ENGINEERING DESIGN GUIDE: TRANQUILITY 27 TWO-STAGE (TT) SERIES 2 TO 5.5 TON HORIZONTAL AND VERTICAL EARTHPURE UNITS

Similar documents
ENGINEERING DESIGN GUIDE: GENESIS STANDARD (GR) SERIES 0.5 TO 5 TON HORIZONTAL AND VERTICAL UNITS

ENGINEERING DESIGN GUIDE: GENESIS COMPACT (GC) SERIES 0.5 TO 5 TON HORIZONTAL AND VERTICAL UNITS

Commercial and Residential Water Source Heat Pumps Boiler/Tower and Geothermal Applications

THE SMART SOLUTION FOR ENERGY EFFICIENCY ENGINEERING DESIGN GUIDE: CONSOLE (CCE) SERIES 0.5 TO 1.5 TON CONSOLE UNITS WATER-SOURCE HEAT PUMP SYSTEMS

THE TRANQUILITY 16 COMPACT (TC) SERIES

Tranquility 30 Two-Stage (TT) Series

Tranquility Console (TRC) Series Submittal Data

HEAT CONTROLLER, INC. HSS Series 1 1/2 to 5 Tons Indoor Split System Geothermal Heat Pumps

Tranquility Vertical Stack (TSL) Series

VERTICAL STACK (VHS) SERIES

Tranquility Vertical Stack (TSM) Series

Greensource Residential Geothermal Heat Pumps. Invisible Comfort. Si Series: CE Model. boschheatingandcooling.com

Reinventing Energy Efficiency

ClimaDry II. Table of Contents. ClimaDry II Whole House Dehumidification Option. Tranquility 30 Tranquility 20

*20D082-05NN* 20D082-05NN

Greensource Residential Water Source Heat Pumps. Simply Smart. i Series: SV Model. boschheatingandcooling.com

Genesis Compact (GC) Series Submittal Data

Tranquility Vertical Stack (TSM) Series Submittal Data

Water Source Heat Pumps

Tranquility 22 Compact Ultra Efficiency (TY) Series Submittal Data

Geothermal. Comfort Systems

Water Source Heat Pumps. Energy efficient heating and cooling commercial applications

GEOTHERMAL SPLIT SYSTEMS CLIMATEMASTER

Greensource Residential Geothermal Heat Pumps. Simply Smart. CDi Series: SM Model. boschheatingandcooling.com

Geothermal HIGH EFFICIENCY HEATING & COOLING. the logical choice for energy efficient residential heating and cooling

Richard Hiles ClimateMaster

EP Model. EP Model Water Source Heat Pump. ½ to 6 Ton

Greensource iseries Water Source Heat Pumps. SV Model. Made in Florida boschheatingandcooling.com

GEOTHERMAL: THE SMARTER CHOICE

Technical Development Program COMMERCIAL HVAC SYSTEMS. Water Source Heat Pump Systems PRESENTED BY: Ray Chow. Sales Engineer

50 Series AQUAZONE Water Source Heat Pumps

Greensource Residential Water Source Heat Pumps

Product Data. Single-Package Horizontally Mounted Water Source Heat Pumps with Electronic

Geothermal Comfort Systems

PERFECT SOLUTIONS WATERFURNACE COMMERCIAL PRODUCTS. Water Source/Geothermal Heat Pumps

Greensource Residential Geothermal Heat Pumps. Think Green Think Renewable Think. iseries: SV Model Split System. boschheatingandcooling.

GEOTHERMAL COMFORT SYSTEMS

ENGINEERING. Edition No. 13 October 2002

RESIDENTIAL PRODUCT GUIDE CLIMATEMASTER GEOTHERMAL HEATING & COOLING DECLARE YOUR PERSONAL ENERGY INDEPENDENCE

Geothermal Comfort Systems

RESIDENTIAL PRODUCT GUIDE CLIMATEMASTER GEOTHERMAL HEATING & COOLING DECLARE YOUR PERSONAL ENERGY INDEPENDENCE

Mammoth Water Source Heat Pumps

FORCED AIR + HYDRONIC

Compact, Self-Contained unit that offer low installation cost plus dependable performance.

Vapor-Compression Refrigeration

DXair Pool Dehumidifiers

MAC-060HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

ENGINEERING SPECIFICATIONS

ENGINEERING SPECIFICATIONS

Best regards, John Bailey, Jr. Senior Vice President of Sales

MAC-036HE-02-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-048HE-01-L High Efficiency Air-Cooled Chiller Air-Cooled Chillers for Global Residential and Light Commercial Micro Climates Rev 1.

MAC-120HE-03 Air-Cooled Chiller

HYDRO-TEMP. Earth Coupled Heat Pumps HYDRO-TEMP CORPORATION P.O. BOX HWY 67 S POCAHONTAS, AR 72455

Product Data. Features/Benefits. AQUAZONE 50PCH,PCV Compact Water Source Heat Pumps with PURON Refrigerant (R-410A) 50 Hz

MHCCW Chilled Water Ceiling Concealed With 5kW Electric Heat 2-Pipe Heat / Cool Fan Coil 30,000 BTUH

MHCCW Chilled Water Ceiling Concealed Without Electric Heat 2-Pipe Heat / Cool Fan Coil 18,000 BTUH

GUIDE SPECIFICATIONS AQUARIUS ii

T-CLASS Commercial Split Systems Up to 20-Ton TSA/TPA Models

COMMERCIAL PRODUCT LINE

From 230 tons to. Water-Source Heat Pump Products. Premium Performance Environmentally Friendly Superior Construction

Performance and rugged durability. Commercial Split Systems Up to 20-Ton TSA/TPA Models

ENGINEERING GUIDE. Water-Cooled Self-Contained Units C-Series, Vertical

TRANQUILITY WATER-TO-WATER SERIES

Engineered for flexibility and performance

LM Split Systems Water Source Heat Pump

Product Data. AQUAZONE 50HQP Large Capacity Horizontal Water Source Heat Pumps with PURON Refrigerant (R-410A) 6 to 10 Nominal Tons

Product Specifications. Vertical Floor Consoles By First Co.

GT-PW (50YEW) Water-To-Water Series. WATER-TO-WATER PURON SYSTEMS SIZE 010 [10 kw]

Catalog SmartSource Two-Stage Horizontal & Vertical Water Source Heat Pumps

Enfinity Horizontal Ceiling Catalog Water Source Heat Pumps

MHNCCW (4-Pipe) Chilled/Hot Water Ceiling Concealed 208/230V 4-Pipe Heating & Cooling Fan Coil 12,000 BTUH

Product Data. Features/Benefits. 50HS Single-Package Heat Pump Units 50 Hz

Climate control precision in Hi-tech environments Jupiter and Mercury Close Control Units

Series. Chillers and. Features: Application Flexibility Minimizes Installation Time and Reduces Cost

That s why we call it Smarter from the Ground Up.

water to water heat pumps

LV Split Systems Water Source Heat Pump

GUIDE SPECIFICATIONS. WW Series Water-to-Water Reverse Cycle Chillers & Low Temp Boilers. WW Reverse Cycle Chillers / Low Temperature Boilers

Table of Contents. Commercial Horizontal & Vertical Packaged Water-Source Heat Pumps

HEATING COOLING HOT WATER PRODUCT LINE

SECTION WATER-SOURCE UNITARY HEAT PUMPS

VERSECON Indoor Vertical Self-Contained Air Conditioner YSWU Ton Water-Cooled

Product Data. Features/Benefits. OMNIZONE 50BV Remote Air-Cooled and Water-Cooled Indoor Self-Contained Systems and Water Source Heat Pumps

VERTICAL FAN COIL UNITS

Product Data. Features/Benefits Carrier s Aquazone WSHPs are an efficient, compact alternative for all boiler/tower and retrofit applications

HYBRID ADIABATIC Cooling System

Product Data. 50HS Single-Package Heat Pumps to 5 Nominal Tons

30RB Air-Cooled Liquid Chillers. Nominal cooling capacity 8-14 kw. Features. Quiet operation

Mission Critical. Series 6, 8 & 9. vertical floor mount Ton Units. Air Conditioning Systems

Refrigeration/Troubleshooting Manual

PRODUCT GUIDE EARTHLINKED TECHNOLOGIES GEOTHERMAL RENEWABLE ENERGY SYSTEMS SIMPLE. EFFICIENT. EFFECTIVE.

FCC Fan-Coil Units High-Performance, Vertical

EP Model Water Source Heat Pump

GTIP60 ISO GT Series, Inch Pounds - 60 Hz GT (iso) Spec Guide Drawings Spec Sheets Low Temp Heating P/T Charts

Think Green Think Renewable Think

SPECIFICATION CATALOG. Commercial 0.75 to 6 Tons. Geothermal/Water Source Heat Pump

CA Model Water Source Heat Pump

AC, HP and Air Handler Units Up to 20 Tons. Commercial Split Systems. Reliable, cost-effective and servicefriendly split systems inside and out

Performance Rating of Variable Refrigerant Flow (VRF) Multi-split Air-conditioning and Heat Pump Equipment

Transcription:

THE SMART SOLUTION FOR ENERGY EFFICIENCY ENGINEERING DESIGN GUIDE: TRANQUILITY 27 TWO-STAGE (TT) SERIES 2 TO 5.5 TON HORIZONTAL AND VERTICAL EARTHPURE UNITS WATER-SOURCE HEAT PUMP SYSTEMS

The Smart Choice for Energy Efficiency TABLE OF CONTENTS Commercial HVAC...2 System Comparisons...3 Water-Source Heat Pumps...4 Geothermal Heat Pumps...5 An Application Example...6 The ClimateMaster Advantage...8 TT Unit Features and Performance...12 About ARI/ISO...14 ARI/ISO Data...15 Model Nomenclature Reference Calculations, Legend, & Correction Tables...16 Selection Example...20 Performance Data...22 Physical Data...30 Physical Dimensions (Horizontal Units)...31 Physical Dimensions (Vertical Units)...35 Physical Dimensions (Downflow Units)...39 Blower Performance Data...44 Electrical Data...45 Wiring Diagram Matrix...46 Typical Wiring Diagram - CXM...47 Typical Wiring Diagram - DXM...48 CXM/DXM Control Features...49 CXM/DXM Feature Comparison...51 TT WSHP Specifications...52 Guide Revision Log...61 Revised: 07/24/06D 1

ClimateMaster Water-Source Heat Pumps Tranquility 27 Two-Stage (TT) Series 2 to 5.5 Ton Horizontal and Vertical EarthPure Units COMMERCIAL HVAC The ever-changing environment of commercial construction offers exciting breakthroughs in technology and materials, but it is not without some heartburn. Today, owners, architects, and contractors face many challenges in the design and construction of their projects. Challenges such as usable space, indoor air quality, energy efficiency, maintenance costs, building longevity, and the LEED program all come to the forefront of the design process. When considering the solutions to these challenges, the type of HVAC system chosen directly affects each one. USABLE SPACE It has been said that the reason real estate grows in value is because no one is making any more. As cities continue to grow and spread out, the value of maximizing usable space becomes increasingly important. When selecting an HVAC system, you positively or negatively impact the usable space on a project. As an example, VAV (Variable Air Volume) systems utilize complicated ductwork systems along with extensive equipment rooms to deliver conditioned air into the building space. Additionally, VAV duct systems many times require more ceiling height which increases floor-to-floor space thus increasing building costs. By comparison, ClimateMaster Water-Source and Geothermal Heat Pump systems require little to no equipment room space and use a very simple, compact, and independent ductwork system. INDOOR AIR QUALITY As important as the actual temperature of a building space is, the quality of air within that space is equally important. The American Society of Heating, Refrigerating, and Air Conditioning Engineers (ASHRAE) has implemented Standard 62, which requires significantly higher amounts of fresh outdoor air for buildings. The challenge now becomes how to properly introduce, condition, and deliver this fresh air into the building space. Traditional options like two- and four-pipe Fan Coil systems must be up-sized significantly to handle the additional conditioning load. This means larger, more expensive units, larger, more expensive piping, and larger more expensive boilers and chillers. In comparison, ClimateMaster systems offer a variety of options that can actually lower the overall system size, introduce 100% outdoor air, and lower system usage cost. ENERGY EFFICIENCY Today s offices equipped with computers, copiers and other office tools can dramatically affect the heating and cooling load of a given space. When considering heating and cooling loads, rising energy costs demand an HVAC system that is efficient while building designs require a system that is also flexible. ClimateMaster has a solution for practically any application, and does so with some of most energy efficient HVAC systems available on the market today. In fact, all of ClimateMaster s products either meet or exceed the new federal mandated efficiency minimums. MAINTENANCE COSTS Complex systems such as two- and four-pipe fan coils and VAV systems require advanced maintenance and the trained personnel to perform it. Large equipment rooms filled with chillers, air handlers, or large-scale boilers require personnel for monitoring and maintenance, which consume building space and leasing profits. The effect to the bottom line becomes significant when considering the potential of a complete system failure along with costly parts and equipment replacement. However, Water-Source and Geothermal Heat Pumps require very little monitoring and maintenance - aside from routine filter changes. With factory installed DDC controls, the entire building can be accessed via any web-enabled computer for monitoring and set point control. No muss, no fuss, no worries. BUILDING LONGEVITY New innovations offer longer life expectancies for today s buildings. You should expect the same from the HVAC systems being placed inside these buildings. However, when it comes to longevity, not all systems are created equal. Complex chillers and air handling systems often have a large number of moving parts that will wear out over time. Water-Source and Geothermal Heat Pumps offer the advantage of very few moving parts. Fewer moving parts lower the occurrence of parts replacement and extend equipment life. This simplicity of design allows ClimateMaster systems to provide average life spans of 20 years or more. In fact, there are a number of ClimateMaster units that are still performing after 50 years - providing the continual comfort our customers have come to expect. 2

The Smart Choice for Energy Efficiency MANY CHOICES, ONE SOLUTION When choosing a HVAC system for a project, there are four basic types from which to choose. FAN COILS Fan coil systems are comprised of water-to-air coil air handlers connected via a two- or four-pipe insulated water loop. Fan coils require complex chillers and boilers to provide water loop fluid in a particular temperature range (i.e. chilled water for cooling and hot water for heating). Two-pipe fan coils have a major disadvantage as control is substantially limited to whatever mode the system is currently set at (i.e. cooling or heating). A four-pipe version can be installed that requires both chilled and heated water to be available at the same time. Four-pipe systems also require twice the piping and twice the circulation equipment of a two-pipe system, which makes a four-pipe system one of the most expensive systems to install. VARIABLE AIR VOLUME (VAV) Variable Air Volume, or VAV, is one of the most common types of HVAC systems used in large commercial buildings today. A typical system is usually comprised of a large air handler, central ductwork system, and a relatively large equipment room. Conditioned air is distributed throughout the building via a central ductwork system and is regulated via dampers in each space. VAV systems typically have a higher first cost than Water-Source Heat Pumps, and may have similar operating costs, resulting in overall increased life cycle costs. ROOFTOP Rooftop systems are similar to VAV systems in that they use a central ductwork system to distribute conditioned air into the building space. However, instead of one central unit, the system is comprised of multiple units which can be tasked for different conditioning requirements. Rooftop systems usually require additional structural reenforcement as well as cranes or other lifting equipment to place the units. Control in a particular zone is limited to what the system is currently set to (i.e. cooling or heating). Rooftop installation costs are low to moderate, but operating costs are typically 50% higher than Water-Source Heat Pumps. Additionally, the systems are exposed to the elements and are subject to damage and vandalism. WATER-SOURCE AND GEOTHERMAL HEAT PUMPS Water-Source and Geothermal Heat Pump systems are comprised of individual packaged units that transfer heat via a single- or two-pipe water loop. Each unit can be used in either heating or cooling mode year-round and loop temperature is maintained via a boiler/tower combination or earth-coupled loop. Each zone has complete control of its heating/cooling mode and each unit is independent from the others. This means if one unit goes down, the whole system is not affected. Controls can be as simple as one unit, one thermostat. Water-Source and Geothermal Heat Pump systems are the most energy, cost, and space efficient of any system in the industry. SYSTEM COMPARISON System Ease of Design Ease of Installation Installation Space Installation Cost Maintenance Requirements Maintenance Costs Future System Expansion Sound Levels Operating Costs Total Zone Failure Chance Individual Tenant Control Options Additional Auxiliary Equipment Needed Structure Modification Needs System Longevity Two-Pipe Fan Coils Low Low High Med High High Low Low Med High Low Low High High Med Four-Pipe Fan Coils Low Low High High High High Low Low High High Low Low High High Med PTAC / PTHP Low Low Low Low High High Med High High Low Med Low Med High Low VAV Low Low High Med High High Low Med Med High Low Low High High Med Rooftop Low Low High Low Med High Low Med Med High Low Low Med High Med Water-source Heat Pumps High High Low Low Low Low High Low Low Low High High Low Low High Geothermal Heat Pumps High High Low Low Low Low High Low Low Low High High Low Low High 3

ClimateMaster Water-Source Heat Pumps Tranquility 27 Two-Stage (TT) Series 2 to 5.5 Ton Horizontal and Vertical EarthPure Units WATER-SOURCE HEAT PUMPS As the most energy efficient HVAC systems on the market, Water-Source Heat Pumps are uniquely simple in design. Heat is moved through an interconnected water loop and either rejected through a cooling tower, or put to work in other areas. Each unit is an independent, packaged system, eliminating the chance of a total system failure. If one unit goes down, the other units are not affected. Conveniently located above the ceiling or in a closet, units can be easily accessed. to maintain a constant temperature of 60 to 70 F in the water loop during high heating demand months. Within this temperature range, the units can operate in either heating or cooling mode. SYSTEM MODES Water-Source Heat Pump systems can operate in one of four modes depending on the space conditioning requirements. The versatility of operation allows Water- Source Heat Pumps to show their full potential as a solution for customized comfort and flexibility. COOLING MODE BALANCED MODE The system extracts heat from the air and rejects it into the water loop through the coaxial refrigerant-to-water heat exchanger. This heat can either be moved to a different part of the building to satisfy a heating mode requirement, or be rejected out of the building via a cooling tower. HEATING MODE The system extracts heat from the water loop through the coaxial heat exchanger and compresses it to a higher temperature. This heat is then transferred into the air through the air coil and used to condition the building space. A nominally sized boiler is often used A mixture of units in heating mode and units in cooling mode create a constant temperature in the water loop. In Balanced Mode, there is no need for heat injection or rejection via the boiler or cooling tower. The heat is simply moved from one zone to another. DEHUMIDIFICATION MODE The system, using a multi-speed blower and separate humidistat, slows the air movement across the air-coil to extract moisture and provide a more comfortable space. An additional reheat coil is available on select products for those climates where high humidity is a problem. 4

The Smart Choice for Energy Efficiency GEOTHERMAL SYSTEMS These Boilerless/Towerless Heat Pump systems use the natural thermal properties of the Earth to dissipate or capture heat for the water loop. Geothermal Heat Pumps operate in an identical fashion to Water-Source Heat Pump units. However, without the need for a boiler or cooling tower, they save substantial energy costs and space. The water loop system is underground and the units are inside the building. Thus, the environmentally friendly geothermal system preserves the architectural design of a building naturally. GEOTHERMAL EARTH LOOPS Geothermal Earth Loops come in several different configurations depending on space availability and soil properties. Chances are at some point you have either stood over, or walked across a geothermal loop field. Loop fields can be located under parking lots, landscaped areas, or any number of other locations. All earth loops use high-density polyethylene pipe to circulate either water or an antifreeze mixture. All joints and connection fittings are thermally fused to prevent leaks and most piping comes with a 25-year or longer warranty. VERTICAL LOOPS Vertical loops utilize bore holes drilled to an average depth of 250 feet. Once the loop pipe is inserted into the bore, it is grouted using a Bentonite mixture for maximum thermal conductivity. When space is a limited, vertical loops are the most common type of geothermal loop installed. Horizontal Loops LAKE LOOPS Lake loops utilize a slinky assembly of geothermal loop piping placed at the bottom of a pond, lake, or other large body of water. An extremely cost effective loop system, lake loops are an easy alternative if the option is available. Lake Loops WELL SYSTEMS Most commonly known as Open Loop, well systems pump water out of a nearby body of water or water well, and then discharge the water into another body of water or water well. Well systems usually employ a plate heat exchanger inside the building to keep the building water loop separated from the well water. This prevents any contaminates from affecting unit performance and extends system life. Well systems are often the most efficient as the well water is always at the same temperature year-round. Vertical Loops HORIZONTAL LOOPS Horizontal loops utilize trenches dug to an average depth of four to six feet. As one of the more cost effective loops to install, horizontal loops are commonly found in open fields, parks or under parking lots. Well Systems 5

ClimateMaster Water-Source Heat Pumps Tranquility 27 Two-Stage (TT) Series 2 to 5.5 Ton Horizontal and Vertical EarthPure Units A WATER-SOURCE EXAMPLE As an example of how Water-source Heat Pumps can handle a variety of different applications, the building shown to the right is a fictional bronze statue foundry company in the midwest portion of the United States. The first floor comprises their production floor and office space. The second floor of the building is reserved for future use. The cooling tower and boiler work as needed to maintain an average loop temperature between 60 to 95 F. Water-source Heat Pumps can efficiently operate in either heating, or cooling mode under these conditions. This gives individual and specialized zone control for maximum comfort and the ability to change operation modes as needed. A mixture of units in heating mode and units in cooling mode create a constant temperature in the water loop. In Balanced Mode, there is no need for heat injection or rejection via the boiler or cooling tower. The heat is simply moved from one zone to another. WARM WEATHER (HIGH COOLING DEMAND) GCH024 GCH024 GCH024 GCH024 GLH120 GLH120 Conference Room Office Restroom Breakroom Computer Room Cooling Tower Production Floor GCH048 Cubicles GCH048 Cubicles GCH048 Mechanical Room Boiler GLV160 GCH012 GCH012 GCH012 GCH012 GCH012 GCH012 Office Office Office Office Office Office Lobby COOL WEATHER (HIGH HEATING DEMAND) GCH024 GCH024 GCH024 GCH024 GLH120 GLH120 Conference Room Office Restroom Breakroom Computer Room Cooling Tower Production Floor GCH048 Cubicles GCH048 Cubicles GCH048 Mechanical Room Boiler GLV160 GCH012 GCH012 GCH012 GCH012 GCH012 GCH012 Office Office Office Office Office Office Lobby 6

The Smart Choice for Energy Efficiency A GEOTHERMAL EXAMPLE Using the same building model, the cooling tower and boiler are replaced with a geothermal vertical loop field. Identical in overall zone operation, the building benefits by having less overall equipment and reduced operation costs. Building aesthetics are also improved by eliminating outdoor equipment and additional space is gained by eliminating the boiler and additional support equipment. WARM WEATHER (HIGH COOLING DEMAND) GRH024 GRH024 GRH024 GRH024 GLH120 GLH120 Conference Room Office Restroom Breakroom Computer Room Production Floor GRH048 Cubicles GRH048 Cubicles GRH048 Storage GLV160 GRH012 GRH012 GRH012 GRH012 GRH012 GRH012 Office Office Office Office Office Office Lobby The cooling tower and boiler can be eliminated in the geothermal application freeing up space used for equipment for other use. Only a small amount of room is needed for loop circulation equipment. 7

ClimateMaster Water-Source Heat Pumps Tranquility 27 Two-Stage (TT) Series 2 to 5.5 Ton Horizontal and Vertical EarthPure Units THE CLIMATEMASTER ADVANTAGE WHO IS CLIMATEMASTER? Who is ClimateMaster? ClimateMaster emerged from the marriage of several Water-Source heat pump companies in a blending of strengths to form a focused organization. For over 50 years, we have been focused on enhancing business and home environments around the world. Our mission as the world s largest and most progressive leader in the Water-Source and geothermal heat pump industry reveals our commitment to excellence - not only in the design and manufacture of our products, but in our people and services. CLIMATEMASTER DESIGN From concept to product, ClimateMaster s Integrated Product Development Team brings a fusion of knowledge and creativity that is unmatched in the industry today. Drawing from every aspect of our business: Engineering, Sales, Marketing, and Manufacturing, our Development Team has created some of the most advanced, efficient, and versatile products available. INNOVATION, CONCEPT, NEEDS Great products are born from necessity. Whether it is a need to reduce sound, fit in a smaller space, make easier to service, achieve better efficiencies, or due to changing technologies, or new government regulations, ClimateMaster leads the industry in advancing the form, fit and function of Water-Source and geothermal heat pumps. Our Design Team continually strives for even the slightest improvement to our products. It is this continual drive for excellence that sets ClimateMaster apart from all other manufacturers. START TO FINISH At ClimateMaster, every product development project begins with a comprehensive set of specifications. These specifications are a culmination of input from the market, a specific need, or a number of other factors. From these detailed specifications, prototypes are constructed and testing begins. After a rigorous testing period in ClimateMaster s own state-of-the-art lab facility, the data is compared to the project specifications. Once the Design Team is satisfied that all of the specs are met, the unit is sent to the production department for pilot runs. After the pilot runs are completed, unit literature is finalized and the product is released to the marketplace. Every unit we produce follows this strict and sequenced path insuring no stone is left unturned, and no detail is missed. CLIMATEMASTER PRODUCTION Innovative products demand innovative manufacturing processes. ClimateMaster s integrated production process combines every aspect of the manufacturing of our equipment into an organized, balanced, and controlled whole. FABRICATION Every sheet-metal component of a ClimateMaster unit is produced in our fabrication department. Panels are precisely constructed of galvanized or stainless steel using computerized cutting, punching, and forming equipment. This precise fabrication means a tighter fit that makes for a more solid unit and reduced vibration, which equals reduced noise. On certain series, an optional epoxy powder coating is then applied to increase corrosion resistance and enhance the look of the unit. The final step is the addition of fiberglass insulation to the inside as an additional layer of sound deadening. This insulation meets stringent NFPA regulations, and includes antibacterial material. ASSEMBLY ClimateMaster s 250,000 square foot production facility produces over 50,000 units per year using the most stringent quality control standards in the industry. Each unit is assembled under the close supervision of our Integrated Process Control System or IPCS. This multi-million dollar computer system watches each unit as it comes down the assembly line. To back up the IPCS system, our Quality department is stationed on each line and performs random audits not only on the units, but also on component parts. All component parts must pass each and every quality checkpoint before a unit is packaged and shipped. These systems and processes are maximized due to the comprehensive and ongoing training every employee receives from the date they are hired. 8

The Smart Choice for Energy Efficiency COMPONENT PARTS To produce a quality unit, you have to start with quality components. ClimateMaster s purchasing department is relentless in its search for the best components for our products - while securing these components at prices that keep costs low. Any new component must go through a grueling testing phase before it ever sees the production line. Working closely with vendors and their engineers, we continually find new ways to not only improve our units, but to ensure component quality as well. Sister companies like KOAX, who produce our coaxial heat exchangers, allow ClimateMaster to provide components specifically designed for our applications CLIMATEMASTER CERTIFICATION ClimateMaster leads the industry in product awards and certifications. From 100% Air-Conditioning and Refrigeration Institute (ARI) performance ratings to industry awards for innovation, ClimateMaster applies cutting-edge technology to every product we design and manufacture. ClimateMaster s new Tranquility 27 series has won multiple awards and is taking the industry by storm. Hot off the heels of winning The News Bronze Dealer Design Award, the Tranquility 27 won Best of Show at ComforTech in September 2004. You know you are doing great things when a lot of people tell you so. ENGINEERING LAB FACILITIES ClimateMaster has one of the largest testing facilities of any Water-Source heat pump manufacturer. Innovation and product improvements are a mainstay of the ClimateMaster Engineering Lab. Our people are what make the difference in the development of superior products in a timely manner. Our certified facility has six automated test cells capable of testing a wide variety of unit types under varying conditions. These cells are capable of producing data twenty-four hours a day, seven days a week. The development time of equipment is significantly reduced allowing ClimateMaster Engineers and Lab Technicians to spend more time on the actual development process. This team effort has allowed us to maintain a high degree of competence in our industry. Our test cells and test equipment are calibrated and certified periodically, per recognized industry standards, to insure the data is accurate and repeatable. In addition to testing new concept units, the lab continually audits production units throughout the year to insure quality performance and reliability. INDUSTRY AFFILIATIONS AND ASSOCIATIONS ClimateMaster works closely with the International Standards Organization (ISO), the American Society of Heating, Refrigerating, and Air Conditioning Engineers (ASHRAE), the Canadian Standards Association (CSA-US), the Electrical Testing Laboratories (ETL), and Conformité Européene (CE) to insure that our equipment not only meets the highest performance standards, but meets the highest industry standards as well. In a recent milestone, ClimateMaster celebrated three consecutive years of 100% success rate in ARI s performance certification program. An uncommon feat in the industry, this award is a testament to the craftsmanship, design, and construction of every ClimateMaster unit. CUSTOMER SERVICE ClimateMaster has gone to great lengths to meet our customers business-to-business needs. ClimateMaster provides great products and our customer support is second to none. Our highly trained and experienced Customer Service department is available to assist you. Visit our on-line Business Center or contact Tech Services for any information you may need. WWW.CLIMATEMASTER.COM Our web site has become the central hub for all of our customers information needs. Current literature, specifications, presentations, and other resources are readily available in an intuitive, easy- to-navigate format. At the click of a mouse, our new on-line Business Center allows you to check the status of your orders, lookup sales history, manage contact information, and even order literature, accessories, and units. Combined with our unique EZ-ORDER and EZ-SEND software, we take all the effort and guesswork out of unit orders. 9

ClimateMaster Water-Source Heat Pumps Tranquility 27 Two-Stage (TT) Series 2 to 5.5 Ton Horizontal and Vertical EarthPure Units ENGINEERING DESIGN SPECIFICATIONS Advanced units need advanced specifications. ClimateMaster s new Engineering Design specifications provide the most detailed information for your next project. LITERATURE At ClimateMaster, Innovation never sleeps. As new advances are made, and new products are released, the need for accurate literature becomes critical. Every piece of technical literature that ClimateMaster produces is printed in our state-of-the-art on-demand printing facility. What this means is that we print only the literature we need at the time we need it. This insures that only the most current and accurate data is in the field. SHIPPING When you need that critical service part or piece of literature for your next presentation, you may rest assured that ClimateMaster has a shipping option for you. Networked with a variety of carriers such as FedEx, Watkins, Estes, Central Freight, Dugan, and many others, we provide fast and reliable shipping to anywhere in the world. THE FUTURE OF CLIMATEMASTER Our long history of innovation has paved the way for future endeavors with a solid platform of success. Growing markets in Europe and Asia demand a different way of not only manufacturing our products, but also successfully marketing them. New government regulations will phase out R-22 refrigerant at the beginning of 2010 paving the way for new R-410a, a much more environmentally friendly refrigerant. Additionally, new federally mandated efficiency increases of 30% becomes effective in January of 2006. In looking ahead, we continually strive for better processes, better designs, and better innovations that will keep ClimateMaster as the Global Leader in Water-Source and Geothermal Heat Pumps. ADVANTAGE EXCLUSIVES Being a leader in innovation, ClimateMaster brings industry firsts, as well as industry exclusives, to our family of products. CONTROLS ClimateMaster offers two levels of solid-state digital controls; the CXM and DXM control board. CXM Our standard CXM control board comes programmed with ClimateMaster s Unit Performance Sentinel (UPS) which monitors unit performance and notifies the owner of potential unit problems before a lockout occurs. Additionally, the CXM s eight standard safeties protect the unit from damage. Anti-Short Cycle Low Voltage High Voltage High Refrigerant Pressure Low Refrigerant Pressure (Loss of Charge) Air Coil Freeze (Excluding GC Series) Water Coil Freeze Condensate Overflow DXM Our enhanced controls option, the DXM control board offers all of the advantages of the CXM board but adds the following additional features: Multi-Stage Operation Night Setback Emergency Override Reheat Control Boilerless Electric Heat DDC CONTROLS Factory mounted LONWorks or Multi-ProtoCol (MPC) DDC controllers are an available option on all ClimateMaster products. These controllers give owners the ability to implement a variety of building automation systems such as BACnet, ModBus, and Johnson N2. Through a web enabled PC, individual units, unit zones, and entire building systems can be monitored and controlled with the click of a mouse. The systems provide unit status, set-point control, performance curves, and fault indications. CONFIGURATIONS No other manufacturer provides as many size, 10

The Smart Choice for Energy Efficiency performance, configuration, and cost options as the ClimateMaster family of products offers. From our smallest horizontal unit in the GCH006, to our largest vertical in the GLV300, to our Rooftop series with available 100% make-up air (when mated with the Rx ERV), to the console, water-to-water, and two-stage Tranquility 27, we have a unit to fit your application. SOUND Prior to the recently adopted sound standard ARI 260-2000 there had been no standard for the evaluation of Water-Source heat pump sound per for mance. Also, those manufacturers who did generate and publish their own sound data, did so in their own labs making it difficult to have the data in de pen dent ly certified and accurate comparisons were therefore, impossible. Now that a standard has been established, it is critical to compare the data correctly. If data from two man u fac tur ers is compared using different test procedures, results are not comparable. ClimateMaster has tested its product line for both ducted discharge and free inlet air combined with case radiated tests. Comfort has never been so quiet with our intelligent sound design. Our products use a variety of technologies to maintain our lead as the quietest units in the industry. DUAL LEVEL VIBRATION ISOLATION ClimateMaster units use an exclusive double isolation compressor mounting system. This dual level isolation deadens vibration and provides quiet operation. TORSION-FLEX BLOWERS Blower motors,on select models, are mounted with a unique torsionflex mounting system which not only allows for easy service, but also reduces vibration from the blower motor during operation. ULTRAQUIET ClimateMaster s optional additional sound suppression package enhances our already excellent sound performance through the use of dual density acoustical insulation and other strategically placed sound attenuating materials. No other manufacturer s mute package comes close to matching the performance of the UltraQuiet package. E-COATED AIR COILS All ClimateMaster Water-Source heating and cooling systems (excluding the RE series rooftop) are available with an E-Coated air-coil option. This process provides years of protection against coil corrosion from airborne chemicals resulting from modern building material outgassing and most airborne environmental chemicals. In fact, ClimateMaster s exclusive E-Coated air-coils enhance corrosion protection to nearly 20 times that of a traditional uncoated coil.* * Test based upon ASTM B117 Salt Spray test hours. CLIMADRY REHEAT Continuing to lead the industry in IAQ (Indoor Air Quality) solutions, select ClimateMaster units are available with an innovative method (patent pending) of reheating the air. The ClimaDry microprocessor-controlled option will automatically provide 100% reheat by adjusting the amount of reheat capacity based upon supply air temperature. This new approach to reheat provides dehumidified, neutral temperature supply air, while eliminating the problem of overcooling the space when loop temperatures drop. All components are internal to the unit, saving space and keeping installation costs low. A simple humidistat or DDC controls activates the option. VOLTAGES ClimateMaster units are available in a wide variety of commercial voltages, providing maximum flexibility in building design. Available voltages are as follows: 208-230/60/1 208-230/60/3 265/60/1 460/60/3 575/60/3 220-240/50/1 380-420/50/3 * Not all units are available with every voltage combination shown above. ACCESSORIES ClimateMaster offers a complete line of accessories to complete any project, including hoses, thermostats, valves, pumps, fittings, controllers, sensors, filters and more. 11

ClimateMaster Water-Source Heat Pumps Tranquility 27 Two-Stage (TT) Series 2 to 5.5 Ton Horizontal and Vertical EarthPure Units THE TRANQUILITY 27 TWO-STAGE (TT) SERIES As the highest efficiency water-source heat pump on the planet, the Tranquility 27 series raises the bar for watersource heat pump efficiencies, features and application flexibility. Not only does the Tranquility 27 far exceed ASHRAE 90.1 efficiencies, but it also uses EarthPure HFC-410A zero ozone depletion refrigerant, making it an extremely environmentally-friendly option. Tranquility 27 is eligible for additional LEED (Leadership in Energy and Environmental Design) points because of the green technology design. Available in sizes 2 tons (7.0 kw) through 5-1/2 tons (19.3 kw) with multiple cabinet options (vertical upflow, vertical downflow and horizontal) the Tranquility 27 offers a wide range of units for most any installation. The Tranquility 27 has an extended range refrigerant circuit, capable of ground loop (geothermal) applications as well as water loop (boiler-tower) applications. Standard features are many. Copeland UltraTech twostage unloading scroll compressor, GE ECM variable fan motor, microprocessor controls, galvanized steel cabinet, epoxy powder coat paint, stainless steel drain pan and foil-backed air handler insulation are just some of the features of the innovative Tranquility 27 series. ClimateMaster s exclusive double isolation compressor mounting system makes the Tranquility 27 the quietest unit on the market. Compressors are mounted on vibration isolation springs to a heavy gauge mounting plate, which is then isolated from the cabinet base with rubber grommets for maximized vibration/sound attenuation. The unique low profile slanted control box makes installing and maintaining the unit easier than any other water-source heat pump currently in production. Options such as e-coated air coil, DDC controls, internal pump and high efficiency MERV 11 two-inch (51mm) air filters allow customized design solutions. UNIT FEATURES Sizes 026 (2 ton, 7.0 kw) through 064 (5.5 tons, 19.3 kw) EarthPure HFC-410A refrigerant Copeland UltraTech two-stage unloading scroll compressors GE ECM variable speed fan motor with soft start Exceeds ASHRAE 90.1 efficiencies Part load operation significantly lowers annual operating costs Galvanized steel construction with attractive black mat epoxy powder coat paint and silver accents Stainless steel drain pan Foil-backed insulation in air handler section Unique double isolation compressor mounting with vibration isolation springs for quiet operation Insulated divider and separate compressor/air handler compartments TXV metering device Extended range (20 to 120 F, -6.7 to 48.9 C) operation Microprocessor controls standard (optional DXM and/ or DDC controls) LonWorks, BACnet, Modbus and Johnson N2 compatibility options for DDC controls Field convertible discharge air arrangement for horizontal units Low profile slanted control box for easy access Internally trapped condensate drain line (vertical units only) Flush securely-mounted corner post water connections (no backup wrench required) Unit Performance Sentinel performance monitoring system Eight Safeties Standard Wide variety of options including e-coated air coils and internal pumps The Tranquility 27 (TT) Series water-source heat pumps are designed to meet the challenges of today s HVAC demands with one of the most innovative products available on the market. 12

The Smart Choice for Energy Efficiency Easy to remove blower housing for quick service with General Electric ECM variable speed motor Standard stainless steel insulated drain pan with condensate overflow protection Foil faced insulation in the blower section with fiberglass insulation in the compressor section Easy Service Access from multiple sides Factory installed hanger brackets Copeland UltraTech two-stage compressor with double spring and grommet isolation Easy access control box contains advanced digital controls with Remote Service Sentinel Optional Enhanced controls (DXM) & DDC Controllers 13

ClimateMaster Water-Source Heat Pumps Tranquility 27 Two-Stage (TT) Series 2 to 5.5 Ton Horizontal and Vertical EarthPure Units About ARI/ISO/ASHRAE 13256-1 The performance standard ARI/ASHRAE/ISO 13256-1 became effective January 1, 2000 and replaces ARI Stan dards 320, 325, and 330. This new standard has three major categories: Water Loop (com pa ra ble to ARI 320), Ground Water (ARI 325), and Ground Loop (ARI 330). Although these standards are similar there are some differences: Entering Water Conditions Changes Entering water temperatures have changed to reflect the centigrade temperature scale. For instance the water loop heating test is performed with 68 F (20 C) water instead of 70 F. Entering Air Condition Changes Entering air temperatures have changed to reflect the centigrade temperature scale. For instance the cooling tests are performed with 80.6 F (27 C) dry bulb and 66.2 F (19 C) wet bulb entering air instead of the traditional 80 F DB and 67 F WB entering air temperatures. 80/67 and 70 data (as presented in performance data on pages 16-26) may be converted to the new ISO conditions of 80.6/66.2 and 68 using the entering air correction table on page 14. Pump Power Correction Within each model, only one water flow rate is specified for all three groups and pumping watts are calculated using the following formula. This additional power is added onto the existing power consumption. Pump power correction = (gpm x 0.0631) x (Press Drop x 2990) / 300 Where 'gpm' is waterflow in gpm and 'Press Drop' is the pressure drop through the unit heat ex chang er at rated water flow in feet of head. Fan Power Correction Fan power is corrected to zero external static pressure using the following equation. The nominal airflow is rated at a specific external static pressure. This effectively reduces the power con sump tion of the unit and increases cooling capacity but decreases heating capacity. These watts are sig nifi cant enough in most cases to increase EER and COP's fairly dramatically over ARI 320, 325, and 330 ratings. Fan Power Cor rec tion = (cfm x 0.472) x (esp x 249) / 300 Where 'cfm' is airflow in cfm and esp is the external static pressure at rated airflow in inches of water gauge. ISO Capacity and Efficiency Equations The following equations illustrate cooling calculations: ISO Cooling Capacity = Cooling Capacity (Btuh) + (Fan Power Correction (Watts) x 3.412) ISO EER Efficiency (W/W) = [ISO Cooling Capacity (Btuh) 3.412] / [Power Input (watts) Fan Power Correction (watts) + Pump Power Correction (watt)] The following equations illustrate heating calculations: ISO Heating Capacity = Heating Capacity (Btuh) - (Fan Power Correction (Watts) x 3.412) ISO COP Efficiency (W/W) = [ISO Heating Capacity (Btuh) 3.412] / [Power Input (watts) - Fan Power Correction (watts) + Pump Power Correction (watt)] ARI 320 ISO WLHP ARI 325 ISO GWHP ARI 330 ISO GLHP Cooling Entering Air -DB/WB F 80/67 80.6/66.2 80/67 80.6/66.2 80/67 80.6/66.2 Entering Water - F 85 86 50/70 59 77 77 Fluid Flow Rate Note 1 Note 2 Note 2 Note 2 Note 2 Note 2 Heating Entering Air - F 70 68 70 68 70 68 Entering Water - F 70 68 50/70 50 32 32 Fluid Flow Rate Note 1 Note 2 Note 2 Note 2 Note 2 Note 2 Note 1: Flow rate is set by 10 F rise in standard cooling test. Note 2: Flow rate is specified by manufacturer. Rev.: 3/09/01 14

The Smart Choice for Energy Efficiency ARI/ISO/ASHRAE 13256-1 Data ASHRAE/ARI/ISO 13256-1. English (IP) Units Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump Model TTH/V/D 026 TTH/V/D 038 TTH/V/D 049 TTH/V/D 064 Capacity Modulation Cooling 86 F Heating 68 F Cooling 59 F Heating 50 F Capacity Btuh EER Btuh/W Capacity Btuh COP Capacity Btuh EER Btuh/W Capacity Btuh COP Cooling Full Load 77 F Part Load 68 F Capacity Btuh EER Btuh/W Heating Full Load 32 F Part Load 41 F Capacity Btuh Full 25,300 15.9 30,800 5.3 28,900 24.5 25,700 4.8 26,600 18.5 19,800 4.0 Part 19,400 18.3 22,400 6.1 22,200 30.8 18,600 5.1 21,300 26.0 16,500 4.6 Full 36,200 15.6 44,800 5.3 41,200 23.0 36,700 4.7 38,200 18.2 29,000 4.0 Part 26,200 18.5 30,800 6.3 30,200 31.5 24,800 5.1 28,900 27.0 2,100 4.5 Full 48,400 15.7 59,900 5.2 54,600 22.5 48,300 4.7 50,600 17.9 37,500 4.0 Part 36,100 18.0 44,300 6.2 40,700 28.7 35,400 5.1 39,600 24.9 31,200 4.6 Full 61,500 15.0 72,300 5.0 68,600 22.0 59,600 4.4 64,800 17.5 48,000 3.9 Part 44,900 17.6 51,100 5.7 51,900 29.7 41,800 4.7 49,800 25.3 37,500 4.3 COP Cooling capacities based upon 80.6 F DB, 66.2 F WB entering air temperature Heating capacities based upon 68 F DB, 59 F WB entering air temperature Ground Loop Heat Pump ratings based on 15% antifreeze solution All ratings based upon operation at lower voltage of dual voltage rated models ASHRAE/ARI/ISO 13256-1. Metric (SI) Units Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump Model TTH/V/D 026 TTH/V/D 038 TTH/V/D 049 TTH/V/D 064 Capacity Modulation Cooling 30 C Heating 20 C Cooling 15 C Heating 10 C Capacity Watts EER W/W Capacity Watts COP Capacity Watts EER W/W Capacity Watts COP Cooling Full Load 25 C Part Load 20 C Capacity Watts EER W/W Heating Full Load 0 C Part Load 5 C Capacity Watts Full 7,415 4.7 9,027 5.3 8,470 7.2 7,532 4.8 7,796 5.4 5,803 4.0 Part 5,686 5.4 6,565 6.1 6,506 9.0 5,451 5.1 6,243 7.6 4,836 4.6 Full 10,610 4.6 13,130 5.3 12,075 6.7 10,756 4.7 11,196 5.3 8,499 4.0 Part 7,679 5.4 9,027 6.3 8,851 9.2 7,268 5.1 8,470 7.9 6,477 4.5 Full 14,185 4.6 17,556 5.2 16,002 6.6 14,156 4.7 14,830 5.2 10,991 4.0 Part 10,580 5.3 12,984 6.2 11,928 8.4 10,375 5.1 11,606 7.3 9,144 4.6 Full 18,025 4.4 21,190 5.0 20,106 6.4 17,468 4.4 18,992 5.1 14,068 3.9 Part 13,159 5.2 14,977 5.7 15,211 8.7 12,251 4.7 14,596 7.4 10,991 4.3 COP Cooling capacities based upon 27 C DB, 19 C WB entering air temperature Heating capacities based upon 20 C DB, 15 C WB entering air temperature Ground Loop Heat Pump ratings based on 15% antifreeze solution All ratings based upon operation at lower voltage of dual voltage rated models 15

ClimateMaster Water-Source Heat Pumps Tranquility 27 Two-Stage (TT) Series 2 to 5.5 Ton Horizontal and Vertical EarthPure Units Model Nomenclature 1 2 TT Model Type TT = Tranquility Two-Stage Scroll 3 V 4 5 6 7 8 9 10 11 12 13 14 0 2 6 A G C 3 0 C L K Supply Air & Motor Option Configuration Option Supply Configuration Motor V = Vertical Upflow K Top TSV ECM H = Horizontal D = Vertical Downflow N Down TSD ECM P Back TSH ECM W Straight TSH ECM Unit Size 026 038 Return Air 049 064 15 S L = Left Return R = Right Return Standard S = Standard Revision Level A = Current Revision Voltage G = 208-230/60/1 H = 208-230/60/3 F = 460/60/3 Controls C = CXM D = DXM L = CXM w/lon M = DXM w/lon N = CXM w/mpc P = DXM w/mpc Cabinet Insulation 1 = Extended Range 2 = Extended Range w/ultraquiet 3 = Standard Range 4 = Standard Range w/ultraquiet Heat Exchanger & Valve Options Non Coated Air Coil Coated Air Coil Copper Cupro-Nickel Copper Cupro-Nickel Standard ClimaDry Reheat C E N P Water Circuit Options 0 = None 2 = HWG (Coil Only) 5 = Secondary Circulating Pump 6 = HWG (Coil Only) w/auto Flow Regulator 2.5 GPM/Ton 7 = HWG (Coil Only) w/auto Flow Regulator 3.0 GPM/Ton 8 = Auto Flow Regulator 2.5 GPM/Ton 9 = Auto Flow Regulator 3.0 GPM/Ton A D J F Motorized Valve T S U W Rev.: 03/02/06D Reference Calculations Heating LWT = EWT - LAT = EAT + HE GPM x 500 HC CFM x1.08 HR LWT = EWT + GPM x 500 LAT (DB) = EAT (DB) - Cooling SC CFM x1.08 LC = TC - SC S/T = SC TC Legend and Glossary of Abbreviations BTUH = BTU( British Thermal Unit) per hour CFM = airfl ow, cubic feet/minute COP = coefficient of performance = BTUH output/btuh input DB = dry bulb temperature ( F) EAT = entering air temperature, Fahrenheit (dry bulb/wet bulb) EER = energy effi ciency ratio = BTUH output/watt input ESP = external static pressure (inches w.g.) EWT = entering water temperature GPM = water fl ow in U.S. gallons/minute HE = total heat of extraction, BTUH HC = air heating capacity, BTUH HR = total heat of rejection, BTUH HWC = hot water generator (desuperheater) capacity, Mbtuh KW = total power unit input, kilowatts LAT = leaving air temperature, F LC = latent cooling capacity, BTUH LWT = leaving water temperature, F MBTUH = 1000 BTU per hour S/T = sensible to total cooling ratio SC = sensible cooling capacity, BTUH TC = total cooling capacity, BTUH WB = wet bulb temperature ( F) WPD = waterside pressure drop (psi & ft. of hd.) Conversion Table - to convert inch-pound (English) to SI (Metric) Air Flow Water Flow Ext Static Pressure Water Pressure Drop Airflow (L/s) = CFM x 0.472 Water Flow (L/s) = gpm x 0.0631 ESP (Pa) = ESP (in of wg) x 249 PD (kpa) = PD (ft of hd) x 2.99 16

The Smart Choice for Energy Efficiency Full Load Correction Tables Air Flow Correction Table Airfl ow Cooling Heating % of Rated Total Capacity Sensible Capacity Power Heat of Rejection Heating Capacity Power Heat of Extraction 60% 0.925 0.788 0.913 0.922 0.946 1.153 0.896 69% 0.946 0.829 0.926 0.942 0.959 1.107 0.924 75% 0.960 0.861 0.937 0.955 0.969 1.078 0.942 81% 0.972 0.895 0.950 0.968 0.977 1.053 0.959 88% 0.983 0.930 0.965 0.979 0.985 1.032 0.974 94% 0.992 0.965 0.982 0.990 0.993 1.014 0.988 100% 1.000 1.000 1.000 1.000 1.000 1.000 1.000 106% 1.007 1.033 1.020 1.009 1.006 0.989 1.011 113% 1.012 1.064 1.042 1.018 1.012 0.982 1.019 119% 1.016 1.092 1.066 1.025 1.018 0.979 1.027 125% 1.018 1.116 1.091 1.032 1.022 0.977 1.033 130% 1.019 1.132 1.112 1.037 1.026 0.975 1.038 Entering Air Correction Table Entering Air DB F Heating Heating Capacity Power Heat of Extraction 40 1.052 0.779 1.120 45 1.043 0.808 1.102 50 1.035 0.841 1.084 55 1.027 0.877 1.065 60 1.019 0.915 1.045 65 1.010 0.957 1.023 68 1.004 0.982 1.010 70 1.000 1.000 1.000 75 0.989 1.045 0.974 80 0.976 1.093 0.946 * = Sensible capacity equals total capacity ARI/ISO/ASHRAE 13256-1 uses entering air conditions of Cooling - 80.6 F DB/66.2 F WB, 1 and Heating - 68 F DB/59 F WB entering air temperature Entering Air WB F Total Capacity Cooling Sensible Cooling Capacity Multiplier - Entering DB F 60 65 70 75 80 80.6 85 90 95 100 Power Heat of Rejection 45 0.832 1.346 1.461 1.603 * * * * * * * 0.946 0.853 50 0.850 1.004 1.174 1.357 * * * * * * * 0.953 0.870 55 0.880 0.694 0.902 1.115 1.331 * * * * * * 0.964 0.896 60 0.922 0.646 0.875 1.103 1.329 1.356 * * * * 0.977 0.932 65 0.975 0.639 0.869 1.096 1.123 1.320 * * * 0.993 0.979 66.2 0.990 0.582 0.812 1.039 1.066 1.262 1.482 * * 0.997 0.991 67 1.000 0.545 0.774 1.000 1.027 1.223 1.444 * * 1.000 1.000 70 1.040 0.630 0.853 0.880 1.075 1.297 1.517 * 1.011 1.035 75 1.117 0.601 0.627 0.821 1.046 1.275 1.510 1.033 1.101 17

ClimateMaster Water-Source Heat Pumps Tranquility 27 Two-Stage (TT) Series 2 to 5.5 Ton Horizontal and Vertical EarthPure Units Part Load Correction Tables Air Flow Correction Table Airfl ow Cooling Heating % of Rated Total Capacity Sensible Capacity Power Heat of Rejection Heating Capacity Power Heat of Extraction 60% 0.920 0.781 0.959 0.927 0.946 1.241 0.881 69% 0.942 0.832 0.964 0.946 0.960 1.163 0.915 75% 0.956 0.867 0.696 0.959 0.969 1.115 0.937 81% 0.969 0.901 0.975 0.970 0.978 1.076 0.956 88% 0.981 0.934 0.982 0.981 0.986 1.043 0.973 94% 0.991 0.967 0.990 0.991 0.993 1.018 0.988 100% 1.000 1.000 1.000 1.000 1.000 1.000 1.000 106% 1.007 1.033 1.011 1.008 1.006 0.990 1.010 113% 1.013 1.065 1.023 1.015 1.012 0.986 1.017 119% 1.018 1.098 1.036 1.021 1.017 0.983 1.024 125% 1.021 1.131 1.051 1.026 1.021 0.981 1.030 130% 1.023 1.159 1.063 1.030 1.024 0.979 1.034 Entering Air Correction Table Entering Air DB F Heating Heating Capacity Power Heat of Extraction 40 1.084 0.732 1.161 45 1.073 0.764 1.140 50 1.060 0.802 1.117 55 1.046 0.846 1.090 60 1.031 0.893 1.061 65 1.016 0.945 1.031 68 1.006 0.978 1.013 70 1.000 1.000 1.000 75 0.984 1.058 0.968 80 0.968 1.117 0.936 Entering Air WB F Total Capacity * = Sensible capacity equals total capacity ARI/ISO/ASHRAE 13256-1 uses entering air conditions of Cooling - 80.6 F DB/66.2 F WB, 1 and Heating - 68 F DB/59 F WB entering air temperature Cooling Sensible Cooling Capacity Multiplier - Entering DB F 60 65 70 75 80 80.6 85 90 95 100 Power Heat of Rejection 45 0.876 1.286 1.302 1.389 * * * * * * * 0.981 0.895 50 0.883 1.002 1.099 1.241 * * * * * * * 0.985 0.901 55 0.903 0.706 0.871 1.060 1.271 * * * * * * 0.989 0.918 60 0.935 0.617 0.844 1.079 1.319 1.349 * * * * 0.993 0.945 65 0.979 0.595 0.849 1.096 1.128 1.342 * * * 0.998 0.982 66.2 0.991 0.531 0.789 1.040 1.070 1.284 1.522 * * 0.999 0.993 67 1.000 0.486 0.747 1.000 1.030 1.245 1.481 * * 1.000 1.000 70 1.035 0.583 0.842 0.873 1.090 1.327 1.552 * 1.003 1.030 75 1.105 0.552 0.584 0.811 1.057 1.290 1.510 1.008 1.088 18

The Smart Choice for Energy Efficiency Antifreeze Correction Table Antifreeze & Water Valve Correction Tables Antifreeze Type Anitfreeze % Cooling Heating EWT 90 F EWT 30 F Total Cap Sens Cap Power Htg Cap Power WPD Corr. Fct. EWT 30 F Water 0 1.000 1.000 1.000 1.000 1.000 1.000 Propylene Glycol Methanol Ethanol Ethylene Glycol 5 0.995 0.995 1.003 0.989 0.997 1.070 15 0.986 0.986 1.009 0.968 0.990 1.210 25 0.978 0.978 1.014 0.947 0.983 1.360 5 0.997 0.997 1.002 0.989 0.997 1.070 15 0.990 0.990 1.007 0.968 0.990 1.160 25 0.982 0.982 1.012 0.949 0.984 1.220 5 0.998 0.998 1.002 0.981 0.994 1.140 15 0.994 0.994 1.005 0.944 0.983 1.300 25 0.986 0.986 1.009 0.917 0.974 1.360 5 0.998 0.998 1.002 0.993 0.998 1.040 15 0.994 0.994 1.004 0.980 0.994 1.120 25 0.988 0.988 1.008 0.966 0.990 1.200 Motorized Water Valve Corrections Model Cv MOPD WPD Adders (Part Load) WPD Adders (Full Load) GPM PSI FT GPM PSI FT 10.3 125 3.5 0.12 0.27 4.0 0.15 0.35 026 10.3 125 5.8 0.31 0.72 6.0 0.34 0.78 10.3 125 7.0 0.46 1.07 8.0 0.60 1.39 10.3 125 4.0 0.15 0.35 4.5 0.19 0.44 038 10.3 125 6.0 0.34 0.78 6.8 0.43 0.99 10.3 125 8.0 0.60 1.39 9.0 0.76 1.76 10.3 125 5.5 0.29 0.66 6.0 0.34 0.78 049 10.3 125 8.3 0.64 1.48 9.0 0.76 1.76 10.3 125 11.0 1.14 2.63 12.0 1.36 3.14 8.9 125 7.0 0.62 1.43 7.5 0.71 1.64 064 8.9 125 10.5 1.39 3.22 11.3 1.60 3.69 8.9 125 14.0 2.47 5.72 15.0 2.84 6.56 19

ClimateMaster Water-Source Heat Pumps Tranquility 27 Two-Stage (TT) Series 2 to 5.5 Ton Horizontal and Vertical EarthPure Units Unit Model Number Des ig na tion TTH = Horizontal Heat Pump TTV = Vertical Heat Pump TTD = Downflow Heat Pump Capacity Table Index TT 026-064 - See Page 22-29. Glossary of Terms See Page 16. Selection Procedure Step 1 Determine the actual heating and cooling loads at the desired dry bulb and wet bulb conditions. Step 2 Obtain the following de sign parameters: Entering water temperature, water flow rate in GPM, air flow in CFM, water flow pressure drop and design wet and dry bulb temperatures. Air flow CFM should be between 300 and 450 CFM per ton. Unit water pressure drop should be kept as close as possible to each other to make water balancing easier. Go to the ap pro pri ate tables and find the proper indicated water flow and water tem per a ture. Step 3 Select a unit based on total and sensible cooling conditions. Select a unit which is closest to, but no larger than, the actual cooling load. Step 4 Enter tables at the design water flow and water temperature. Read the total and sensible cooling capacities (Note: interpolation is per mis si ble, ex trap o la tion is not). Step 5 Read the heating capacity. If it exceeds the design criteria it is acceptable. It is quite normal for Water- Source Heat Pumps to be selected on cooling capacity only since the heating output is usually greater than the cooling capacity. Step 6 Determine the correction factors associated with the variable factors of dry bulb and wet bulb (page 14). Corrected Total Cooling = tabulated total cooling x wet bulb correction. Corrected Sensible Cooling = tabulated sensible cooling x wet/dry bulb correction. Step 7 Compare the corrected capacities to the load re quire ments. Normally if the capacities are within 10% of the loads, the equipment is ac cept able. It is better to undersize than oversize, as undersizing improves humidity control, reduces sound levels and extends the life of the equip ment. Step 8 When completed, calculate water temperature rise and assess the selection. If the units selected are not within 10% of the load cal cu la tions, then review what effect chang ing the GPM, water temperature and/or air flow and air tem per a ture would have on the corrected capacities. If the desired capacity cannot be achieved, select the next larger or smaller unit and repeat the procedure. Remember, when in doubt, undersize slightly for best performance. Example Equipment Selection For Cool ing Step 1 Load Determination: Assume we have determined that the appropriate cooling load at the desired dry bulb 80 F and wet bulb 65 F con di tions is as follows: Total Cooling...22,100 BTUH Sensible Cooling...16,500 BTUH Entering Air Temp... 80 F Dry Bulb / 65 F Wet Bulb Step 2 Design Conditions: Similarly, we have also obtained the following design pa ram e- ters: Entering Water Temp... 90 F Water Flow (Based upon 10 F rise in temp.) 6.0 GPM Air Flow...730 CFM Step 3, 4 & 5 HP Selection: After making our preliminary selection (TTH026 - Full Load), we enter the tables at design water flow and water tem per a ture and read Total Cooling, Sens. Cooling and Heat of Rej. ca pac i ties: Total Cooling...24,200 BTUH Sensible Cooling...16,300 BTUH Heat of Rejection...29,900 BTUH Step 6 & 7 Entering Air and Airflow Corrections: Next, we determine our correction factors. Table Ent Air Air Flow Cor rect ed Corrected Total Cooling = 24,200 x 0.975 x 0.978 = 23,076 Corrected Sens Cooling = 16,300 x 1.096 x 0.926 = 16,543 Corrected Heat of Reject = 29,900 x 0.979 x 0.978 = 28,628 Step 8 Water Temperature Rise Calculation & As sess ment: Actual Temperature Rise 9.5 F When we compare the Corrected Total Cooling and Corrected Sensible Cooling figures with our load re quire ments stated in Step 1, we discover that our selection is within +/- 10% of our sensible load requirement. Fur ther more, we see that our Cor rect ed Total Cooling figure is within 1,000 Btuh the actual in di cat ed load. 20

The Smart Choice for Energy Efficiency For operation in the shaded area when water is used in lieu of an anti-freeze solution, the LWT (Leaving Water Temperature) must be calculated. Flow must be maintained to a level such that the LWT is maintained above 40 F [4.4*C] when the JW3 jumper is not clipped (see example below). This is due to the potential of the refrigerant temperature being as low as 32 F [0 C] with 40 F [4.4 C] LWT, which may lead to a nuisance cutout due to the activation of the Low Temperature Protection. JW3 should never be clipped for standard range equipment or systems without antifreeze. Example: At 50 F EWT (Entering Water Temperature) and 1.5 gpm/ ton, a 3 ton unit has a HE of 22,500 Btuh. To calculate LWT, rearrange the formula for HE as follows: HE = TD x GPM x 500, where HE = Heat of Extraction (Btuh); TD = temperature difference (EWT - LWT) and GPM = U.S. Gallons per Minute. Heating - EAT 70 F Performance Data Selection Notes Airfl ow ER CFM HC kw HE LAT COP 0 710 11.6 1.05 8.2 85.1 3.25 0 825 11.7 1.02 8.4 83.2 3.38 38.3 710 13.6 1.09 10.1 87.8 3.66 38.3 825 13.8 1.06 10.3 85.5 3.81 39.2 710 14.2 1.09 10.7 88.5 3.81 39.2 825 14.4 1.06 10.9 86.1 3.97 4 39.8 710 14.4 1.09 10.9 88.8 3.86 7 39.8 825 14.6 1.06 11.1 86.3 4.02 35.3 710 16.1 1.15 12.3 90.9 4.08 5 35.3 825 16.2 1.12 12.6 88.2 4.25 37.9 710 16.7 1.15 13.0 91.8 4.25 37.9 825 16.9 1.12 13.3 89.0 4.42 38.3 710 16.9 1.16 13.2 92.1 4.30 38.3 825 17.1 1.12 13.5 89.2 4.47 30.7 710 18.3 1.18 14.5 93.9 4.56 30.7 825 18.5 1.14 14.8 90.8 4.75 33.4 710 19.1 1.18 15.2 94.8 4.73.4 825 19.3 1.15 15.5 91.6 4.93 710 19.3 1.18 15.4 95.1 4.78 825 19.5 1.15 15.7 91.9 4.98 710 20.4 1.21 16.5 96.6 4.93 20.6 1.18 16.8 93.2 5 21.2 1.22 17.3 97.7 118 176 TD = HE / (GPM x 500) TD = 22,500 / (4.5 x 500) TD = 10 F LWT = EWT - TD LWT = 50-10 = 40 F In this example, as long as the EWT does not fall below 50 F, the system will operate as designed. For EWTs below 50 F, higher fl ow rates will be required (open loop systems, for example, require at least 2 gpm/ton when EWT is below 50 F). 21

ClimateMaster Water-Source Heat Pumps Tranquility 27 Two-Stage (TT) Series 2 to 5.5 Ton Horizontal and Vertical EarthPure Units Performance Data TT 026 Part Load 725 CFM Nominal (Rated) Airflow Cooling, 825 CFM Nominal (Rated) Airfl ow Heating Performance capacities shown in thousands of Btuh WPD Cooling - EAT 80/67 F Heating - EAT 70 F EWT GPM F Airflow PSI FT CFM TC SC Sens/Tot Airfl ow Ratio kw HR EER CFM HC kw HE LAT COP 20 7.0 4.5 10.3 0 0 0 0 0 0 0 710 11.6 1.05 8.2 85.1 3.25 20 Operation not recommended 20 7.0 4.5 10.3 0 0 0 0 0 0 0 825 11.7 1.02 8.4 83.2 3.38 30 3.5 1.2 2.8 620 22.2 14.0 0.63 0.58 24.1 38.3 710 13.6 1.09 10.1 87.8 3.66 30 3.5 1.2 2.8 725 22.5 14.7 0.65 0.59 24.4 38.3 825 13.8 1.06 10.3 85.5 3.81 30 5.8 2.9 6.6 620 22.4 14.0 0.63 0.57 24.3 39.2 710 14.2 1.09 10.7 88.5 3.81 30 30 5.8 2.9 6.6 725 22.7 14.7 0.65 0.58 24.7 39.2 825 14.4 1.06 10.9 86.1 3.97 30 7.0 4.1 9.4 620 22.5 14.0 0.62 0.56 24.4 39.8 710 14.4 1.09 10.9 88.8 3.86 30 7.0 4.1 9.4 725 22.8 14.7 0.65 0.57 24.7 39.8 825 14.6 1.06 11.1 86.3 4.02 40 3.5 1.1 2.5 620 22.9 15.1 0.66 0.65 25.1 35.3 710 16.1 1.15 12.3 90.9 4.08 40 3.5 1.1 2.5 725 23.3 15.8 0.68 0.66 25.5 35.3 825 16.2 1.12 12.6 88.2 4.25 40 5.8 2.6 5.9 620 23.1 15.1 0.65 0.61 25.2 37.9 710 16.7 1.15 13.0 91.8 4.25 40 40 5.8 2.6 5.9 725 23.4 15.9 0.68 0.62 25.5 37.9 825 16.9 1.12 13.3 89.0 4.42 40 7.0 3.6 8.4 620 23.2 15.1 0.65 0.6 25.2 38.3 710 16.9 1.16 13.2 92.1 4.30 40 7.0 3.6 8.4 725 23.5 15.9 0.68 0.61 25.6 38.3 825 17.1 1.12 13.5 89.2 4.47 50 3.5 1.0 2.3 620 22.7 15.4 0.68 0.74 25.2 30.7 710 18.3 1.18 14.5 93.9 4.56 50 3.5 1.0 2.3 725 23.0 16.2 0.70 0.75 25.6 30.7 825 18.5 1.14 14.8 90.8 4.75 50 5.8 2.4 5.6 620 22.9 15.5 0.67 0.69 25.3 33.4 710 19.1 1.18 15.2 94.8 4.73 50 50 5.8 2.4 5.6 725 23.3 16.3 0.70 0.70 25.6 33.4 825 19.3 1.15 15.5 91.6 4.93 50 7.0 3.4 7.9 620 23.0 15.5 0.67 0.67 25.3 34.1 710 19.3 1.18 15.4 95.1 4.78 50 7.0 3.4 7.9 725 23.3 16.3 0.70 0.68 25.6 34.1 825 19.5 1.15 15.7 91.9 4.98 60 3.5 1.0 2.2 620 21.9 15.3 0.70 0.85 24.8 25.9 710 20.4 1.21 16.5 96.6 4.93 60 3.5 1.0 2.2 725 22.2 16.1 0.73 0.86 25.1 25.9 825 20.6 1.18 16.8 93.2 5.13 60 5.8 2.3 5.2 620 22.4 15.5 0.69 0.78 25.1 28.6 710 21.2 1.22 17.3 97.7 5.10 60 60 5.8 2.3 5.2 725 22.7 16.3 0.72 0.80 25.4 28.6 825 21.5 1.18 17.6 94.1 5.31 60 7.0 3.2 7.4 620 22.5 15.5 0.69 0.77 25.1 29.4 710 21.5 1.22 17.5 98.0 5.15 60 7.0 3.2 7.4 725 22.9 16.3 0.71 0.78 25.5 29.4 825 21.7 1.19 17.8 94.3 5.36 70 3.5 0.9 2.1 620 20.7 14.8 0.72 0.97 24.0 21.4 710 22.4 1.23 18.4 99.2 5.35 70 3.5 0.9 2.1 725 21.0 15.6 0.74 0.98 24.3 21.4 825 22.7 1.19 18.8 95.4 5.57 70 5.8 2.1 4.9 620 21.4 15.1 0.71 0.90 24.4 23.8 710 23.3 1.24 19.3 100.4 5.52 70 70 5.8 2.1 4.9 725 21.7 15.9 0.73 0.91 24.8 23.8 825 23.5 1.20 19.6 96.4 5.75 70 7.0 3.0 7.0 620 21.6 15.2 0.71 0.88 24.6 24.5 710 23.5 1.24 19.5 100.7 5.57 70 7.0 3.0 7.0 725 21.9 16.0 0.73 0.89 24.9 24.5 825 23.8 1.20 19.9 96.7 5.80 80 3.5 0.8 1.9 620 19.3 14.2 0.73 1.10 23.1 17.5 710 24.4 1.25 20.3 101.8 5.73 80 3.5 0.8 1.9 725 19.6 14.9 0.76 1.12 23.4 17.5 825 24.6 1.21 20.7 97.7 5.97 80 5.8 2.0 4.6 620 20.1 14.5 0.72 1.03 23.6 19.5 710 25.3 1.26 21.2 103.0 5.90 80 80 5.8 2.0 4.6 725 20.4 15.3 0.75 1.04 23.9 19.5 825 25.6 1.22 21.6 98.7 6.15 80 7.0 2.8 6.5 620 20.3 14.6 0.72 1.01 23.7 20.1 710 25.6 1.26 21.5 103.4 5.95 80 7.0 2.8 6.5 725 20.6 15.4 0.75 1.02 24.0 20.1 825 25.9 1.22 21.9 99.0 6.20 85 3.5 0.8 1.9 620 18.7 13.9 0.75 1.18 22.7 15.9 710 25.3 1.26 21.2 103.0 5.91 85 3.5 0.8 1.9 725 18.9 14.6 0.77 1.19 23.0 15.9 825 25.6 1.22 21.7 98.7 6.15 85 5.8 1.9 4.5 620 19.3 14.2 0.73 1.10 23.1 17.5 710 26.3 1.27 22.2 104.3 6.08 85 85 5.8 1.9 4.5 725 19.6 14.9 0.76 1.12 23.4 17.5 825 26.6 1.23 22.6 99.9 6.33 85 7.0 2.7 6.3 620 19.5 14.3 0.73 1.08 23.2 18.0 710 26.6 1.27 22.5 104.7 6.13 85 7.0 2.7 6.3 725 19.8 15.0 0.76 1.10 23.6 18.0 825 26.9 1.24 22.9 100.2 6.38 90 3.5 0.8 1.8 620 18.0 13.7 0.76 1.25 22.3 14.4 710 26.3 1.27 22.2 104.3 6.08 90 3.5 0.8 1.8 725 18.3 14.4 0.78 1.27 22.6 14.4 825 26.6 1.23 22.6 99.8 6.33 90 5.8 1.9 4.4 620 18.6 13.8 0.74 1.18 22.6 15.8 710 27.3 1.28 23.1 105.6 6.25 90 90 5.8 1.9 4.4 725 18.9 14.6 0.77 1.20 22.9 15.8 825 27.6 1.24 23.6 101.0 6.51 90 7.0 2.7 6.2 620 18.8 13.9 0.74 1.16 22.7 16.3 710 27.6 1.28 23.4 106.0 6.30 90 7.0 2.7 6.2 725 19.1 14.7 0.77 1.17 23.1 16.3 825 27.9 1.25 23.9 101.3 6.56 100 3.5 0.8 1.8 620 16.6 13.0 0.78 1.41 21.4 11.7 0 0 0 0 0 0 100 3.5 0.8 1.8 725 16.8 13.7 0.81 1.43 21.7 11.7 0 0 0 0 0 0 100 5.8 1.8 4.2 620 17.1 13.2 0.77 1.34 21.7 12.7 0 0 0 0 0 0 100 100 5.8 1.8 4.2 725 17.4 13.8 0.80 1.36 22.0 12.7 0 0 0 0 0 0 100 7.0 2.6 6.0 620 17.3 13.3 0.77 1.32 21.8 13.1 0 0 0 0 0 0 100 7.0 2.6 6.0 725 17.5 13.9 0.79 1.34 22.1 13.1 0 0 0 0 0 0 110 3.5 0.7 1.7 620 15.5 12.7 0.82 1.59 20.9 9.7 0 0 0 0 0 0 110 3.5 0.7 1.7 725 15.7 13.4 0.85 1.61 21.2 9.7 0 0 0 0 0 0 110 5.8 1.7 4.0 620 15.8 12.7 0.80 1.53 21.0 10.3 0 0 0 0 0 0 110 110 5.8 1.7 4.0 725 16.0 13.3 0.83 1.55 21.3 10.3 0 Operation 0 0 not recommended 0 0 0 110 7.0 2.5 5.7 620 16.0 12.7 0.80 1.50 21.1 10.6 0 0 0 0 0 0 110 7.0 2.5 5.7 725 16.2 13.4 0.83 1.52 21.4 10.6 0 0 0 0 0 0 120 3.5 0.7 1.6 620 14.5 12.6 0.87 1.84 20.8 7.9 0 0 0 0 0 0 120 3.5 0.7 1.6 725 14.7 13.3 0.90 1.86 21.1 7.9 0 0 0 0 0 0 120 5.8 1.7 3.9 620 14.8 12.5 0.85 1.73 20.7 8.6 0 0 0 0 0 0 120 120 5.8 1.7 3.9 725 15.0 13.2 0.88 1.76 21.0 8.6 0 0 0 0 0 0 120 7.0 2.4 5.5 620 14.9 12.5 0.84 1.71 20.7 8.7 0 0 0 0 0 0 120 7.0 2.4 5.5 725 15.1 13.2 0.87 1.73 21.0 8.7 0 0 0 0 0 0 Interpolation is permissible; extrapolation is not. All entering air conditions are 80 F DB and 67 F WB in cooling, and 70 F DB in heating. ARI/ISO certifi ed conditions are 80.6 F DB and 66.2 F WB in cooling and 68 F DB in heating. Table does not refl ect fan or pump power corrections for ARI/ISO conditions. All performance is based upon the lower voltage of dual voltage rated units. Operation below 40 F EWT is based upon a 15% antifreeze solution. Operation below 60 F EWT requires optional insulated water/refrigerant circuit. See performance correction tables for operating conditions other than those listed above. See Performance Data Selection Notes for operation in the shaded areas. 22

The Smart Choice for Energy Efficiency Performance Data TT 026 Full Load 850 CFM Nominal (Rated) Airflow Cooling, 950 CFM Nominal (Rated) Airfl ow Heating Performance capacities shown in thousands of Btuh WPD Cooling - EAT 80/67 F Heating - EAT 70 F EWT GPM F Airfl ow PSI FT CFM TC SC Sens/Tot Airfl ow Ratio kw HR EER CFM HC kw HE LAT COP 20 8.0 5.6 12.9 0 0 0 0 0 0 0 820 15.0 1.47 10.2 86.9 3.00 20 Operation not recommended 20 8.0 5.6 12.9 0 0 0 0 0 0 0 950 15.3 1.41 10.6 84.9 3.19 30 4.0 1.5 3.5 730 30.2 17.9 0.59 0.97 33.4 31.0 820 17.8 1.53 12.7 90.1 3.41 30 4.0 1.5 3.5 850 30.9 19.6 0.63 1.02 34.3 30.4 950 18.1 1.46 13.2 87.7 3.63 30 6.0 3.1 7.2 730 30.3 17.9 0.59 0.93 33.4 32.7 820 18.6 1.54 13.5 91.0 3.53 30 30 6.0 3.1 7.2 850 31.1 19.6 0.63 0.97 34.4 32.1 950 19.0 1.48 14.0 88.5 3.76 30 8.0 5.1 11.7 730 30.5 17.9 0.59 0.91 33.5 33.7 820 19.1 1.55 13.9 91.5 3.59 30 8.0 5.1 11.7 850 31.2 19.6 0.63 0.95 34.5 33.1 950 19.4 1.49 14.4 88.9 3.82 40 4.0 1.4 3.1 730 29.9 18.2 0.61 1.07 33.5 28.1 820 21.2 1.61 15.9 94.0 3.88 40 4.0 1.4 3.1 850 30.6 20.0 0.65 1.11 34.4 27.5 950 21.6 1.54 16.4 91.1 4.12 40 6.0 2.8 6.5 730 30.2 18.3 0.61 1.01 33.6 29.8 820 22.2 1.63 16.7 95.0 3.99 40 40 6.0 2.8 6.5 850 30.9 20.0 0.65 1.06 34.5 29.2 950 22.6 1.56 17.3 92.0 4.24 40 8.0 4.6 10.5 730 30.3 18.3 0.60 0.99 33.6 30.7 820 22.7 1.64 17.2 95.6 4.05 40 8.0 4.6 10.5 850 31.0 20.0 0.65 1.03 34.5 30.1 950 23.1 1.57 17.8 92.5 4.31 50 4.0 1.3 2.9 730 29.1 18.3 0.63 1.17 33.1 24.8 820 24.4 1.69 18.7 97.5 4.24 50 4.0 1.3 2.9 850 29.8 20.0 0.67 1.23 34.0 24.3 950 24.9 1.62 19.4 94.2 4.51 50 6.0 2.6 6.1 730 29.6 18.4 0.62 1.11 33.4 26.7 820 25.4 1.71 19.6 98.7 4.34 50 50 6.0 2.6 6.1 850 30.3 20.1 0.66 1.16 34.3 26.1 950 25.9 1.64 20.3 95.2 4.62 50 8.0 4.3 9.9 730 29.9 18.4 0.62 1.08 33.5 27.6 820 25.9 1.73 20.1 99.3 4.40 50 8.0 4.3 9.9 850 30.6 20.2 0.66 1.13 34.4 27.0 950 26.4 1.66 20.8 95.7 4.68 60 4.0 1.2 2.8 730 28.0 17.9 0.64 1.30 32.4 21.6 820 27.2 1.77 21.3 100.8 4.52 60 4.0 1.2 2.8 850 28.6 19.6 0.69 1.35 33.3 21.2 950 27.8 1.69 22.0 97.1 4.81 60 6.0 2.5 5.7 730 28.7 18.1 0.63 1.23 32.8 23.4 820 28.3 1.8 22.2 101.9 4.62 60 60 6.0 2.5 5.7 850 29.3 19.9 0.68 1.28 33.7 22.9 950 28.8 1.72 23.0 98.1 4.91 60 8.0 4.0 9.3 730 29.0 18.2 0.63 1.19 33.0 24.3 820 28.8 1.81 22.7 102.6 4.66 60 8.0 4.0 9.3 850 29.7 20.0 0.67 1.24 33.9 23.8 950 29.4 1.74 23.5 98.6 4.96 70 4.0 1.1 2.6 730 26.6 17.3 0.65 1.43 31.4 18.5 820 29.9 1.84 23.6 103.7 4.75 70 4.0 1.1 2.6 850 27.2 19.0 0.70 1.50 32.3 18.2 950 30.5 1.77 24.4 99.7 5.05 70 6.0 2.3 5.4 730 27.4 17.7 0.65 1.36 31.9 20.2 820 31.0 1.88 24.6 105.0 4.83 70 70 6.0 2.3 5.4 850 28.0 19.4 0.69 1.42 32.8 19.8 950 31.6 1.80 25.4 100.8 5.14 70 8.0 3.8 8.7 730 27.7 17.8 0.64 1.32 32.2 21.0 820 31.5 1.90 25.1 105.6 4.87 70 8.0 3.8 8.7 850 28.4 19.5 0.69 1.38 33.1 20.6 950 32.1 1.82 25.9 101.3 5.18 80 4.0 1.0 2.4 730 25.0 16.6 0.67 1.59 30.4 15.7 820 32.3 1.92 25.8 106.5 4.93 80 4.0 1.0 2.4 850 25.6 18.3 0.71 1.66 31.2 15.4 950 33.0 1.84 26.7 102.1 5.24 80 6.0 2.2 5.0 730 25.8 17.0 0.66 1.50 30.9 17.2 820 33.5 1.96 26.8 107.8 5.01 80 80 6.0 2.2 5.0 850 26.4 18.7 0.71 1.57 31.8 16.8 950 34.1 1.88 27.7 103.2 5.32 80 8.0 3.5 8.1 730 26.3 17.2 0.66 1.46 31.2 17.9 820 34.0 1.98 27.3 108.4 5.04 80 8.0 3.5 8.1 850 26.9 18.9 0.70 1.53 32.1 17.6 950 34.7 1.90 28.2 103.8 5.36 85 4.0 1.0 2.4 730 24.2 16.3 0.67 1.68 29.9 14.4 820 33.5 1.96 26.8 107.9 5.01 85 4.0 1.0 2.4 850 24.7 17.8 0.72 1.75 30.7 14.1 950 34.2 1.88 27.8 103.3 5.33 85 6.0 2.1 4.9 730 25.0 16.7 0.67 1.59 30.4 15.7 820 34.7 2.00 27.8 109.1 5.08 85 85 6.0 2.1 4.9 850 25.6 18.3 0.71 1.66 31.3 15.4 950 35.3 1.92 28.8 104.4 5.40 85 8.0 3.4 7.9 730 25.4 16.8 0.66 1.55 30.7 16.5 820 35.2 2.02 28.4 109.8 5.12 85 8.0 3.4 7.9 850 26.0 18.5 0.71 1.61 31.5 16.1 950 35.9 1.93 29.3 105.0 5.44 90 4.0 1.0 2.3 730 23.3 15.9 0.68 1.77 29.4 13.2 820 34.7 2.00 27.9 109.2 5.09 90 4.0 1.0 2.3 850 23.9 17.4 0.73 1.84 30.2 13.0 950 35.4 1.92 28.8 104.5 5.41 90 6.0 2.1 4.8 730 24.2 16.3 0.67 1.67 29.9 14.4 820 35.9 2.04 28.9 110.5 5.16 90 90 6.0 2.1 4.8 850 24.7 17.9 0.72 1.75 30.7 14.2 950 36.6 1.95 29.9 105.6 5.48 90 8.0 3.4 7.8 730 24.6 16.5 0.67 1.63 30.2 15.1 820 36.5 2.06 29.4 111.2 5.19 90 8.0 3.4 7.8 850 25.2 18.1 0.72 1.70 31.0 14.8 950 37.2 1.97 30.4 106.2 5.52 100 4.0 1.0 2.2 730 21.7 15.2 0.70 1.97 28.4 11.0 0 0 0 0 0 0 100 4.0 1.0 2.2 850 22.2 16.7 0.75 2.05 29.2 10.8 0 0 0 0 0 0 100 6.0 2.0 4.6 730 22.5 15.5 0.69 1.86 28.9 12.1 0 0 0 0 0 0 100 100 6.0 2.0 4.6 850 23.0 17.0 0.74 1.95 29.7 11.8 0 0 0 0 0 0 100 8.0 3.2 7.4 730 22.9 15.7 0.69 1.81 29.1 12.6 0 0 0 0 0 0 100 8.0 3.2 7.4 850 23.4 17.2 0.74 1.89 29.9 12.4 0 0 0 0 0 0 110 4.0 0.9 2.1 730 20.1 14.6 0.72 2.19 27.7 9.2 0 0 0 0 0 0 110 4.0 0.9 2.1 850 20.6 16.0 0.77 2.29 28.4 9.0 0 0 0 0 0 0 110 6.0 1.9 4.4 730 20.9 14.8 0.71 2.08 28.0 10.0 0 0 0 0 0 0 110 110 6.0 1.9 4.4 850 21.3 16.3 0.76 2.17 28.8 9.8 0 Operation 0 0 not recommended 0 0 0 110 8.0 3.1 7.2 730 21.2 15.0 0.71 2.03 28.2 10.5 0 0 0 0 0 0 110 8.0 3.1 7.2 850 21.7 16.4 0.76 2.11 29.0 10.3 0 0 0 0 0 0 120 4.0 0.9 2.0 730 18.8 14.1 0.75 2.45 27.2 7.7 0 0 0 0 0 0 120 4.0 0.9 2.0 850 19.2 15.5 0.80 2.55 28.0 7.5 0 0 0 0 0 0 120 6.0 1.8 4.2 730 19.4 14.3 0.74 2.32 27.4 8.3 0 0 0 0 0 0 120 120 6.0 1.8 4.2 850 19.8 15.7 0.79 2.43 28.2 8.2 0 0 0 0 0 0 120 8.0 3.0 6.9 730 19.7 14.4 0.73 2.26 27.5 8.7 0 0 0 0 0 0 120 8.0 3.0 6.9 850 20.2 15.8 0.78 2.36 28.3 8.5 0 0 0 0 0 0 Interpolation is permissible; extrapolation is not. All entering air conditions are 80 F DB and 67 F WB in cooling, and 70 F DB in heating. ARI/ISO certifi ed conditions are 80.6 F DB and 66.2 F WB in cooling and 68 F DB in heating. Table does not refl ect fan or pump power corrections for ARI/ISO conditions. All performance is based upon the lower voltage of dual voltage rated units. Operation below 40 F EWT is based upon a 15% antifreeze solution. Operation below 60 F EWT requires optional insulated water/refrigerant circuit. See performance correction tables for operating conditions other than those listed above. See Performance Data Selection Notes for operation in the shaded areas. 23

ClimateMaster Water-Source Heat Pumps Tranquility 27 Two-Stage (TT) Series 2 to 5.5 Ton Horizontal and Vertical EarthPure Units Performance Data TT 038 Part Load 1000 CFM Nominal (Rated) Airflow Cooling, 1000 CFM Nominal (Rated) Airflow Heating Performance capacities shown in thousands of Btuh WPD Cooling - EAT 80/67 F Heating - EAT 70 F EWT GPM F Airfl ow PSI FT CFM TC SC Sens/Tot Airfl ow Ratio kw HR EER CFM HC kw HE LAT COP 20 8.0 4.7 10.9 0 0 0 0 0 0 0 860 17.5 1.60 12.4 88.9 3.21 20 Operation not recommended 20 8.0 4.7 10.9 0 0 0 0 0 0 0 1000 17.7 1.55 12.6 86.4 3.34 30 4.0 1.2 2.8 860 30.4 19.2 0.63 0.79 33.0 38.3 860 19.3 1.61 14.1 90.8 3.52 30 4.0 1.2 2.8 1000 30.8 20.2 0.66 0.80 33.5 38.3 1000 19.5 1.56 14.4 88.1 3.67 30 6.0 2.6 6.1 860 30.7 19.2 0.63 0.75 33.2 40.9 860 20.0 1.61 14.8 91.5 3.64 30 30 6.0 2.6 6.1 1000 31.1 20.2 0.65 0.76 33.6 40.9 1000 20.2 1.56 15.1 88.7 3.79 30 8.0 4.5 10.4 860 30.9 19.3 0.63 0.73 33.3 42.2 860 20.4 1.61 15.2 91.9 3.70 30 8.0 4.5 10.4 1000 31.3 20.3 0.65 0.74 33.8 42.2 1000 20.6 1.57 15.5 89.1 3.85 40 4.0 1.1 2.5 860 31.1 20.8 0.67 0.90 34.1 34.5 860 22.0 1.62 16.8 93.7 3.98 40 4.0 1.1 2.5 1000 31.6 21.8 0.69 0.91 34.6 34.5 1000 22.3 1.57 17.1 90.6 4.15 40 6.0 2.6 5.9 860 31.3 20.8 0.66 0.84 34.2 37.3 860 22.9 1.63 17.6 94.6 4.12 40 40 6.0 2.6 5.9 1000 31.8 21.9 0.69 0.85 34.6 37.3 1000 23.1 1.58 18.0 91.4 4.30 40 8.0 4.4 10.2 860 31.5 20.8 0.66 0.81 34.2 38.8 860 23.3 1.63 18.1 95.1 4.20 40 8.0 4.4 10.2 1000 32.0 21.9 0.69 0.82 34.7 38.8 1000 23.6 1.58 18.4 91.9 4.37 50 4.0 1.0 2.2 860 30.9 21.4 0.69 1.04 34.4 29.8 860 24.9 1.64 19.6 96.8 4.45 50 4.0 1.0 2.2 1000 31.3 22.5 0.72 1.05 34.8 29.8 1000 25.2 1.59 20.0 93.3 4.64 50 6.0 2.5 5.7 860 31.2 21.6 0.69 0.96 34.4 32.6 860 25.9 1.64 20.6 97.9 4.62 50 50 6.0 2.5 5.7 1000 31.7 22.7 0.72 0.97 34.9 32.6 1000 26.2 1.60 21.0 94.3 4.81 50 8.0 4.2 9.7 860 31.4 21.6 0.69 0.92 34.5 34.1 860 26.5 1.65 21.1 98.5 4.70 50 8.0 4.2 9.7 1000 31.8 22.7 0.71 0.93 35.0 34.1 1000 26.8 1.60 21.5 94.8 4.89 60 4.0 0.9 2.0 860 29.7 21.5 0.72 1.19 33.8 25.0 860 27.8 1.66 22.5 100.0 4.93 60 4.0 0.9 2.0 1000 30.2 22.6 0.75 1.21 34.2 25.0 1000 28.1 1.61 22.9 96.1 5.13 60 6.0 2.4 5.5 860 30.4 21.7 0.71 1.10 34.2 27.7 860 29.0 1.66 23.7 101.3 5.12 60 60 6.0 2.4 5.5 1000 30.9 22.8 0.74 1.11 34.6 27.7 1000 29.4 1.62 24.1 97.2 5.33 60 8.0 4.1 9.5 860 30.7 21.7 0.71 1.06 34.3 29.1 860 29.7 1.67 24.3 102.0 5.22 60 8.0 4.1 9.5 1000 31.2 22.8 0.73 1.07 34.8 29.1 1000 30.0 1.62 24.8 97.8 5.44 70 4.0 0.8 1.8 860 28.2 20.9 0.74 1.37 32.8 20.6 860 30.9 1.68 25.4 103.2 5.40 70 4.0 0.8 1.8 1000 28.6 22.0 0.77 1.39 33.3 20.6 1000 31.2 1.63 25.9 98.9 5.63 70 6.0 2.3 5.3 860 29.1 21.3 0.73 1.27 33.4 23.0 860 32.3 1.68 26.8 104.8 5.62 70 70 6.0 2.3 5.3 1000 29.5 22.4 0.76 1.28 33.8 23.0 1000 32.7 1.64 27.4 100.3 5.85 70 8.0 4.0 9.2 860 29.5 21.4 0.73 1.22 33.6 24.3 860 33.1 1.69 27.6 105.6 5.74 70 8.0 4.0 9.2 1000 29.9 22.5 0.75 1.23 34.1 24.3 1000 33.5 1.64 28.1 101.0 5.98 80 4.0 0.7 1.7 860 26.4 20.1 0.76 1.56 31.7 16.9 860 34.0 1.70 28.5 106.7 5.88 80 4.0 0.7 1.7 1000 26.8 21.2 0.79 1.59 32.2 16.9 1000 34.4 1.65 29.1 101.9 6.13 80 6.0 2.3 5.2 860 27.4 20.6 0.75 1.45 32.3 18.8 860 35.7 1.71 30.2 108.4 6.13 80 80 6.0 2.3 5.2 1000 27.8 21.6 0.78 1.47 32.8 18.8 1000 36.1 1.66 30.7 103.4 6.38 80 8.0 3.9 9.0 860 27.9 20.8 0.75 1.40 32.6 19.9 860 36.6 1.71 31.0 109.4 6.27 80 8.0 3.9 9.0 1000 28.3 21.8 0.77 1.42 33.1 19.9 1000 37.0 1.66 31.7 104.3 6.53 85 4.0 0.7 1.6 860 25.5 19.7 0.77 1.67 31.2 15.3 860 35.7 1.71 30.1 108.4 6.13 85 4.0 0.7 1.6 1000 25.9 20.8 0.80 1.70 31.7 15.3 1000 36.1 1.66 30.7 103.4 6.38 85 6.0 2.2 5.1 860 26.5 20.2 0.76 1.56 31.8 17.0 860 37.5 1.72 31.9 110.3 6.39 85 85 6.0 2.2 5.1 1000 26.9 21.2 0.79 1.58 32.2 17.0 1000 37.9 1.67 32.5 105.1 6.66 85 8.0 3.8 8.8 860 27.0 20.4 0.76 1.50 32.1 17.9 860 38.5 1.73 32.8 111.4 6.54 85 8.0 3.8 8.8 1000 27.4 21.4 0.78 1.53 32.5 17.9 1000 38.9 1.67 33.5 106.0 6.81 90 4.0 0.7 1.5 860 24.7 19.3 0.78 1.79 30.7 13.8 860 37.3 1.72 31.7 110.2 6.37 90 4.0 0.7 1.5 1000 25.0 20.3 0.81 1.81 31.2 13.8 1000 37.7 1.67 32.3 104.9 6.63 90 6.0 2.1 4.9 860 25.6 19.7 0.77 1.67 31.2 15.3 860 39.2 1.73 33.6 112.2 6.65 90 90 6.0 2.1 4.9 1000 25.9 20.8 0.80 1.69 31.7 15.3 1000 39.7 1.68 34.2 106.7 6.92 90 8.0 3.7 8.5 860 26.1 20.0 0.77 1.61 31.5 16.2 860 40.3 1.74 34.6 113.4 6.80 90 8.0 3.7 8.5 1000 26.4 21.0 0.79 1.63 32.0 16.2 1000 40.8 1.69 35.3 107.7 7.08 100 4.0 0.6 1.4 860 23.1 18.8 0.81 2.03 30.0 11.4 0 0 0 0 0 0 100 4.0 0.6 1.4 1000 23.4 19.7 0.84 2.06 30.4 11.4 0 0 0 0 0 0 100 6.0 2.1 4.8 860 23.8 19.0 0.80 1.90 30.3 12.5 0 0 0 0 0 0 100 100 6.0 2.1 4.8 1000 24.2 20.0 0.83 1.93 30.8 12.5 0 0 0 0 0 0 100 8.0 3.6 8.3 860 24.3 19.2 0.79 1.84 30.5 13.2 0 0 0 0 0 0 100 8.0 3.6 8.3 1000 24.6 20.2 0.82 1.87 31.0 13.2 0 0 0 0 0 0 110 4.0 0.6 1.3 860 21.9 18.6 0.85 2.30 29.7 9.5 0 0 0 0 0 0 110 4.0 0.6 1.3 1000 22.2 19.6 0.88 2.34 30.2 9.5 0 0 0 0 0 0 110 6.0 2.0 4.6 860 22.4 18.6 0.83 2.16 29.8 10.4 0 0 0 0 0 0 110 110 6.0 2.0 4.6 1000 22.7 19.6 0.86 2.19 30.2 10.4 0 Operation 0 0 not recommended 0 0 0 110 8.0 3.4 7.9 860 22.7 18.7 0.82 2.10 29.9 10.8 0 0 0 0 0 0 110 8.0 3.4 7.9 1000 23.0 19.6 0.85 2.13 30.3 10.8 0 0 0 0 0 0 120 4.0 0.5 1.2 860 21.0 18.2 0.87 2.58 29.9 8.2 0 0 0 0 0 0 120 4.0 0.5 1.2 1000 21.3 19.2 0.90 2.61 30.3 8.2 0 0 0 0 0 0 120 6.0 1.9 4.5 860 21.5 18.6 0.87 2.45 29.9 8.8 0 0 0 0 0 0 120 120 6.0 1.9 4.5 1000 21.8 19.6 0.90 2.49 30.3 8.8 0 0 0 0 0 0 120 8.0 3.3 7.7 860 21.7 18.7 0.86 2.41 29.9 9.0 0 0 0 0 0 0 120 8.0 3.3 7.7 1000 22.0 19.7 0.90 2.45 30.3 9.0 0 0 0 0 0 0 Interpolation is permissible; extrapolation is not. All entering air conditions are 80 F DB and 67 F WB in cooling, and 70 F DB in heating. ARI/ISO certifi ed conditions are 80.6 F DB and 66.2 F WB in cooling and 68 F DB in heating. Table does not refl ect fan or pump power corrections for ARI/ISO conditions. All performance is based upon the lower voltage of dual voltage rated units. Operation below 40 F EWT is based upon a 15% antifreeze solution. Operation below 60 F EWT requires optional insulated water/refrigerant circuit. See performance correction tables for operating conditions other than those listed above. See Performance Data Selection Notes for operation in the shaded areas. 24

The Smart Choice for Energy Efficiency Performance Data TT 038 Full Load 1250 CFM Nominal (Rated) Airfl ow Cooling, 1250 CFM Nominal (Rated) Airflow Heating Performance capacities shown in thousands of Btuh WPD Cooling - EAT 80/67 F Heating - EAT 70 F EWT GPM F Airfl ow PSI FT CFM TC SC Sens/Tot Airfl ow Ratio kw HR EER CFM HC kw HE LAT COP 20 9.0 5.9 13.7 0 0 0 0 0 0 0 1080 25.7 2.28 18.2 92.0 3.30 20 Operation not recommended 20 9.0 5.9 13.7 0 0 0 0 0 0 0 1250 26.2 2.18 18.8 89.4 3.51 30 4.5 1.7 3.9 1080 43.1 27.4 0.64 1.55 48.3 27.9 1080 27.9 2.32 20.2 93.9 3.52 30 4.5 1.7 3.9 1250 44.1 30.1 0.68 1.61 49.6 27.3 1250 28.4 2.22 20.9 91.1 3.75 30 6.8 3.3 7.7 1080 43.3 27.5 0.63 1.44 48.1 30.0 1080 29.2 2.35 21.4 95.0 3.64 30 30 6.8 3.3 7.7 1250 44.3 30.1 0.68 1.51 49.4 29.4 1250 29.7 2.25 22.1 92.0 3.87 30 9.0 5.7 13.1 1080 43.4 27.5 0.63 1.39 48.1 31.2 1080 29.9 2.36 22.0 95.6 3.71 30 9.0 5.7 13.1 1250 44.4 30.1 0.68 1.45 49.4 30.6 1250 30.4 2.26 22.8 92.5 3.94 40 4.5 1.5 3.5 1080 42.3 27.5 0.65 1.69 48.0 25.0 1080 31.8 2.40 23.8 97.2 3.88 40 4.5 1.5 3.5 1250 43.3 30.1 0.69 1.77 49.4 24.5 1250 32.4 2.30 24.6 94.0 4.12 40 6.8 3.2 7.4 1080 42.9 27.6 0.64 1.59 48.2 27.1 1080 33.3 2.44 25.2 98.6 4.01 40 40 6.8 3.2 7.4 1250 43.9 30.2 0.69 1.66 49.6 26.5 1250 33.9 2.34 26.0 95.1 4.26 40 9.0 5.4 12.5 1080 43.1 27.6 0.64 1.53 48.3 28.1 1080 34.1 2.46 25.9 99.3 4.08 40 9.0 5.4 12.5 1250 44.1 30.3 0.69 1.60 49.6 27.6 1250 34.8 2.35 26.8 95.8 4.33 50 4.5 1.3 3.1 1080 41.1 27.1 0.66 1.85 47.4 22.2 1080 35.7 2.49 27.4 100.6 4.20 50 4.5 1.3 3.1 1250 42.1 29.7 0.70 1.93 48.7 21.8 1250 36.4 2.39 28.3 97.0 4.47 50 6.8 3.1 7.2 1080 42.0 27.4 0.65 1.74 47.9 24.2 1080 37.5 2.54 29.0 102.2 4.34 50 50 6.8 3.1 7.2 1250 43.0 30.0 0.70 1.81 49.2 23.7 1250 38.3 2.43 30.0 98.3 4.61 50 9.0 5.2 12.0 1080 42.4 27.5 0.65 1.68 48.1 25.2 1080 38.5 2.56 29.9 103.0 4.41 50 9.0 5.2 12.0 1250 43.4 30.1 0.69 1.75 49.4 24.8 1250 39.3 2.46 30.9 99.1 4.68 60 4.5 1.2 2.8 1080 39.6 26.4 0.67 2.02 46.4 19.6 1080 39.8 2.60 31.0 104.1 4.50 60 4.5 1.2 2.8 1250 40.5 29.0 0.72 2.11 47.7 19.2 1250 40.6 2.49 32.1 100.1 4.78 60 6.8 3.0 6.9 1080 40.7 26.9 0.66 1.90 47.1 21.4 1080 41.9 2.65 32.9 105.9 4.63 60 60 6.8 3.0 6.9 1250 41.7 29.5 0.71 1.98 48.4 21.0 1250 42.7 2.54 34.1 101.6 4.92 60 9.0 5.0 11.6 1080 41.2 27.1 0.66 1.84 47.4 22.4 1080 43.1 2.69 34.0 106.9 4.70 60 9.0 5.0 11.6 1250 42.2 29.7 0.70 1.92 48.7 22.0 1250 43.9 2.58 35.1 102.5 5.00 70 4.5 1.1 2.5 1080 37.8 25.7 0.68 2.22 45.3 17.0 1080 44.0 2.71 34.8 107.7 4.75 70 4.5 1.1 2.5 1250 38.7 28.2 0.73 2.32 46.6 16.7 1250 44.8 2.60 36.0 103.2 5.05 70 6.8 2.9 6.7 1080 39.1 26.2 0.67 2.08 46.1 18.8 1080 46.4 2.79 36.9 109.8 4.88 70 70 6.8 2.9 6.7 1250 40.0 28.8 0.72 2.17 47.4 18.4 1250 47.3 2.67 38.2 105.0 5.19 70 9.0 4.8 11.0 1080 39.7 26.5 0.67 2.01 46.5 19.7 1080 47.8 2.83 38.2 111.0 4.95 70 9.0 4.8 11.0 1250 40.6 29.0 0.72 2.10 47.8 19.3 1250 48.7 2.71 39.5 106.1 5.27 80 4.5 1.0 2.3 1080 35.8 24.8 0.69 2.44 44.2 14.7 1080 48.3 2.84 38.6 111.4 4.98 80 4.5 1.0 2.3 1250 36.7 27.2 0.74 2.55 45.4 14.4 1250 49.2 2.73 39.9 106.5 5.29 80 6.8 2.8 6.6 1080 37.2 25.4 0.68 2.29 45.0 16.3 1080 51.1 2.93 41.1 113.8 5.10 80 80 6.8 2.8 6.6 1250 38.0 27.9 0.73 2.39 46.2 15.9 1250 52.1 2.81 42.5 108.6 5.43 80 9.0 4.5 10.4 1080 37.8 25.7 0.68 2.21 45.4 17.1 1080 52.7 2.99 42.4 115.1 5.17 80 9.0 4.5 10.4 1250 38.7 28.2 0.73 2.31 46.6 16.8 1250 53.7 2.86 43.9 109.8 5.50 85 4.5 1.0 2.2 1080 34.8 24.3 0.70 2.57 43.6 13.6 1080 50.5 2.92 40.6 113.3 5.08 85 4.5 1.0 2.2 1250 35.6 26.7 0.75 2.68 44.8 13.3 1250 51.5 2.80 41.9 108.1 5.40 85 6.8 2.8 6.4 1080 36.2 25.0 0.69 2.40 44.4 15.0 1080 53.5 3.02 43.2 115.9 5.20 85 85 6.8 2.8 6.4 1250 37.0 27.4 0.74 2.51 45.6 14.7 1250 54.5 2.89 44.7 110.4 5.53 85 9.0 4.5 10.3 1080 36.8 25.3 0.69 2.33 44.8 15.8 1080 55.2 3.07 44.7 117.3 5.26 85 9.0 4.5 10.3 1250 37.7 27.7 0.73 2.43 46.0 15.5 1250 56.3 2.95 46.2 111.7 5.59 90 4.5 0.9 2.1 1080 33.8 23.9 0.71 2.70 43.0 12.5 1080 52.7 2.99 42.5 115.2 5.17 90 4.5 0.9 2.1 1250 34.6 26.2 0.76 2.81 44.2 12.3 1250 53.7 2.86 44.0 109.8 5.50 90 6.8 2.7 6.2 1080 35.1 24.5 0.70 2.52 43.8 13.9 1080 55.9 3.10 45.3 117.9 5.29 90 90 6.8 2.7 6.2 1250 36.0 26.9 0.75 2.63 45.0 13.7 1250 57.0 2.97 46.9 112.2 5.62 90 9.0 4.4 10.2 1080 35.8 24.8 0.69 2.44 44.2 14.7 1080 57.7 3.16 46.9 119.5 5.35 90 9.0 4.4 10.2 1250 36.7 27.2 0.74 2.55 45.4 14.4 1250 58.8 3.03 48.5 113.6 5.69 100 4.5 0.8 1.9 1080 31.8 22.9 0.72 2.99 42.0 10.6 0 0 0 0 0 0 100 4.5 0.8 1.9 1250 32.5 25.2 0.77 3.12 43.2 10.4 0 0 0 0 0 0 100 6.8 2.6 6.1 1080 33.1 23.5 0.71 2.80 42.6 11.8 0 0 0 0 0 0 100 100 6.8 2.6 6.1 1250 33.8 25.8 0.76 2.92 43.8 11.6 0 0 0 0 0 0 100 9.0 4.2 9.7 1080 33.7 23.9 0.71 2.70 43.0 12.5 0 0 0 0 0 0 100 9.0 4.2 9.7 1250 34.5 26.2 0.76 2.82 44.2 12.2 0 0 0 0 0 0 110 4.5 0.8 1.8 1080 29.8 22.1 0.74 3.34 41.3 8.9 0 0 0 0 0 0 110 4.5 0.8 1.8 1250 30.5 24.2 0.79 3.49 42.4 8.7 0 0 0 0 0 0 110 6.8 2.5 5.9 1080 31.0 22.6 0.73 3.12 41.7 10.0 0 0 0 0 0 0 110 110 6.8 2.5 5.9 1250 31.7 24.8 0.78 3.25 42.9 9.8 0 Operation 0 0 not recommended 0 0 0 110 9.0 4.0 9.2 1080 31.7 22.9 0.72 3.01 42.0 10.5 0 0 0 0 0 0 110 9.0 4.0 9.2 1250 32.4 25.1 0.77 3.14 43.1 10.3 0 0 0 0 0 0 120 4.5 0.7 1.6 1080 28.0 21.3 0.76 3.74 40.9 7.5 0 0 0 0 0 0 120 4.5 0.7 1.6 1250 28.7 23.3 0.81 3.91 42.0 7.3 0 0 0 0 0 0 120 6.8 2.5 5.9 1080 29.1 21.7 0.75 3.49 41.1 8.3 0 0 0 0 0 0 120 120 6.8 2.5 5.9 1250 29.8 23.8 0.80 3.64 42.2 8.2 0 0 0 0 0 0 120 9.0 3.8 8.8 1080 29.7 22.0 0.74 3.36 41.2 8.8 0 0 0 0 0 0 120 9.0 3.8 8.8 1250 30.4 24.1 0.79 3.51 42.4 8.6 0 0 0 0 0 0 Interpolation is permissible; extrapolation is not. All entering air conditions are 80 F DB and 67 F WB in cooling, and 70 F DB in heating. ARI/ISO certifi ed conditions are 80.6 F DB and 66.2 F WB in cooling and 68 F DB in heating. Table does not reflect fan or pump power corrections for ARI/ISO conditions. All performance is based upon the lower voltage of dual voltage rated units. Operation below 40 F EWT is based upon a 15% antifreeze solution. Operation below 60 F EWT requires optional insulated water/refrigerant circuit. See performance correction tables for operating conditions other than those listed above. See Performance Data Selection Notes for operation in the shaded areas. 25

ClimateMaster Water-Source Heat Pumps Tranquility 27 Two-Stage (TT) Series 2 to 5.5 Ton Horizontal and Vertical EarthPure Units Performance Data TT 049 Part Load 1300 CFM Nominal (Rated) Airfl ow Cooling, 1400 CFM Nominal (Rated) Airfl ow Heating Performance capacities shown in thousands of Btuh WPD Cooling - EAT 80/67 F Heating - EAT 70 F EWT GPM F Airflow PSI FT CFM TC SC Sens/Tot Ratio kw HR EER Airflow CFM HC kw HE LAT COP 20 11.0 4.0 9.3 0 0 0 0 0 0 0 1200 23.2 2.16 16.2 87.9 3.14 20 Operation not recommended 20 11.0 4.0 9.3 0 0 0 0 0 0 0 1400 23.5 2.10 16.6 85.5 3.27 30 5.5 1.1 2.5 1120 38.6 24.0 0.62 1.20 42.6 32.0 1200 25.6 2.20 18.6 89.8 3.42 30 5.5 1.1 2.5 1300 39.1 25.2 0.64 1.22 43.3 32.0 1400 25.9 2.14 18.9 87.2 3.56 30 8.3 2.3 5.2 1120 38.8 24.0 0.62 1.14 42.6 34.2 1200 26.6 2.21 19.4 90.5 3.52 30 30 8.3 2.3 5.2 1300 39.4 25.3 0.64 1.15 43.2 34.2 1400 26.9 2.15 19.8 87.8 3.67 30 11.0 3.9 8.9 1120 39.0 24.0 0.61 1.10 42.7 35.4 1200 27.1 2.22 19.9 90.9 3.58 30 11.0 3.9 8.9 1300 39.6 25.2 0.64 1.12 43.3 35.4 1400 27.4 2.15 20.3 88.1 3.73 40 5.5 1.0 2.3 1120 40.8 26.2 0.64 1.37 45.5 29.9 1200 29.6 2.24 22.4 92.9 3.88 40 5.5 1.0 2.3 1300 41.4 27.6 0.67 1.38 46.1 29.9 1400 30.0 2.18 22.9 89.8 4.04 40 8.3 2.2 5.0 1120 41.2 26.3 0.64 1.28 45.5 32.1 1200 30.9 2.25 23.6 93.8 4.02 40 40 8.3 2.2 5.0 1300 41.8 27.6 0.66 1.30 46.2 32.1 1400 31.2 2.19 24.1 90.7 4.19 40 11.0 3.7 8.6 1120 41.3 26.3 0.64 1.25 45.5 32.9 1200 31.6 2.26 24.3 94.4 4.10 40 11.0 3.7 8.6 1300 41.9 27.6 0.66 1.27 46.1 32.9 1400 31.9 2.19 24.8 91.1 4.27 50 5.5 0.9 2.1 1120 40.8 26.8 0.66 1.49 45.9 27.3 1200 34.0 2.28 26.7 96.3 4.38 50 5.5 0.9 2.1 1300 41.4 28.2 0.68 1.51 46.5 27.3 1400 34.4 2.21 27.2 92.8 4.56 50 8.3 2.1 4.9 1120 41.2 26.9 0.65 1.41 45.9 29.1 1200 35.6 2.29 28.2 97.5 4.56 50 50 8.3 2.1 4.9 1300 41.7 28.2 0.68 1.43 46.6 29.1 1400 36.0 2.23 28.8 93.8 4.74 50 11.0 3.6 8.3 1120 41.3 26.9 0.65 1.40 46.0 29.4 1200 36.5 2.30 29.1 98.2 4.65 50 11.0 3.6 8.3 1300 41.9 28.3 0.67 1.42 46.7 29.4 1400 36.9 2.23 29.6 94.4 4.85 60 5.5 0.8 2.0 1120 40.0 27.1 0.68 1.73 45.9 23.2 1200 38.7 2.32 31.2 99.8 4.89 60 5.5 0.8 2.0 1300 40.6 28.5 0.70 1.75 46.5 23.2 1400 39.1 2.25 31.8 95.9 5.09 60 8.3 2.0 4.7 1120 40.7 27.2 0.67 1.62 46.2 25.1 1200 40.6 2.33 33.0 101.3 5.10 60 60 8.3 2.0 4.7 1300 41.3 28.6 0.69 1.64 46.9 25.1 1400 41.1 2.27 33.7 97.2 5.31 60 11.0 3.5 8.1 1120 41.0 27.2 0.67 1.57 46.3 26.1 1200 41.7 2.34 34.1 102.1 5.21 60 11.0 3.5 8.1 1300 41.5 28.7 0.69 1.59 46.9 26.1 1400 42.1 2.27 34.7 97.9 5.43 70 5.5 0.8 1.8 1120 38.2 26.5 0.69 1.94 44.8 19.7 1200 43.4 2.36 35.7 103.5 5.39 70 5.5 0.8 1.8 1300 38.8 27.9 0.72 1.97 45.4 19.7 1400 43.9 2.29 36.4 99.0 5.62 70 8.3 2.0 4.6 1120 39.3 26.9 0.68 1.82 45.5 21.6 1200 45.6 2.38 37.9 105.2 5.62 70 70 8.3 2.0 4.6 1300 39.9 28.3 0.71 1.85 46.1 21.6 1400 46.1 2.31 38.6 100.5 5.85 70 11.0 3.3 7.5 1120 39.8 27.1 0.68 1.76 45.7 22.6 1200 46.8 2.39 39.0 106.1 5.73 70 11.0 3.3 7.5 1300 40.3 28.4 0.71 1.79 46.4 22.6 1400 47.3 2.32 39.7 101.3 5.97 80 5.5 0.7 1.7 1120 35.9 25.7 0.71 2.17 43.3 16.5 1200 48.0 2.40 40.2 107.1 5.86 80 5.5 0.7 1.7 1300 36.5 27.0 0.74 2.20 43.9 16.5 1400 48.6 2.33 41.0 102.1 6.10 80 8.3 1.9 4.5 1120 37.2 26.2 0.70 2.04 44.2 18.2 1200 50.4 2.43 42.5 108.9 6.07 80 80 8.3 1.9 4.5 1300 37.7 27.5 0.73 2.07 44.8 18.2 1400 50.9 2.36 43.3 103.7 6.33 80 11.0 3.2 7.3 1120 37.8 26.4 0.70 1.98 44.6 19.1 1200 51.6 2.45 43.7 109.8 6.18 80 11.0 3.2 7.3 1300 38.4 27.8 0.72 2.01 45.2 19.1 1400 52.2 2.38 44.5 104.5 6.44 85 5.5 0.7 1.7 1120 34.7 25.2 0.73 2.30 42.5 15.0 1200 50.2 2.43 42.3 108.8 6.06 85 5.5 0.7 1.7 1300 35.2 26.5 0.75 2.34 43.1 15.0 1400 50.8 2.36 43.1 103.6 6.31 85 8.3 1.9 4.3 1120 36.0 25.7 0.71 2.17 43.4 16.6 1200 52.6 2.46 44.6 110.6 6.26 85 85 8.3 1.9 4.3 1300 36.5 27.0 0.74 2.20 44.0 16.6 1400 53.2 2.39 45.4 105.2 6.52 85 11.0 3.1 7.3 1120 36.6 25.9 0.71 2.10 43.8 17.4 1200 53.8 2.48 45.7 111.5 6.35 85 11.0 3.1 7.3 1300 37.1 27.3 0.73 2.13 44.4 17.4 1400 54.4 2.41 46.6 106.0 6.62 90 5.5 0.7 1.6 1120 33.4 24.7 0.74 2.44 41.7 13.7 1200 52.4 2.46 44.4 110.5 6.25 90 5.5 0.7 1.6 1300 33.9 25.9 0.77 2.47 42.3 13.7 1400 53.0 2.39 45.3 105.1 6.51 90 8.3 1.8 4.2 1120 34.7 25.2 0.73 2.30 42.6 15.1 1200 54.8 2.50 46.7 112.3 6.44 90 90 8.3 1.8 4.2 1300 35.2 26.5 0.75 2.33 43.2 15.1 1400 55.4 2.42 47.6 106.7 6.70 90 11.0 3.1 7.2 1120 35.4 25.5 0.72 2.23 43.0 15.9 1200 56.0 2.52 47.8 113.2 6.52 90 11.0 3.1 7.2 1300 35.9 26.8 0.75 2.26 43.6 15.9 1400 56.7 2.45 48.8 107.5 6.79 100 5.5 0.7 1.5 1120 30.9 23.7 0.77 2.73 40.2 11.3 0 0 0 0 0 0 100 5.5 0.7 1.5 1300 31.3 24.9 0.80 2.77 40.7 11.3 0 0 0 0 0 0 100 8.3 1.8 4.1 1120 32.1 24.2 0.75 2.58 40.9 12.5 0 0 0 0 0 0 100 100 8.3 1.8 4.1 1300 32.6 25.4 0.78 2.62 41.5 12.5 0 0 0 0 0 0 100 11.0 3.0 6.8 1120 32.8 24.4 0.74 2.50 41.3 13.1 0 0 0 0 0 0 100 11.0 3.0 6.8 1300 33.3 25.7 0.77 2.54 41.9 13.1 0 0 0 0 0 0 110 5.5 0.6 1.5 1120 28.5 22.9 0.80 3.07 39.0 9.3 0 0 0 0 0 0 110 5.5 0.6 1.5 1300 28.9 24.1 0.83 3.11 39.6 9.3 0 0 0 0 0 0 110 8.3 1.7 4.0 1120 29.6 23.3 0.79 2.90 39.5 10.2 0 0 0 0 0 0 110 110 8.3 1.7 4.0 1300 30.0 24.5 0.81 2.94 40.1 10.2 0 Operation 0 0 not recomended 0 0 0 110 11.0 2.8 6.6 1120 30.2 23.5 0.78 2.82 39.8 10.7 0 0 0 0 0 0 110 11.0 2.8 6.6 1300 30.6 24.7 0.81 2.86 40.4 10.7 0 0 0 0 0 0 120 5.5 0.6 1.4 1120 26.7 22.7 0.85 3.45 38.4 7.7 0 0 0 0 0 0 120 5.5 0.6 1.4 1300 27.0 23.8 0.88 3.50 39.0 7.7 0 0 0 0 0 0 120 8.3 1.7 3.8 1120 27.5 22.7 0.83 3.26 38.6 8.4 0 0 0 0 0 0 120 8.3 1.7 3.8 1300 27.9 23.9 0.86 3.31 39.2 8.4 0 0 0 0 0 0 120 11.0 2.7 6.3 1120 27.9 22.8 0.82 3.17 38.8 8.8 0 0 0 0 0 0 120 11.0 2.7 6.3 1300 28.3 24.0 0.85 3.22 39.3 8.8 0 0 0 0 0 0 Interpolation is permissible; extrapolation is not. All entering air conditions are 80 F DB and 67 F WB in cooling, and 70 F DB in heating. ARI/ISO certified conditions are 80.6 F DB and 66.2 F WB in cooling and 68 F DB in heating. Table does not reflect fan or pump power corrections for ARI/ISO conditions. All performance is based upon the lower voltage of dual voltage rated units. Operation below 40 F EWT is based upon a 15% antifreeze solution. Operation below 60 F EWT requires optional insulated water/refrigerant circuit. See performance correction tables for operating conditions other than those listed above. See Performance Data Selection Notes for operation in the shaded areas. 26

The Smart Choice for Energy Efficiency Performance Data TT 049 Full Load 1550 CFM Nominal (Rated) Airfl ow Cooling, 1650 CFM Nominal (Rated) Airfl ow Heating Performance capacities shown in thousands of Btuh WPD Cooling - EAT 80/67 F Heating - EAT 70 F EWT GPM F Airflow PSI FT CFM TC SC Sens/Tot Ratio kw HR EER Airflow CFM HC kw HE LAT COP 20 12.0 4.8 11.0 0 0 0 0 0 0 0 1430 31.6 2.90 22.1 90.5 3.20 20 Operation not recommended 20 12.0 4.8 11.0 0 0 0 0 0 0 0 1650 32.3 2.78 22.9 88.1 3.40 30 6.0 1.3 2.9 1330 56.1 32.1 0.57 2.13 63.2 26.4 1430 34.7 2.98 24.9 92.5 3.41 30 6.0 1.3 2.9 1550 57.4 35.1 0.61 2.22 65.0 25.9 1650 35.4 2.86 25.7 89.9 3.62 30 9.0 2.7 6.1 1330 56.5 32.1 0.57 2.01 63.2 28.2 1430 36.3 3.03 26.3 93.5 3.51 30 30 9.0 2.7 6.1 1550 57.9 35.2 0.61 2.09 65.0 27.6 1650 37.0 2.90 27.2 90.8 3.73 30 12.0 4.6 10.5 1330 56.8 32.1 0.57 1.94 63.3 29.3 1430 37.2 3.05 27.0 94.1 3.57 30 12.0 4.6 10.5 1550 58.2 35.2 0.61 2.03 65.1 28.7 1650 37.9 2.93 28.0 91.3 3.79 40 6.0 1.1 2.7 1330 55.8 33.0 0.59 2.32 63.6 24.1 1430 40.0 3.13 29.6 95.9 3.75 40 6.0 1.1 2.7 1550 57.1 36.2 0.63 2.42 65.4 23.6 1650 40.8 3.00 30.6 92.9 3.99 40 9.0 2.6 5.9 1330 56.4 33.0 0.59 2.19 63.7 25.8 1430 42.0 3.18 31.4 97.2 3.87 40 40 9.0 2.6 5.9 1550 57.7 36.2 0.63 2.28 65.5 25.3 1650 42.8 3.05 32.4 94.0 4.11 40 12.0 4.4 10.1 1330 56.6 33.0 0.58 2.12 63.8 26.7 1430 43.1 3.21 32.4 97.9 3.94 40 12.0 4.4 10.1 1550 58.0 36.2 0.62 2.22 65.5 26.2 1650 43.9 3.08 33.5 94.6 4.19 50 6.0 1.1 2.5 1330 54.5 33.3 0.61 2.51 63.0 21.8 1430 45.5 3.27 34.6 99.5 4.08 50 6.0 1.1 2.5 1550 55.8 36.5 0.65 2.62 64.7 21.3 1650 46.4 3.14 35.8 96.0 4.34 50 9.0 2.5 5.7 1330 55.6 33.4 0.60 2.37 63.6 23.5 1430 48.0 3.33 36.8 101.1 4.22 50 50 9.0 2.5 5.7 1550 56.9 36.6 0.64 2.47 65.4 23.0 1650 48.9 3.20 38.0 97.4 4.48 50 12.0 4.2 9.6 1330 56.0 33.4 0.60 2.30 63.7 24.3 1430 49.3 3.37 38.0 101.9 4.29 50 12.0 4.2 9.6 1550 57.3 36.7 0.64 2.40 65.5 23.8 1650 50.3 3.23 39.3 98.2 4.56 60 6.0 1.0 2.3 1330 52.5 32.6 0.62 2.71 61.7 19.4 1430 51.3 3.42 39.8 103.2 4.39 60 6.0 1.0 2.3 1550 53.7 35.8 0.67 2.82 63.4 19.0 1650 52.3 3.28 41.1 99.3 4.67 60 9.0 2.4 5.5 1330 54.0 33.1 0.61 2.56 62.7 21.1 1430 54.2 3.50 42.4 105.1 4.54 60 60 9.0 2.4 5.5 1550 55.3 36.3 0.66 2.67 64.4 20.7 1650 55.2 3.36 43.8 101.0 4.83 60 12.0 4.0 9.2 1330 54.7 33.3 0.61 2.49 63.1 21.9 1430 55.8 3.54 43.8 106.1 4.62 60 12.0 4.0 9.2 1550 55.9 36.5 0.65 2.60 64.8 21.5 1650 56.9 3.40 45.3 101.9 4.91 70 6.0 0.9 2.2 1330 49.9 31.7 0.64 2.93 59.9 17.1 1430 57.2 3.58 45.1 107.1 4.68 70 6.0 0.9 2.2 1550 51.1 34.8 0.68 3.06 61.6 16.7 1650 58.3 3.44 46.6 102.7 4.98 70 9.0 2.3 5.4 1330 51.7 32.4 0.63 2.77 61.1 18.7 1430 60.6 3.68 48.1 109.2 4.83 70 70 9.0 2.3 5.4 1550 53.0 35.5 0.67 2.89 62.8 18.3 1650 61.7 3.53 49.7 104.7 5.13 70 12.0 3.8 8.8 1330 52.6 32.7 0.62 2.7 61.7 19.5 1430 62.4 3.73 49.7 110.4 4.90 70 12.0 3.8 8.8 1550 53.8 35.8 0.67 2.81 63.4 19.1 1650 63.6 3.58 51.4 105.7 5.21 80 6.0 0.9 2.1 1330 47.1 30.6 0.65 3.18 57.9 14.8 1430 63.2 3.76 50.5 111.0 4.94 80 6.0 0.9 2.1 1550 48.2 33.6 0.70 3.32 59.5 14.5 1650 64.5 3.60 52.2 106.2 5.25 80 9.0 2.3 5.2 1330 49.0 31.4 0.64 3.01 59.3 16.3 1430 67.0 3.87 53.8 113.4 5.07 80 80 9.0 2.3 5.2 1550 50.2 34.4 0.69 3.14 60.9 16.0 1650 68.3 3.71 55.7 108.3 5.39 80 12.0 3.6 8.3 1330 50.0 31.7 0.63 2.92 59.9 17.1 1430 69.1 3.94 55.7 114.8 5.14 80 12.0 3.6 8.3 1550 51.2 34.8 0.68 3.05 61.6 16.8 1650 70.5 3.78 57.6 109.5 5.47 85 6.0 0.9 2.0 1330 45.5 30.1 0.66 3.32 56.9 13.7 1430 66.3 3.85 53.2 112.9 5.04 85 6.0 0.9 2.0 1550 46.6 33.0 0.71 3.47 58.5 13.4 1650 67.6 3.69 55.0 107.9 5.36 85 9.0 2.2 5.1 1330 47.5 30.8 0.65 3.14 58.2 15.1 1430 70.3 3.98 56.7 115.5 5.18 85 85 9.0 2.2 5.1 1550 48.6 33.8 0.69 3.28 59.8 14.8 1650 71.6 3.82 58.6 110.2 5.50 85 12.0 3.6 8.2 1330 48.5 31.2 0.64 3.05 58.9 15.9 1430 72.5 4.06 58.6 116.9 5.24 85 12.0 3.6 8.2 1550 49.6 34.2 0.69 3.19 60.5 15.6 1650 73.9 3.89 60.6 111.5 5.57 90 6.0 0.9 2.0 1330 44.0 29.5 0.67 3.47 55.9 12.7 1430 69.3 3.95 55.8 114.9 5.15 90 6.0 0.9 2.0 1550 45.0 32.4 0.72 3.62 57.4 12.4 1650 70.7 3.78 57.7 109.7 5.47 90 9.0 2.2 5.0 1330 46.0 30.2 0.66 3.28 57.2 14.0 1430 73.5 4.09 59.5 117.6 5.27 90 90 9.0 2.2 5.0 1550 47.1 33.2 0.70 3.42 58.8 13.8 1650 74.9 3.92 61.6 112.1 5.60 90 12.0 3.5 8.1 1330 47.0 30.6 0.65 3.18 57.9 14.8 1430 75.8 4.17 61.5 119.1 5.33 90 12.0 3.5 8.1 1550 48.1 33.6 0.70 3.32 59.5 14.5 1650 77.3 4.00 63.6 113.4 5.66 100 6.0 0.8 1.9 1330 40.9 28.5 0.70 3.80 53.9 10.7 0 0 0 0 0 0 100 6.0 0.8 1.9 1550 41.8 31.2 0.75 3.97 55.4 10.5 0 0 0 0 0 0 100 9.0 2.1 4.8 1330 42.8 29.1 0.68 3.59 55.1 11.9 0 0 0 0 0 0 100 100 9.0 2.1 4.8 1550 43.8 31.9 0.73 3.74 56.6 11.7 0 0 0 0 0 0 100 12.0 3.3 7.7 1330 43.8 29.4 0.67 3.48 55.8 12.6 0 0 0 0 0 0 100 12.0 3.3 7.7 1550 44.9 32.3 0.72 3.64 57.3 12.3 0 0 0 0 0 0 110 6.0 0.8 1.8 1330 37.8 27.6 0.73 4.19 52.2 9.0 0 0 0 0 0 0 110 6.0 0.8 1.8 1550 38.7 30.2 0.78 4.38 53.7 8.8 0 0 0 0 0 0 110 9.0 2.0 4.7 1330 39.6 28.1 0.71 3.95 53.2 10.0 0 0 0 0 0 0 110 110 9.0 2.0 4.7 1550 40.6 30.8 0.76 4.12 54.7 9.8 0 Operation 0 0 not recommended 0 0 0 110 12.0 3.2 7.3 1330 40.6 28.4 0.70 3.83 53.7 10.6 0 0 0 0 0 0 110 12.0 3.2 7.3 1550 41.5 31.1 0.75 4.00 55.2 10.4 0 0 0 0 0 0 120 6.0 0.8 1.7 1330 34.9 27.0 0.77 4.65 51.0 7.5 0 0 0 0 0 0 120 6.0 0.8 1.7 1550 35.8 29.6 0.83 4.86 52.4 7.4 0 0 0 0 0 0 120 9.0 2.0 4.5 1330 36.6 27.3 0.75 4.37 51.6 8.4 0 0 0 0 0 0 120 120 9.0 2.0 4.5 1550 37.4 29.9 0.80 4.57 53.1 8.2 0 0 0 0 0 0 120 12.0 3.0 7.0 1330 37.4 27.5 0.73 4.24 52.0 8.8 0 0 0 0 0 0 120 12.0 3.0 7.0 1550 38.3 30.1 0.79 4.43 53.5 8.7 0 0 0 0 0 0 Interpolation is permissible; extrapolation is not. All entering air conditions are 80 F DB and 67 F WB in cooling, and 70 F DB in heating. ARI/ISO certified conditions are 80.6 F DB and 66.2 F WB in cooling and 68 F DB in heating. Table does not reflect fan or pump power corrections for ARI/ISO conditions. All performance is based upon the lower voltage of dual voltage rated units. Operation below 40 F EWT is based upon a 15% antifreeze solution. Operation below 60 F EWT requires optional insulated water/refrigerant circuit. See performance correction tables for operating conditions other than those listed above. See Performance Data Selection Notes for operation in the shaded areas. 27

ClimateMaster Water-Source Heat Pumps Tranquility 27 Two-Stage (TT) Series 2 to 5.5 Ton Horizontal and Vertical EarthPure Units Performance Data TT 064 Part Load 1500 CFM Nominal (Rated) Airflow Cooling, 1650 CFM Nominal (Rated) Airflow Heating Performance capacities shown in thousands of Btuh WPD Cooling - EAT 80/67 F Heating - EAT 70 F EWT GPM F Airfl ow PSI FT CFM TC SC Sens/Tot Airfl ow Ratio kw HR EER CFM HC kw HE LAT COP 20 14.0 4.1 9.4 0 0 0 0 0 0 0 1430 28.7 2.85 19.5 88.6 2.95 20 20 14.0 4.1 9.4 0 0 Operation 0 not 0 recommended 0 0 0 1650 29.0 2.77 19.9 86.3 3.07 30 7.0 0.5 1.1 1280 49.1 33.2 0.68 1.54 54.2 31.8 1430 31.7 2.87 22.5 90.5 3.24 30 7.0 0.5 1.1 1500 49.7 35.0 0.70 1.56 55.0 31.8 1650 32.0 2.78 22.9 88.0 3.37 30 10.5 1.9 4.4 1280 50.1 33.6 0.67 1.5 55.1 33.4 1430 32.7 2.87 23.4 91.2 3.34 30 30 10.5 1.9 4.4 1500 50.8 35.3 0.70 1.52 55.9 33.4 1650 33.0 2.79 23.9 88.5 3.47 30 14.0 3.9 9.0 1280 51.6 34.4 0.67 1.48 56.6 34.7 1430 33.2 2.87 24.0 91.5 3.39 30 14.0 3.9 9.0 1500 52.3 36.2 0.69 1.51 57.4 34.7 1650 33.6 2.79 24.4 88.8 3.53 40 7.0 0.4 0.9 1280 51.9 35.8 0.69 1.68 57.6 30.9 1430 36.1 2.89 26.8 93.4 3.67 40 7.0 0.4 0.9 1500 52.7 37.6 0.71 1.71 58.4 30.9 1650 36.5 2.80 27.4 90.5 3.82 40 10.5 1.8 4.3 1280 52.3 35.8 0.68 1.60 57.7 32.7 1430 37.4 2.89 28.1 94.2 3.79 40 40 10.5 1.8 4.3 1500 53.1 37.7 0.71 1.63 58.5 32.7 1650 37.8 2.81 28.6 91.2 3.95 40 14.0 3.7 8.6 1280 52.7 35.9 0.68 1.57 57.9 33.6 1430 38.1 2.90 28.8 94.7 3.86 40 14.0 3.7 8.6 1500 53.4 37.7 0.71 1.59 58.8 33.6 1650 38.5 2.81 29.3 91.6 4.02 50 7.0 0.3 0.7 1280 52.0 36.5 0.70 1.88 58.4 27.7 1430 40.9 2.91 31.5 96.5 4.11 50 7.0 0.3 0.7 1500 52.8 38.4 0.73 1.91 59.2 27.7 1650 41.3 2.83 32.1 93.2 4.28 50 10.5 1.8 4.1 1280 52.6 36.5 0.69 1.76 58.5 29.8 1430 42.4 2.92 33.0 97.5 4.26 50 50 10.5 1.8 4.1 1500 53.3 38.4 0.72 1.79 59.3 29.8 1650 42.9 2.83 33.6 94.1 4.43 50 14.0 3.6 8.2 1280 52.7 36.5 0.69 1.71 58.5 30.8 1430 43.2 2.92 33.8 98.0 4.33 50 14.0 3.6 8.2 1500 53.5 38.4 0.72 1.74 59.4 30.8 1650 43.7 2.84 34.4 94.5 4.51 60 7.0 0.3 0.6 1280 50.2 35.8 0.71 2.12 57.3 23.7 1430 45.7 2.94 36.2 99.6 4.55 60 7.0 0.3 0.6 1500 50.9 37.6 0.74 2.15 58.2 23.7 1650 46.2 2.86 36.9 95.9 4.74 60 10.5 1.7 4.0 1280 51.3 36.2 0.71 1.98 58.0 25.9 1430 47.5 2.96 37.9 100.8 4.71 60 60 10.5 1.7 4.0 1500 52.0 38.1 0.73 2.01 58.8 25.9 1650 48.0 2.87 38.7 97.0 4.91 60 14.0 3.4 7.8 1280 51.8 36.4 0.70 1.91 58.3 27.1 1430 48.5 2.96 38.9 101.4 4.79 60 14.0 3.4 7.8 1500 52.5 38.3 0.73 1.94 59.1 27.1 1650 49.0 2.88 39.6 97.5 4.99 70 7.0 0.2 0.5 1280 47.5 34.5 0.73 2.41 55.7 19.8 1430 50.6 2.98 40.9 102.8 4.97 70 7.0 0.2 0.5 1500 48.2 36.3 0.75 2.44 56.5 19.8 1650 51.2 2.90 41.7 98.7 5.18 70 10.5 1.7 3.9 1280 49.1 35.2 0.72 2.24 56.7 21.9 1430 52.6 3.01 42.9 104.1 5.13 70 70 10.5 1.7 3.9 1500 49.7 37.1 0.74 2.28 57.5 21.9 1650 53.2 2.92 43.7 99.9 5.35 70 14.0 3.3 7.5 1280 49.8 35.6 0.71 2.17 57.1 23.0 1430 53.7 3.02 43.9 104.8 5.22 70 14.0 3.3 7.5 1500 50.5 37.4 0.74 2.20 57.9 23.0 1650 54.3 2.93 44.8 100.5 5.43 80 7.0 0.2 0.4 1280 44.5 33.0 0.74 2.74 53.8 16.2 1430 55.4 3.04 45.6 105.9 5.35 80 7.0 0.2 0.4 1500 45.1 34.7 0.77 2.78 54.5 16.2 1650 56.1 2.95 46.5 101.5 5.57 80 10.5 1.6 3.8 1280 46.1 33.8 0.73 2.56 54.8 18.0 1430 57.6 3.07 47.7 107.3 5.50 80 80 10.5 1.6 3.8 1500 46.8 35.6 0.76 2.59 55.6 18.0 1650 58.3 2.98 48.6 102.7 5.73 80 14.0 3.1 7.2 1280 46.9 34.2 0.73 2.47 55.3 19.0 1430 58.8 3.09 48.8 108.1 5.58 80 14.0 3.1 7.2 1500 47.6 36.0 0.76 2.51 56.1 19.0 1650 59.5 3.00 49.7 103.4 5.81 85 7.0 0.2 0.4 1280 42.8 32.3 0.75 2.93 52.8 14.6 1430 57.8 3.08 47.8 107.4 5.51 85 7.0 0.2 0.4 1500 43.5 34.0 0.78 2.97 53.6 14.6 1650 58.4 2.99 48.7 102.8 5.73 85 10.5 1.6 3.7 1280 44.5 33.1 0.74 2.74 53.8 16.2 1430 60.0 3.11 49.9 108.9 5.65 85 85 10.5 1.6 3.7 1500 45.1 34.8 0.77 2.78 54.6 16.2 1650 60.7 3.02 50.9 104.1 5.88 85 14.0 3.0 7.0 1280 45.3 33.5 0.74 2.65 54.3 17.1 1430 61.2 3.14 51.0 109.6 5.72 85 14.0 3.0 7.0 1500 46.0 35.2 0.77 2.68 55.1 17.1 1650 61.9 3.04 52.0 104.7 5.96 90 7.0 0.1 0.3 1280 41.2 31.6 0.77 3.12 51.8 13.2 1430 60.1 3.11 50.0 108.9 5.66 90 7.0 0.1 0.3 1500 41.8 33.2 0.79 3.16 52.6 13.2 1650 60.8 3.02 51.0 104.1 5.90 90 10.5 1.5 3.6 1280 42.9 32.3 0.75 2.92 52.8 14.7 1430 62.4 3.16 52.1 110.4 5.80 90 90 10.5 1.5 3.6 1500 43.5 34.0 0.78 2.96 53.6 14.7 1650 63.1 3.06 53.2 105.4 6.04 90 14.0 3.0 6.8 1280 43.7 32.7 0.75 2.82 53.3 15.5 1430 63.6 3.18 53.2 111.2 5.86 90 14.0 3.0 6.8 1500 44.3 34.4 0.78 2.86 54.1 15.5 1650 64.3 3.09 54.3 106.1 6.10 100 7.0 0.1 0.2 1280 38.1 30.3 0.79 3.54 50.2 10.8 0 0 0 0 0 0 100 7.0 0.1 0.2 1500 38.7 31.9 0.82 3.59 50.9 10.8 0 0 0 0 0 0 100 10.5 1.5 3.5 1280 39.6 30.9 0.78 3.33 51.0 11.9 0 0 0 0 0 0 100 100 10.5 1.5 3.5 1500 40.2 32.5 0.81 3.38 51.7 11.9 0 0 0 0 0 0 100 14.0 2.8 6.5 1280 40.4 31.2 0.77 3.22 51.4 12.5 0 0 0 0 0 0 100 14.0 2.8 6.5 1500 41.0 32.8 0.80 3.27 52.1 12.5 0 0 0 0 0 0 110 7.0 0.1 0.2 1280 35.5 29.6 0.83 4.02 49.3 8.8 0 0 0 0 0 0 110 7.0 0.1 0.2 1500 36.0 31.1 0.86 4.08 49.9 8.8 0 0 0 0 0 0 110 10.5 1.5 3.3 1280 36.7 29.8 0.81 3.79 49.6 9.7 0 0 0 0 0 0 110 110 10.5 1.5 3.3 1500 37.2 31.4 0.84 3.84 50.3 9.7 0 Operation 0 0 not recomended 0 0 0 110 14.0 2.7 6.2 1280 37.3 30.0 0.80 3.67 49.9 10.2 0 0 0 0 0 0 110 14.0 2.7 6.2 1500 37.9 31.6 0.83 3.73 50.6 10.2 0 0 0 0 0 0 120 7.0 0.1 0.1 1280 33.7 29.2 0.87 4.57 49.3 7.4 0 0 0 0 0 0 120 7.0 0.1 0.1 1500 34.2 30.7 0.90 4.63 50.0 7.4 0 0 0 0 0 0 120 10.5 1.4 3.2 1280 34.4 29.3 0.85 4.30 49.1 8.0 0 0 0 0 0 0 120 120 10.5 1.4 3.2 1500 34.9 30.8 0.88 4.36 49.8 8.0 0 0 0 0 0 0 120 14.0 2.6 6.0 1280 34.9 29.5 0.85 4.18 49.1 8.3 0 0 0 0 0 0 120 14.0 2.6 6.0 1500 35.4 31.0 0.88 4.24 49.8 8.3 0 0 0 0 0 0 Interpolation is permissible; extrapolation is not. All entering air conditions are 80 F DB and 67 F WB in cooling, and 70 F DB in heating. ARI/ISO certifi ed conditions are 80.6 F DB and 66.2 F WB in cooling and 68 F DB in heating. Table does not refl ect fan or pump power corrections for ARI/ISO conditions. All performance is based upon the lower voltage of dual voltage rated units. Operation below 40 F EWT is based upon a 15% antifreeze solution. Operation below 60 F EWT requires optional insulated water/refrigerant circuit. See performance correction tables for operating conditions other than those listed above. See Performance Data Selection Notes for operation in the shaded areas. 28

The Smart Choice for Energy Efficiency Performance Data TT 064 Full Load 1825 CFM Nominal (Rated) Airflow Cooling, 2050 CFM Nominal (Rated) Airflow Heating Performance capacities shown in thousands of Btuh WPD Cooling - EAT 80/67 F Heating - EAT 70 F EWT GPM F Airfl ow PSI FT CFM TC SC Sens/Tot Airfl ow Ratio kw HR EER CFM HC kw HE LAT COP 20 15.0 5.0 11.6 0 0 0 0 0 0 0 1750 41.0 3.87 28.3 91.7 3.10 20 20 15.0 5.0 11.6 0 0 Operation 0 not 0 recommended 0 0 0 2050 41.8 3.71 29.2 88.9 3.30 30 7.5 0.6 1.5 1580 65.8 41.6 0.63 2.78 75.1 23.7 1750 44.6 3.96 31.5 93.6 3.29 30 7.5 0.6 1.5 1825 67.3 45.6 0.68 2.9 77.2 23.2 2050 45.4 3.8 32.6 90.5 3.50 30 11.3 2.3 5.3 1580 66.7 42.1 0.63 2.65 75.7 25.2 1750 46.4 4.01 33.1 94.6 3.39 30 30 11.3 2.3 5.3 1825 68.3 46.2 0.68 2.77 77.8 24.7 2050 47.3 3.85 34.3 91.4 3.6 30 15.0 4.8 11 1580 68.1 42.9 0.63 2.60 76.8 26.2 1750 47.4 4.04 34.0 95.1 3.44 30 15.0 4.8 11 1825 69.7 47.1 0.68 2.71 78.9 25.7 2050 48.3 3.88 35.2 91.8 3.65 40 7.5 0.5 1.2 1580 67.5 43.1 0.64 3.00 77.6 22.5 1750 50.6 4.13 36.9 96.8 3.59 40 7.5 0.5 1.2 1825 69.1 47.3 0.68 3.13 79.8 22.0 2050 51.5 3.96 38.1 93.3 3.82 40 11.3 2.2 5.1 1580 68.4 43.4 0.63 2.85 78.0 24 1750 52.8 4.19 38.8 97.9 3.69 40 40 11.3 2.2 5.1 1825 70.0 47.6 0.68 2.98 80.2 23.5 2050 53.8 4.02 40.2 94.3 3.92 40 15.0 4.5 10.4 1580 68.7 43.5 0.63 2.78 78 24.7 1750 53.9 4.22 39.9 98.5 3.74 40 15.0 4.5 10.4 1825 70.3 47.7 0.68 2.90 80.2 24.2 2050 55.0 4.05 41.3 94.8 3.98 50 7.5 0.4 1.0 1580 67.7 43.9 0.65 3.27 78.7 20.7 1750 56.7 4.30 42.4 100.0 3.86 50 7.5 0.4 1.0 1825 69.3 48.1 0.69 3.41 80.9 20.3 2050 57.8 4.12 43.8 96.1 4.11 50 11.3 2.1 4.9 1580 68.4 43.9 0.64 3.08 78.8 22.2 1750 59.3 4.37 44.7 101.4 3.97 50 50 11.3 2.1 4.9 1825 70.1 48.1 0.69 3.21 81.0 21.8 2050 60.4 4.19 46.2 97.3 4.22 50 15.0 4.3 9.9 1580 68.8 43.9 0.64 2.99 78.9 23.0 1750 60.7 4.41 45.9 102.1 4.03 50 15.0 4.3 9.9 1825 70.4 48.2 0.68 3.13 81.1 22.5 2050 61.8 4.23 47.5 97.9 4.28 60 7.5 0.4 0.8 1580 65.8 43.4 0.66 3.56 77.9 18.5 1750 63.0 4.48 48.0 103.3 4.12 60 7.5 0.4 0.8 1825 67.3 47.6 0.71 3.72 80.0 18.1 2050 64.2 4.30 49.6 99.0 4.38 60 11.3 2.1 4.8 1580 67.2 43.8 0.65 3.35 78.6 20.1 1750 66.0 4.57 50.6 104.9 4.23 60 60 11.3 2.1 4.8 1825 68.8 48.0 0.70 3.49 80.7 19.7 2050 67.3 4.38 52.4 100.4 4.50 60 15.0 4.1 9.4 1580 67.8 43.9 0.65 3.25 78.8 20.9 1750 67.6 4.62 52.1 105.8 4.29 60 15.0 4.1 9.4 1825 69.4 48.1 0.69 3.39 80.9 20.5 2050 68.9 4.43 53.9 101.1 4.57 70 7.5 0.3 0.7 1580 63.1 42.5 0.67 3.91 76.4 16.1 1750 69.4 4.67 53.7 106.7 4.36 70 7.5 0.3 0.7 1825 64.6 46.7 0.72 4.08 78.5 15.8 2050 70.8 4.48 55.6 102.0 4.63 70 11.3 2.0 4.6 1580 65.0 43.2 0.66 3.66 77.5 17.8 1750 72.9 4.78 56.8 108.6 4.48 70 70 11.3 2.0 4.6 1825 66.6 47.3 0.71 3.82 79.6 17.4 2050 74.4 4.58 58.8 103.6 4.76 70 15.0 3.9 8.9 1580 65.9 43.4 0.66 3.54 77.9 18.6 1750 74.9 4.83 58.6 109.6 4.54 70 15.0 3.9 8.9 1825 67.5 47.6 0.71 3.70 80.1 18.2 2050 76.3 4.63 60.6 104.5 4.83 80 7.5 0.2 0.5 1580 59.8 41.4 0.69 4.31 74.5 13.9 1750 76.1 4.87 59.7 110.3 4.58 80 7.5 0.2 0.5 1825 61.2 45.4 0.74 4.50 76.6 13.6 2050 77.6 4.67 61.7 105.1 4.87 80 11.3 2.0 4.5 1580 62.1 42.2 0.68 4.03 75.8 15.4 1750 80.2 5.00 63.3 112.4 4.70 80 80 11.3 2.0 4.5 1825 63.6 46.3 0.73 4.21 77.9 15.1 2050 81.8 4.79 65.4 106.9 5.00 80 15.0 3.7 8.4 1580 63.2 42.6 0.67 3.90 76.4 16.2 1750 82.5 5.07 65.3 113.6 4.77 80 15.0 3.7 8.4 1825 64.7 46.7 0.72 4.07 78.6 15.9 2050 84.1 4.86 67.5 108.0 5.07 85 7.5 0.2 0.5 1580 58.0 40.7 0.70 4.54 73.6 12.8 1750 79.6 4.98 62.8 112.1 4.69 85 7.5 0.2 0.5 1825 59.4 44.7 0.75 4.74 75.6 12.5 2050 81.2 4.78 64.9 106.7 4.98 85 11.3 1.9 4.4 1580 60.4 41.6 0.69 4.24 74.9 14.2 1750 84.0 5.12 66.6 114.5 4.81 85 85 11.3 1.9 4.4 1825 61.8 45.6 0.74 4.43 76.9 14.0 2050 85.6 4.91 68.9 108.7 5.11 85 15.0 3.6 8.2 1580 61.5 42.0 0.68 4.10 75.5 15.0 1750 86.5 5.20 68.8 115.8 4.88 85 15.0 3.6 8.2 1825 63.0 46.1 0.73 4.28 77.6 14.7 2050 88.1 4.98 71.2 109.8 5.19 90 7.5 0.2 0.4 1580 56.2 40.1 0.71 4.78 72.6 11.8 1750 83.1 5.09 65.9 114.0 4.79 90 7.5 0.2 0.4 1825 57.5 43.9 0.76 4.99 74.6 11.5 2050 84.7 4.88 68.1 108.3 5.09 90 11.3 1.9 4.3 1580 58.7 41.0 0.70 4.46 73.9 13.2 1750 87.8 5.24 70.0 116.5 4.91 90 90 11.3 1.9 4.3 1825 60.0 44.9 0.75 4.65 75.9 12.9 2050 89.5 5.02 72.4 110.4 5.22 90 15.0 3.5 8.0 1580 59.9 41.4 0.69 4.31 74.6 13.9 1750 90.5 5.32 72.3 117.9 4.98 90 15.0 3.5 8.0 1825 61.3 45.4 0.74 4.49 76.6 13.6 2050 92.2 5.10 74.8 111.7 5.30 100 7.5 0.1 0.3 1580 52.4 38.6 0.74 5.32 70.7 9.8 0 0 0 0 0 0 100 7.5 0.1 0.3 1825 53.6 42.3 0.79 5.55 72.6 9.7 0 0 0 0 0 0 100 11.3 1.8 4.2 1580 54.9 39.6 0.72 4.96 71.9 11.1 0 0 0 0 0 0 100 100 11.3 1.8 4.2 1825 56.2 43.4 0.77 5.18 73.9 10.9 0 0 0 0 0 0 100 15.0 3.3 7.6 1580 56.1 40.1 0.71 4.79 72.5 11.7 0 0 0 0 0 0 100 15.0 3.3 7.6 1825 57.5 43.9 0.76 5.00 74.6 11.5 0 0 0 0 0 0 110 7.5 0.1 0.2 1580 48.6 37.1 0.76 5.95 69.0 8.2 0 0 0 0 0 0 110 7.5 0.1 0.2 1825 49.7 40.7 0.82 6.21 71.0 8.0 0 0 0 0 0 0 110 11.3 1.8 4.0 1580 51.0 38.1 0.75 5.54 70.0 9.2 0 0 0 0 0 0 110 110 11.3 1.8 4.0 1825 52.2 41.7 0.80 5.78 72.0 9.0 0 Operation 0 0 not recommended 0 0 0 110 15.0 3.1 7.2 1580 52.2 38.6 0.74 5.34 70.6 9.8 0 0 0 0 0 0 110 15.0 3.1 7.2 1825 53.5 42.3 0.79 5.58 72.5 9.6 0 0 0 0 0 0 120 7.5 0.1 0.1 1580 44.9 35.7 0.80 6.67 67.9 6.7 0 0 0 0 0 0 120 7.5 0.1 0.1 1825 46.0 39.2 0.85 6.97 69.8 6.6 0 0 0 0 0 0 120 11.3 1.7 3.9 1580 47.1 36.6 0.78 6.21 68.5 7.6 0 0 0 0 0 0 120 120 11.3 1.7 3.9 1825 48.3 40.1 0.83 6.48 70.5 7.4 0 0 0 0 0 0 120 15.0 2.9 6.8 1580 48.3 37.0 0.77 5.99 69.0 8.1 0 0 0 0 0 0 120 15.0 2.9 6.8 1825 49.5 40.6 0.82 6.25 70.9 7.9 0 0 0 0 0 0 Interpolation is permissible; extrapolation is not. All entering air conditions are 80 F DB and 67 F WB in cooling, and 70 F DB in heating. ARI/ISO certifi ed conditions are 80.6 F DB and 66.2 F WB in cooling and 68 F DB in heating. Table does not reflect fan or pump power corrections for ARI/ISO conditions. All performance is based upon the lower voltage of dual voltage rated units. Operation below 40 F EWT is based upon a 15% antifreeze solution. Operation below 60 F EWT requires optional insulated water/refrigerant circuit. See performance correction tables for operating conditions other than those listed above. See Performance Data Selection Notes for operation in the shaded areas. 29

ClimateMaster Water-Source Heat Pumps Tranquility 27 Two-Stage (TT) Series 2 to 5.5 Ton Horizontal and Vertical EarthPure Units Physical Data Model 026 038 049 064 Compressor (1 Each) Two-Stage Scroll Factory Charge R410A (oz) [kg] 58 [1.64] 78 [2.21] 81 [2.30] 144 [4.08] ECM Fan Motor & Blower Fan Motor (hp) [W] 1/2 [373] 1/2 [373] 1 [746] 1 [746] Blower Wheel Size (dia x w) - (in) [mm] Water Connection Size 9 x 7 [229 x 178] 11 x 10 [279 x 254] 11 x 10 [279 x 254] 11 x 10 [279 x 254] IPT (in) 3/4 3/4 1 1 HWG Connection Size IPT (in) 1/2 1/2 1/2 1/2 Coax Volume Volume (US Gallons) [liters] 0.76 [2.88] 0.92 [3.48] 1.24 [4.69] 1.56 [5.91] Vertical Upflow/Downflow Air Coil Dimensions (h x w) - (in) [mm] Standard Filter - 1 [25.4mm] Throwaway, qty (in) [mm] 28 x 20 [711 x 508] 28 x 24 [711 x 610] 28 x 25 [711 x 635] 28 x 30 [711 x 762] 32 x 25 [813 x 635] 2-16 x 30 [406 x 762] 36 x 25 [914 x 635] 1-16 x 30 [813 x 762] 1-20 x 30 [508 x 762 Weight - Operating, (lbs) [kg] 266 [121] 327 [148] 416 [189] 443 [201] Weight - Packaged, (lbs) [kg] 276 [125] 337 [153] 426 [193] 453 [205] Horizontal Air Coil Dimensions (h x w) - (in) [mm] Standard Filter - 1 [25.4mm] Throwaway, qty (in) [mm] 18 x 31 [457 x 787] 2-18 x 18 [457 x 457] 20 x 25 [508 x 889] 1-12 x 20 [305 x 508] 1-20 x 24 [508 x 635] 20 x 40 [508 x 1016] 1-18 x 20 [457 x 508] 1-20 x 24 [508 x 610] 20 x 45 [508 x 1143] 2-20 x 24 [508 x 610 Weight - Operating, (lbs) [kg] 266 [121] 327 [148] 416 [189] 443 [201] Weight - Packaged, (lbs) [kg] 276 [125] 337 [153] 426 [193] 453 [205] All units have spring compressor mountings, and 1/2 [12.2mm] & 3/4 [19.mm] electrical knockouts. 30

The Smart Choice for Energy Efficiency TTH026 Dimensions 2ft [61cm] Service Access Notes: 1. While clear access to all removable panels is not required, installer should take care to comply with all building codes and allow adequate clearance for future fi eld service. 2. Horizontal units shipped with fi lter bracket only. This bracket should be removed for return duct connection 3. Discharge flange and hanger brackets are factory installed. Legend: CAP = Control Access Panel BSP = Blower Service Panel (this panel requires adequate service access) CSP = Compressor Access Panel ASP = Alternative Service Panel Right Return, Straight Discharge 2ft [61cm] Optional Service Access Note: Choose either straight or back discharge Straight Discharge Back Discharge Left Return, Straight Discharge Right Return, Back Discharge Right Return, Right View Left Return, Back Discharge Left Return, Left View Front Front 31

ClimateMaster Water-Source Heat Pumps Tranquility 27 Two-Stage (TT) Series 2 to 5.5 Ton Horizontal and Vertical EarthPure Units TTH038 Dimensions Right Return, Straight Discharge Left Return, Straight Discharge 2ft [61cm] Service Access 2ft [61cm] Optional Service Access Note: Choose either straight or back discharge Notes: 1. While clear access to all removable panels is not required, installer should take care to comply with all building codes and allow adequate clearance for future field service. 2. Horizontal units shipped with filter bracket only. This bracket should be removed for return duct connection 3. Discharge flange and hanger brackets are factory installed. Legend: CAP = Control Access Panel BSP = Blower Service Panel (this panel requires adequate service access) CSP = Compressor Access Panel ASP = Alternative Service Panel Straight Discharge Back Discharge Right Return, Right View Right Return, Back Discharge Left Return, Left View Left Return, Back Discharge Front Front 32

The Smart Choice for Energy Efficiency TTH049 Dimensions Right Return, Straight Discharge 2ft [61cm] Service Access Notes: 1. While clear access to all removable panels is not required, installer should take care to comply with all building codes and allow adequate clearance for future field service. 2. Horizontal units shipped with filter bracket only. This bracket should be removed for return duct connection 3. Discharge flange and hanger brackets are factory installed. Legend: CAP = Control Access Panel BSP = Blower Service Panel (this panel requires adequate service access) CSP = Compressor Access Panel ASP = Alternative Service Panel Left Return, Straight Discharge 2ft [61cm] Optional Service Access Note: Choose either straight or back discharge Right Return, Right View Straight Discharge Back Discharge Right Return, Back Discharge Left Return, Left View Left Return, Back Discharge Front Front 33

ClimateMaster Water-Source Heat Pumps Tranquility 27 Two-Stage (TT) Series 2 to 5.5 Ton Horizontal and Vertical EarthPure Units TTH064 Dimensions Right Return, Straight Discharge 2ft [61cm] Service Access Notes: 1. While clear access to all removable panels is not required, installer should take care to comply with all building codes and allow adequate clearance for future fi eld service. 2. Horizontal units shipped with fi lter bracket only. This bracket should be removed for return duct connection 3. Discharge fl ange and hanger brackets are factory installed. Legend: CAP = Control Access Panel BSP = Blower Service Panel (this panel requires adequate service access) CSP = Compressor Access Panel ASP = Alternative Service Panel Left Return, Straight Discharge 2ft [61cm] Optional Service Access Note: Choose either straight or back discharge Straight Discharge Back Discharge Right Return, Right View Right Return, Back Discharge Left Return, Left View Left Return, Back Discharge Front Front 34

The Smart Choice for Energy Efficiency TTV026 Dimensions Notes: 1. While clear access to all removable panels is not required, installer should take care to comply with all building codes and allow adequate clearance for future fi eld service. 2. Front & Side access is preferred for service access. However, all components may be serviced from the front access panel if side access is not available. 3. Discharge flange is field installed. Legend: CAP = Control Access Panel BSP = Blower Service Panel (this panel requires adequate service access) CSP = Compressor Access Panel ASP = Alternative Service Panel Right Return, Top Discharge Front Factory installed fi lter bracket (not shown) for 1 deep fi lter size Front Optional 2 [61cm] Service Access Left Return, Top Discharge 2 [61cm] Service Access Front 35

ClimateMaster Water-Source Heat Pumps Tranquility 27 Two-Stage (TT) Series 2 to 5.5 Ton Horizontal and Vertical EarthPure Units TTV038 Dimensions Notes: 1. While clear access to all removable panels is not required, installer should take care to comply with all building codes and allow adequate clearance for future field service. 2. Front & Side access is preferred for service access. However, all components may be serviced from the front access panel if side access is not available. 3. Discharge fl ange is fi eld installed. Legend: CAP = Control Access Panel BSP = Blower Service Panel (this panel requires adequate service access) CSP = Compressor Access Panel ASP = Alternative Service Panel Right Return, Top Discharge Front Factory installed filter bracket (not shown) for 1 deep filter size Front Optional 2 [61cm] Service Access Left Return, Top Discharge 2 [61cm] Service Access Front 36

The Smart Choice for Energy Efficiency TTV049 Dimensions Notes: 1. While clear access to all removable panels is not required, installer should take care to comply with all building codes and allow adequate clearance for future field service. 2. Front & Side access is preferred for service access. However, all components may be serviced from the front access panel if side access is not available. 3. Discharge flange is field installed. Legend: CAP = Control Access Panel BSP = Blower Service Panel (this panel requires adequate service access) CSP = Compressor Access Panel ASP = Alternative Service Panel Front Right Return, Top Discharge Factory installed filter bracket (not shown) for 1 deep fi lter size Front Optional 2 [61cm] Service Access Left Return, Top Discharge 2 [61cm] Service Access Front 37

ClimateMaster Water-Source Heat Pumps Tranquility 27 Two-Stage (TT) Series 2 to 5.5 Ton Horizontal and Vertical EarthPure Units TTV064 Dimensions Notes: 1. While clear access to all removable panels is not required, installer should take care to comply with all building codes and allow adequate clearance for future fi eld service. 2. Front & Side access is preferred for service access. However, all components may be serviced from the front access panel if side access is not available. 3. Discharge flange is field installed. Legend: CAP = Control Access Panel BSP = Blower Service Panel (this panel requires adequate service access) CSP = Compressor Access Panel ASP = Alternative Service Panel Front Right Return, Top Discharge Factory installed filter bracket (not shown) for 1 deep filter size Front Optional 2 [61cm] Service Access Left Return, Top Discharge 2 [61cm] Service Access Front 38

The Smart Choice for Energy Efficiency TTD026 Dimensions Notes: 1. While clear access to all removable panels is not required, installer should take care to comply with all building codes and allow adequate clearance for future field service. 2. Front & Side access is preferred for service access. However, all components may be serviced from the front access panel if side access is not available. Legend: CAP = Control Access Panel BSP = Blower Service Panel (this panel requires adequate service access) CSP = Compressor Access Panel ASP = Alternative Service Panel Right Return, Bottom Discharge Front Factory installed fi lter bracket (not shown) for 1 deep fi lter size Air Coil Front Optional 2 [61cm] Service Access Air Coil Left Return, Bottom Discharge Optional 2 [61cm] Service Access 2 [61cm] Service Access Front 39

ClimateMaster Water-Source Heat Pumps Tranquility 27 Two-Stage (TT) Series 2 to 5.5 Ton Horizontal and Vertical EarthPure Units TTD038 Dimensions Notes: 1. While clear access to all removable panels is not required, installer should take care to comply with all building codes and allow adequate clearance for future fi eld service. 2. Front & Side access is preferred for service access. However, all components may be serviced from the front access panel if side access is not available. Legend: CAP = Control Access Panel BSP = Blower Service Panel (this panel requires adequate service access) CSP = Compressor Access Panel ASP = Alternative Service Panel Right Return, Bottom Discharge Front Factory installed fi lter bracket (not shown) for 1 deep fi lter size Air Coil Front Optional 2 [61cm] Service Access Air Coil Left Return, Bottom Discharge Optional 2 [61cm] Service Access 2 [61cm] Service Access Front 40

The Smart Choice for Energy Efficiency TTD049 Dimensions Notes: 1. While clear access to all removable panels is not required, installer should take care to comply with all building codes and allow adequate clearance for future fi eld service. 2. Front & Side access is preferred for service access. However, all components may be serviced from the front access panel if side access is not available. Legend: CAP = Control Access Panel BSP = Blower Service Panel (this panel requires adequate service access) CSP = Compressor Access Panel ASP = Alternative Service Panel Front Factory installed fi lter bracket (not shown) for 1 deep fi lter size Air Coil Right Return, Bottom Discharge Optional 2 [61cm] Service Access Front Air Coil Left Return, Bottom Discharge Optional 2 [61cm] Service Access 2 [61cm] Service Access Front 41

ClimateMaster Water-Source Heat Pumps Tranquility 27 Two-Stage (TT) Series 2 to 5.5 Ton Horizontal and Vertical EarthPure Units TTD064 Dimensions Notes: 1. While clear access to all removable panels is not required, installer should take care to comply with all building codes and allow adequate clearance for future fi eld service. 2. Front & Side access is preferred for service access. However, all components may be serviced from the front access panel if side access is not available. Legend: CAP = Control Access Panel BSP = Blower Service Panel (this panel requires adequate service access) CSP = Compressor Access Panel ASP = Alternative Service Panel Front Factory installed filter bracket (not shown) for 1 deep filter size Air Coil Right Return, Bottom Discharge Front Optional 2 [61cm] Service Access Air Coil Left Return, Bottom Discharge Optional 2 [61cm] Service Access 2 [61cm] Service Access Front 42

The Smart Choice for Energy Efficiency Corner Weights for TTH Series Units Model Total Left-Front* Right-Front* Left-Back* Right-Back* 026 Lbs 266 78.8 67.2 69.9 50.2 kg 121 35.7 30.5 31.7 22.7 038 Lbs 327 104.4 74.9 83.7 64.0 kg 148 47.4 34.0 38.0 29.0 049 Lbs 416 145.0 92.6 98.1 80.3 kg 189 65.8 42.0 44.5 36.4 064 Lbs 441 182.3 72.5 78.4 107.8 kg 200 82.7 32.9 35.6 48.9 *Front is control box end. 43

ClimateMaster Water-Source Heat Pumps Tranquility 27 Two-Stage (TT) Series 2 to 5.5 Ton Horizontal and Vertical EarthPure Units Blower Performance Data Airfl ow in CFM with wet coil and clean air filter Model TT H/V/D 026 TT H/V/D 038 TT H/V/D 049 TT H/V/D 064 Max ESP (in. wg) Fan Motor (hp) Tap Setting Cooling Mode Dehumid Mode Heating Mode Stg 1 Stg 2 Fan Stg 1 Stg 2 Fan Stg 1 Stg 2 Fan Residential Units Only AUX CFM Aux/ Emerg Mode 0.50 1/2 4 810 950 475 630 740 475 920 1060 475 4 1060 0.50 1/2 3 725 850 425 560 660 425 825 950 425 3 950 0.50 1/2 2 620 730 370 490 570 370 710 820 370 2 820 0.50 1/2 1 520 610 300 600 690 300 1 690 0.50 1/2 4 1120 1400 700 870 1090 700 1120 1400 700 4 1400 0.50 1/2 3 1000 1250 630 780 980 630 1000 1250 630 3 1350 0.50 1/2 2 860 1080 540 670 840 540 860 1080 540 2 1350 0.50 1/2 1 730 900 450 730 900 450 1 1350 0.75 1 4 1460 1730 870 1140 1350 870 1560 1850 870 4 1850 0.75 1 3 1300 1550 780 1020 1210 780 1400 1650 780 3 1660 0.75 1 2 1120 1330 670 870 1040 670 1200 1430 670 2 1430 0.75 1 1 940 1120 560 1010 1200 560 1 1350 0.75 1 4 1670 2050 1020 1300 1600 1020 1860 2280 1020 4 2280 0.75 1 3 1500 1825 920 1160 1430 920 1650 2050 920 3 2040 0.75 1 2 1280 1580 790 1000 1230 790 1430 1750 790 2 1750 0.75 1 1 1080 1320 660 1200 1470 660 1 1470 Factory shipped on Tap Setting 2 During Auxiliary operation (residential units only) the CFM will run at the higher if the heating (delay jumper) or AUX settings Airfl ow is controlled within +/- 5% up to Max ESP shown with wet coil and standard 1 fi berglass fi lter Do not select Dehumidification mode if HP CFM is on setting 1 All units ARI/ISO/ASHRAE 13256-1 rated HP (Cooling) Delay (Heating) CFM Setting 3 Tranquility 27 (TT) Series with ClimaDry Reheat Option All Tranquility 27 (TT) units have an ECM fan motor as a standard feature. The small additional pressure drop of the reheat coil causes the ECM motor to slightly increase RPM to overcome the added pressure drop, and maintain selected CFM up to the maximum ESP. 44

The Smart Choice for Energy Efficiency Unit Electrical Data Units with ClimaDry Reheat All TT Units Standard TT Units TT Units with ClimaDry Reheat Model TTH/V/D 026 TTH/V/D 038 TTH/V/D 049 TTH/V/D 064 Voltage Code Voltage Min/Max Voltage Compressor QTY RLA LRA Fan Motor FLA Total Unit FLA Min Circuit Amp Max Fuse/ HACR Reheat Pump FLA Total Unit FLA Min Circuit Amp G 208-230/60/1 197/254 1 10.3 52.0 4.3 14.6 17.2 25 0.8 15.4 18.0 25 G 208-230/60/1 197/254 1 16.7 82.0 4.3 21.0 25.2 40 0.8 21.8 26.0 40 H 208-230/60/3 197/254 1 11.2 58.0 4.3 15.5 18.3 25 0.8 16.3 19.1 30 F* 460/60/3 414/506 1 4.5 29.0 4.1 8.6 9.7 15 0.7 9.3 10.4 15 G 208-230/60/1 197/254 1 21.2 96.0 7.0 28.2 33.5 50 1.07 29.3 34.6 50 H 208-230/60/3 197/254 1 13.5 88.0 7.0 20.5 23.9 35 1.07 21.6 24.9 35 F* 460/60/3 414/506 1 6.4 41.0 6.9 13.3 14.9 20 1.07 14.4 16.0 20 G 208-230/60/1 197/254 1 25.6 118.0 7.0 32.6 39.0 60 1.07 33.7 40.1 60 H 208-230/60/3 197/254 1 17.6 123.0 7.0 24.6 29.0 45 1.07 25.7 30.1 45 F* 460/60/3 414/506 1 9.0 62.0 6.9 15.9 18.2 25 1.07 17.7 19.2 25 Max Fuse/ HACR *460V with ECM motor requires a neutral wire. 460V with Reheat requires a neutral wire. Reheat pump and ECM motor are rated 265V and are wired between one hot leg and neutral HACR circuit breaker in USA only Wire length based on one way measurement with 2% voltage drop Wire size based on 60 C copper conductor All fuses Class RK-5 Units with Secondary Pump All TT Units Standard TT Units TT Units with Secondary Pump Model TTH/V/D 026 TTH/V/D 038 TTH/V/D 049 TTH/V/D 064 Voltage Code Voltage Min/Max Voltage Compressor QTY RLA LRA Fan Motor FLA Total Unit FLA Min Circuit Amp Max Fuse/ HACR Pump FLA Total Unit FLA Min Circuit Amp G 208-230/60/1 197/254 1 10.3 52.0 4.3 14.6 17.2 25 0.43 15.0 17.6 25 G 208-230/60/1 197/254 1 16.7 82.0 4.3 21.0 25.2 40 0.8 21.8 26.0 40 H 208-230/60/3 197/254 1 11.2 58.0 4.3 15.5 18.3 25 0.8 16.3 19.1 30 F* 460/60/3 414/506 1 4.5 29.0 4.1 8.6 9.7 15 0.7 9.3 10.4 15 G 208-230/60/1 197/254 1 21.2 96.0 7.0 28.2 33.5 50 0.8 29.0 34.3 50 H 208-230/60/3 197/254 1 13.5 88.0 7.0 20.5 23.9 35 0.8 21.3 24.7 35 F* 460/60/3 414/506 1 6.4 41.0 6.9 13.3 14.9 20 0.7 14.0 15.6 20 G 208-230/60/1 197/254 1 25.6 118.0 7.0 32.6 39.0 60 1.07 33.7 40.1 60 H 208-230/60/3 197/254 1 17.6 123.0 7.0 24.6 29.0 45 1.07 25.7 30.1 45 F* 460/60/3 414/506 1 9.0 62.0 6.9 15.9 18.2 25 1.07 17.0 19.2 25 Max Fuse/ HACR *460V with ECM motor requires a neutral wire. 460V with secondary pump requires a neutral wire. Pump and ECM motor are rated 265V and are wired between one hot leg and neutral HACR circuit breaker in USA only Wire length based on one way measurement with 2% voltage drop Wire size based on 60 C copper conductor All fuses Class RK-5 45

ClimateMaster Water-Source Heat Pumps Tranquility 27 Two-Stage (TT) Series 2 to 5.5 Ton Horizontal and Vertical EarthPure Units Unit Wiring Diagram Matrix Only CXM and DXM diagrams, with a representative diagram of LON and MPC Options are pre sented in this submittal. Other diagrams can be lo cated online at www.climatemaster.com using the part num bers presented below. Model Refrigerant Wiring Diagram Part Number Electrical Control DDC Fan Motor 96B0006N18-96B0006N16 CXM LON ECM TT Series Single Phase EarthPure HFC410A 96B0006N14 96B0006N19 96B0006N17 96B0006N15 208-230/60/1, 265/60/1 DXM MPC - LON MPC ECM 96B0038N66 ClimaDry 96B0007N18 - TT Series Three Phase (230 Style) EarthPure HFC410A 96B0007N16 96B0007N14 96B0007N19 96B0007N17 96B0007N15 208-230/60/3 CXM DXM LON MPC - LON MPC ECM ECM 96B0007N29 ClimaDry 96B0008N18 - TT Series Three Phase (460 Style) EarthPure HFC410A 96B0008N16 96B0008N14 96B0008N19 96B0008N17 460/60/3 CXM DXM LON MPC - LON ECM ECM 96B0008N15 MPC All wiring diagrams available at www.climatemaster.com. 46

The Smart Choice for Energy Efficiency Typical Wiring Diagram - CXM Controls - Single Phase 47

ClimateMaster Water-Source Heat Pumps Tranquility 27 Two-Stage (TT) Series 2 to 5.5 Ton Horizontal and Vertical EarthPure Units Typical Wiring Diagram - DXM Controls - Single Phase 48

The Smart Choice for Energy Efficiency CXM AND DXM SERIES CONTROLLERS The CXM and DXM Series Controllers are designed to enhance Water-Source Heat Pump unit performance with the ability to coordinate complete systems. CXM Series controllers offer complete stand-alone unit control. DXM Series controls add advanced unit operation and system control features. Either control can allow you to connect your heat pump system to a LonWorks or MPC (Multiple ProtoCol -- BACNET, N2, Modbus) DDC control system which includes lighting and other energy saving controls. The CXM and DXM Series are the most advanced controllers made by any heat pump man u fac tur er today. STANDARD CXM CONTROL FUNCTIONS The CXM controller package offers all of the basic features available with elec tro me chan i cal systems, plus 15 additional standard functions. This group of added features includes condensate overflow, antishort cycle, random start, aircoil low temperature limit (except GC Series and water-to-water units), under/over voltage protection, and intelligent reset, designed to automatically restart a unit within a specific period of time following a fault, given the fault has been adequately corrected. Also included are LED fault and status indication to aid in diagnostics and troubleshooting. These added features, and the many others provided, are specifically designed to improve the life expectancy, reliability, and serviceability of Water-Source Heat Pumps. The CXM is compatible with most heat pump thermostats. ADDITIONAL DXM CONTROL FUNCTIONS The DXM controller adds system functions such as emergency shutdown and night setback with override to the stand-alone capability provided by the CXM. Fully configured, the DXM offers 17 additional features over the CXM, including advanced system control capabilities such as intelligent fan speed, reheat control, two-stage compressor, and boilerless electronic heat. The DXM is compatible with almost any type of thermostat, whether heat pump or heat/cool. CXM Control Board DXM Control Board COMFORT CONTROL User se lect able or in tel li gent control of fan speed, de hu mid i fi ca tion modes, out door air damper control, and a com plete of fer ing of ac cu rate electronic thermostats add up to in creased comfort through superior unit control. DIAGNOSTICS ClimateMaster controls provide on-board diagnostics which highlight eight (seven for GC Series) different reasons for unit malfunction, speeding up service time, elim i nat ing un nec es sary service charges, and minimizing down time. The exclusive UPS (Unit Performance Sentinel) provides an early warning of inefficient operating conditions before unit shutdown actually occurs. Fault types are not only indicated at the control, but are kept in memory after a user reset for future service use. And another ClimateMaster exclusive, fault types can be displayed on a conventional thermostat if equipped with a fault LED, or can be remotely communicated with the DDC option. UNIT/SYSTEM OPERATING EFFICIENCY Emergency shutdown, night setback, pump restart and advanced unit functional control all work to enhance the performance of your system. These features are stan dard on DXM Series Electronic Controllers. 49

ClimateMaster Water-Source Heat Pumps Tranquility 27 Two-Stage (TT) Series 2 to 5.5 Ton Horizontal and Vertical EarthPure Units OPEN-PROTOCOL DDC CAPABILITY The CXM and DXM Series can be upgraded with the ad di tion of a separate LonMark or MPC (Multiple ProtoCol -- BACNET, N2, Modbus) DDC module, ei ther as a factory option, or field installed at a later date. LonWorks is an open protocol DDC network, which can be in te grat ed with most third-par ty building automation systems. In addition, the MPC controller offers the other popular building management system protocols (BACNET, N2, Modbus). ClimateMaster's DDC options pro vide the flexibility to upgrade your control system as your de mands require, and gives you the freedom to interface with most any DDC sys tem vendor. Leaving air and water tem per a ture sensors are factory mounted, for remote mon i tor ing, and a wide range of wall sen sors are avail able. The wall sensors utilize a simple interface and can provide dig i tal display and the unit control ca pa bil i ty found in conventional thermostats. ASW Wall Sensors for Lon or MPC DDC Systems 50