FORMULATION OF FIRE SAFETY REQUIREMENTS FOR NEW RAILWAY INFRASTRUCTURES

Similar documents
Smoke Control Requirements for New Railway Infrastructure. Ir Peter Law

Prescriptive Requirement for Smoke Control

Provisions for the Means of Escape and Means of Access by Using Lifts and Escalators in the MTRC Main (U/G) Station

Third Runway Project APM Depot Fire Engineering Design. Presented by Ir Wilson Sau-kit TSANG

technical specification smoke venting systems

incorporating Guidance to Shafts for Smoke Control A useful guide to practical smoke shaft principals and specifications

Technical Seminar on the Code of Practice for Fire Safety in Buildings 2011

REVIEW OF TECHNICAL STANDARDS AND CALCULATION METHODS FOR DIMENSIONING OF SMOKE AND HEAT CONTROL SYSTEMS IN CASE OF FIRE IN UNDERGROUND CAR PARKS

LONGITUDINAL VENTILATION FOR SMOKE CONTROL IN A TILTED TUNNEL BY SCALE MODELING

Mechanical Smoke Extract Shaft Systems

SURVEY ON FIRE SERVICE INSTALLATIONS FOR OFFICE BUILDINGS IN HONG KONG

NEW PROJECTS DOCUMENTATION FOR OCCUPATION - REGULATION 38 FIRE STRATEGIES, DRAWINGS & INFORMATION EMPLOYER S REQUIREMENTS

Module 7. Control of Smoke & Highlights of Code Requirements

Loss Prevention Standards

CHAPTER 7 MECHANICAL VENTILATION AND SMOKE CONTROL SYSTEMS 7.1 AIR CONDITIONING & MECHANICAL VENTILATION SYSTEMS

NUMERICAL STUDIES ON BARE CABIN FIRES WITH OPERATION OF SMOKE EXTRACTION SYSTEM

ICC CODE CORNER 2012 IFC Code & Commentary

GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT

UCL PRINCIPAL CONTRACTOR SITE FIRE SAFETY RISK REVIEW & MITIGATION MEASURES

Life Safety Damper Installation ASHRAE St Louis Chapter Feb. 9,2015. Peter McDonnell, PE, LEED AP BD+C McClure Engineering

SHEVTEC Extended Travel Distance. System for Chettles Yard, Nottingham

Interaction of Water Extinguishing Systems and Smoke and Heat Exhaust Ventilation Systems (SHEVS)

Part 6 Additional class notations Chapter 6 Additional fire protection for passenger vessels

HIGH-RISE RETROFIT ORDINANCES - NO and NO

B. Use UT Austin specifications and equipment schedule format for HVAC equipment where available.

Design Guidelines Fire Safety in New and Refurbished Buildings

Delhi Metro System. Emergency and Fire Safety Measures in. - by Sanjeev Kumar & Kailash Chandra Joshi. Fire Protection & Safety

Building Standards Division. Whisky Maturation Warehouses Storage Buildings (Class 1) Automatic Fire Suppression Systems

M E M O R A N D U M. NFPA Technical Committee on Building Services and Fire Protection Equipment

M E M O R A N D U M. NFPA 5000 A2011 ROP Letter Ballot

DUKE CLINIC SITE-SPECIFIC FIRE PLAN Part II General Statement. Fire Procedures

GAUTENG DEPARTMENT OF INFRUSTRUCTURE DEVELOPMENT

Fire resistance. Appendix E. E.1 Fire resistance. Appendix. (A copy of this Appendix is available on /)

DMRC at a Glance. Registered : May Construction Commenced : Oct Operation Commenced : Dec Operates 213 RKM in 7 lines, 158 Stations

HCD DSA OSHPD 1 2 1/AC AC SS SS/CC

Our Ref: CD/FSSD/12/02/03/01 DID: FAX:

GUIDELINES FOR HIGHRISE BUILDING CONSTRUCTION PROJECTS (MECHANICAL VENTILATION)

MSC Guidelines for General Emergency Alarm & Public Address Systems

Fire protection documentation. CFPA-E Guideline No 13:2015 F

The Singapore Fire safety Engineering Guidelines (SFEG)

Fire Safety Policy SH HS 06. Version: 4. Summary:

Increasing Fire Safety of Cologne Main Station by High Pressure Water Mist

IMO WORK PROGRAMME. Central control stations and safety centres on passenger ships. Submitted by Argentina and ICCL

Fire Safety Management Audit Specification August 2017

Uniclass L7535 EPIC L13. CI/SfB (57) X. secontrols.com. Smoke Ventilation, Natural Ventilation and Window Automation

First Aspen Federal Regulation Set: K LSC 2000 Health Existing

THE LOCAL GOVERNMENT GROUP GUIDE: FIRE SAFETY IN PURPOSE-BUILT BLOCKS OF FLATS

SOCIETY OF FIRE PROTECTION ENGINEERS POSITION STATEMENT P THE ROLE OF THE FIRE PROTECTION ENGINEER IN THE CONSTRUCTION DESIGN PROCESS

Fire safety policy. Contents. This policy was approved by the Trustees on 3 September 2015 and will be reviewed not later than every 3 years.

Task Force on Kai Tak Harbourfront Development

THE SCOTTISH PARLIAMENT PLANNED FIRE EVACUATION EXERCISE: 12 DECEMBER 2008 EXERCISE REPORT

- CONSTRUCTION FIRE SAFETY STANDARDS

A Study into the Standardization of Using Fire Detectors in Rail Vehicles for China

BSI the UK National Standards Body: The Role of Standards

General Principles of Smoke Control

NOTTINGHAM CITY HOMES

A. General: Refer to paragraph entitled "SUBMITTAL" in Section Include the following data:

Policy for Safe Evacuation of Persons with Disabilities

TYPE 1 FIRE RISK ASSESSMENT REVIEW (NO DESTRUCTIVE AUDIT)

FIRE RISK ASSESSMENT

Ventilation for Smoke Control, Fire Control & Life Safety in Tunnels. Dr. Ricky Carvel BRE Centre for Fire Safety Engineering University of Edinburgh

This document is a preview generated by EVS

Fire Enforcement Report

highline SVCS-1 INSTALLATION & USER MANUAL SMOKE VENT CONTROL SYSTEM * enclosure design may vary software version: SVCS1r6 SVCS1r7 SVCS1r10

WHITE PLAINS SMOKE CONTROL CODE PART 1. GENERAL REQUIREMENTS

The Code of Practice for Fire Safety in Buildings 2011 It comprises 7 parts and 1 annex:

Design of Fire safety in Multi Occupancy Residential Accommodation

AVAILABLE TO DOWNLOAD ON THE APOLLO APP. Pocket guide to. Fire Alarm Systems Design BS Standard

Fire Risk Assessment

Tunnel Fire Dynamics and Evacuation Simulations

LYHA Fire Safety Policy

Case Study 1 Underground Car Park

RETOS Y TENDENCIAS DESARROLLO DE INFRAESTRUCTURA EN AUSTRIA. Leonardo Rosas Sánchez Bogotá Agosto 9 de 2018

Hong Kong Institute of Surveyors Pre-qualification Structural Learning. Code of Practice for Fire Safety in Buildings 2011 July 2012

Unit 2 Fire Safety (Zone 1)

IFireSS International Fire Safety Symposium Coimbra, Portugal, 20 th -22 nd April 2015

Nirmal Chandra Sinha. Supposed to complete(dd/ MM/YYYY) Comments after Physical Inspection

Executive Review Panel Report on Arson Incident

International Water Mist Conference, Istanbul October 22-23, 2014 The background and development of the guidelines in IMO Resolution A.

Part 3 BUILDING CODE MYTHS & INTERPRETATIONS

AIR DISTRIBUTION. C. Section Building Automation and Control System Guidelines. D. Section Fire Alarm System & Detection Systems

OFFSHORE SUPPORT VESSELS 2014

Emergency Ventilation System Design - Preliminary Report Shishir Gupta

Technical Information

Guidance Note FIA Application Guidance on BS :2015

ctbuh.org/papers Fire Engineering the Tallest Building in the Historic City of Manchester, UK Title:

FIRE SAFETY POLICY. Executive Management Team. Health, Safety and Fire Steering Group.

PERSONAL EMERGENCY EVACUATION PLANS (PEEP s)

THE REGULATORY REFORM (FIRE SAFETY) ORDER 2005 FIRE RISK ASSESSMENT NO 68 (ENGLISH AND PHILOSOPHY)

National Building Code (NBC) and the subsequent revisions

Mechanical smoke ventilation systems. CI/SfB 37.4 Xy

Advanced Air. Hard Wired Damper Control Panels. Systems 10, 11, & 12. Hard-Wired Systems. Bespoke Systems Available. Value Engineered Solutions

Firefighting operations on multi-tiered vehicle stacking buildings F5-13 GD

incorporating Contractors guide to car park ventilation A no-nonsense guide to the safe ventilation of underground and covered car parks

Underground fires in metro systems failures, accidents and terrorism

Management Standard: Fire Safety

Tunnel Axial Flow Fan

EARLY FIRE DETECTION IN SWISS ROAD TUNNELS WITH MORE THAN FIREGUARD SENSORS

Fire Detection and Fire Fighting Testing and Approval on Railway Vehicles

CLOUD CEILINGS: FIRE DYNAMICS AND CODE CONTEXT

Transcription:

FORMULATION OF FIRE SAFETY REQUIREMENTS FOR NEW RAILWAY INFRASTRUCTURES Ir Law Chi Keung, Peter Hong Kong Fire Services Department, Railway Development Strategy Division, 2/F Tung Lo Wan Fire Station, 111 Victoria Park Road, Causeway Bay, HK Abstract. In the past decades, railway development in Hong Kong has experienced very fast growth. Railway projects become complicated and with plenty of fire engineering design. Fire safety has an important role to play in developing the rail network. Without preceding project references, Hong Kong Fire Services Department (FSD) in collaboration with Railway Corporation and other Government Departments draw up fire safety requirements for railway infrastructures to provide the most appropriate fire safety protection to passengers, operational staff and emergency personnel in the event of a fire. To facilitate stakeholders of the railway industry to adopt a consistent fire safety design towards new railway infrastructures, Guidelines on Formulation of Fire Safety Requirements for New Railway Infrastructures (Guidelines) was first promulgated in January 2013. A new practical guidelines on smoke control systems for new railway infrastructures are being developed for dynamic smoke extraction system, staircase pressurization system and tunnel ventilation system and incorporated into Appendix VII of the existing Guidelines. This paper gives an overview of railway development and regulatory regime for railway fire safety in Hong Kong, as well as highlights some key issues of the new practical guidelines on smoke control systems. Keywords: Fire Safety, Railway Infrastructures, Guidelines, Smoke Control Systems, Regulatory Regime 1. BACKGROUND OF RAILWAY DEVELOPMENT IN HONG KONG Railways provide a reliable, fast and safe services to alleviate the pressure on the road network. With the rapid growth of social and economic development, promotion of safe and efficient rail transport system is the first priority among various transport policies in many metropolitan areas over the world. In the past decades, railway development in Hong Kong has experienced very fast growth. The urban rail network has already covered most of the urban areas in Hong Kong. The existing railway network in Hong Kong has a total rail length of over 220 kilometers. To further enhance the usage of the public transport, various extensions of railway lines are also being planned and constructed. After the full commissioning of the West Island Line (WIL) in March 2015, there are four new railway projects under construction, namely, Kwun Tong Line Extension (KTE), South Island Line (East) (SIL(E)), Guangzhou-Shenzhen-Hong Kong Express Rail Link (XRL) and Shatin to Central Link (SCL). The Government announced the Railway Development Strategy 2014 in September 2014. Having regard to transport demand, cost-effectiveness and the development needs of New Development Areas and other new development projects, the Strategy recommends that seven new railway projects be completed in the planning horizon up to 2031. When all the new railway projects recommended are completed, the total length of the railways will extend from 270 kilometers in 2021 to over 300 kilometers by 2031.

2. REGULATORY REGIME FOR RAILWAY FIRE SAFETY The Railway Development Strategy (RDS) Division of Hong Kong Fire Services Department (FSD) was established in early 2001 subsequent to the implementation of the Railway Development Strategy 2000. Instead of submitting building plans through the Centralized Processing System for ordinary building projects, three committees namely Station and Transport Integration Committee (STIC), Safety and Security Coordinating Committee (SSCC) and Trackside Safety and Security Committee (TSSC) are formed to ensure that railway infrastructures are designed, built and operated to the required safety standards. As one of the core members of STIC, SSCC and TSSC, FSD is responsible for giving advice on fire safety requirements to railway projects. Railway projects become complicated and with plenty of fire engineering design. Fire safety has an important role to play in developing the rail network. The development of railway fire safety design in Hong Kong evolved from the first underground railway project in around 1970s. Without preceding project references and prescriptive requirements under the Codes of Practice for Minimum Fire Service Installations and Equipment and Inspection, Testing and Maintenance of Installations and Equipment (CoP), FSD in collaboration with Railway Corporation and other Government Departments draw up fire safety requirements for railway infrastructures to provide the most appropriate fire safety protection to passengers, operational staff and emergency personnel in the event of a fire. 3. GUIDELINES ON FORMULATION OF FIRE SAFETY REQUIREMENTS FOR NEW RAILWAY INFRASTRUCTURES Railway premises generally include stations, tunnels, depots and ventilation buildings. Owing to the unique and complex design nature of railway stations and its associated premises, performance-based fire engineering designs have been widely adopted in the planning of railway projects. The aim is to provide for an overall level of safety that is equivalent to that which would result if fire safety was achieved through full compliance with the prescriptive provisions of the relevant codes of practice and to demonstrate adequate fire safety provisions and efficient allocation of resources to those higher risk areas. To facilitate stakeholders of the railway industry to adopt a consistent fire safety design towards new railway infrastructures, Guidelines on Formulation of Fire Safety Requirements for New Railway Infrastructures (Guidelines) is developed to provide general guidance on formulation fire safety requirements by incorporating the latest fire safety measures of various railway lines under construction in Hong Kong. 1 st edition of the guidelines was promulgated in January 2013 by introducing the essential fire safety measures of various railway lines under construction in Hong Kong with due regard to past experience and relevant international standards on railway safety. 2 nd edition of the guidelines was then issued in August 2013 which is a bilingual version incorporating supplementary fire safety provisions such as: the requirements of emergency access point (EAP), emergency egress point (EEP) and cross passage (CP) for the trackside, general fire safety requirements for construction site office and engineering site office and special features of the deep railway station. To meet the ever-increasing public expectation on railway safety and align with the world s enhanced fire safety requirements, FSD aims to review current fire safety measures for elevating the fire safety standard of railway development in Hong Kong. Smoke control is one of the important subjects for achieving overall fire safety of railway project. A new practical guidelines on smoke control systems for new railway infrastructures are being developed for dynamic smoke extraction system, staircase pressurization system and tunnel ventilation

system and incorporated into Appendix VII of the existing Guidelines. The new Appendix VII is devised with due consideration of the special nature of railway project to provide invaluable guidance to the designer for their early planning and system design on various smoke control systems. 4. FEATURES OF SMOKE CONTROL SYSTEMS IN RAILWAY PROJECTS Smoke and hot gases are recognized as the major hazard and a threat to life. The production of smoke from a fire is a more immediate hazard than the heat release. A fire environment is likely to create untenable conditions before the fire has reached its peak-heat release rate. The control and essential removal of smoke from the premise is a vital component in any fire safety schemes. The provisions of smoke control system provide smoke free conditions with a sufficient period for the protection of life and property and to reduce fire damage. Smoke control systems, including dynamic smoke extraction system, staircase pressurization system and tunnel ventilation system, are required to maintain a tenable environment and control the smoke spread for facilitating massive evacuation and fire-fighting. 5. DYNAMIC SMOKE EXTRACTION SYSTEM Dynamic smoke extraction system is provided for maintaining a Place of Safe Passage clear of smoke for a minimum of 60 minutes and containing smoke within the reservoir of a Concession Area by means of Cabin Concept. It is necessary to establish conservatively higher design fire as this form the basis of risk assessment and the provision of dynamic smoke extraction system. Annex A of the Appendix VII is devised for dynamic smoke extraction system. Technical requirements and system configuration of dynamic smoke extraction system are elaborated. 5.1. Fire Compartmentation When fan room accommodated more than one smoke extraction system, separate fire rated enclosure shall be provided to each smoke extraction system in order to maintain proper fire compartment of different service spaces. All fans of the dynamic smoke extraction system forming part of a fire rated duct shall be enclosed in the same fire rated enclosure if no dedicated fan room is allocated for single smoke extraction system. The fan room housing smoke extraction system shall contain no other services. Services or ductwork other than smoke extraction system shall not pass through the fan room of smoke extraction system. 5.2. Verification on System Performance The designer of dynamic smoke extraction system shall be a register professional engineer under Cap. 409 in the discipline of building services, fire or mechanical engineering. The designer shall be responsible for all statutory submissions. Each drawing and all calculations shall be verified and certified by the designer. To further verify the system performance of dynamic smoke extraction system, hot smoke test shall be conducted in accordance with the requirements as stated in FSD Circular Letter 2/2002.

5.3. Smoke Discharge Arrangement Dedicated vent shaft shall be designed for smoke extraction purpose and it shall contain no other services. In order to prevent re-circulation of smoke into the system through the vent shaft, the smoke discharge outlet and fresh air intake louver shall be separated by not less than 5m in any direction from all air inlets or other building openings. The outlets shall not discharge into any means of escape nor a fireman s staircase. No discharges shall be at a height above the surrounding horizontal surface of less than 3m to the bottom of the outlet and where below 6m shall not discharge downwards. 5.4. Fire Protection of Concession Areas The Cabin Concept is applied to concession areas of the station because these are identified as areas of higher fire load and risk as compared to the general station areas. For smoke extraction system of concession area, the sprinkler-controlled fire shall be adopted for calculating the smoke extraction rate. The smoke reservoir can be arranged to lie above a false ceiling, with the smoke barriers being concealed within the ceiling void. In such cases the ceiling must be perforated to permit smoke to flow freely into the reservoir above. The Cabin Concept provides a high level of fire protection by using a combination of smoke detection, sprinklers and a designated smoke extraction system. A sketch of the Cabin Concept is shown in Figure 1. FIGURE 1. Sketch of the Cabin Concept 5.5. System Operation For parallel arrangement of smoke extraction fans and make up air fans, motorized fire and smoke dampers shall be provided for both suction side and discharge side to avoid system short circuit and smoke re-circulation. The proposed arrangement is shown in Figure 2.

FIGURE 2. Proposed parallel arrangement of smoke extraction fans / mark-up air fans. The smoke extraction system and associated ductwork/ equipment shall be operated at 250 o C for not less than one hour. The actual duration shall be justified by technical evaluation to suit the operating environment and conditions. In case the smoke temperature is higher than 250 o C, additional smoke extraction rate shall be provided to allow sufficient make-up air inside the smoke zone to be entrained and ensure the airstream temperature inside the system is less than 250 o C. Otherwise, fire rated protection with higher fire rating shall be applied to the smoke extraction system and associated ductwork/ equipment to withstand the smoke temperature and maintain normal operation of the smoke control system. The designer shall substantiate the smoke extraction rate and smoke temperature based on the design fire size and clear smoke height. For fan operation, extraction fans and make-up air fans shall be electrically interlocked such that the failure of the extraction fan shall automatically shut down the corresponding make-up air fan. Moreover, the failure of make-up air fan shall not affect the operation of the extraction fan. For system actuation, smoke extraction system shall be actuated by a smoke detection system, at the same time, the operation of a sprinkler flow switch and/ or manual override facility shall be considered as last resort when the smoke detection fails. Once started, smoke extraction fans and make up air fan shall run continuously until stopped manually. 5.6. System Reliability In order to improve the system reliability, two dedicated electrical supplies shall be routed separately into the plant room and then connected into the switchboard for smoke extraction system. The switchboard serving the fan/ motor/ drive sets of smoke extraction system shall be located in plant room next to the fan room of smoke extraction system. The plant room shall not contain other equipment. Switchboard for smoke extraction system shall not be grouped with other services or installations. The proposed power distribution arrangement of dynamic smoke extraction system is shown in Figure 3.

FIGURE 3. Proposed power distribution arrangement of dynamic smoke extraction system For single smoke extraction system, smoke extraction fan shall be installed in duplicate with automatic changeover facilities. 6. STAIRCASE PRESSURIZATION SYSTEM Pressurization is commonly applied to smoke control systems in which a supply of fresh air to a space within a building is used to maintain that space at a slightly higher pressure than the rest of the building. For railway project, staircase pressurization system is required for fireman s staircases and corresponding staircase lobbies and fireman s lift lobbies. Annex B of the Appendix VII is devised for staircase pressurization system. Technical requirements and system configuration of staircase pressurization system are elaborated. 6.1. Fire Compartmentation In order to maintain proper fire compartment, dedicated pressurization fans shall be designed for the staircase and protected lobbies. The supply air duct serving the pressurized staircase has to penetrate the staircase enclosure, the portion of the duct where it traverses outside the staircase shall be enclosed by the same fire rating as the pressurized space or fire compartment passed, whichever is greater. Other non-essential services shall not pass through / not be installed at the protected lobby / staircase. Figure 4 illustrates proper

arrangement of staircase pressurization system. FIGURE 4. Arrangement of staircase pressurization system 6.2. Verification on System Performance The designer of staircase pressurization system shall be a register professional engineer under Cap. 409 in the discipline of building services, fire or mechanical engineering. The provision of air release is crucial for staircase pressurization system and shall be provided to the accommodation and to comply with the requirements as stated in BS5588: Part 4 and FSD Circular Letter No. 2/2006. The air release fan, ductwork and other associated equipment shall be suitable for continuous operation for the appropriate period of time and temperature as specified in the BS5588: Part 4 and FSD Circular Letter No. 2/2006. The designer shall be responsible for all submissions. Each drawing and all calculations shall be verified and certified by the designer. 6.3. Smoke Discharge Arrangement The smoke discharge shall be remote from and preferably down-wind of the intake of fresh air in order to prevent re-circulation of smoke. In addition, the discharge end / louvre of air release shall not be mixed with other louvre or system. Air release discharge outlets for staircase pressurization system shall be separated by not less than 5m in any direction from all air inlets or other openings into any building. The outlets shall not discharge into any means of escape nor a free air fireman s staircase. No discharges shall be at a height above the surrounding horizontal surface of less than 3m to the bottom of the outlet and where

below 6m shall not discharge downwards. 6.4. System Configuration Dedicated plant room and vent shaft shall be allocated for staircase pressurization system. Service ductwork not serving staircase pressurization system shall not pass through the plant room. All fans of the staircase pressurization system for serving different fire compartments shall be installed in separate plant rooms with appropriate fire rated enclosure. Fans form part of a fire rated duct shall be enclosed in the same fire rated enclosure if no dedicated plant room is allocated for the staircase pressurization system. The provision of air release and pressure relief shall be vented by dedicated vent shaft. Other services or ductworks shall not be connected to the vent shaft for any other purpose. 6.5. System Operation For parallel arrangement of staircase pressurization fans, motorized fire and smoke dampers shall be provided at both suction side and discharge side to avoid system short circuit. When fire occurred within a pressurized staircase and detected by smoke detectors, the activation of the associated pressurization system shall be disabled. The staircase pressurization systems of other staircases shall be activated. In the event of a fire excluding that within the pressurized staircase, the fire alarm signal shall activate the pressurization system(s). The pressurization system(s) shall be kept in operation even though smoke spilling into the pressurized staircase and activated the smoke detector. Once started, staircase pressurization fan(s) shall run continuously until stopped manually. 6.6. System Reliability To enhance the system reliability, duplicate fans instead of dual motors shall be adopted. Dedicated switchboard shall be designed for the staircase pressurization system and shall not be grouped with other systems. The switchboard shall be located in the plant room next to the fan room for the staircase pressurization system. The plant room shall not contain other equipment. If not, the switchboard shall be provided with proper fire rated enclosure. The plant room for the switchboard shall be provided with heat detector. 7. TUNNEL VENTILATION SYSTEM In the event of train fire or tunnel fire in any sections of the tunnel, the tunnel ventilation system will be activated to draw in fresh air from one end of the affected tunnel and expel smoke at the other end via vent shaft. In order to prevent back layering of smoke in the direction of passenger evacuation, the designed tunnel air flow velocity in the incident tunnel shall be equal to or greater than the critical velocity at the fire site. Tunnel ventilation system is provided inside tunnel or enclosed trackway to maintain a smoke free path for emergency evacuation and fireman s access in case of fire. Annex C of the Appendix VII is devised for tunnel ventilation system. Technical requirements and system configuration of tunnel ventilation system are elaborated. Figure 5 shows the typical plant room arrangement of the fan room tunnel ventilation system.

FIGURE 5. Typical plant room arrangement of the fan room tunnel ventilation system 7.1. Fire Compartmentation Up-track and down-track of the tunnel shall be considered as different fire compartments. No other services or equipment shall be installed or located inside the tunnel. Essential equipment servicing the tunnel and supporting daily train operation, such equipment shall be installed properly and physically separated from the tunnel. When plant room houses more than one tunnel ventilation system to serve fire mode operation, separate fire rated enclosure shall be provided to each tunnel ventilation system in order to maintain fire compartment between different protected zones. Fans form part of a fire rated duct shall be enclosed in the same fire rated enclosure if no dedicated plant room is allocated for single tunnel ventilation system, they shall be enclosed in the same fire rated enclosure. 7.2. Verification on System Performance The designer of tunnel ventilation system shall be a register professional engineer under Cap. 409 in the discipline of building services, fire or mechanical engineering. The designer shall be responsible for all submissions. Each drawing and all calculations shall be verified and certified by the designer. The tunnel ventilation system shall generate sufficient longitudinal air velocity to prevent back-layering of smoke due to tunnel fire. For the calculation of critical velocity, total fire heat release rate (fire size) shall be adopted instead of convective heat release rate. 7.3. Smoke Discharge Arrangement In order to prevent re-circulation of smoke into the system via vent shaft, the smoke discharge outlets shall be separated by not less than 5m in any direction from all air inlets or other openings into any building. The outlets shall not discharge into any means of escape nor a free air fireman s staircase. No discharges shall be at a height above the surrounding horizontal surface of less than 3m to the bottom of the outlet and where below 6m shall not discharge downwards.

7.4. System Configuration The tunnel ventilation system shall be designed to prevent the hot smoke flowing from the incident tunnel to non-incident tunnel via the cross-over area and cross-wall / cross-passage door. Cross-wall or cross-passage doors shall be of fire rated and self-closing type. If there are a dedicated Means of Access (MoA) corridor and MoA / EAP staircase near the overrun tunnel / main tunnel, provisions such as smoke lobby shall be provided to prevent smoke spilling into the MoA corridor and MoA / EAP staircase. Tunnel ventilation control panel shall be provided for tunnel ventilation systems and located adjacent to main fire control panel at Station Control Room (SCR) / Fire Control Room (FCR). Plant room housing the switchboard for tunnel ventilation system shall be provided with heat detector and contain no other services. 7.5. System Operation The tunnel ventilation system with associated ductwork and equipment shall be operated at 250 C for not less than two hours. The actual durat ion shall be justified by technical evaluation to suit the operating environment and conditions. In case the smoke temperature is higher than 250 C, additional smoke extraction r ate shall be provided to allow sufficient make-up air inside the smoke zone to be entrained and ensure the airstream temperature inside the system is less than 250 C. Otherwise, fi re rated protection with higher fire rating shall be applied to the tunnel ventilation system with associated ductwork and equipment to withstand the smoke temperature and maintain normal operation of the tunnel ventilation system. The designer shall substantiate the smoke extraction rate and smoke temperature based on the design fire size and critical velocity. For parallel arrangement of tunnel ventilation fans, motorized fire and smoke dampers shall be provided at both suction side and discharge side to avoid system short circuit. When tunnel ventilation system start under fire mode, tunnel ventilation fans shall run continuously until stopped manually. The tunnel ventilation system shall not be controlled or under the influence of any building management or automation system. Overall operating status of related mode of the tunnel ventilation system should be individually monitored by the affected stations. 7.6. System Reliability Switchboard for tunnel ventilation system shall not be grouped with other services or installations. The switchboard serves the fan/motor/drive sets of tunnel ventilation system shall be located in plant room next to fan room of tunnel ventilation fan. The plant room shall not contain other equipment. Two dedicated electrical supplies shall be routed separately into the plant room and then connected into the switchboard for tunnel ventilation system. 8. CONCLUSION To meet the higher public expectation on fire safety of railway services and align with the world s enhanced fire safety requirements, FSD has been taking parallel actions positively in offering persistent support to new railway projects and promulgating a guidelines on fire safety requirements for new railway infrastructures. A rational system for fire engineering design of a railway premise requires the fire safety strategy to be identified explicitly. In order to achieve the agreed fire safety strategy, suitable fire safety protections are required to be developed for railway premise. Achieving the proper level of protection is not possible with just one system or single procedure. It is the synergistic effect of all fire safety systems working together that keep facilities safe. Smoke

control systems play a pivotal role in maintaining overall fire safety level of railway premises. With the collaboration with Railway Corporation, a new practical guidelines on smoke control systems for new railway infrastructures are being developed for dynamic smoke extraction system, staircase pressurization system and tunnel ventilation system and incorporated into Appendix VII of the existing Guidelines. Key issues of the new practical guidelines on smoke control systems are elaborated. FSD will take proactive approach in elevating fire safety standards of railway development in Hong Kong. ACKNOWLEDGMENTS The authors would like to acknowledge the support provided by (1) Assistant Director (Fire Safety) of Hong Kong Fire Services Department Dr Shane S. H. Lo, (2) Project Director of MTR Corporation Ir Dr Philco N. K. Wong and (3) Project Manager of MTR Corporation Ir Dr Dono K. W. Tong for carrying out studies and research work reported in this paper. REFERENCES [1] Fire Services Department, Codes of Practice for Minimum Fire Service Installations and Equipment and Inspection, Testing and Maintenance of Installations and Equipment (CoP), April 2012. [2] Fire Services Department, Guidelines on Formulation of Fire Safety Requirements for New Railway Infrastructures 2 nd issue, September 2013. [3] Buildings Department, Codes of Practice for Fire Safety in Buildings 2011, April 2012. [4] British Standards Institution, BS 5588-4:1998 Fire precautions in the design, construction and use of buildings Part 4: Code of practice for smoke control using pressure differentials, March 1998. [5] The Chartered Institution of Building Services Engineers (CIBSE), CIBSE Guide E: Fire safety engineering, third edition, May 2010.