Basic Ventilation Considerations for Livestock or Poultry Housing

Similar documents
Ventilation Basics How Do Your Pigs Feel? Amy Woods, DVM Rensselaer Swine Services, P.C.

Ventilate Your Swine Nursery Building

Heat Exchangers in Swine Facilities

ENVIRONMENTAL CONTROL FOR CONFINEMENT LIVESTOCK HOUSING

FAN VENTILATION PRINCIPLES AND RATES

Natural Ventilation for Poultry

HOG FINISHING FACILITY PERFORMANCE

Manure Pit Ventilation in Confinement Livestock Buildings

Construction, Insulation, and Ventilation of Game Bird Facilities 1

, 'I... " ENTILATION FOR SWINE / I / / I / I / UNIVERSITY OF flunois / I / SGRICULTUR~.uBRM~ '" ""'... I I \ / I I. , I \ CIRCULA~~G COpy I 1// 1\\

SowBridge. Basic Environmental Factors & Their Effects on Pigs. Importance of Ventilation for Pig Comfort

Dairy Housing Ventilation Options for Free-Stall Barns H.K. House, P.Eng.

Facility Maintenance and Modernization

9/5/12. Emergency Thermostats Is this your override thermostat? Verify Emergency Equipment. Routine Test and Written History of Test

Novel Livestock Housing Webinar A Novel Approach to Confined Calf Barn Ventilation

Considering Filtration. Austin Baker Ventilation Director Hog Slat, Inc

EVALUATION OF SWINE FACILITIES VENTILATION

HOG HOUSES. Departments of. Animal Husbandry. and. Agricultural Engineering. Federal Cooperative Extension Service. Oregon State College.

EDSTROM Cooling Systems for Swine

Outline. Mixing fans / Cooling fans. Ventilation means air must. Ventilation. Energy Efficiency for Animal Housing. Environmental Control Systems

Poultry Housing Tips Radiant Tube Heater Floor Heating Patterns Volume 17 Number 5 April, 2005

TEMPERATURE MAPPING OF CAGE LAYER HOUSES

Greener Finisher Barns Could Reduce Emissions and Improve the Bottom Line.

AUTOMATIC MAKE-UP AIR DAMPER WITH TRANSFORMER READ AND SAVE THESE INSTRUCTIONS

INFORMATION FOR TANKLESS WATER HEATERS

VENTILATING POULTRY laying HOUSES

Some Devices for Flushing Animal Wastes 1

Please note: 1. The farm case studies in the following pages are in no particular order. 2. The order the case studies appear in the following pages

Select an agricultural ventilation fan for the

DeLaval solutions for cooling cows

Minimum Ventilation to Maximise Broiler Farm Performance. Ing.. Winfridus Bakker Cobb-Vantress

Control Strategies and Considerations for Livestock and Other Farm Buildings

Design and Management. Managing Your Unseen Employee: The Ventilation System

Solving the Problem of Heat Stress in Pigs

PLAN THE INSTALLATION Planning the installation first requires selecting the most appropriate installation approach. The chart below offers suggestion

AGRI-AIDE Ventilation Equipment. AGRI-AIDE Ventilation Key to Unlocking...

Momentum in Greenhouse Air Movement

Building and Remodeling to Save Energy 1

INSTRUCTIONS Livestock Machinery and Equipment Award 2015 WINNER Made in Britain

Building Science Basics

TPA 2018 Educational Seminar

Technical college/ Baghdad 4th Year Week No. :- 11. The objectives of this lesson are to: Introduction:

Greenhouse Temperature Management

TANKLESS WATER HEATING

Cooling Load Analysis and Computation Worksheet Answers Part 1 Psychrometrics

Grain and Soybean Drying on Georgia Farms

High Pressure Fog System

MECHANICAL VENTILATION

Acknowledgements. Copyright 2005, Aviagen, Inc., all rights reserved.

Ventilation and Cooling of Greenhouses NATURAL VENTILATION

Dairy Focus at Illinois Newsletter. Summer is around the corner make sure your cows don t get stressed. Volume 3, Number 3

How Much Energy is Really Being Wasted?

Environmental Control for Greenhouse Tomatoes

Open Cooling Tower. Equipment Layout Guide

Ministry of Agriculture, Food and Fisheries

Management of In-Bin Natural Air Grain Drying Systems to Minimize Energy Cost

Compost. Composted vs. uncomposted manure. Higher investment of time or money Lower investment of time or money

Compost. Composted vs. uncomposted manure. Higher investment of time or money Lower investment of time or money

Chapter 14 GAS VAPOR MIXTURES AND AIR-CONDITIONING

Managing Your Unseen Employee: The Ventilation System. The Pig and It s Environment. Keeping Pigs Eating in Hot Weather

Aerating Grain in Storage

Ventilation for New Low-Rise Residential Buildings July 20, 2015

As a homeowner in the Pacific Northwest, you

Selecting Fans and Determining Airflow for Grain Drying and Storage

VENTILATING AND HEATING SMALL LIVESTOCK ROOMS

EVAPORATIVE COOLING How an Evaporative Cooler Works

Use this Construction/HVAC Glossary to answer the questions below.

Gas Piping Facts. Information for properly sizing gas lines for use with tankless water heaters and other gas appliances TANKLESS WATER HEATING

Comparative analysis of power supply single speed air mover and an entire electronics enclosure system fan

IMPORTANT WARNINGS IMPORTANT SAFETY INSTRUCTIONS

CHAPTER I INTRODUCTION. In the modern life, electronic equipments have made their way

Cooling Load Analysis and Computation Worksheet

Equipment Layout Manual. For Cooling Towers, Evaporative Condensers & Closed Circuit Coolers

University oflllinois at Urbana-Champaign Small Homes Council-Building Research Council COUNCIL NOTES I ~ (f.) G6.0 SUMMER COMFORT {I)

Fresh air supply systems

How to Select and Size Enclosure Thermal Management Systems: White Paper, Title Page. How to Select and Size Enclosure Thermal Management Systems

Cumberland Heating Systems

Chore-Time Fan Guide For Tunnel and Other Applications

radon Keeping your home safe from radon

Low Profile Layout Guidelines

Poultry Housing Tips Circulation Fans in Houses with Radiant Brooders Volume 13 Number 1 January, 2001

INSTALLATION AND INSTRUCTION MANUAL FOR BAC AERATION CONTROLLER

R07. Answer any FIVE Questions All Questions carry equal marks *****

Cooling Swine. Extension Bulletin E-1748 February 1987 (Reprint) HOUSING. Heat Dissipation

Scraper Systems for Removing Manure From Swine Facilities

b.) Technical Information:

Good News at Home Hankey & Brown Inspection Service June 2013

Series V Layout Guidelines

WCD-1. Evaporative Cooling Modules. WCD Series. Alton. Keeps You. Cool

THE PSYCHROMETRIC CALCULATOR By: Stanley F. Gallos, The Bastian-Blessing Company INTRODUCTION PROPERTIES OF THE RSES CALCULATOR

Price increases since % 38% 53% 63% 115% Ground Beef. Electricity Eggs White Bread

Energy Saving Fact Sheet Agriculture & Horticulture

Thermodynamics II Chapter 6 Mixtures & Psychrometry

Green Flag Level Two Survey: Indoor Air Quality Program

Supplement A- Improving Forced Air Heating Systems

Florida Energy Extension Service

Environmental Control for Greenhouse Tomatoes

Jet Compressors. Circulate Steam Boost Low-Pressure Steam Compress and Mix Gases in Desired Proportion

Dehumidification Strategies Application Note

Evaporative Cooling Systems

Transcription:

PNW 307 Reprinted June 1993 Basic Ventilation Considerations for Livestock or Poultry Housing J. A. Moore Most producers would agree that all buildings that house livestock and poultry need ventilation. The real discussion begins when you try to determine how much ventilation you must provide. Any discussion of how much ventilation is needed must start by asking, Why ventilate? The answer varies with season, type of building and floor, number and age of livestock, and your waste-handling system. We ventilate to remove moisture, gases like ammonia and hydrogen sulfide, disease organisms, and heat. Ventilation air also replenishes oxygen consumed by gas brooders used to heat some poultry buildings. Under most conditions, we ventilate in the summer to remove heat and in the winter to remove moisture. When the ventilation rates are adequate to remove heat or moisture, the organisms and gases are usually well diluted and present no problem. But a lot depends on your type of waste-handling system and on how frequently you clean the building and empty your manure storage units. Heat balance While ventilation is important at all times, perhaps winter ventilation is the most critical. We humans can measure heat (temperature) quite well when we determine summer ventilation needs, but we have some problem sensing moisture levels (humidity) when we try to regulate winter flow rates. Let s use a winter example to demonstrate how the heat balance determines the required ventilation rate and possible needs in the building for supplemental heat. The heat coming into the building takes two forms (excluding mechanical heat from lights, motors, etc.). The primary source, in most buildings, is generated by the animals. The second is supplemental heat from furnaces, brooders, or lamps. This quantity of heat must satisfy three heat losses to keep the room/ building at some selected temperature: 1. There will be a heat loss through the doors, walls, etc., depending on the type of construction and the level of insulation. 2. Some heat will be lost in the exhausted ventilating air. 3. You ll need heat to evaporate water. The heat added to the system tends to raise the air temperature. The heat lost to each of these three sources tends to cool the air. If the building temperature is to remain constant (for this example, 60 F), the heat produced or generated in the building must heat the incoming air to 60 F and provide enough other heat to equal these three losses. A further examination of these relationships reveals that we can easily calculate the heat lost from the building when we know the room size, type of construction, level of insulation, and the inside and outside temperatures. With the building size, we know the animal capacity, and we can look up both the heat and moisture generated by the housed animals. We can determine the heat lost in the ventilation air if we know inside and outside air temperatures and the recommended ventilation rate for the number of animals we house. Table 1 provides these values. So, for any given set of conditions outside and inside temperature, building conditions, animal numbers you can calculate whether you ll need supplemental heat to maintain the indoor temperature you select. If you do need supplemental heat but choose not to provide it the inside James A. Moore is Extension agricultural engineer at Oregon State University. A Pacific Northwest Extension Publication Oregon Washington Idaho

Table 1. Recommended minimum ventilation rates for livestock a and poultry Ventilation, cfm/hd Cold Mild Hot Weight weather weather weather (lb) rate rate rate Sow and litter 400 20 80 500 Prenursery pig 12-30 2 10 25 Nursery pig 30-75 3 15 35 Growing pig 75-150 7 24 75 Finishing pig 150-220 10 35 120 Gestating sow 325 12 40 400 Boar 400 14 50 300 Sheep 1000 25 100 200 Dairy cows 1400 50 170 470 Heifers, 2-12 mo 20 60 130 12-24 mo 30 80 180 Calves, 0-2 mo 15 50 100 Broilers System capacity, cfm/1000 birds (below 35 F) (35-75 F) (over 75 F) Up to 3 wk 300 b 600 b 1000 3-6 wk 1500 b 3000 5000 5-8 wk 2500 b 5000 8000 Layers, 4-6 lb 2500 b 5000 8000 Breeders, 5-9 lb 3000 b 6000 15000 Turkeys Up to 2 lb (up to 4 wk) 600 1250 2500 2-5 lb (4-7 wk) 2000 3000 7000 5-8 lb (7-9 wk) 3500 5000 10000 8-12 lb (9-12 wk) 6000 7500 15000 12-15 lb (12-14 wk) 7500 9500 19000 15-20 lb (up to 18 wk) 8500 12500 25000 a Adapted from publications of the Midwest Plan Service, Iowa State University, Ames, Iowa: Sheep Housing Handbook, Dairy Housing Handbook, and Swine and Equipment Handbook. These rates are for solid-floor systems, which evaporate all the moisture. Slatted-floor, partial slatted-floor, and flushing-waste systems remove some of the moisture (urine and water); therefore, they can use lower cold weather ventilation rates. All rates shown are actual air-delivery rates. Extra capacity allowance must be made for losses caused by dust on fan blades or louvers or by other air-restricting conditions. b At these low air-exchange rates, increase the air mixing or recirculation of the heat inside the structure by using paddle fans, centrifugal fans, or fan-powered convection tube recirculation systems. temperature will fall. This cooler air will reduce the amount of water carried from the building in the ventilation air, and humid conditions will prevail (see figure 1). Other solutions would be to increase the heat input (provide more animals) or reduce the losses (add insulation to the building). Unfortunately, too many operators try to save heat by reducing the ventilation rate which usually causes odor and moisture problems. While you can t accomplish these calculations quickly, the concept is rather simple. You can calculate a heat balance for your set of conditions to answer questions about your ventilation system. This design logic works for evaluating the ventilation and heating needs of any livestock or poultry building. Characteristics of air Researchers have measured the heat and moisture produced by the different kind, sizes, and species of livestock and poultry. Other researchers have studied the characteristics of air and have determined its moisture and heatcarrying capacity at different temperatures. The higher the air temperature, the greater is its ability to carry moisture in the form of water vapor. Figure 2 shows a simple relationship between temperature and water-holding ability. Complete properties of air are shown on a psychrometric chart. It s a good idea to have a chart of your own; you ll find that it can help you better understand the relationships between air and moisture. (I ll be glad to send you a chart.) You use the moisture-holding capacity of air when you calculate the quantity of air necessary for winter ventilation to carry water vapor (from breathing, urine, and spilled water) from the building. 2

Figure 1. Stains on purlins show excess moisture, which collected against the cold roof and condensed. An increased ventilation rate will solve this problem. 0.5 0.8 Pounds of water per 1,000 pounds of dry air 1.3 2.2 3.4 10 0 10 20 30 40 50 60 70 Air temperature, F Figure 2. A simple relationship between temperature and the water-holding capacity of air. 5.2 7.7 11.1 15.8 A second important characteristic that you use in ventilation systems is that cool air sinks and warm air rises. We use this phenomenon to locate and size air inlets and outlets in natural ventilation systems. You can calculate an adequate air flow rate by using the number of animals in the building and outside air conditions. Researchers have done this for general conditions, and table 1 shows their recommended ventilation rates in cubic feet per minute (cfm) per head or per 1,000 birds. These rates are designed to remove adequate moisture in the winter and heat in the summer. They re calculated to remove the unwanted moisture (urine, spilled water, etc.) from a building with a solid floor. A different floor type, such as a slatted floor, removes some of the moisture and allows a reduction in winter ventilation rates. Natural and mechanical systems There are two possible systems that you can select to provide the required ventilation air natural and mechanical. The natural system uses no fans; it relies only on the wind and animal heat thermal buoyancy (the fact that warm air rises) to move air. The advantages of this system are its low initial cost (no fans to buy) and its ability to move air without requiring any electricity (no operating cost). The disadvantage is that natural systems require some management to set the inlet openings that control the range of ventilation rates. The actual ventilation rate and building temperature cycle through the day. This range is influenced by air temperature, wind, insulation level, and animal numbers and their activity level in the building. 3

Because the wind is one of the driving forces, the building orientation influences the design of inlets, outlets, and controls. This orientation must reflect the needs of the building in a natural ventilation system. This type of system is most often used to ventilate housing for rabbits, mature chickens and turkeys, weaned lambs, ewes, calves, finishing hogs, and gestating sows situations where building temperature variations and drafts cause few, if any, problems. Mechanical ventilation uses fans to provide the required air flow rate. These systems are common in poultry houses and in swine-farrowing and nurseries units. Their advantages include: 1. better control of the air flow rate to match the needs of the livestock in the building (this allows you to mix the air, warm it up, direct it over the floor, and evaporate water); 2. a reduced number of drafts; 3. better, more efficient use of building heat; and, 4. when you must add supplemental heat, the fact that this system might be used to distribute and blend the warmer air. The major disadvantages are cost (initial purchase and operating expenses) and the serious problems you could have during hot weather if a power outage stops all fans in a building full of livestock or poultry. Basic system types When fans pull air from the building and exhaust it outside, this is called negative pressure. In this design, the static air pressure inside the building is lower than outside (atmospheric) pressure, so it s negative. Negative pressure designs are commonly used in livestock housing. Outside In a positive pressure design, fans blow outside air into the building, creating an increase in pressure inside. The major disadvantage is that warm, moist air is under pressure and moves into all the cracks in the building walls and ceiling (seeking openings to the lower pressure outside). In the winter, air cools as it moves toward the outside, and moisture condenses in the walls and attic. This makes the insulation wet, causing it to get heavy and compress, which in turn reduces the effectiveness of the insulation. An additional disadvantage is that this moisture will eventually cause structural problems. Unless you have a vapor barrier, the recommendation is that you do not use fiberglass, mineral wool, and cellulose insulation with positive pressure systems. 4 Inside Open tube 1/8" Colored water Figure 3. The manometer is used to determine building static pressure. The term static pressure means the difference between the air pressure inside and outside the building. It s easy to measure this pressure and knowing it is necessary when you select a fan and adjust inlets. Figure 3 shows a simple manometer, a section of clear plastic tubing partially full of water bent into a U shape. You can place this U-tube inside or outside the building. Note, however, that you always expose one end of the tube to the outside air pressure and the other to the inside conditions. You can make a manometer with a piece of tubing (as in figure 3) or buy one from a fan supplier. In a negative pressure design, the air is moving from the outside into the building. In figure 3, the manometer is inside the building, and the outside air is pushing the water up the tube that s exposed to the pressure inside the building. This room has less pressure inside than outside, a negative pressure system.

Warm air Warm air No ceiling obstructions Cold air With proper inlet adjustment, high-velocity cold air sweeps the ceiling and mixes with warm air. Cold air With too wide an inlet, cold air sinks to floor rapidly, causing cold drafts. Warm air Figure 4. With proper adjustment, inlets direct high-velocity cold air along the ceiling, which allows mixing with the warm air. Figure 5. Openings may be moving enough air, but it appears that inlet distribution is not uniform. Your system operates best when the manometer shows a reading between 1/16 and 3/16 inch of water. Pressures below 1/16 inch make it difficult to uniformly distribute the incoming air. Pressures above 3/16 inch (generally caused by inadequate inlet area) reduce the fan capacity, reduce efficiency, and increase operating costs. Ventilation inlets and outlets Inlets. In both the natural and mechanical systems, the inlet controls the direction, path, and distribution of fresh air into the room (see figure 4). Inlets are perhaps the most important part of your ventilation system. By opening or closing the inlet, you regulate the thickness of the air jet, the air velocity, and (therefore) the distance the air flows into the room. See figure 5. When you need more air because of seasonal changes, adjust the inlet to maintain the air flow path and velocity. Inlets can be self-adjustable (for example, by using weighted curtains), or you can adjust them manually as required by temperature changes through the season. In poultry buildings with large rooms, the inlets are designed with the building. In swine units, plan the locations of the inlets after you ve selected the sleeping and dunging areas. You need the best air in the sleeping area; direct the poorest air into the dunging area. The best air will be the warmest in the winter and coolest in the summer. Feeders and waterers also influence inlet selections. Summer inlets should provide lots of turbulence and volume their purpose is to cool the building and animals. Winter air flows are smaller, but proper control and distribution are quite important. The large winter temperature differences between inside 5

and outside air can make drafts a big health problem. In most cases, you ll need a different inlet system for summer and winter. In some natural ventilation systems, however, you can adjust the same inlets to function properly in all seasons. Outlets in mechanical systems can usually be located on any wall. In swine and calf units, air should not have to move more than 40 feet to get to a fan. Poultry units use larger fans and can increase this distance to 50 feet. Locating the fan on a wall away from the wind or providing a fan shield will ensure uniform and consistent air flow rates. The outlet in natural systems should be at the ridge to ensure that warm, moist air is exhausted from the building. This takes advantage of the fact that warm air rises and usually carries additional moisture with it as it leaves the building. In single-sloped buildings, the outlet should be along the top of the tallest wall. A final word... Proper ventilation of livestock facilities can reduce disease and death loss and can improve your rate of gain and feed-conversion efficiency. Unfortunately, most livestock and poultry buildings need improved ventilation systems. Pacific Northwest Extension publications are jointly produced by the three Pacific Northwest states Oregon, Washington, and Idaho. Similar crops, climate, and topography create a natural geographic unit that crosses states lines. Since 1949 the PNW program has published more than 450 titles. Joint writing, editing, and production have prevented duplication of effort, broadened the availability of faculty specialists, and substantially reduced the costs for participating states. Published and distributed in furtherance of the Acts of Congress of May 8 and June 30, 1914, by the Oregon State University Extension Service, O.E. Smith, director; Washington State University Cooperative Extension, Larry G. James, interim director; the University of Idaho Cooperative Extension System, LeRoy D. Luft, director; and the U.S. Department of Agriculture cooperating. The three participating Extension Services offer educational programs, activities, and materials without regard to race, color, national origin, sex, age, or disability as required by Title VI of the Civil Rights Act of 1964, Title IX of the Education Amendments of 1972, and Section 504 of the Rehabilitation Act of 1973. The Oregon State University Extension Service, Washington Stale University Cooperative Extension, and the University of Idaho Cooperative Extension System are Equal Opportunity Employers. $1.50/$1.50/$1.50