, FTEN2, & FTEN4 1, 2 & 4 ZONE FIRE DETECTION AND ALARM CONTROL PANELS

FA-300 Series. LED Fire Alarm Control Panel. User Guide. FA-300 SERIES Fire Alarm Control Panel. FA-300 SERIES Fire Alarm Control Panel

SIMPLICITY CO CARBON MONOXIDE DETECTION & VENTILATION PANEL

USER MANUAL COMBINED FIRE & EXTINGUISHING CONTROL PANEL COMPLIES WITH BS EN PART 1 & EN54 PARTS 2 & 4

Control Panel. 1.0 GENERAL SCOPE OF WORK Introduction... 2

Area Systems While the alarm bell or siren is sounding, enter your user code. The system silences the alarm bell or siren.

Watchguard WGAP864 User Manual

SFC-200 SERIES LED FIRE ALARM PANEL

EST3X User Guide P/N EN REV 1.0 ISS 10MAY11

Fire Command Keypad. XR5 User s Guide

TECHNICAL DATA. multi-hazard. model vfr400. Release Control Panel 290a. January 16, 2014

DS9400 Series. Release Notes for Firmware V2.07. Fire Alarm Control Panel

Excel-EN Conventional Fire Control Panel

intelligent fire alarm ID60series panels

VIGILANT MX1-Au Fire detection and alarm system Engineer s Specification

User Guide ems25plus. Page 1. Normal operation. Product interface

CSP-204 CSP-208 CSP-104 CSP-108

USER MANUAL, MAINTENANCE GUIDE & LOG BOOK

KFP-CF Series Operation Manual

i.c³ User Guide For Helmer i.series Ultra-Low Freezers A/A

ZXSe Range Data Sheet

FIRE CONTROL PANEL. Revision 1.1 January 1997 USER MANUAL. Emergi-Lite Safety Systems Ltd Bruntcliffe Lane Morley Leeds LS27 9LL

FIRE ALARM CONTROL PANEL FVC01-08

False Alarm Management

The ID51 & ID52 can be upgraded to 2 loops without the need to change back box. FEATURES. Intelligent Features

TrueAlarm Fire Alarm Systems

Contact ID as of 2/2/2015

CONTENTS Installation Precautions... 1 Chapter 1 Product Introduction... 2 Chapter 2 Technical Specifications... 3

Electro-Detectors Page 2. Revision History. EDA-Z Installation and Operation Manual

Flopurge TS. Operation Manual

HARDWIRED CONTROL PANELS

Fire Operator Workstation (Fire OWS) User s Guide

Contents. Glossary

Understanding the Code Pad lights...4. Code Pad tones...5. Fully arming the system On MODE...6. Fully arming the system - Quick Arm MODE...

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION FIRE ALARM SYSTEM

Control/Communicator

Transcription:

ZM2 OPERATING AND MAINTENANCE INSTRUCTIONS CONTENTS 1. System Overview 2. User responsibilities 3. First Line controls and indications 3.1 Logging on to the fire alarm system 3.2 Checking system status 3.3 Displaying or printing maintenance reports 3.4 Displaying the alarm history 3.5 Performing a lamp test 3.6 Silencing the panel buzzer 3.7 Resetting the fire alarm system 3.8 Silencing sounders 3.9 Sounding an alarm 3.10 Disabling and enabling a matrix group 3.11 Disabling and enabling a time control 3.12 Switching fire alarm sensitivity 3.13 Switching event message routes 3.14 Setting the system time and date 3.15 Restarting the fire alarm system

1. System Overview The Clymac ZM2 system is a microprocessor based fire detection and alarm system. The control panel accepts signals from call points, smoke sensors, heat sensors and interface units. It also has outputs for audible and visual alarm devices together with auxiliary outputs for plant shutdown control. 1.1 Addressable devices Smoke detectors, heat detectors, call points and interface units are all addressable devices. This means that the control panel is able to individually identify a fire or fault alarm from each device. Each device is therefore allocated a number or address when the system is commissioned. Each address is then programmed with one line of ten characters and a second line of 16 characters for the text label, which will in turn be displayed on the control panel s text display in the event of an alarm. An addressable system therefore enables the exact source of the incident to be identified quickly reducing the search time and improving the chances of containing the incident. 1.2 Analogue detection The ZM2 system utilises analogue detection techniques to detect fire and fault incidents. An analogue system is a very accurate method of detection and monitors the rate at which the activity within a detector's sensing chamber changes. An analogue detection system therefore reduces the occurrence of false alarms and increases detection performance of a real fire. It will also identify faulty and dirty detectors thus reducing the cost of maintenance activities. 1.3 Controls and indications All of the fire and fault occurrences are displayed on the control panel s liquid crystal display together with the text label when relevant 1.4 Continuous monitoring The ZM2 system provides the user with total peace of mind. All of the control panel functions and system devices are continuously monitored for their correct operation. The cable used to interconnect all of the detectors, call points, interface units and sounders is also continuously monitored for failure.

2. User Responsibilities Daily The British Standard code of practice for fire detection and alarm system; BS5839 Part 1 states that the system should be inspected daily to ensure that it is indicating a normal condition and that any previously indicated fault/warning condition has received appropriate attention. It recommends entry into the log book provided of all system events for future reference. Weekly At weekly intervals a different fire detector or manual call point should be tested. Any entry should be made in the log book quoting the particular trigger device that has been used to initiate the test. The test should be performed at a regular time to avoid confusion between a test and a genuine alarm. Quarterly At quarterly intervals the system should be thoroughly inspected and tested by a trained engineer. The quarterly test would normally be part of an annual maintenance agreement taken out by the end user with a trained alarm specialist.

Chapter 3 First Line Controls & Indications Summary This chapter provides instructions for operating the fire alarm system from the control panel CPU/Display Unit. It is intended for those who might be expected to operate the control panel in a fire alarm emergency. Content 3.1 Logging on to the fire alarm system 3.2 Checking system status 3.3 Displaying or printing maintenance reports 3.4 Displaying the alarm history 3.5 Performing a lamp test 3.6 Silencing the panel buzzer 3.7 Resetting the fire alarm system 3.8 Silencing sounders 3.9 Sounding an alarm 3.10 Disabling and enabling a matrix group 3.11 Disabling and enabling a time control 3.12 Switching fire alarm sensitivity 3.13 Switching event message routes 3.14 Setting the system time and date 3.15 Restarting the fire alarm system

3.1 Logging on to the fire alarm system Before you can operate any of the system commands, you must first log on to the fire alarm system. The password you use to log on to the fire alarm system determines which command menus you are allowed to use. The password levels are described as follows: The level 2 password lets you use the level 2 command menus The level 3 password lets you use the level 3 command menus The level 4 password lets you use the level 4 command menus Note: The level 1 command menus do not require a password. The control panel continues to let you use the command menus for the password you entered until you log on with a different password or until the user time-out period expires. For EN 54 systems the user time-out period is twenty-five seconds. After the user time-out period expires, the control panel automatically returns to using the level 1 command menus. For more information, see the topic "Command menu organisation" in Chapter 1. To log on to the fire alarm system: 1. Press Menu. 2. Choose Login. 3. Enter the password for the desired command level.

3.2 Checking system status The Status menu commands let you check the status of the fire alarm system. Each command generates a list that you can view on the alphanumeric display or print for later use. Displaying a list of abnormal points Use the All Active command on the Status menu to display a list of all points in the system that are not in the normal condition. To display a list of abnormal points: 1. Press Status. 2. From the Status menu, choose All Active. 3. Press Enter to accept the default (all panels). 4. On the Report Output menu, choose the following: Displaying a list of abnormal fire alarm points Use the Fire command on the Status menu to display a list of fire alarm points (i.e. call point, heat, smoke, verified smoke, and sprinkler inputs) that are not in the normal condition. The list also includes any fire-related pseudo points. To display a list of abnormal fire alarm points: 1. Press Status. 2. From the Status menu, choose Fire. 3. Press Enter to accept the default (all panels). 4. On the Report Output menu, choose the following: Displaying a list of abnormal supervisory points Use the Supervisory command on the Status menu to display a list of supervisory points (i.e., latching supervisory, latching tamper, supervisory, and tamper inputs) that are not in the normal condition. The list also includes any supervisoryrelated pseudo points. To display a list of abnormal supervisory points: 1. Press Status. 2. From the Status menu, choose Supervisory.

3. Press Enter to accept the default (all panels). 4. On the Report Output menu, choose the following: Displaying a list of abnormal monitor points Use the Monitor command on the Status menu to display a list of monitor points (i.e., monitor inputs) that are not in the normal condition. The list also includes any monitor-related pseudo points. To display a list of abnormal monitor points: 1. Press Status. 2. From the Status menu, choose Monitor. 3. Press Enter to accept the default (all panels). 4. On the Report Output menu, choose the following: Displaying a list of abnormal output points Use the Outputs command on the Status menu to display a list of output points (i.e., relay, common alarm, supervised, audible, and visible outputs) that are not in the normal condition. The list also includes LED-switch card LEDs. To display a list of abnormal output points: 1. Press Status. 2. From the Status menu, choose Outputs. 3. Press Enter to accept the default (all panels). 4. On the Report Output menu, choose one of the following: Displaying a list of points in a fault condition Use the Fault command on the Status menu to display or list of points that are in a fault condition. To display a list of points in a fault condition: 1. Press Status. 2. From the Status menu, choose Fault. 3. Press Enter to accept the default (all panels). 4. On the Report Output menu, choose one of the following:

Displaying or a list of abnormal points in an active service group Use the Test command on the Status menu to display a list of points in an active service group that are not in the normal condition. The list also includes the name of the active service group. To display a list of abnormal points in an active service group: 1. Press Status. 2. From the Status menu, choose Test. 3. Press Enter to accept the default (all panels). 4. On the Report Output menu, choose one of the following: Display a list of disabled points Use the Disabled Pts command on the Status menu to display a list of points that are disabled. The list shows the device type, address, and the event message for each disabled point. To display a list of disabled points: 1. Press Status. 2. From the Status menu, choose Disabled Pts. 3. Press Enter to accept the default (all panels). 4. On the Report Output menu, choose one of the following: Displaying power supply voltages Use the Internal command on the Status menu to display the current power supply voltages. To display power supply voltages: 1. Press Status. 2. From the Status menu, choose Internal. 3. Press Enter to accept the default (all panels). 4. On the Report Output menu, choose one of the following:

3.3 Displaying maintenance reports There are four maintenance reports available to help you determine whether any fire alarm sensors require servicing. You can view each report on the alphanumeric display. Display a Dirty>80% report Use the Dirty>80% command on the Maintenance menu to display a Dirty>80% report. A Dirty>80% report lists all fire alarm sensors whose compensation levels exceed 80%. The compensation level value is an indication of a fire alarm sensor's inability to compensate for environmental conditions. Note: Fire alarm sensors on this list require servicing as soon as possible. To display a Dirty>80% report: 1. Press Menu. 2. From the main menu, choose Reports, then Maintenance, and then Dirty>80%. 3 Press Enter to accept the default (panel 01). 4. On the Report Output menu, choose the following: Display a Dirty>20% report Use the Dirty>20% on the Maintenance menu to display a Dirty>20% report. A Dirty>20% report lists all fire alarm sensors whose compensation levels exceed 20%. The compensation level value is an indication of a fire alarm sensor's inability to compensate for environmental conditions. Note: Fire alarm sensors on this list may require servicing and should be watched carefully. To display a Dirty>20% report: 1. Press Menu. 2. From the main menu, choose Reports, then Maintenance, and then Dirty>20%. 3 Press Enter to accept the default (panel 01). 3. On the Report Output menu, choose the following:

Display a Single Device report Use the Single Device command on the Maintenance menu to display a Single Device report. A Single Device report lists the configuration settings for an individual fire alarm sensor. The report includes the following information: The device address The detector type The location description (if programmed) The compensation level (percent dirty) The primary alarm sensitivity setting The alternate alarm sensitivity setting To display a Single Device report: 1. Press Menu. 2. From the main menu, choose Reports, then Maintenance, and then Single Device. 3. Enter the panel-card-device address (PPCCDDD) of the fire alarm sensor. 4. On the Report Output menu, choose the following: Display a Card Devices report Use the Card Devices command on the Maintenance menu to display a Card Devices report. A Card Devices report lists the operating parameters for all fire alarm sensors on a specific loop controller. To display a Card Devices report: 1. Press Menu. 2. From the main menu, choose Reports, then Maintenance, and then Card Devices. 3 Enter the panel-card address (PPCC) of the loop controller. 4. On the Report Output menu, choose the following:

3.4 Displaying the alarm history Use the Alarm History command on the Reports menu to display the alarm history while the control panel is in an abnormal condition. The alarm history display shows how many times the control panel has entered the fire alarm condition. To display the alarm history: 1. Press Menu. 2. From the main menu, choose Reports then Alarm History.

3.5 Performing a lamp test Use the Lamp Test command on the Test menu to verify the operation of the alphanumeric display and the LED indicators. The lamp test command temporarily turns on the panel buzzer, all LED indicators, and every pixel on the alphanumeric display. Note: When operated from the control panel CPU/Display Unit, the lamp test command only tests the control panel. When operated from a repeater panel CPU/Display Unit, the lamp test command tests all repeater panels at the same time. To perform a lamp test: 1. Press Menu. 2. From the main menu, choose Test, and then Lamp Test.

3.6 Silencing the panel buzzer The panel buzzer sounds whenever an event message is received at the control panel. Pressing the Panel Silence switch silences the panel buzzer and acknowledges all current event messages. Unless programmed otherwise, the panel buzzer automatically re-sounds twenty-four hours after being silenced provided that no new event messages are received at the control panel. Note: The panel buzzer can be programmed to sound periodically as a reminder that there is a fault in the system. To silence the panel buzzer: 1. Press Panel Silence. 2. Enter the level 2 password.

3.7 Resetting the fire alarm system Pressing the Reset switch restores the fire alarm system to its normal state provided there are no inputs still in a latched (active) condition. If any inputs are still in a latched condition at the end of the reset cycle, sounders, if silenced, will re-sound and the panel buzzer, if silenced, will re-sound. Caution: Do not reset the fire alarm system until the proper authorities have determined that the threat of fire is no longer present. To reset the fire alarm system: 1. Press Reset. 2. Enter the level 2 password.

3.8 Silencing sounders Pressing the Silence Alarms switch silences all audible, visible, and common alarm outputs except in the following instances: When a sprinkler switch is active and the system is not programmed to allow silencing when a sprinkler switch is active When the system is programmed to delay the silencing of fire alarm signals, in which case the Silence Alarms switch may not be operational for up to five minutes after the initial fire alarm event Silenced outputs automatically re-sound when: The Silence Alarms switch is pressed a second time Another zone is activated A subsequent point in the same zone is activated and the system is programmed allow zone resounding. Note: Visible outputs, if used, can be programmed to disregard the Silence Alarms switch. To silence sounders: 1. Press Silence Alarms. 2. Enter the level 2 password.

3.9 Sounding an alarm Pressing the Sound Alarms switch activates all audible (sounder) and common alarm outputs. Visible outputs are also activated, unless programmed otherwise. Pressing the Sound Alarms switch a second time returns these outputs to their normal condition. To sound an alarm: 1. Press Sound Alarms. 2. Press Enter to confirm that you want to sound all alarms. 3. Enter the level 2 password.

3.10 Disabling and enabling a matrix group The fire alarm system can comprise one or more matrix groups. Matrix groups initiate a set of responses when a specific number of fire detectors are activated or when two fire detectors within a defined search radius are activated. You can disable and enable matrix groups from the control panel using the Matrix command on the Disable Group and Enable Group menus. Disabling a matrix group Use the Matrix command on the Disable Group menu to temporarily take a matrix group out of service and prevent it from initiating a set of responses. To disable a matrix group: 1. Log on using the level 2 password. 2. Choose Disable, then Group, and then Matrix. 3. Select a matrix group from the pick list, then press Enter. Enabling a matrix group Use the Matrix command on the Enable Group menu to return a disabled matrix group to service and allow it to initiate a set of responses. To enable a matrix group: 1. Log on using the level 2 password. 2. Choose Enable, then Group, and then Matrix. 3. Select a matrix group from the pick list, then press Enter.

3.11 Disabling and enabling a time control The fire alarm system can be programmed with one or more time controls. Time controls initiate a set of responses at a specific time and date as determined by the system clock. You can disable and enable time controls from the control panel using the Time Control command on the Disable Group and Enable Group menus. Disabling a time control Use the Time Control command on the Disable Group menu to temporarily take a time control out of service and prevent it from initiating a set of responses. To disable a time control: 1. Log on using the level 2 password. 2. Choose Disable, then Group, and then Time Control. 3. Select a time control from the pick list, then press Enter. Enabling a time control Use the Time Control command on the Enable Group to return a disabled time control to service and allow it to initiate a set of responses. To enable a time control: 1. Log on using the level 2 password. 2. Choose Enable, then Group, and then Time Control. 3. Select a time control from the pick list, then press Enter.

3.12 Switching fire alarm sensitivity Fire alarm sensors have two separate alarm sensitivity settings. The alarm sensitivity setting determines how easily fire alarm sensors can sense a fire alarm condition. Typically, the primary alarm sensitivity setting is programmed for daytime operation and the alternate alarm sensitivity setting is programmed for night time and weekend operation. In most applications, a time control is used to automatically switch fire alarm sensors over to their alternate sensitivity setting. When the time control is restored, fire alarm sensitivity is automatically switched back to the primary sensitivity settings. You can override the sensitivity settings in effect using the Alternate Sensitivity command on the Activate menu and Primary Sensitivity command on the Restore menu. Note: The default setting for both primary and alternate alarm sensitivity is "Low." When both alarm sensitivity settings are the same, switching alarm sensitivity does not have any effect. Switching from primary to alternate alarm sensitivity Use the Alt Sens (alternate sensitivity) command on the Activate menu to cause fire alarm sensors to use their alternate alarm sensitivity setting instead of their primary alarm sensitivity setting. To switch from primary to alternate sensitivity: 1. Log on using the level 2 password. 2. From the main menu, choose Activate, then Alt Sens. Switching from alternate to primary alarm sensitivity Use the Prm Sens (primary sensitivity) command on the Restore menu to cause fire alarm sensors to use their primary alarm sensitivity setting instead of their alternate alarm sensitivity setting. To switch from alternate to primary sensitivity: 1. Log on using the level 2 password. 2. From the main menu, choose Restore, then Prm Sens.

3.13 Switching event message routes Event messages are programmed with a primary and an alternate message route. Typically, a fire alarm system uses the primary message route during daytime operation and the alternate message route during night time operation. In most applications, a time control is used to automatically switch event messages over to their alternate route setting. When the time control is restored, event messages are automatically switched back to their primary route settings. You can override the event message route in effect using the Alternate Message Route command on the Activate menu and the Primary Message Route command on the Restore menu. Note: The default setting for both primary and alternate message routes is "All Cabinets." When both event message route settings are the same, switching message routes does not have any effect. Switching from primary to alternate message routing Use the Alt Msg Route (alternate message route) command on the Activate menu to switch event message routing from primary message routing to alternate message routing. To switch from primary to alternate message routing: 1. Log on using the level 2 password. 2. From the main menu, choose Activate, then Alt Msg Route. Switching from alternate to primary message routing Use the Prm Msg Route (primary message route) command on the Restore menu to switch event messages routing from alternate message routing to primary message routing. To switch from alternate to primary message routing: 1. Log on using the level 2 password. 2. From the main menu, choose Restore, then Prm Msg Route.

3.14 Setting the system time and date The control panel includes a system clock that it uses to time stamp events and to activate time controls. The time is presented in 24-hour format. The date is presented in day-month-year format. To set the system clock for the current time:

3.15 Restarting the fire alarm system Use the Restart command on the Program menu to re-initialise the fire alarm system without removing power. To restart the fire alarm system: 1. Log on using the level 2 password. 2. From the main menu, choose Program, then Restart. 3. Enter a panel number or press Enter to accept the default (all panels).