HVAC Myths and Realities Trane Engineers Newsletter Live Series

Similar documents
Trane Engineers Newsletter Live

Fan Laws. Keith Miller. Samuel Tepp Associates. Paul Cenci, P. E.-Principal Brian England-Principal. Samuel Tepp Associates 1/6/10

EarthWise System Seminar

Introduction to Fans. The Basics of Fan Principles and Terminology

Fan Selection. and Energy Savings

System Components with ` Emphasis on Packaged Rooftop Application and Installation. Jerry Cohen President Jacco & Assoc.

AC SYSTEM CONFIGURATION- CENTRAL CHILLER PLANT

Designing Energy Efficient Outdoor Air Systems

Agenda and Objectives

Technical Development Program

INTRODUCTION TO: ASHRAE STANDARD 90.1, HVAC System Requirements for Reducing Energy Consumption in Commercial Buildings

Chiller Plant Design. Application Guide AG McQuay International. Elevation Difference. Column Height When Pump Is Off

Introduction to HVAC. American Standard Inc Air Conditioning Clinic TRG-TRC018-EN

Adding More Fan Power Can Be a Good Thing

Summary Comparison of Simulation Program Features

APPLICATION GUIDE BEAMS

UNIVERSITY OF MISSOURI Heating Ventilating and Air-Conditioning (HVAC) 2016 Q1

Energy-Efficient Makeup Air Units BY HUGH CROWTHER, P.ENG., MEMBER ASHRAE

Method to test HVAC equipment at part load conditions

Agenda and Objectives

Pharmaceutical Facility Design

ASHRAE WILL GIVE YOU THE WORLD. This ASHRAE Distinguished Lecturer is brought to you by the Society Chapter Technology Transfer Committee

Technical Development Program

HVAC Mandatory Provisions Part II, Page 1

RT-OA TM Rooftop Outdoor-Air (DOAS)

Trane CDQ Desiccant Dehumidification

Appendices. Included in this section are

INTRODUCTION HVAC BASICS AND HVAC SYSTEM EFFICIENCY IMPROVEMENT SECTION O 4/19/2012

To Keep Docs Cool, Dry and Happy

HVAC Systems What the Rater Needs to Know in the Field CALCS-PLUS

AHRI 920 & ASHRAE 90.1

Redesign of Bennett Hall HVAC System

Presented By: John Dolan, P.E.

H3/V3 Series Horizontal and Vertical Indoor Air Handling Units. Engineering Catalog

RT-OA TM Rooftop Outdoor-Air (DOAS)

2009 IECC Commercial Mechanical Requirements

Energy Recovery with Cooling and Heating Model ERCH

Fans: Features and Analysis

LGH/LCH WARNING. CAUTION Danger of sharp metallic edges. Can cause injury. Take care when servicing unit to avoid accidental contact with sharp edges.

Energy Recovery with Cooling and Heating

Best Practices for Applied Rooftop ` Systems, Applications and. Jerry Cohen President Jacco & Assoc. Installation

Trane Engineers Newsletter Live

Air System Sizing Summary for Lobby System Project Name: Existing Lobby 04/04/2005 Prepared by: psuae

Dehumidifying with Dedicated Outdoor Air

UNIVERSITY OF MISSOURI Central Station Air-Handling Units March

State of the art building simulation software... Frenger Radiant chilled beam performance at 1 Shelly St - Sydney

Mechanical Systems Design

CTI Sponsored Educational Program

CARRIER edesign SUITE NEWS. Interpreting High (Low) Peak Design Airflow Sizing Results for HVAC. Equipment Selection.

Session: HVAC 101 HVAC 101. Steve Sain Sain Engineering Associates, Inc. August 9, Rhode Island Convention Center Providence, Rhode Island

ASHRAE Region VI CRC Track III: Session 3 Ventilation Energy Recovery. Steven T. Taylor, PE Principal Taylor Engineering

PINNACLE SERIES DEDICATED OUTDOOR AIR SYSTEM ENERGY EFFICIENT DEHUMIDIFICATION

Partial Load Performance Of Refrigeration System

BRINE CIRCULATED ICE THERMAL STORAGE SYSTEM DESIGN - CASE ILLUSTRATION - Partial Ice Storage for Air Conditioning Application

Best Practices for Condensing Boilers

AHRI 920 Performance Rating and Comparisons of DX-DOAS Unit Efficiency

D-PAC. Digital Precise Air Control System. Functionality Factory Testing Ease of Installation Ease of Maintenance Energy Efficiency

Ducted Propeller. Airflow Volume

Andrea Borowski The Pennsylvania State University University Park, PA November 11, 2002 Consultant: Dr. Bahnfleth Technical Assignment M-3

Design Considerations For Dedicated OA Systems BY HUGH CROWTHER, P.ENG, MEMBER ASHRAE; YI TENG MA, ASSOCIATE MEMBER ASHRAE

Description of All Alternatives Considered-

Air Conditioning Clinic

CHAPTER 4. HVAC DELIVERY SYSTEMS

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 11/11/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

Civil Engineering Building

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

FAST AND ROBUST BUILDING SIMULATION SOFTWARE. Chilled Beam Performance: 1 Shelly Street, Sydney

terminal units only provide sensible cooling, a separate dehumidification system is usually needed.

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

Math. The latent heat of fusion for water is 144 BTU s Per Lb. The latent heat of vaporization for water is 970 Btu s per Lb.

Technical Development Program. COMMERCIAL HVAC PACKAGED EQUIPMENT Split Systems PRESENTED BY: Ray Chow Sigler

Building Systems: HVAC

Air System Sizing Summary for AHU/CU-1 Project Name: Wilton Manors Fire Station#16 06/26/2016 Prepared by: L.N.I.

Best Practices for Applied Rooftop ` Systems - Application and. Jerry Cohen President Jacco & Assoc. Installation

Selecting the Correct Fan

ASHRAE Standard 90.1 Energy Requirements Wrap-Around Heat Pipes

SYNOPSIS. Part-Load Control Strategies for Packaged Rooftop Units. In this issue... Bin Hour Profile Charlotte, NC

Update Dedicated Heat Recovery Chiller Technology. Don Frye. Gulf South

Service Step by Step Trouble-Shooting Check-List

A/C Cooling Load calculation and measurement

City of Duluth Festival Center 04/25

SECTION SEQUENCE OF OPERATIONS FOR HVAC CONTROLS

Performance Rating of Computer and Data Processing Room Air Conditioners

Mechanical Engineering Laboratory

HAP e-help. Modeling Induction Beams in HAP v4.8 QB TIP 001

Standards and Guidelines. Presented by: Aric Murray December 12, 2014

ENGINEERING BULLETIN. Overview of Chilled Beam Technology. Purpose. Summary. Theory

ASHRAE S DOAS WEBCAST: A DEEPER EXAMINATION OF THE ROLE OF HEAT PIPES

Technical Assignment 3 11/15/04. Executive Summary

THE ULTIMATE ROOFTOP SOLUTION

MECHANICAL INFRASTRUCTURE ASSESSMENT FOR VICTOR VALLEY COLLEGE

Multi-Path RTU-TYPE 2

VertiCool Aurora Engineering Guide

Agenda and Objectives

C13-Series Engineering Guide

100 TON AIR-COOLED SCROLL PACKAGED. Call us today! (800) SPECIFICATIONS GENERAL DIMENSIONS ELECTRICAL DATA ADDITIONAL INFORMATION

A. Base Bid: 1. Heating Contractor provide: a. Control sequences for HVAC systems, subsystems, and equipment.

Commercial Buildings Chilled water systems efficiency By Jens Nørgaard, Senior Application Manager, Grundfos, Denmark

2. CURRICULUM. Sl. No.

R7DA Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. 6 and 7 ½ Ton DOAS Packaged Gas/Electric Units

Transcription:

HVAC Myths and Realities Trane Engineers Newsletter Live Series

AGENDA Low delta T is unavoidable 55 F supply air temperature is adequate for today s loads ASHRAE Standard 15 has to be updated before new refrigerants can be used Single-zone VAV units do not need hot gas reheat VFDs and affinity laws Small changes in pressure can have a huge impact on airflow for flat fan curves and may cause the system to surge New chilled-water systems need to be variable-primary flow System airflow issues are the fans fault Claims to energy savings

Myth Number 1 Low delta T is unavoidable.

Transport Energy is low delta T unavoidable? Tons= ( T GPM)/24 Solving for gpm GPM= (Tons 24) / T Pumping power Frictional Head Flow 2 Water HP (bhp)= (GPM head (ft))/3960 Water HP Flow 3 Delta T 3

Coil Delta T is low delta T unavoidable? AHRI Certified Coil Air Flow (VAV) unloading v ASHRAE 90.1-2016 6.5.4.7 Chilled-Water Coil Selection Chilled-water cooling coils shall be selected to provide a 15 F or higher temperature difference between leaving and entering water temperatures and a minimum of 57 F leaving water temperature at design conditions. 2015 Engineer s Newsletter Live Coil Selection and Optimization

Reason 1: 3-Way Control Valves undesirable mixing in variable flow systems 50% Coil Load 1. 3-way control valves Eliminate them! Coil LVG 59 F Coil Delta T = 17 F System Delta T = 8.5 F CHWR 50.5 F Bypass 42 F CHWS 42 F CHWR = [(42 x 50) + (59 x 50)] / 100 = 50.5

Reason 2: Supply Air Setpoint Depression overdriving coil capacity 1. 3-way control valves 2. Control setpoint depression Avoid, limit and return 55 LAT = 16 DT 52 LAT = 11 DT 50 LAT = 8.5 DT CHW Delta T 25 20 15 10 5 0 50 52 54 56 58 60 leaving air setpoint

Reason 3: Warmer Chilled Water Supply reduced heat transfer driving force LMTD 1. 3-way control valves 2. LAT setpoint depression 3. Warmer chilled water Chilled water reset only at part load CHW Delta T 25 20 15 10 42 CHWS = 16 DT 47 CHWS = 7.5 DT 50 CHWS = 5 DT 5 0 35 40 45 50 entering CHW temperature

Reason 4: Deficient Control Valves poor flow control at full and part loads 1. 3-way control valves 2. LAT setpoint depression 3. Warmer chilled water 4. Deficient control valves Control Valve Issues 1. Improperly Selected / Oversized 2. Worn-out 3. Unstable control 4. $29.95 (cheap) 5. 3-way valves

Reason 4: Deficient Control Valves poor flow control 1. 3-way control valves 2. LAT setpoint depression 3. Warmer chilled water 4. Deficient control valves Specify quality valves specific to use 8 th floor control point 20 ft pd 2 nd floor pressure 90 ft pd

Reason 4: Deficient Control Valves poor flow control 1. 3-way control valves 2. LAT setpoint depression 3. Warmer chilled water 4. Deficient control valves Pressure independent valves? (PIV) 1. Mechanical 2. Electronic Pressure independent valves Not required May be beneficial

Reason 5: Tertiary Pumping undesirable mixing is hard to prevent 1. 3-way control valves 2. LAT setpoint depression 3. Warmer chilled water 4. Deficient control valves 5. Tertiary pumping / bridge tender circuits Don t mix to the return simply pressure boost CHWS Bypass Valve DP CHWR

Design Delta T and Greater is Achievable 1. AHRI certified coil selections 2. AHU set point limits 3. Chilled water reset only at part load 4. Properly selected / high quality valves 5. Pressure boosting no tertiary mixing

Myth Number 1 Low Delta T is unavoidable.

Myth Number 2 55 F supply air temperature is adequate for today s loads.

full load OA 96 F DB, 76 F WB RA 74 F DB, 52% RH MA 80 F DB SA 30 55 F DB (1,500 cfm) 40 50 SA 60 70 RA 80 MA full load OA 180 160 140 120 100 80 60 40 20 humidity ratio, grains/lb of dry air 30 40 50 60 70 80 90 100 dry-bulb temperature, F 110

full load OA 96 F DB, 76 F WB RA 74 F DB, 57% RH MA 86 F DB SA 30 55 F DB (800 cfm) 40 50 SA 60 70 RA' RA 80 MA full load OA 180 160 140 120 100 80 60 40 20 humidity ratio, grains/lb of dry air 30 40 50 60 70 80 90 100 dry-bulb temperature, F 110

full load OA 96 F DB, 76 F WB RA 74 F DB, 52% RH MA 89 F DB SA 30 51 F DB (630 cfm) 40 50 SA' SA 60 70 RA 80 MA full load OA 180 160 140 120 100 80 60 40 20 humidity ratio, grains/lb of dry air 30 40 50 60 70 80 90 100 dry-bulb temperature, F 110

Improving Dehumidification Cool and reheat Face-and-bypass dampers Reduce airflow Dual paths Desiccants

full load OA 96 F DB, 76 F WB RA 74 F DB, 52% RH MA 86 F DB SA 30 52 (55) F DB (800 cfm) 40 50 60 SA CA SA' 70 RA 80 MA full load OA 180 160 140 120 100 80 60 40 20 humidity ratio, grains/lb of dry air 30 40 50 60 70 80 90 100 dry-bulb temperature, F 110

Type III Series Desiccant (CDQ) C 50 F DB 97% RH 52 gr/lb CA 55 F DB 64% RH 42 gr/lb (43 F DP) SA 8-12 rph MA' MA 75 F DB 67% RH 87 gr/lb (64 F DP) 80 F DB 50% RH 77 gr/lb (60 F DP) (10,000 cfm)

full load OA 96 F DB, 76 F WB RA 74 F DB, 52% RH MA 81 F DB SA 30 63 F DB (1,350 cfm) 40 50 SA 70 60 CA SA' 80 MA' MA RA full load OA 180 160 140 120 100 80 60 40 20 humidity ratio, grains/lb of dry air 30 40 50 60 70 80 90 100 dry-bulb temperature, F 110

Myth Number 2 55 F supply air temperature is adequate for today s loads.

Myth Number 3 Single-zone VAV units do not need hot gas reheat.

Classroom Example basic CV system peak DB outdoor condition sensible load latent load space SHR supply airflow outdoor airflow space temp supply air temp 96 F DB, 76 F WB 29,750 Btu/h 5,250 Btu/h 0.85 1,500 cfm 450 cfm 74 F 55.7 F 1,500 cfm = Jacksonville, Florida 29,750 Btu/h 1.085 (74 F T supply )

Example: K-12 Classroom OA RA MA SA CV full load 96 F DBT 68 F DPT (450 cfm) 74 F DBT 52% RH 81 F DBT 55 F DBT (1500 cfm) (4.8 tons) CV part load 84 F DBT 76 F DPT (450 cfm) 74 F DBT 67% RH 77 F DBT 63 F DBT (1500 cfm) 30 40 50 SA 60 SA 70 RA 80 RA MA MA peak DPT OA Jacksonville, FL 180 peak DBT OA 160 140 120 100 80 60 40 20 humidity ratio, grains/lb of dry air 30 40 50 60 70 80 90 100 dry-bulb temperature, F 110

Example: K-12 Classroom OA RA MA SA CV full load 96 F DBT 68 F DPT (450 cfm) 74 F DBT 52% RH 81 F DBT 55 F DBT (1500 cfm) (4.8 tons) CV part load 84 F DBT 76 F DPT (450 cfm) 74 F DBT 67% RH 77 F DBT 63 F DBT (1500 cfm) (3.7 tons) 30 40 50 SA 60 SA 70 80 MA RA RA MA peak DPT OA Jacksonville, FL 180 peak DBT OA 160 140 120 100 80 60 40 20 humidity ratio, grains/lb of dry air 30 40 50 60 70 80 90 100 dry-bulb temperature, F 110

Example: K-12 Classroom peak DPT day zone humidity, %RH 67% cooling load, tons 3.7 fan airflow, cfm 1500 mild/rainy day constant-speed fan zone humidity, %RH 73% cooling load, tons 1.6 fan airflow, cfm 1500

Hot Gas Reheat packaged DX units MA evaporator CA reheat coil condenser reheat valve

Example: K-12 Classroom constant-speed fan constant-speed fan with hot gas reheat peak DPT day zone humidity, %RH 67% cooling load, tons 3.7 fan airflow, cfm 1500 mild/rainy day zone humidity, %RH 73% cooling load, tons 1.6 fan airflow, cfm 1500 compressor energy 60% 2.4 1500 55% 3.7 1500 Space humidity is maintained

Improved Part-Load Dehumidification EA RA 1050 cfm zone 74 F OA 450 cfm 96 F DBT 68 F DPT 1500 cfm 55 F SA

Example: K-12 Classroom OA RA MA SA CV full load 96 F DBT 68 F DPT (450 cfm) 74 F DBT 52% RH 81 F DBT 55 F DBT (1500 cfm) (4.8 tons) CV part load 84 F DBT 76 F DPT (450 cfm) 74 F DBT 67% RH 77 F DBT 63 F DBT (1500 cfm) (3.7 tons) 30 40 SZVAV part load 84 F DBT 76 F DPT (450 cfm) 74 F DBT 57% RH 79 F DBT 55 F DBT (900 cfm) (4.0 tons) 50 SA 60 SA 70 80 MA RA RA MA peak DPT OA Jacksonville, FL 180 160 140 120 100 80 60 40 20 humidity ratio, grains/lb of dry air 30 40 50 60 70 80 90 100 dry-bulb temperature, F 110

Example: K-12 Classroom peak DPT day constant-speed fan zone humidity, %RH 67% cooling load, tons 3.7 fan airflow, cfm 1500 constant-speed fan with hot gas reheat variable-speed fan 57% 4.0 900 mild/rainy day zone humidity, %RH 73% cooling load, tons 1.6 fan airflow, cfm 1500 60% 2.4 1500 55% 3.7 1500 60% 1.9 750

SZVAV Dehumidification Performance VAV may be enough Consider hot gas reheat for: Even lower space humidity levels Widely varying loads Oversized units

Example: K-12 Classroom OA RA MA SA SZVAV full load 96 F DBT 68 F DPT (450 cfm) 74 F DBT 52% RH 81 F DBT 55 F DBT (1500 cfm) SZVAV Oversized 96 F DBT 68 F DPT (450 cfm) 74 F DBT 56% RH 80 F DBT 58 F DBT (1750 cfm) 30 40 SZVAV part load 84 F DBT 76 F DPT (450 cfm) 74 F DBT 59% RH 78 F DBT 58 F DBT (1050 cfm) 50 SA SA 60 SA 70 RA 80 MA RA RA MA MA peak DPT OA Jacksonville, FL 180 peak DBT OA 160 140 120 100 80 60 40 20 humidity ratio, grains/lb of dry air 30 40 50 60 70 80 90 100 dry-bulb temperature, F 110

Avoid Oversizing! Oversizing supply airflow leads to: Warmer supply-air temperature Less dehumidification (in non-arid climates) Elevated indoor humidity Examples include: Auditoriums Gymnasiums Church sanctuaries Etc.

Humidity Control with SZVAV Avoid oversizing equipment Verify proper fan speed and discharge air temperature setpoints Equip the unit with hot gas reheat, if necessary

Myth Number 4 Single-zone VAV units do not need hot gas reheat

Myth Number 4 Slap on a VFD and you are entitled to get full advantage of the affinity laws. = Speed 3 Savings

The Affinity Laws dynamic compression fans/impellers Background: 1. Fans, pump impellers and other dynamic compression devices. 2. Application limited to systems with only frictional flow losses. 3. Ignoring changes in device efficiency at different conditions. If and only if the above are true then: 1. Pressure varies proportionally to the square of the impeller speed. 2. Flow produced varies proportionally to the impeller speed. 3. Power (BHP) required varies in a cubic proportion to the impeller speed.

The Affinity Laws Graphically dynamic compression fans/impellers Device performance in frictional pressure loss systems Pressure is proportional to the speed squared Flow is proportional to the speed Power is proportional to the speed cubed flow/pressure/power (%) 100 75 50 25 pressure flow power 0 0 25 50 75 100 speed (%)

Systems and the Affinity Laws compliant systems Systems that comply Cooling towers Single zone VAV air systems.

Cooling Tower Fans affinity laws 100% flow 100% pressure 100% power Cooling Tower OFF 15 kw Cooling Tower 60 HZ speed/pressure/power (%) 100 75 50 25 speed pressure power 85 F 100 F P 0 0 25 50 75 100 flow (%)

Cooling Tower Fans affinity laws For Free Discharge Fans W2 = W1 x (S2 / S1) 3 W2 = 15 kw x (30 / 60) 3 W2 = 1.88 kw Cooling Tower OFF 1.88 kw Cooling Tower 60 HZ speed/pressure/power (%) 100 75 50 25 speed pressure power 85 F 92.5 F P 0 0 25 50 75 100 flow (%)

Systems and the Affinity Laws non-compliant systems Systems that don t comply: Chilled water Hot water MultiZone VAV Condenser water HVAC cooling units HVAC heating units (HP) Non-compliant characteristics: Control valves and setpoints Fixed lift Refrigeration lift / heat exchangers / minimum flows

VPF Chilled Water Systems systems and the affinity laws Non-compliance factors Pump minimum speed limits speed/pressure/power (%) 100 75 50 25 speed pressure power 0 0 25 50 75 100 flow (%)

Pump Minimum Speed Impact VPF chilled-water systems Non-compliance factors Pump minimum speed limits 33% minimum speed speed/pressure/power (%) 100 75 50 25 pump min speed pressure power 0 0 25 50 75 100 flow (%)

Differential Pressure Control Impact VPF chilled-water systems Non-compliance factors Pump minimum speed limits A fixed pressure control setpoint 20 ft. setpoint 80 ft. frictional loss speed/pressure/power (%) 100 75 50 25 DP pressure setpoint speed power 0 0 25 50 75 100 flow (%)

Heat Exchanger Minimum Flow Impact VPF chilled-water systems Non-compliance factors Pump minimum speed limits A fixed pressure control setpoint Heat exchanger minimum flow limits 50% minimum flow speed/pressure/power (%) 100 75 50 25 HX min flow pressure power 0 0 25 50 75 100 flow (%)

Combined Limit Power Impact VPF chilled-water systems Non-compliance factors Pump minimum speed limits A fixed pressure control setpoint Heat exchanger minimum flow limits speed/pressure/power (%) 100 75 50 25 Pump min speed HX min flow DP setpoint 0 0 25 50 75 100 flow (%) affinity power

High HX Minimum Flow Impact VPF chilled-water systems Non-compliance factors Pump minimum speed limits A fixed pressure control setpoint Heat exchanger minimum flow limit 70% speed/pressure/power (%) 100 75 50 25 HX min flow pressure power 0 0 25 50 75 100 flow (%)

Myth Number 4 Slap on a VFD and you are entitled to get full advantage of the affinity laws. Systems that comply Cooling towers Single zone VAV HVAC systems. Systems that don t comply Chilled water Hot water Condenser water Multi-zone VAV HVAC cooling units HVAC heating units (HP)

Myth Number 5 Small changes in pressure can have a huge impact on airflow for flat fan curves and may cause a fan system to surge.

Small Changes in Pressure Static pressure inches w.g. 6 5 4 3 2 1 Forward Curved (FC) Fan Do not select region 1100 RPM 900 RPM 700 RPM 500 RPM 50% WOCFM 60% 70% 80% 90% peak pressure Far from peak some may select here 0 0 4 8 12 16 20 CFM in 1000s

Fan Performance Test 7 blocked off 14 total static pressure (in H 2 O) 6 5 4 3 2 1 restricted less restricted wide open 12 10 8 6 4 2 Brake horsepower (bhp) 0 0 2500 5000 7500 10000 12500 15000 17500 20000 22500 airflow (cfm) 0

Pressure = f(airflow) 6 Forward Curved (FC) Fan 50% WOCFM 60% static pressure inches w.g. 5 4 3 2 1100 RPM 900 RPM 700 RPM 70% 80% 90% 1 500 RPM 0 0 4 8 12 16 20 CFM in 1000s

Two Different Systems 6 Forward Curved (FC) Fan 50% WOCFM 60% static pressure inches w.g. 5 4 3 2 1100 RPM 900 RPM 700 RPM actual system Design system 70% 80% 90% 1 500 RPM 0 0 4 8 12 16 20 CFM in 1000s

System Fan static pressure inches w.g. Is dependent on the Fan Is dependent on the System CFM

System Change: Steep Fan Curve 25-inch steep fan curve 8 45 % WO 50 % WO 7 60 % WO total static pressure (in H 2 O) 6 5 4 1500 RPM 1300 RPM 0.5 change 3 2 1 1000 RPM 700 RPM 14,500 cfm (vs. 15,000 cfm) 3.3% loss 70 % WO 80 % WO 90 % WO 0 100 RPM 150 RPM 200 RPM 300 RPM 500 RPM 1750 RPM 1000 RPM 1500 RPM 2000 RPM 0 5000 10000 15000 20000 25000 airflow (cfm)

System Change: Flat Fan Curve 25-inch flat fan curve 5.0 800 RPM 25 % WO 4.5 50 % WO total static pressure (in H 2 O) 4.0 3.5 0.5 change 3.0 2.5 2.0 1.5 1.0 700 RPM 600 RPM 500 RPM 400 RPM 14,500 cfm (vs. 15,000 cfm) 6.7% loss 60 % WO 70 % WO 80 % WO 90 % WO 0.5 0 0 300 RPM 500 bhp 750 bhp 1000 bhp 1500 bhp 2000 bhp 5000 10000 15000 20000 25000 30000 35000 40000 45000 airflow (cfm)

Myth Number 6 Small changes in pressure can have a huge impact on airflow for flat fan curves and may cause a fan system to surge.

Myth Number 6 A chilled water system needs to be variable primary flow to be efficient.

Variable Primary Flow (VPF) Savings First cost: 4-8% Annual energy: 3-8% Life-cycle cost: 3-5% Compared VPF and Primary-Secondary

Low Pump Power Install pump VSD Use VSD to set design flow rate Open balancing valve Employ chilled water reset If system is constant flow reduce design flow rate further

Design Flow ~ Minimum Flow Chilled water Ts ASHRAE GreenGuide (16-18 F T) 90.1-2016 Section 6.5.4.7 Coil shall be selected to provide 15 F or higher temperature difference between leaving and entering temperatures. Chillers with limited evaporator choices

Design Flow ~ Minimum Flow Flow turndown = Design flow / Minimum flow Single chiller Turndown > 1.3 Two chillers Turndown > 1.5 Consider piping the chillers in series

Conversion from Primary-Secondary Convert to VPF If entire plant is being re-piped anyway Additional capacity is needed Install chiller where primary pumps used to be Change to Variable-Primary/ Variable-Secondary Cooling capacity is adequate Piping changes are minimal

Convert to Variable Primary/Variable Secondary VFDs DP ΔT = 1 or 2 ºF DP Placeholder for Manifolded P-S System picture (Beth to supply)

Plant Operator Doesn t understand the plant Wants to manually control VPF

Myth Number 7 A chilled water system needs to be variable primary flow to be efficient.

Myth Number 7 Fans often don t deliver the airflow they are supposed to and it s the fan s fault.

ANSI/ASHRAE 51 (AMCA 210-07) Figure 12: Outlet Chamber Setup-Multiple Nozzles in Chamber Test chamber

System Effect: Developing a Uniform Velocity Profile fan Not enough space to fully develop uniform velocity profile

Free and Abrupt Discharge Hidden loss as high as 1.0 inches w.g. OA

AMCA Publication 201, Fans and Systems Prediction of common System Effect Factors

Common System Effects Open discharge, elbow, branch, turning vanes, or damper located too close to the fan outlet Elbow, turning vanes, air straightener, or other obstruction located too close to the fan inlet Pre-swirling the air prior to it entering the fan wheel Use of an inlet plenum or cabinet

Flex Duct Problems Good Bad flex duct

Low Airflow Troubleshooting Common problems: Unexpectedly high system pressures Leaks Fan installed or running backwards Close-coupled fittings From A Practical Guide to Noise and Vibration Control for HVAC Systems (M. Schaffer, 1991)

Fan Rotation Forward-curved Backward-tended Backward-inclined Backward-curved Airfoil

Low Airflow Troubleshooting Over-amping problems: Bad component (motor or bearings) Installation: Wheel-cone overlap Belt tension, belt/shaft alignment Wheel-cone overlap

Low Airflow Troubleshooting Uncommon problems: Wrong fan installed Cutoff issues (housed fans only) Software/catalog error Quantum mechanics & string theory Fan cutoff (split in this case)

Field Measurements Evaluating the right parameters: Airflow Pressure Speed Power Things to watch out for: VFD settings Damper position (systems with a return or exhaust fan) Parameter measurement error

Parameter Measurement Error Your duct system?

Parameter Measurement Error AMCA 203 Field Performance Measurement of Fan Systems http://www.amca.org/

AMCA Fan Application Manual Publication 201 Fans and Systems Lists possible causes for low flow, including: Improper inlet duct design Improper outlet duct design Improper fan installation Unexpected system resistance characteristics Improper allowance for fan system effect Dirty filters, ducts, coils Performance determined using uncertain field measurement techniques Includes much help for system effect corrections

AMCA Fan Application Manual Publication 202 Troubleshooting Lists possible causes for low airflow, including: Improper fan installation or assembly Damage in handling or transit System design error Deterioration of system Faulty controls Poor fan selection Includes detailed troubleshooting checklists

Myth Number 8 Fans often don t deliver the airflow they are supposed to and it s the fan s fault.

Myth Number 8 You can save (20, 30, 40, 50 80) percent.just by doing this

Savings Claims 40 is the new 30!

50 is the New 40 improved system efficiency of up to 54%

And now from an online brochure

Percent Savings: Questions to Ask Compared to what? What is the baseline? What else changed? (particularly for retrofits).

Percent Savings: Questions to Ask Compared to what? What is the baseline? What else changed? (particularly for retrofits). Is the comparison valid for Your building? Your application and load profile? Your climate?

78.5 Percent Claim Indirect evaporative cooling Compared to compressor cooling Dry climate Water is available Does the solution meet my customers needs?

Myth Number 8 You can save (20, 30, 40, 50 80) percent.just by doing this Make sure the baseline and comparison are valid for the specific project Perform an analysis on energy savings, energy cost savings, and ROI Help the client determine if the solution is in both their short-term and long-term interests

Myth Number 9 Anti-freeze doesn t have much affect on chilled water systems.

Example Fluid Properties and Impacts Fluid Property Compared to Water Impact Result Viscosity Increases Pressure drop increases Pump power increases Film heat transfer coefficient Drops Heat transfer worsens More flow required Specific heat Drops More flow required Pressure drop and pump power increase Specific gravity Rises Less flow required Pressure drop and pump power increase

Fluid Properties at 60 F Property Water 25% EG 25% PG Viscosity (lb/hr-ft) 2.68 5.25 6.49 Thermal conductivity (Btu/ hr-ft- F) Specific heat (Btu/lb- F) 0.3445 0.2894 0.2773 1.0016 0.9066 0.9410 Specific gravity 1.0000 1.0331 1.0216

ASHRAE, www.ashrae.org. (2016) ASHRAE Handbook HVAC Systems and Equipment.

Antifreeze Affect on the Coil heat transfer capability can change by 40% or more when antifreeze solutions are used consult the manufacturer s rating data in glycol systems.

Antifreeze Affect on the Chiller 17% Reduction ASHRAE, www.ashrae.org. (2016) ASHRAE Handbook HVAC Systems and Equipment.

Required Flow Tons= 500 gpm T cp /12,000 ( ῤ/ ῤw ɤ ) Tons(water)= gpm T /24 Tons(25% EG)= gpm T /25.5 Tons(25% PG)= gpm T /25

Antifreeze Affect Water: 25% EG: 25% PG: gpm = 24 x tons x ΔT gpm = 25.5 x tons x ΔT gpm = 25 x tons x ΔT More flow is required

Affect of Antifreeze on Flow ΔP (Flow2 / Flow1) 2 Δ Pump Power (Flow2 / Flow1) 3 Antifreeze Flow increase (%) Pressure drop increase (%) Pump power increase (%) 25% EG 6.2 13 20 25% PG 4.2 8.5 13

Affect of Antifreeze Viscosity Pressure drop increase 25% EG: 9% 25% PG: 17% ASHRAE, www.ashrae.org. (2016) ASHRAE Handbook HVAC Systems and Equipment.

Reality: Affects of Antifreeze Capacity Coil Chiller Pump Flow Pressure Power It s all bad except the system doesn t freeze

Guidance use the smallest possible concentration to produce the desired antifreeze properties. ASHRAE, www.ashrae.org. (2016) ASHRAE Handbook HVAC Systems and Equipment.

Freeze and Burst Protection Burst protection Keep pipes from bursting Crystal formation is ok Use when equipment is not going to run in winter Freeze protection Solution must remain 100% liquid Necessary when equipment operates in freezing conditions

Freeze and Burst Protection Ethylene Glycol % Propylene Glycol % Temperature ( F) Freeze Burst Freeze Burst 20 16.8 11.5 18 12 10 26.2 17.8 29 20 0 34.6 23.1 36 24-10 40.9 27.3 42 28-20 46.1 31.4 46 30-30 50.3 31.4 50 33-40 54.5 31.4 54 35

Myth Number 10 Anti-freeze doesn t have much affect on chilled water systems.