HVAC BASIC MATERIAL AND METHODS 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS

Similar documents
SECTION METERS AND GAGES FOR HVAC PIPING

SECTION METERS AND GAGES FOR PLUMBING PIPING

STEAM AND CONDENSATE PIPING AND PUMPS DESIGN AND CONSTRUCTION STANDARD

University of Delaware

B. HI Compliance: Design, manufacture, and install pumps in accordance with HI "Hydraulic Institute Standards."

1. Division 23 Section "Steam and Condensate Heating Piping" for steam and condensate meters.

D. NEMA Compliance: Provide electric motors and components which comply with NEMA standards.

C. ASSE 1013: Performance Requirements for Reduced Pressure Principle Backflow Preventers.

SECTION METERS AND GAUGES FOR HVAC PIPING

PROJ. NO SECTION METERS AND GAGES FOR HVAC PIPING

4. Provide brass valve tags marked for the service. See pertinent service specification for valve type.

A. ASME Compliance: Fabricate and install hydronic piping in accordance with ASME B31.9 "Building Services Piping.

Essex County College - West Essex Campus Addition And Renovations dib # / SECTION HYDRONIC PIPING SPECIALTIES PART 1- GENERAL

SECTION HYDRONIC PIPING AND SPECIALTIES

. ECTION METERS AND GAGES

SECTION METERS AND GAGES

Division 23 - HVAC Switzerland Beallsville K-12. Section HYDRONIC PIPING SECTION HYDRONIC PIPING PART 1 - GENERAL

B. Unit construction shall comply with ASHRAE 15 Safety Code, NEC, and ASME applicable codes (U.S.A. codes).

B. Product Certificates: For each type of meter and gage, from manufacturer.

SECTION SECTION DESIGN REQUIREMENTS

TECHNICAL. Series 18. Pump Packages

RESEARCH AND TECHNOLOGY BUILDING RENOVATION 05/18/09 SECTION REFRIGERANT PIPING AND SPECIALITIES

UNIVERSITY OF MISSOURI Building Hydronic Piping and Pump Systems 2017 Q3

OKLAHOMA STATE UNIVERSITY - BUILDING DESIGN STANDARDS

D-11 OUTLINE SPECIFICATION FOR HTHW (ABOVE GRADE) HYDRONIC PIPING

Copyright 2003 and 2005 by The American Institute of Architects (AIA) Modified by MSU Physical Plant / Engineering and Architectural Services

NATURAL GAS PIPING

B. Shop Drawings: Detail fabrication of pipe anchors, hangers, special pipe support assemblies, alignment guides, expansion joints and loops,

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

SECTION HYDRONIC PIPING

A. This Section includes the following domestic water piping specialties:

HEAT GENERATION 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS. B. Section HVAC Basic Materials and Methods

SECTION HYDRONIC PIPING

DOCUMENT TABLE OF CONTENTS

Main Steam Vents. Hoffman Specialty Regulators. How to Select Steam Vents

PROJ. NO SECTION REFRIGERANT PIPING

YALE Site Specifications AIR VENT SCHEDULE

DENVER PUBLIC SCHOOLS DESIGN AND CONSTRUCTION STANDARDS This Standard is for guidance only. SECTION PUMPS

SECTION LABORATORY and DE-IONIZED WATER SYSTEMS STANDARD CONSTRUCTION STANDARD

SECTION GENERAL-SERVICE COMPRESSED-AIR SYSTEMS

REFRIGERANT PIPING

CONTENTS. A. Summary. Yale University Design Standards. Valves. Change History

DIVISION 23 HVAC Hydronic Piping Systems

SECTION BASIC MATERIALS AND METHODS

SECTION HEATING AND AIR CONDITIONING PIPING SYSTEMS. A. Provisions of Division 01 apply to this section. 1. Chilled Water System.

Ratio Architects, Inc. Section Refrigerant Piping

DESIGN STANDARDS SECTION 15600

UNDP / PAPP OFFICE BUILDING RAMALLAH HVAC WORKS

1.1 This section applies to air handling units for HVAC Systems.

Water Piping and Pumps

SECTION REFRIGERANT PIPING

SECTION STEAM CONDENSATE PUMPS

MLA Architects Pierz Public Schools ISD #484 Healy High School Multi-Purpose & Choir Additions Pioneer Elementary School Class Room Addition Pierz, MN

VENTS. Main Steam Vents. How to Select Steam Vents. For Steam Vent selection information, please refer to Selection Guidelines on page 133.

REFRIGERANT PIPING SYSTEM

SECTION DOMESTIC WATER PIPING SPECIALTIES

Wayne State University WSU Project No Chatsworth Tower Apts. Misc. Bldg. Upgrades DSD Project No

FORMAT 1. Technical specifications content and numbering system shall be based on the 2004 version of CSI MasterSpec.

FIRE PROTECTION. 1. Vertical fire pumps shall not be used at the University.

SECTION COMPRESSED AIR SYSTEM. A. Pipe and pipe fittings, including valves, unions and couplings.

A. Operation and Maintenance Data: For pumps to include in emergency, operation, and maintenance manuals.

Intelligent Refrigeration Solutions

Update In Progress. Division 23 Heating, Ventilation, and Air Conditioning Page Section FLUID SYSTEMS EQUIPMENT PART 1 GENERAL

THE JAMES RUSHTON EARLY LEARNING AND FAMILY SUCCESS CENTER #2616 ISSUE FOR CONSTRUCTION

DARTMOUTH COLLEGE DESIGN November 15, 2007 & CONSTRUCTION GUIDELINES

1. Product Data for Prerequisite EQ 1: Documentation indicating that units comply with ASHRAE 62.1, Section 5 - "Systems and Equipment.

Brown University Revised August 3, 2012 Facilities Design & Construction Standards SECTION AIR HANDLING UNITS

A. Air Handling Units shall be designed to the specific requirements of the application: Recirculation or 100% Makeup.

DIVISION 23 HEATING, VENTILATING AND AIR CONDITIONING (HVAC) 2006 Edition, Published January 1, 2006; Division Revision Date: February 28, 2018

Design and Construction Standards SECTION PLUMBING EQUIPMENT

HYDRONIC SPECIALTIES TACO AC(F)-CA 05/08/2008

SECTION PLUMBING EQUIPMENT

PROJECT NAME: DPW Idaho State University Liberal Arts Building Chiller Replacement

CHILLED WATER SYSTEM 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS. B. Section HVAC Basic Materials and Methods

1.1 Refer to Section for General Mechanical Requirements. 1.3 Refer to Section for Pipe and Equipment Identification Requirements.

HYDRONIC SPECIALTIES TACO MPT Tank(s) 05/30/2012. A. Multi-Purpose Tank buffer tank, air separator, and hydraulic decoupler

C. ASME Compliance: Fabricate and label water chiller heat exchangers to comply with ASME Boiler and Pressure Vessel Code: Section VIII, Division 1.

Appendix B. Symbols for Drawings. Table B.1. Air moving devices and ductwork symbols. Air Movement. Fans. Axial flow fan.

A. This section includes design and performance information for fire protection and suppression systems.

Mercy Hospital of Buffalo Catholic Health System 2 nd Floor Patient Holding Center 3 rd Floor Locker Rooms Shaflucas Architects, PC Project No.

SECTION (15530) - REFRIGERANT PIPING

DIVISION 15 MECHANICAL

SECTION STEAM AND CONDENSATE HEATING PIPING

PROJ. NO SECTION HYDRONIC PIPING

A. ASHRAE Handbook HVAC Applications, Snow Melting and Freeze Protection

B. Provide unique numbers for all applicable equipment, valves, and similar.

SECTION (15486) - FUEL-FIRED, DOMESTIC WATER HEATERS

HYDRONIC SPECIALTIES TACO AC(F)-PAX 05/15/2008

Engineering Specifications

WELLSPAN ECH HEALTH PAVILION ADDITION AND RENOVATION RFMA

HERZ Regulating valve 4002

SECTION (15530) - REFRIGERANT PIPING

Lee s Summit West High School Boiler #3 Replacement SECTION CONDENSING BOILERS

HERZ Differential Pressure Control Valve 4002

SECTION WET-PIPE SPRINKLER SYSTEMS

KINGS COUNTY JAIL EXPANSION PHASE III COUNTY OF KINGS SECTION

System and equipment drains shall be piped to a floor drain. Gauges shall be provided on the suction and discharge side of all pumps installed.

TABLE OF CONTENTS DIVISION 23 HVAC PIPING AND EQUIPMENT

SPRINKLERS TABLE OF CONTENTS

SECTION PLUMBING EQUIPMENT

Transcription:

230500 HVAC BASIC MATERIAL AND METHODS PART 1 GENERAL 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS A. Section 230000 Basic HVAC Requirements B. Section 230523 Valves C. Section 230510 Chilled Water Systems D. Section 230520 Heat Generation E. Section 232300 Refrigeration F. Section 238216 Coils 1.02 SCOPE A. This section applies to HVAC materials installed within the perimeter of the structure from the meter or utility connection to points of utilization with the building. For service piping outside the building perimeter, please contact Cornell Utilities. PART 2 PRODUCTS 2.01 GENERAL A. Use of grooved joint fittings are strictly prohibited on campus chilled water systems. B. Use Teflon tape for threaded pipe; use joint compound on high pressure steam. C. The only type of copper pressure seal fitting system that is allowed to be used on campus are those that use a mechanical joint that crimps on both sides of the O-ring, and shall be limited to use on hydronic heating and process chilled water systems. The only acceptable manufacturer is Viega. D. Piping shall be fully labeled throughout (mechanical rooms, chases and throughout buildings). Labels should include name of system, flow arrow, color code and size of pipe. Stencils are acceptable. Label every 25 feet, and at all penetrations and branches. E. Provide vents and drains (minimum ½-inch) with brass hose connector and cap at all high and low points in piping systems. DATE: 6/30/17 DATE: 6/30/15 Page 1 of 6

F. On chilled water systems, use a Schedule 80 galvanized steel nipple between the steel piping and the first isolation valve on all connections to steel pipe below 3-inches. G. Processed chilled water systems are defined as being an independent cooling loop separated from the campus chilled water distribution system by a plate and frame heat exchanger that is intended to serve as a heat rejection sink for water cooled equipment, such as walk-in coolers, lasers, etc. A chilled beam cooling loop is not considered a process chilled water system. H. Due to Cornell s experience with increased frequency of maintenance, the following piping specialties are not allowed on campus: 1. Dielectric Unions 2. Automatic Flow Control Valves 3. Combination balancing and shutoff valve 4. Triple Duty Valves I. Please consult with Facilities Engineering for deviations from these standards. 2.02 HOSES AND HOSE BIBBS A. All hose bibbs and other fittings with hose connections shall be provided with vacuum breakers. B. Hose bibbs on building exteriors shall be frost-free type. 2.03 GATE VALVES A. Gate valves are generally not acceptable. Use ball and butterfly valves only. See Cornell Design and Construction Standard 230523. 2.04 PRESSURE GAUGES A. On devices such as pumps, strainers, coils, etc., where the differential pressure is the desired information, install only one pressure gauge with valved connections to the upstream and downstream pressure taps. Include a P/T test port in addition to the pressure gauge. Provide a second set of isolating valves at the gauge if gauge location is not within reach of tap points. B. Pressure gauges shall be stainless steel case, non-repairable, silicone filled with minimum 3-1/2 inch diameter case. Gauges shall have 3% accuracy over the appropriate range of 0-30 psi, 0-100, or 0-160; and shall include a shut-off ball valve (gauge cocks are not permitted). Include a pigtail cooling loop on all steam gauges. DATE: 6/30/17 DATE: 6/30/15 Page 2 of 6

Scale should be selected to provide a reading at mid-scale during normal operation. No snubbers. 2.05 THERMOMETERS A. Thermowells: All thermowells for steam service shall be stainless steel and for water service shall be brass. Thermowell length shall be in accordance with ISA standards and shall include the appropriate extension to allow for pipe installation. Extension neck shall be included when required to match thermowell and insulation thickness. B. Thermometers: Provide one of the following: 2.06 PUMPS 1. Industrial stick type, mercury free, 9-inch case, with locking adjustable angle body and a case of aluminum or non-metallic material. Thermometer shall be secured to well by tapered bushing and not by set screws. Provide the following characteristics: a. Scale Graduations: 2 F. b. Range: Select to provide a mid-scale reading at normal operating temperature. c. Accuracy: 1%. 2. Industrial light-powered digital thermometer with adjustable-angle stem and a case of aluminum or high impact ABS plastic. Thermometer shall be secured to thermowell by tapered bushing and not by set screws. Installation shall insure that thermometer is accessible and has been adjusted to be readable from a 5- foot level as viewed from the floor. Display shall be LCD with digits a minimum of 0.5-inch high with the following characteristics: a. Resolution: 0.1 F. b. Range: -40 to 300 F. c. Sensor: Glass passivated thermistor. d. Accuracy: 1%. 3. Acceptable Manufacturers: a. Trerice b. Weiss Instruments c. Weksler A. All pumps shall have mechanical seals with carbon and ceramic seats. B. All pump bases shall be grouted. C. All vibration isolators shall be installed parallel to the pump shaft. DATE: 6/30/17 DATE: 6/30/15 Page 3 of 6

D. Install pressure gauge manifold to gauge tappings in pump body. E. The Engineer can consider the use of vertically mounted in-line pumps for all hydronic system applications as they save space and are, in general, easier to maintain than other centrifugal pump designs. 2.07 PIPING ACCESSORIES A. Pressure/temperature test ports shall be provided on each coil bank, heat exchanger, fan coil, and at all permanent pressure gauge locations. Use extended body style to allow for insulation thickness. Seals shall be appropriate for operating water temperature and pressure as follows: 1. Hot Water, Glycol - Nordel Seat 2. Cold Water, Chilled Water - Neoprene Seat B. All coils and heat exchangers shall be equipped to measure and adjust flow. Adjustable valves with flow measuring taps are preferred. The balancing valve shall not be used for coil isolation--provide ball or butterfly isolation valves in addition to the balancing valves. C. If a balancing valve with flow taps cannot be used (larger than 12-inch), use a nonlubricated eccentric plug valve (such as Dezurik) combined with a flowmetering run and an Annubar flowmeter. 2.08 METERS A. Steam service: See Cornell Design and Construction Standard 230520. B. Chilled Water Service: See Cornell Design and Construction Standard 230510. C. Provide a water meter on large permanent hard piped make-up lines to water systems (radiation, closed loop cooling, or systems with underground piping) to track makeup to these systems. DATE: 6/30/17 DATE: 6/30/15 Page 4 of 6

2.09 PIPE, FITTINGS AND JOINING MATERIALS A. Chilled Water 2.5-inch & below ASTM B88 ASME B16.22 ASTM B32 Type L Hard Copper Wrought Copper Solder 95 Sn / 5 Sb 95.5 Sn / 4 Cu / 0.5 Ag 3-inch & above ASTM A53 ASME B16.9 ASME B16.9 B. Process Chilled Water All sizes ASTM B88 ASME B16.22 ASTM B32 Type L Hard Copper Wrought Copper Solder 95 Sn / 5 Sb 95.5 Sn / 4 Cu / 0.5 Ag 2-inch & below ASTM B88 ASME B16.22 ASME B16.22 Type L Hard Copper Wrought Copper Copper Pressure Seal EPDM Sealing Element C. Heating Hot Water 2.5-inch & below ASTM B88 ASME B16.22 ASTM B32 Type L Hard Copper Wrought Copper Solder 95 Sn / 5 Sb 95.5 Sn / 4 Cu / 0.5 Ag 3-inch & above ASTM A53 ASME B16.9 ASME B16.9 2-inch & below ASTM B88 ASME B16.22 ASME B16.22 Type L Hard Copper Wrought Copper Copper Pressure Seal EPDM Sealing Element DATE: 6/30/17 DATE: 6/30/15 Page 5 of 6

D. Low Pressure Steam, 15 psig and below 2-inch & below ASTM A53 ASTM A126 ASME B16.4 Sch 40 Black Steel ASME B16.4 Threaded Cast Iron 2.5-inch & above ASTM A53 ASME B16.9 ASME B16.9 E. High Pressure Steam, Above 15 psig 2-inch & below ASTM A53 ASME B16.9 ASME B16.9 ASME B16.11 ASME B16.11 Forged Steel Socket Weld 2.5-inch & above ASTM A53 ASME B16.9 ASME B16.9 F. Steam Condensate Sizes Pipe Fittings Joint 2-inch & below ASTM A53 ASTM A126 ASME B16.4 Sch 80 Black Steel ASME B16.4 Threaded Cast Iron 2.5-inch & above ASTM A53 ASME B16.9 ASME B16.9 Sch 80 Black Steel Wrought Steel Butt weld G. Refrigeration: See Cornell Design and Construction Standard Section 232300. DATE: 6/30/17 DATE: 6/30/15 Page 6 of 6