Instruction manual. Carlin Combustion Technology, Inc. 70 Maple Street East Longmeadow, MA Ph Fx

Similar documents
COMBUSTION AIR SYSTEM

BIG BOOT COMBUSTION AIR KIT Model: CAS-2BB, CAS-2CB, CAS-2B375

Vent Supplement Ultra-80, -105, -155, -230 & -310

EUTECTIC EC-10DV Series

Vent and air piped through a side wall (concentric termination)

Oil Fired Unit Heaters September, 2008

Venting Supplement. Direct Vent Through-Roof or Through-Unused-Chimney. Water Boiler Series 3 & 4

Do not use this vent pipe or fittings for venting incinerators of any kind.

Instruction manual Supplement

COMBUSTION AIR SYSTEM Model: CAS-3

Installation, Operation and Service Manual

POWER VENTER SYSTEM. Model: PVO-300, PVO-600

GWS. Venting Manual. Gas-Fired Water Boilers. Hazard definitions. Contents. Venting method definitions

Venting Supplement Saf-T Vent 3" venting Special gas vent system vent and combustion air supplement for 3" diameter venting Hazard definitions

COMBUSTION AIR SYSTEM

GOLD. Venting Supplement. Water Boiler Series 3 & 4. for 3" venting

SCS SCS

Direct Vent Addendum For use in conjunction with B-10, or SG atmospheric venting manuals QHT DVF

INSTALLATION INSTRUCTIONS

INSTALLATION INSTRUCTIONS FOR THROUGH-THE-WALL VENTING COMPONENTS

INSTALLATION AND SERVICE MANUAL

200i. Vent/air manual. Installation instructions for vent and air piping. Also read and follow: 200i Boiler manual 200i Control manual

INSTALLATION AND SERVICE MANUAL

GOLD GV. Venting Supplement for 3 venting. Water Boiler Series 3 & 4

INSTALLATION INSTRUCTIONS

TRIAD Boiler Systems, Inc Atlantic Drive, Unit 2 West Chicago, IL

Direct Exhaust Venting Kit Instructions

9. Check condensate piping for sagging and/or leakage. Repair any sags or leaks before restoring power to the appliance.

Installation Instructions T 9822 Gas Dryer. en - US, CA. To prevent accidents

SIDEWALL POWER VENTER KIT

ASX7-4-IOM-6 J

PVC, CPVC, PP & SS Vent Supplement

INSTALLATION AND OPERATION MANUAL FOR 2 STAGE RIELLO BURNER ADDENDUM TO ( Mo 437 manual )

POWER VENTER. Model: PVE Series

GOLD GV. Venting Supplement. Water boiler Series 3. Special gas vent system vent and combustion air supplement. Hazard definitions.

Model Universal Oil Primary Control

Side by side. Cascade Venting System for RTG 199HE. Extension Set for units 3 or Installation instructions

R5-9/09. Price - $5.00

Internet Version for Reference Only INDUCED DRAFT COMMERCIAL WATER HEATERS SUPPLEMENT INSTRUCTIONS TO PART #

SG Oil Fired Boilers From QHT INC. Direct Vent Addendum - Oil For use in conjunction with B-10, or SG atmospheric venting manuals QHT DV OIL WARNING

Back to back. Cascade Venting System for RTG 199HE. Basic Set for units 1 and Installation instructions

INSTALLATION AND OPERATING INSTRUCTIONS TABLE OF CONTENTS IMPORTANT

SAFETY AND INSTALLATION MANUAL MODEL 8100

Installation instructions for the T 9820 Gas Dryer

INSTALLATION OF VENTING SYSTEM COMPONENTS WARNING

PVE SERIES POWER VENTER SYSTEM MANUAL

Instruction manual. Ratings. Contents. Carlin Combustion Technology, Inc. 126 Bailey Road North Haven, CT Phone Fax

Installation & Operation Manual Models:

INSTALLATION INSTRUCTIONS

Installation Instructions Remote Blowers

Installation Instructions

ASX7-5-IOM-3 J

Gas and Electric Dryer user manual

User s Information Manual

Aqua Balance. Direct Exhaust Venting Kit Instructions

Model 601CRD Oil Burner

INFRARED RADIANT TUBE HEATER RSTP15C NATURAL GAS RSTP17C

Boiler Manual. Gas-fired water boilers. Featuring. Flexibility

SEPARATED COMBUSTION WARNING

Direct Vent Supplement

DESIGN CLASS FUNCTION

EMPIRE II SERIES II Models 3EW.65 3EW.75 3EW1.00 4EW.90 4EW1.25 4EW1.50 5EW1.20 5EW1.75

Heat Exchanger Block Replacement Instructions

User s Information Manual

Noble Fire Tube Boiler and Combi Installation & Service Manual NKC NKB

Kallista Bath Flip Drain

Installation Instructions

Single stage operation oil burner

OIL-FIRED CAST IRON HOT WATER BOILER. Parts and Optional Accessories

PrecisionTemp Shower-Mate

Direct Vent System Required

INSTALLATION GUIDE Dual Fuel Ranges

Corr/Guard PRESSURE RATED VENTING SYSTEM IMPORTANT: DO NOT INSTALL WITHOUT FIRST READING THESE INSTRUCTIONS VERY CAREFULLY.

OPERATING INSTRUCTIONS MANUAL (Please retain for future reference) FVN/P-400 INDIRECT FIRED SPACE HEATERS

TECH SUPPORT

TRI-STAR INC SOUTH STANDARD AVENUE, SANTA ANA, CA Ph: Fax: MODEL #. OWNER S MANUAL

Integrated Ventilation System

AquaBalance SERIES 2 WALL MOUNT GAS-FIRED WATER BOILER Boiler Manual. Contents. Page. Hazard definitions

Duct Leakage, Sealing & Testing

FreeStyle Wall Mount Gas-Fired Condensing Boilers Combi & Heat Only Models

Installation Guide. Model: IC15- MF Model: IC15- MFSilent Model: IC30- MF Model: IC30- MFSilent

Fire Tube Combi Boiler Installation & Service Manual Models:

R4-2/06. Price - $5.00

READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY BEFORE PROCEEDING WITH THE INSTALLATION.

P-K MACH GAS-FIRED BOILER C1500H C2000H OUTDOOR BOILER KIT GUIDE

Second Revision No. 3 implements the text of Committee Input No. 36 as proposed in the First Draft Report, along with the following amendments:

ASSEMBLY INSTRUCTIONS - NXS SERIES. INFRARED RADIANT TUBE HEATER Single and Two Stage Pull Through System (Negative Pressure)

INSTALLATION INSTRUCTIONS G2D93CT, G2D93CU, G2D95CT, & G2D95CU High Efficiency Multiposition Gas Furnace with System Sentry Control System WARNING

INSTALLATION INSTRUCTIONS

Installation guide and material checklists

Fire Bowls and Fire Bowl Inserts (Automated Operation) Operating and Maintenance Instructions

GE Monogram. Installation. Instructions. Component Cooktop System. Models ZEW145V ZGW124EN3 ZGW125EN3 ZEW155N ZEW166Y ZEW176Y

Replacement parts. OBTAIN PARTS ONLY THROUGH WEIL-McLAIN THE BOILER CONTAINS CERAMIC FIBER MATERIALS REPLACEMENT PART NUMBERS. REINSTALL Jacket door

Odyssey Model Numbers: CT Version Date:

Installation & Operation Manual Models: WH

CAST 92. Boilers. As an ENERGY STAR Partner, PB Heat, LLC has determined that this product meets the ENERGY STAR guidelines for energy efficiency.

FreeStyle Wall Mount Gas-Fired Condensing Boilers Combi & Heat Only Models 80/120/155

Installation Guide. 5 Series VGC and VGSU Built-In Gas Cooktops

Aqua Balance. Boiler Manual WMB-80/120/155. Wall Mount Gas-Fired Condensing Boilers Combi and Heating Only Models. Quick Start Guide Pages 3 & 4

TECHNICAL INFORMATION COMMUNICATION

Transcription:

Instruction manual Applies to air intake assemblies: 97406 on EZ-1 burners 97406C on EZ-LF burners 97406A or 97406B on EZ-Gas burners Installation also requires a Field Controls Model CAS 1 air hood and vacuum relief valve, supplied by installer. Model 97406 air intake assembly installed on a Carlin EZ-1 oil burner Connecting an outside air supply directly to the burner, using the Carlin air intake system, requires the following: Use only a Carlin 97406 for an EZ-1 oil burner, 97406C for an EZ-LF oil burner, or a 97406A (horizontal) or 97406B (vertical) air boot for an EZ-Gas burner. Obtain and install only a Field Controls Model CAS-1, with 4 inlet air hood and 4 vacuum relief valve. The burner and all components must be installed by a qualified service technician. The burner must be started and set up (using combustion test instruments) according to the burner and appliance manuals and this air intake system manual. Because inlet air temperature affects how much air enters the burner, the installer must use the combustion set-up table in this manual to compensate for the air temperature at the time of combustion adjustment. Installer/servicer Except where specifically stated otherwise, this manual must be used only by a qualified service technician. (In the state of Massachusetts, this product must be installed by a licensed Plumber or Gas Fitter.) Failure to comply with this or other requirements in this manual could result in severe personal injury, death or substantial property damage. Code compliance Follow all applicable state and local codes regarding installation of the burner, appliance, venting and air supply. Copyright 2007 Carlin Combustion Technology, Inc. Carlin Combustion Technology, Inc. 70 Maple Street East Longmeadow, MA 01028 Ph 413-525-7700 Fx 413-525-8306 Tech support 800-989-2275 carlincombustion.com

1. Assemble air intake assembly to the burner (EZ-1 or EZ-LF oil burner) Assemby of 97406 to an EZ-1 or 97406C to an EZ-LF burner 1. 2. 3. 4. 5. 6. Disconnect oil lines as shown above. For burners with integral oil valve fuel units, just disconnect the oil line fitting at the knurled nut as shown. For burners with separate oil valves, disconnect both fuel unit oil lines as shown in Figure 1. Bend the oil lines to fit the new configuration. Remove the two bolts that secure the fuel unit to the burner housing. Then move the fuel unit out of the way (integral oil valve type) or remove the fuel unit as shown in Figure 1 (separate oil valve type). Remove the burner air shutter and air band and discard them. Assemble the air intake assembly to the burner as shown in Figure 1. Reattach the fuel unit to the burner housing with the two bolts removed in step 2. Integral oil valve fuel unit type Reattach the oil valve at the knurled nut. Separate oil valve type Bend the oil lines to fit and reattach both lines to the fuel unit and burner as shown in Figure 1. 2

Figure 1 Assembling an air intake assembly to a Carlin EZ-1 or EZ-LF oil burner 3

1. Assemble air intake assembly to the burner (EZ-Gas gas burner) Assemby of 97406A or B to an EZ-Gas burner 1. 2. 3. Remove the two bolts that secure the airflow switch bracket to the burner housing. Move the airflow switch out of the way. Then remove and discard the air band. Install the air intake assembly and gaskets as shown. Reattach the airflow switch bracket to the burner housing with the two bolts. Make sure the airflow sensing lines are inserted into the holes in the burner housing. 4

Model 97406 Combustion air intake system Instruction manual Figure 2 Assembling a 97406A or B air intake assembly to a Carlin EZ-Gas gas burner 5

2. Install combustion air piping Air piping components Field CAS-1 combustion air system The installer must obtain a Field Controls Model CAS-1 inlet air system. The vent piping must include the vacuum relief valve (4 VRV) and intake air hood (4 IAH Hood) provided in the Model CAS-1 kit. (See Figure 3.) Material Use only corrosion-resistant metal pipe 4 inches in diameter. Joints Air pipe joints must be sealed with duct tape or silicone adhesive sealant. Supports Provide piping supports located to prevent pipe sagging and to support the air piping independently from the burner. Maximum length When using smooth metal pipe, the maximum allowable length of air piping is 30 feet with two or less elbows. Each additional elbow reduces the maximum length of air piping by 7 feet. See the following table. Number of elbows in air piping Maximum total air pipe length 2 30 3 23 4 16 5 9 Figure 3 Air piping components Insulation Cold inlet air can cause condensation to form on the outside of the air piping. For installations where the inlet air temperature can be -10 F or lower, insulate at least the first 10 feet of air pipe (beginning at the air pipe intake air hood location). Component installation Field Controls vacuum relief valve 1. 2. 3. Install the VRV tee in the air piping as shown in Figure 3. Adjust the tee so the opening for the gate is plumb. Install the VRV balance weight on the gate as shown in Figure 3, bottom left. Mount the gate assembly in the VRV tee. Level across the gate pivot points as shown in Figure 3, bottom right. Field Controls intake air hood Air hood location air hood must be: 1. Always mounted with the intake pointed down. 6 2. At least 12 inches above grade (and at least 12 inches above the highest possible snow line). 3. No closer than 12 inches in any direction to the appliance vent outlet if sidewall vented. Air hood installation 1. Cut a 4¼ -diameter hole through the sidewall of the building. 2. Slide the inlet air hood pipe through the opening. 3. Seal the mounting plate with silicone adhesive sealant. 4. Secure the air hood assembly to the wall with appropriate fasteners. Vent pipe installation 1. Secure all joints with screws. Seal all joints using silicone sealant or duct tape. 2. Secure all air piping so the weight is carried completely by the supports. 3. Do not exceed the maximum length given in this manual. 4. Insulate the air pipe if inlet air temperature can be -10 F or colder, or if there is a likelihood of condensation on the vent pipe for any reason.

1. Burner/appliance operation Field Controls vacuum relief valve Table 1 EZ-1 oil burner combustion air settings The vacuum relief valve should open temporarily to allow the burner to use inside air if the air intake piping develops a negative pressure. Negative pressure can occur due to blockage or icing of the air intake or to wind effects on the building. The vacuum relief valve should only open occasionally, and should not remain open for long periods. Vacuum relief valve operation For installations where the appliance space may not be able to provide sufficient air for sustained operation using inside air, instruct the building owner to check the vacuum relief valve periodically. If the vacuum relief valve remains open for sustained periods, the owner should check the air inlet hood to see if it is obstructed. He should clear any obstructions and check to see if the problem persists. If the air inlet hood is not obstructed, or if removing obstructions does not solve the problem, the owner must contact the burner technician immediately to diagnose and correct the reasons for negative pressure in the air piping. Failure to follow these guidelines could result in severe personal injury or death. Adjust the burner using test instruments After installing the Carlin air intake system and air piping, you must adjust the burner air settings as directed below. The burner air setting must be adjusted Adjust the Carlin air intake boot damper to starting setting given in the burner (or appliance) manual. Then follow the burner instruction manual procedure to start the burner and set combustion, using combustion test instruments. EXCEPTION to burner manual combustion settings: Because the inlet air temperature will vary during the year, you must set the (O 2 ) at different values for different inlet air temperatures. Adjust the burner, following the burner manual, to achieve the (O 2 ) values given in Table 1 or Table 2. Make sure to apply the oil values for oil burners (Table 1) and the gas values for gas burners (Table 2). When final adjustments are complete, the or O 2 values must be between the min and max values given in Table 1 or Table 2. Smoke number, as stated in the burner manual, must be zero for oil firing. Failure to properly adjust the burner/appliance following the burner/appliance manuals and the guidelines in this manual could result in severe personal injury, death or substantial property damage. Inlet air temperature during setup Max and O 2 Min at setup #2 Fuel oil min min -20 F to 0 F 8.8 % 10.6 % 8.9 % 6.4 % 5 F to 30 F 9.9 % 11.9 % 7.4 % 4.7 % 35 F to 60 F 10.5 % 12.5 % 6.6 % 3.9 % 65 F or higher 11.0 % 13.2 % 5.9 % 2.9 % Table 2 Inlet air temperature during setup EZ-Gas gas burner combustion air settings Max and O 2 Min at setup Natural gas min min -20 F to 0 F 7.0 % 8.3 % 8.8 % 6.0 % 5 F to 30 F 7.5 % 9.4 % 7.9 % 4.8 % 35 F to 60 F 8.0 % 9.9 % 7.0 % 3.6 % 65 F or higher 8.5 % 10.4 % 6.0 % 3.0 % Inlet air temperature during setup Max and O 2 Min at setup Propane gas min min -20 F to 0 F 7.5 % 9.4 % 8.7 % 5.8 % 5 F to 30 F 8.0 % 10.6 % 8.0 % 4.6 % 35 F to 60 F 8.5 % 11.2 % 7.3 % 3.5 % 65 F or higher 9.5 % 11.8 % 6.0 % 2.9 % 7

8